General Description
The Cutler Hammer FD100 microprocessor based
Diesel Engine Fire Pump Controller is designed to
control and monitor 12 or 24 volt, listed diesel fire
pump engines. These controllers are listed by UL
and ULC, and approved by Factory Mutual and CSA,
as well as meeting or exceeding the requirements
of NFPA 20 and NFPA 70.
The FD100 Diesel Controller includes dual 10Amp,
current limiting, solid state battery chargers which
maintain the proper charge on both sets of batteries
at all times.
Display / Function Panel
Behind the breakable panel on the front of
the FD100 is the “Display/Function Panel” the information and programming center for
the controller. This panel includes (from
top to bottom), alarm and condition
LED indicators, main switch membrane
pushbuttons, LCD battery and system
pressure readout, programming keys and
function keys.
The TRI-colour LED annunciator lights are
color keyed to the urgency of the indication.
All FD100 Controllers come with the features
required for starting and stopping the diesel engine,
monitoring the engine operating conditions, and
alarming (audible and visible) for the engine,
controller, and system conditions.
Green:
Normal running
conditions.
Yellow:
Supervisory alarms.
Operation
These controllers automatically start the fire pump
diesel engine to provide adequate water pressure
to the fire protection system. The FD100 monitors
the fire sprinkler system pressure using a pressure
transducer. Upon detecting a drop in system
pressure, the microprocessor sends a start signal to
the engine, initiating its crank cycle. The starting
process can be initiated by other causes such as
deluge valve opening or remote start pushbutton.
The crank cycle consists of six periods of 15
second duration, separated by five rest periods of
15 second duration alternating on each set of
batteries. If the engine does not start within this
cycle, audible and visible “Fail to Start” alarm is
activated. Should voltage of either battery fall
below 67% of normal during the crank cycle, a
“Battery Failure” alarm will be activated and the
FD100 will alter the sequence by continuing the
process utilizing the remaining “good” battery.
The crank cycle terminates when the engine starts
and the FD100 continues to monitor the batteries
and engine conditions, such as: water temperature,
oil pressure, and speed (rpm).
Red:
Critical alarms.
The LCD readout includes all programming
parameters in addition to battery and
pressure information.
The “F1”, “F2”, “F3”, and “Menu” keys are
used to program the FD100 - set points,
timers, etc.. The “Function” keys are self
explanatory.
Relay Board
• Clearly labeled pull-apart terminal blocks for
ease of wiring and connections.
• All relays labeled with full
description as well as
corresponding three letter
designation as indicated on the
wiring diagram.
• Visual LED indication to show
energized state of relay.
The FD100 comes factory set in the "Manual Stop"
mode. In this configuration, the engine must be
shutdown by either placing the main switch in the
"OFF" position or, if all starting conditions are
satisfied, by pressing the "Stop" pushbutton on the
outside of the enclosure.
• All plug-in relays are identical
3PDT, allowing complete
interchangeability.
The FD100 can be programmed for “Auto Stop”,
which incorporates the RPT timer, without the
addition of any auxiliary equipment.
• Pump Room Trouble and Engine
Trouble common alarm relays are
standard.
The FD100, Diesel Fire Pump Controller is
designed and built to the latest requirements
of NFPA 20.
• All terminal numbers are indicated
on both the stationary and moveable
portion of the terminal blocks.
diesel _brochure -final3
4/18/00 2:55 PM
Page 4
Standard Features
Alarm Messages
• NEMA Type-2 Drip Proof
Enclosure
Auto Mode
• Dual 10 Amp Battery
Low Oil Pressure
Fail to Start
Chargers
Engine Overspeed
• Pressure Transducer
(0-600 psi)
Engine Run
Battery Failure
• Printer / Recorder
Charger Failure
• Relay Energized
Low Fuel Level
Indicator
High Fuel Level
• Weekly Test Timer
Fuel Spill
• Run Period Timer
High Engine Temperature
• AC Power Failure Start
Low Pump Room Temperature
• Sequential Start Timer
High Reservoir Level
• Manual Stop
Low Reservoir Level
• Remote Start
• Deluge Valve Start
Options
• Lamp Test Circuit
• Alarm Silence Button
• Enclosures
• Time Display Button
• Printer Command Button
NEMA 12, 3R, 4, 4X
• (2) sets Form C Relays rated
10A, 220VAC for:
Fuel Solenoid Valve
Heater Only
Drain Solenoid Valve
Heater with Humidistat
• (1) set Form C Relays rated
Heater with Thermostat
• (3) sets Form C Relays rated
10A, 220VAC for:
Manual Mode
OFF Mode
• Anti-Condensation Space
Heaters
10A, 220VAC for:
Engine Trouble
Common Alarm
Pump Room Trouble
Cranking Battery #1
Engine Run
Cranking Battery #2
Printer / Recorder
• Details all alarm and events including:
Cause of alarm/event
Date and Time
Operating mode of controller
at time of alarm
• "Status Print Out" detailing controller parameter configuration
• Excellent troubleshooting tool
• Capable of operating between 8-32VAC/DC
• 12” Floor Mounted Legs
• Pressure switch: 0 - 600psi,
Sea water service
• Energize to stop circuit
diesel _brochure -final3
4/18/00 2:45 PM
Page 1
Electric Fire Pump Controller Family
FD20
FD60
Limited Service
Controller
Auto transformer
Reduced Voltage
FD30
FD70
Across-the-Line
Wye-Delta
Open Transition
Reduced Voltage
FD40
FD80
Part Winding
Reduced Voltage
Wye-Delta
Closed Transition
Reduced Voltage
FD50
FD90
Primary Resistor
Reduced Voltage
Soft Start
Reduced Voltage
FPMP
FT Series
Fire Pump
Multi-Pack
Automatic
Transfer Switch
*All controllers are available with an automatic transfer switch option.
Cutler-Hammer also offers a complete line of Jockey Pumps and Remote Alarm Panels.