Installation Instructions Supplement

advertisement
50FJX,FJY,FKX,FKY,FPX,FPY034-074
50JJX,JJY,JKX,JKY,JPX,JPY034-064
Single Package Electric Cooling Units
with Extended Plenum
Installation Instructions
Supplement
This book is a supplement to the 50FJ,FK,FP,JJ,JK,JP
Installation, Start-Up and Service Instructions and is to
be used with units with optional extended plenum. The
following units are covered in this supplement:
50FJX,FJY,FKX,FKY,FPX,FPY034-074 and 50JJX, JJY, JKX,
JKY, JPX, JPY034-064 units. Units with an X in the fifth
position are extended plenum units. Units with a Y in the
fifth position are extended plenum units with the unit disconnect option.
GENERAL
Units with the extended plenum option are a bottom supply, air arrangement design, intended for mounting on a roof
curb. The unit supply fan is arranged to discharge horizontally into an outlet plenum. The supply air then exits the plenum through the basepan opening into the supply duct.
The extended plenum option is available on standard length
chassis units (units with a F in the third position) and
extended length chassis units (units with a J in the third
position).
The following information is included in this supplement
and should be used for all extended plenum units:
• physical data tables (Table A)
• base unit dimensional drawings (Fig. A-F)
• roof curb dimensional drawings (Fig. G-N)
• rigging data (Fig. O)
• center of gravity and corner weights (Fig P)
• fan drive data (Table B)
Installation of these units follows all procedures described in the base unit installation instructions for curbmounted units.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
PC 111
Catalog No. 565-008
Printed in U.S.A.
Form 50F,J-1SIS
Pg 1
1-99
Replaces: New
Tab 1b
Table A — Physical Data — Extended Plenum Units
50FJ,FK,FP
034
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
With Economizer
COMPRESSORS
Quantity...Type
Capacity Steps (%)
CV Units
VAV Units
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass
With Hot Gas Bypass
CONDENSER COILS
Quantity
Rows...Fins/in.
Aluminum
Copper (Optional)
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Rows...Fins/in.
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
EVAPORATOR FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
EVAPORATOR-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...Model No.
Center Distance Range (in.)
OPTIONAL POWER EXHAUST
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%) High/Premium*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...No.
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters with Prefilters (Optional)
Quantity...Size (in.)
50JJ,JK,JP
034
50FJ,FK,FP
038
30
50JJ,JK,JP
038
35
5970
6270
6470
6770
6150
6450
6650
6950
Semi-Hermetic
2...06D
1...06D, 1...06E
50, 100
17, 33, 50, 66, 83, 100
2
43,100
14, 28, 43, 71, 86, 100
2
29.0/29.0
31.0/29.0
31.0/30.5
29.0/30.5
⁄ -in. Tube Diameter
38
2
2
3...15.0
3...13.7
37.5
3...15.0
3...13.7
37.5
⁄ -in. Tube Diameter
12
1
3...15.0
32.1
TXV...1
1
4...15.0
32.1
TXV...1
Propeller Type
2...30
18,600
1.0...1140
2...30
18,600
1.0...1140
Centrifugal 25 x 25 in.
10,500
15,000
900
111⁄16
12,250
15,000
900
111⁄16
(Any motor available on any unit)
10.0
15.0
215T
254T
7.5
213T
20.0
256T
88.5
89.5
91.0
91.0
91.7
91.7
93.0
93.6
13.6
13.7
13.7
13.7
3.4
4.3
4.9
5.5
438
549
626
703
900
900
900
900
2...BX60
2...5VX630
2...5VX630
2...5VX630
17.74...14.30
17.74...14.30
17.63...14.01
17.63...14.01
Centrifugal, 15 x 15 in. (Any motor available on any unit)
2...3.0
2...5.0
2...7.5
56HZ
184T
213T
81.0/88.5
87.5/89.5
88.5/91.7
6.9
6.9
6.9
3.35
4.12
5.0
13⁄16
13⁄16
13⁄16
843
1040
1264
1300
1300
1300
2...3VX670
2...3VX670
2...3VX710
12...20
4...16
12...20
4...16
6...20
6...20
LEGEND
CV — Constant Volume
TXV — Thermostatic Expansion Valve
VAV — Variable Air Volume
*Premium efficiency motors are not available on 380-v and 575-v units.
