DATA SHEET
DC Surge Protection for Remote Radio Heads
CB Product Series
Overvoltage Protection & Fiber Management Junction Box
powered by
The deployment of Remote Radio
Head (RRH) architecture poses
unique challenges to the mobile
industry. Raycap's innovative
RRH protection solutions mitigate
the risk of damage due to
lightning and provide high levels
of availability and reliability to
radio equipment.
Port size and configuration of enclosure
may differ from what is shown.
Features
Ÿ The CB Product Series utilizes the patented Strikesorb® 30-V1-HV Surge Protective
Device (SPD), specifically designed for the Remote Radio Head (RRH) installation
environment and certified for use in low, 48 volt DC operating applications.
Ÿ The Strikesorb 30-V1-HV is a Class I SPD, certified by VDE per the IEC 61643-11
Safety Standard as suitable for installation in areas where direct lightning exposure is
expected. Strikesorb 30-V1-HV is able to withstand direct lightning currents of up to 5
kA (10/350 µs) and induced surge currents of up to 60 kA (8/20 µs).
Ÿ Provides very low clamping/let-through voltage, unique for a Class I product, as it
does not employ spark gaps or other switching elements.
Ÿ Strikesorb offers unique protection levels to the RRH equipment as well as the
baseband units.
Ÿ Fully Recognized to UL 1449 4th Edition Safety Standard
Ÿ Patent pending design
Benefits
 Offers unique maintenance-free protection against direct lightning currents.
 Protects up to four RRHs and provides connection for fiber optic pairs.
 Utilizes an ingress protection rated, IP 67 enclosure, allowing for indoor or outdoor
installation on a roof or tower top.
 Configurable cable ports are designed to accommodate varying diameters of
hybrid (combined power and fiber optic) or standard cables with diameters up to
1.625" [41.27mm] depending upon port configuration.
 Lightweight design allows for easy tower top installation.
PSM-48
Mounting Bracket Included
www.raycap.com
Strikesorb is a registered trademark of Raycap
© 2016 Raycap All rights reserved.
G02-00-132 160621
DC Surge Protection for Remote Radio Heads
SPECIFICATIONS
CB Product Series
Overvoltage Protection & Fiber Management Junction Box
Electrical
CB Series
Surge Protective Device (SPD) Class to IEC 61643-11
Class I
Nominal Operating DC Voltage [Un]
48 V
Nominal Discharge Current [In]
20 kA 8/20 µs
Maximum Surge Current [Imax]
60 kA 8/20 µs
Maximum Impulse (Lightning) Current [Iimp] per IEC 61643-11
5 kA 10/350 µs
Maximum Continuous Operating DC Voltage [Uc] (MCOV)
75 V
Voltage Protection Rating (VPR) per UL 1449 4th Edition
400 V
Strikesorb Module Type
30-V1-HV
Incoming Power/Fiber
Configurable to customer
specifications
Form C Dry Contacts
Optional Alarm
Mechanical
Connection Terminal (Suppression) Method
Connection Terminal (Suppression) Hardwired
Fiber Connection Method
Compression lug
Copper #14 to #2/0 AWG [2.5 to 70 mm2]
Aluminum #12 to #2/0 AWG [4 to 70 mm2]
LC-LC Single or Dual mode to customer specifications
Environmental Ingress Protection (IP) Rating
IP 67
Operating Temperature
-40° C to +80° C
UV Resistant
Yes
Combined Wind Load
Enclosure Dimension (L × W × H)
Sustained 150 mph: 96 lbs/force [427 N]
Gusts 195 mph: 162 lbs/force [721 N]
13.56" × 5.22" × 13.22" [344.5 × 132.6 × 335.7 mm]
Weight
System 9 lbs [4.08 kg] Mount 4 lbs [1.81 kg] Total 13 lbs [5.89 kg]
Standards Compliance & Certifications
Strikesorb modules are compliant to the following Surge Protective Device (SPD) standards:
Standards UL 1449 4th Ed, IEC 61643-11, EN 61643-11:2012, IEEE C62.41: 2002, IEEE C62.45: 2002,
Certi ications UL, VDE, CE
Associations ANSI, EN, IEC, IEEE, NEC
Product Diagram
[mm]
inches
[162.2]
6.39
[344.5]
13.56
[132.6]
5.22
[203.2]
8.00
[335.7]
13.22
Port size and configuration of
enclosure may differ from
what is shown.
AWG=American Wire Gauge
[323.9]
12.75
www.raycap.com
G02-00-132