diesel _brochure -final3 4/18/00 2:46 PM Page 2 FD100 SERIES diesel _brochure -final3 4/18/00 2:50 PM Page 3 General Description The Cutler Hammer FD100 microprocessor based Diesel Engine Fire Pump Controller is designed to control and monitor 12 or 24 volt, listed diesel fire pump engines. These controllers are listed by UL and ULC, and approved by Factory Mutual and CSA, as well as meeting or exceeding the requirements of NFPA 20 and NFPA 70. The FD100 Diesel Controller includes dual 10Amp, current limiting, solid state battery chargers which maintain the proper charge on both sets of batteries at all times. Display / Function Panel Behind the breakable panel on the front of the FD100 is the “Display/Function Panel” the information and programming center for the controller. This panel includes (from top to bottom), alarm and condition LED indicators, main switch membrane pushbuttons, LCD battery and system pressure readout, programming keys and function keys. The TRI-colour LED annunciator lights are color keyed to the urgency of the indication. All FD100 Controllers come with the features required for starting and stopping the diesel engine, monitoring the engine operating conditions, and alarming (audible and visible) for the engine, controller, and system conditions. Green: Normal running conditions. Yellow: Supervisory alarms. Operation These controllers automatically start the fire pump diesel engine to provide adequate water pressure to the fire protection system. The FD100 monitors the fire sprinkler system pressure using a pressure transducer. Upon detecting a drop in system pressure, the microprocessor sends a start signal to the engine, initiating its crank cycle. The starting process can be initiated by other causes such as deluge valve opening or remote start pushbutton. The crank cycle consists of six periods of 15 second duration, separated by five rest periods of 15 second duration alternating on each set of batteries. If the engine does not start within this cycle, audible and visible “Fail to Start” alarm is activated. Should voltage of either battery fall below 67% of normal during the crank cycle, a “Battery Failure” alarm will be activated and the FD100 will alter the sequence by continuing the process utilizing the remaining “good” battery. The crank cycle terminates when the engine starts and the FD100 continues to monitor the batteries and engine conditions, such as: water temperature, oil pressure, and speed (rpm). Red: Critical alarms. The LCD readout includes all programming parameters in addition to battery and pressure information. The “F1”, “F2”, “F3”, and “Menu” keys are used to program the FD100 - set points, timers, etc.. The “Function” keys are self explanatory. Relay Board • Clearly labeled pull-apart terminal blocks for ease of wiring and connections. • All relays labeled with full description as well as corresponding three letter designation as indicated on the wiring diagram. • Visual LED indication to show energized state of relay. The FD100 comes factory set in the "Manual Stop" mode. In this configuration, the engine must be shutdown by either placing the main switch in the "OFF" position or, if all starting conditions are satisfied, by pressing the "Stop" pushbutton on the outside of the enclosure. • All plug-in relays are identical 3PDT, allowing complete interchangeability. The FD100 can be programmed for “Auto Stop”, which incorporates the RPT timer, without the addition of any auxiliary equipment. • Pump Room Trouble and Engine Trouble common alarm relays are standard. The FD100, Diesel Fire Pump Controller is designed and built to the latest requirements of NFPA 20. • All terminal numbers are indicated on both the stationary and moveable portion of the terminal blocks. diesel _brochure -final3 4/18/00 2:55 PM Page 4 Standard Features Alarm Messages • NEMA Type-2 Drip Proof Enclosure Auto Mode • Dual 10 Amp Battery Low Oil Pressure Fail to Start Chargers Engine Overspeed • Pressure Transducer (0-600 psi) Engine Run Battery Failure • Printer / Recorder Charger Failure • Relay Energized Low Fuel Level Indicator High Fuel Level • Weekly Test Timer Fuel Spill • Run Period Timer High Engine Temperature • AC Power Failure Start Low Pump Room Temperature • Sequential Start Timer High Reservoir Level • Manual Stop Low Reservoir Level • Remote Start • Deluge Valve Start Options • Lamp Test Circuit • Alarm Silence Button • Enclosures • Time Display Button • Printer Command Button NEMA 12, 3R, 4, 4X • (2) sets Form C Relays rated 10A, 220VAC for: Fuel Solenoid Valve Heater Only Drain Solenoid Valve Heater with Humidistat • (1) set Form C Relays rated Heater with Thermostat • (3) sets Form C Relays rated 10A, 220VAC for: Manual Mode OFF Mode • Anti-Condensation Space Heaters 10A, 220VAC for: Engine Trouble Common Alarm Pump Room Trouble Cranking Battery #1 Engine Run Cranking Battery #2 Printer / Recorder • Details all alarm and events including: Cause of alarm/event Date and Time Operating mode of controller at time of alarm • "Status Print Out" detailing controller parameter configuration • Excellent troubleshooting tool • Capable of operating between 8-32VAC/DC • 12” Floor Mounted Legs • Pressure switch: 0 - 600psi, Sea water service • Energize to stop circuit diesel _brochure -final3 4/18/00 2:45 PM Page 1 Electric Fire Pump Controller Family FD20 FD60 Limited Service Controller Auto transformer Reduced Voltage FD30 FD70 Across-the-Line Wye-Delta Open Transition Reduced Voltage FD40 FD80 Part Winding Reduced Voltage Wye-Delta Closed Transition Reduced Voltage FD50 FD90 Primary Resistor Reduced Voltage Soft Start Reduced Voltage FPMP FT Series Fire Pump Multi-Pack Automatic Transfer Switch *All controllers are available with an automatic transfer switch option. Cutler-Hammer also offers a complete line of Jockey Pumps and Remote Alarm Panels. Cutler-Hammer 403 East Lake Blvd., Airdrie, Alberta CAN T4B 2B9 Publication No TD.4Z.01A.T.K March 2000 Printed in Canada / 3M Phone: 403-948-7955 Fax: 403-948-4817 www.chfire.com