2
×
×
×
×
×
×
25
20
25
20
24
20
×
×
×
×
×
×
2
2
2
2
22
22
12...20 ×
4...16 ×
12...20 x
4...16 ×
6...20 ×
6...20 ×
25
20
25
20
24
20
×2
×2
x2
×2
× 22
× 22
Table A — Physical Data — Extended Plenum Units (cont)
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
With Economizer
COMPRESSORS
Quantity...Type
Capacity Steps (%)
CV Units
VAV Units
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass
With Hot Gas Bypass
CONDENSER COILS
Quantity
Rows...Fins/in.
Aluminum
Copper (Optional)
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Rows...Fins/in.
Total Face Area (sq ft)
Refrigerant Feed Device...No. per Circuit
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
EVAPORATOR FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
EVAPORATOR-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...Model No.
Center Distance Range (in.)
OPTIONAL POWER EXHAUST
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%) High/Premium*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...No.
FILTERS
Standard Efficiency Throwaway (Standard)
Quantity...Size (in.)
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters with Prefilters (Optional)
Quantity...Size (in.)
50FJ,FK,FP
044
50JJ,JK,JP
044
50FJ,FK,FP
048
50JJ,JK,JP
048
40
45
6620
6920
7120
7420
6740
7040
7240
7540
Semi-Hermetic
2...06E
2...06E
50, 100
25, 50, 75, 100
2
56, 100
18, 37, 56, 63, 81, 100
2
40.0/40.0
42.0/40.0
43.5/39.0
41.5/39.0
⁄ -in. Tube Diameter
38
2
2
3...15.0
3...13.7
50.0
3...15.0
3...13.7
50.0
⁄ -in. Tube Diameter
12
2
3...15.0
45.5
TXV...2
2
4...15.0
45.5
TXV...2
Propeller Type
3...30
26,000
1.0...1140
3...30
26,000
1.0...1140
Centrifugal 25 × 25 in.
14,000
20,000
900
111⁄16
15,750
20,000
900
111⁄16
(Any motor available on any unit)
10.0
15.0
215T
254T
7.5
213T
20.0
256T
88.5
89.5
91.0
91.0
91.7
91.7
93.0
93.6
13.6
13.7
13.7
13.7
3.4
4.3
4.9
5.5
438
549
626
703
900
900
900
900
2...BX60
2...5VX630
2...5VX630
2...5VX630
17.74...14.30
17.74...14.30
17.63...14.01
17.63...14.01
Centrifugal, 15 x 15 in. (Any motor available on any unit)
2...3.0
2...5.0
2...7.5
56HZ
184T
213T
81.0/88.5
87.5/89.5
88.5/91.7
6.9
6.9
6.9
3.35
4.12
5.0
13⁄16
13⁄16
13⁄16
843
1040
1264
1300
1300
1300
2...3VX670
2...3VX670
2...3VX710
12...20
4...16
12...20
4...16
6...20
6...20
LEGEND
CV — Constant Volume
TXV — Thermostatic Expansion Valve
VAV — Variable Air Volume
*Premium efficiency motors are not available on 380-v and 575-v units.
3
×
×
×
×
×
×
25
20
25
20
24
20
×
×
×
×
×
×
2
2
2
2
22
22
12...20
4...16
12...20
4...16
6...20
6...20
×
×
×
×
×
×
25
20
25
20
24
20
×
×
×
×
×
×
2
2
2
2
22
22
Table A — Physical Data — Extended Plenum Units (cont)
BASE UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Base Unit
With Economizer
COMPRESSORS
Quantity...Type
Capacity Steps (%)
CV Units
VAV Units
Number of Refrigerant Circuits
REFRIGERANT
Operating Charge (lb), Sys 1/Sys 2
Without Hot Gas Bypass
With Hot Gas Bypass
CONDENSER COILS
Quantity
Rows...Fins/in.
Aluminum
Copper (Optional)
Total Face Area (sq ft)
EVAPORATOR COILS
Quantity
Rows...Fins/in.
Total Face Area (sq ft)
Refrigerant Feed Device...
