FE 2029
System No. F-E-2029
ED
CL
SIFI
AS
Classified by
Underwriters Laboratories, Inc.
to UL 1479
3C
1A
2
1B
3A
1C
3A
manner described in the individual G500 Series Design in the UL Fire Resistance Directory, as summarized below:
diam of opening shall be 4 in. (102 mm).
of opening shall be 4 in. (102 mm).
between the pipe or conduit and the periphery of opening shall be min 3/16 in (4.8 mm). to max 5/16 in. (8 mm). Pipe or conduit to be rigidly
supported on both sides of floor-ceiling assembly. The following types and sizes of non-metallic pipes or conduit may be used:
(drain, waste or vent) or closed (process or supply) piping systems.
closed (process or supply) piping systems.
(NFPA 70).
closed (process or supply) or vented (drain, waste or vent) piping systems.
The T Rating is 1/2 Hr for penetrants with a nom diam of 2 in (51 mm) or smaller. The T Rating is 0 Hr for penetrants with a nom diam
greater than 2 in. (51 mm).
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
March 06, 2006
Page: 1 of 2
FE 2029
CL
ED
SIFI
AS
System No. F-E-2029
Classified by
Underwriters Laboratories, Inc.
to UL 1479
strip slid into the annular space such that the bottom edge of the wrap strip extends 1/4 in. (6 mm) from the bottom surface of the ceiling
board.
HILTI CONSTRUCTION CHEMICALS, DIV OF
interface.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI CONSTRUCTION CHEMICALS, DIV OF
*Bearing the UL Classification Mark
+Bearing the UL Listing Mark.
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
March 06, 2006
Page: 2 of 2