FE 2029 System No. F-E-2029 ED CL SIFI AS Classified by Underwriters Laboratories, Inc. to UL 1479 3C 1A 2 1B 3A 1C 3A manner described in the individual G500 Series Design in the UL Fire Resistance Directory, as summarized below: diam of opening shall be 4 in. (102 mm). of opening shall be 4 in. (102 mm). between the pipe or conduit and the periphery of opening shall be min 3/16 in (4.8 mm). to max 5/16 in. (8 mm). Pipe or conduit to be rigidly supported on both sides of floor-ceiling assembly. The following types and sizes of non-metallic pipes or conduit may be used: (drain, waste or vent) or closed (process or supply) piping systems. closed (process or supply) piping systems. (NFPA 70). closed (process or supply) or vented (drain, waste or vent) piping systems. The T Rating is 1/2 Hr for penetrants with a nom diam of 2 in (51 mm) or smaller. The T Rating is 0 Hr for penetrants with a nom diam greater than 2 in. (51 mm). Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. March 06, 2006 Page: 1 of 2 FE 2029 CL ED SIFI AS System No. F-E-2029 Classified by Underwriters Laboratories, Inc. to UL 1479 strip slid into the annular space such that the bottom edge of the wrap strip extends 1/4 in. (6 mm) from the bottom surface of the ceiling board. HILTI CONSTRUCTION CHEMICALS, DIV OF interface. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI CONSTRUCTION CHEMICALS, DIV OF *Bearing the UL Classification Mark +Bearing the UL Listing Mark. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. March 06, 2006 Page: 2 of 2