No. per Circuit
CONDENSER FANS
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
EVAPORATOR FAN
Nominal Cfm
Maximum Allowable Cfm
Maximum Allowable Rpm
Shaft Diameter at Pulley (in.)
EVAPORATOR-FAN MOTOR AND DRIVE
Motor Hp
Motor Frame Size
Efficiency at Full Load (%)
High Efficiency
Premium Efficiency*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
Belts Quantity...Model No.
Center Distance Range (in.)
OPTIONAL POWER EXHAUST
Quantity...Motor Hp
Motor Frame Size
Efficiency at Full Load (%) High/Premium*
Fan Pulley Pitch Diameter (in.)
Motor Pulley Pitch Diameter (in.)
Shaft Diameter at Pulley (in.)
Resulting Fan Rpm
Maximum Allowable Rpm
FILTERS
Standard Efficiency
Throwaway (Standard)
Quantity...Size (in.)
Medium Efficiency (30%) Pleated (Optional)
Quantity...Size (in.)
High Efficiency (90%) Bag Filters
with Prefilters (Optional)
Quantity...Size (in.)
50FJ,FK,FP
054
50JJ,JK,JP
054
50FJ,FK,FP
064
50
50JJ,JK,JP
064
50FJ,FK,FP
074
75
60
8250
8780
8800
9330
2...06E
8550
9100
9080
9630
Semi-Hermetic
2...06E
2...06E
60, 100
20, 40, 60, 80, 100
2
50, 100
17, 33, 50, 66, 83, 100
2
43, 100
14, 28, 43, 71, 85, 100
2
59.0/44.5
62.0/44.5
4
2...17.0, 3...17.0
2...15.7, 3...15.7
72.4
2
3...17.0
61.5
TXV...2
15.0
254T
91.0
93.0
13.7
4.5
575
750
2...5VX1230
48.25...44.00
3...17.0
3...15.7
72.4
1⁄2-in. Tube Diameter
2
4...17.0
61.5
3...17.0
3...15.7
108.4
x
x
x
x
2
2
2
2
15...20
5...16
15...20
5...16
6...20 x 24 x 22
6...24 x 24 x 22
LEGEND
CV — Constant Volume
TXV — Thermostatic Expansion Valve
VAV — Variable Air Volume
*Premium efficiency motors are not available on 380-v and 575-v units.
4
x
x
x
x
25
20
25
20
4
2
4...17.0
61.5
TXV..2
91.0
91.7
93.6
93.6
13.7
13.7
5.1
5.5
651
703
750
750
2...5VX1230
2...5VX1230
48.25...44.00
48.50...44.25
Centrifugal, 18 x 15 in. (Any motor available on any unit)
2...7.5
213T
88.5/91.7
10.6
5.0
17⁄16
820
925
2...5.0
184T
87.5/89.5
10.6
4.5
17⁄16
740
925
25
20
25
20
70.5/64.5
73.5/64.5
Propeller Type
4...30
40,000
1.0...1140
Centrifugal 30 x 27 in.
21,000
30,000
750
111⁄16
(Any motor available on any unit)
20.0
25.0
256T
284T
17,500
25,000
750
111⁄16
x
x
x
x
61.0/61.0
64.0/61.0
3⁄8-in. Tube Diameter
4
TXV...2
4...30
40,000
1.0...1140
15...20
5...16
15...20
5...16
8970
9500
x
x
x
x
2
2
2
2
6...20 x 24 x 22
6...24 x 24 x 22
5...30
50,000
1.0...1140
24,500
30,000
750
111⁄16
30.0
286T
92.4
93.6
15.5
5.9
711
750
2...5VX1250
48.50...44.25
2...10.0
215T
89.5/91.7
10.6
5.6
17⁄16
920
925
15...20
5...16
15...20
5...16
x
x
x
x
25
20
25
20
x
x
x
x
2
2
2
2
6...20 x 24 x 22
6...24 x 24 x 22
NOTES:
1. Dimensions in [
2.
3.
4.
5.
6.
] are in millimeters.
UNIT SIZE
Center of Gravity includes economizer. Unit weight does not include
economizer.
Unit clearances:
Top — Do not restrict condenser fans
Control Box End — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09) [3048]
For smaller service and operating clearances, contact Carrier Application Engineering Department.
