SPD Status Monitoring Network Power Analysis SPD Life Status and Failure Indication Surge Counter, Surge Recorder, Time/Date, Magnitude, Logging Logging of Power Disturbances on Electrical Network Measuring Basic Electric Supply Parameters BE ON THE SAFE SIDE ProAlyser SLS (SPD Life Status) Three phase SPD monitoring Percentage Residual SPD Life - 100% to 0% Warning each 10% degradation of Residual SPD Life Critical Visual and Audible alarm for permanent SPD disconnection, or when Life Status < 30% SURGE COUNTER Visual notification that a surge event has occurred Records: - Date (dd:mm:yy) - Time (hh:mm:ss) - Surge amplitude (kA) Logging of last 10 events in non-volatile memory Running total of number of surges and highest surge recorded POWER QUALITY INDICATOR Log of Temporary Overvoltages (Vn + 10%) Records: - Date (dd:mm:yy) - Time (hh:mm:ss) - Peak voltage (v) Log of Voltage Sags (Brownouts) Records: - Date (dd:mm:yy) - Time (hh:mm:ss) - Peak voltage (v) Log of Power Failures Records: - Date (dd:mm:yy) - Time (hh:mm:ss) Log of Network parameters Records: - MIN/MAX values (V, I, W, Hz, PF) per phase 3-PHASE POWER METER (PER PHASE) Voltage (VRSM) Current (IRMS) Frequency (Hz) Power Pactor (Cos Phi) Peak Voltage (Vpk) Energy Measurment (kWh, kVARh, kVAh) REMOTE INTERFACE RS232 SERIAL LINK AND MONITORING APPLICATION (PROPAC Software) Real-time monitor Last five alarms and measurments Graphical data preview History log of alarms and measurments E-mail notification when alarm is triggered Data can be used for further analysis (Web page, Xml, data export…) ISKRA ZAŠČITE, d.o.o., Surge Voltage Protection Systems, Engineering and Cooperation Stegne 35, 1521 Ljubljana, SLOVENIA T: +386(1)5003 100; F: +386(1)5003 236; E: sales@iskrazascite.si www.iskrazascite.si Published by: ISKRA ZA[^ITE, d.o.o. / March 2011 / Edition 2 SPD Status Monitori ng Network Power Analysis