Downshot ducts designed to be attached to accessory roof curb. If unit is mounted
on dunnage, it is recommended the ducts be supported by cross braces as done on
the accessory roof curb.
When the unit is slab mounted, plug the factory drilled auxiliary condensate drain
holes.
Economizer side hoods are folded inside unit for shipping.
50FJX,FKX,FPX,FJY,FKY,FPY034
50FJX,FKX,FPX,FJY,FKY,FPY038
5
Fig. A — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY034,038 Units
WEIGHT
lb
kg
5970 2714
6150 2770
A
mm
4044
4090
ft-in.
13-31⁄4
13-5
NOTES:
1. Dimensions in [
2.
3.
4.
5.
6.
] are in millimeters.
Center of Gravity includes economizer. Unit weight does not include economizer.
Unit clearances:
Top — Do not restrict condenser fans
Control Box End — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048])
For smaller service and operating clearances, contact Carrier Application
Engineering Department.
Downshot ducts designed to be attached to accessory roof curb. If unit is
mounted on dunnage, it is recommended the ducts be supported by cross
braces as done on the accessory roof curb.
When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes.
Economizer side hoods are folded inside unit for shipping.
UNIT SIZE
50FJX,FKX,FPX,FJY,FKY,FPY044
50FJX,FKX,FPX,FJY,FKY,FPY048
6
Fig. B — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY044,048 Units
WEIGHT
lb
6620
6740
kg
3009
3027
A
mm
4823
4851
ft.in.
15- 97⁄8
15-11
UNIT SIZE
50FJX,FJY,FKX,FKY,FPX,FPY054
50FJX,FJY,FKX,FKY,FPX,FPY064
50FJX,FJY,FKX,FKY,FPX,FPY074
WEIGHT
lb
kg
8250 3750
8550 3886
8970 4077
A
mm
2830
2830
3694
ft-in.
9-33⁄4
9-33⁄4
12-13⁄4
B
mm
6427
6427
5563
C
ft-in.
21-1
21-1
18-3
mm
6045
6045
6477
ft-in.
19-10
19-10
21- 3
D
mm
1163
1163
1163
ft-in.
3-913⁄16
3-913⁄16
3-913⁄16
E
mm
11 140
11 140
12 049
F
ft-in.
36-69⁄16
36-69⁄16
39-63⁄8
mm
11 524
11 524
12 433
ft-in.
37-911⁄16
37-911⁄16
40-91⁄2
NOTES:
1. Dimensions in [
2.
] are in millimeters.
Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans
Control Box End — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048])
For smaller service and operating clearances, contact Carrier Application Engineering
Department.
4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on
dunnage, it is recommended the ducts be supported by cross braces as done on the
accessory roof curb.
5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes.
6. Economizer side hoods are folded inside unit for shipping.
7
Fig. C — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY054-074 Units
NOTES:
1. Dimensions in [
2.
3.
4.
5.
6.
7.
8.
9.
] are in millimeters.
Center of gravity includes economizer. Unit weight does not include economizer or heating coil.
Unit Clearances
Top — Do not restrict condenser fans
Control Box End — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048])
For smaller service and operational clearances, contact Carrier Application Engineering Department.
Downshot ducts designed to be attached to accessory roof curb. If unit is mounted
on dunnage, it is recommended the ducts be supported by cross braces as done on
the accessory roof curb.
When the unit is slab mounted, plug the factory drilled auxiliary condensate drain
holes.
Auxiliary heating coil dimensions (maximum):
Length (header included), 78-01⁄49 [2140]
Width, 08-95⁄89 [244]
Height, 48-515⁄169 [1370]
Auxiliary heating coil field supplied and installed.
Economizer side hoods are folded inside unit for shipping.
Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut.
AUXILIARY COIL PIPE CHASES (See Note 9)
WEIGHT
A
UNIT
SIZE
lb
kg
mm
ft-in.
50JJX,JKX,JPX,JJY,JKY,JPY034
6470
2934
4618
14-515⁄16
50JJX,JKX,JPX,JJY,JKY,JPY038
6650
2991
4474
14-81⁄8
8
Fig. D — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY034,038 Units
NOTES:
1. Dimensions in [
2.
3.
4.
5.
6.
7.
8.
9.
] are in millimeters.
Center of gravity includes economizer. Unit weight does not include economizer or heating coil.
Unit Clearances
Top — Do not restrict condenser fans
Control Box End — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048])
For smaller service and operational clearances, contact Carrier Application Engineering
Department.
Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on
dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb.
When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes.
Auxiliary heating coil dimensions (maximum):
Length — (header included), 78-01⁄49 [2140]
Width, 08-95⁄89 [244]
Height, 48-71⁄29 [1410]
Auxiliary heating coil field supplied and installed.
Economizer side hoods are folded inside unit for shipping.
Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut.
AUXILIARY COIL PIPE CHASES (See Note 9)
9
Fig. E — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY044,048 Units
WEIGHT
A
UNIT
SIZE
lb
kg
mm
ft-in.
50JJX,JKX,JPX,JJY,JKY,JPY044
7120
3229
5211
17-11⁄8
50JJX,JKX,JPX,JJY,JKY,JPY048
7240
3247
5239
17-21⁄4
UNIT
SIZE
50JJX,JKX,JPX,JJY,JKY,JPY054
50JJX,JKX,JPX,JJY,JKY,JPY064
WEIGHT
lb
kg
8800 3990
9100 4127
A
mm
2959
2959
B
C
D
E
F
ft-in.
9-81⁄2
mm
6940
ft-in.
22-93⁄4
mm
6393
ft-in.
20-1111⁄16
mm
1163
ft-in.
3-913⁄16
mm
11 780
ft-in.
38-713⁄16
mm
12 164
ft-in.
39-107⁄8
9-81⁄2
6940
22-93⁄4
6393
20-1111⁄16
1163
3-913⁄16
11 780
38-713⁄16
12 164
39-107⁄8
AUXILIARY COIL PIPE CHASES (See Note 9)
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity includes economizer. Does not include heating coil.
Unit weight does not include economizer or heating coil.
3. Unit Clearances
Top — Do not restrict condenser fans
Control box end — 68-09 [1829]
Sides — 68-09 [1829]
Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048])
For smaller service and operational clearances, contact Carrier Application Engineering Department.
4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted
on dunnage, it is recommended the ducts be supported by cross braces as done
on the accessory roof curb.
5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain
holes.
6. Auxiliary heating coil dimensions (maximum):
Length (header included), 78-01⁄49 [2140]
Width, 08-95⁄89 [244]
Height, 58-69 [1676]
7. Auxiliary heating coil field supplied and installed.
8. Economizer side hoods are folded inside unit for shipping.
9. Pipe chases for auxiliary coil are not provided with unit. Chases must be fieldcut.
10
Fig. F — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY054,064 Units
DIMENSIONS*
(degrees and inches)
A
11
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. G — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY034,038
in.
.75
12
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. H — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY044,048
in.
.75
13
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. I — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY054-074
in.
.75
DIMENSIONS*
(degrees and inches)
A
14
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
4. Pipe chases for auxiliary coil are not
provided with unit. Chases must be
field-cut.
Fig. J — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY034,038
in.
.75
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 ga. [VA03-56] stl.
3. Dimensions in [ ] are millimeters.
4. Pipe chases for auxiliary coil are not
provided with unit. Chases must be
field-cut.
15
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. K — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY044,048
in.
.75
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 ga. [VA03-56] stl.
3. Dimensions in [ ] are millimeters.
4. Suggested hole location for field wiring through
roof curb (holes to be supplied by field).
5. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut.
16
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. L — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY054,064
in.
.75
NOTES:
1. Roof curb is shipped disassembled.
2. Roof curb: 14 gage (VA03-56) steel.
3. Dimensions in [ ] are millimeters.
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
17
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. M — Condenser Section Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY,JJX,JJY,JKX,JKY,JPX,JPY, Sizes 054 and 064
in.
.75
NOTES:
1. Roof curb is shipped disassembled.
2. Dimensions in [ ] are millimeters.
3. Roof curb: 14 gage (VA03-56) steel.
Roof curb pans, 16 gage (VA03-56) steel.
18
DIMENSIONS*
(degrees and inches)
A
Deg
1.0
B
in.
2.0
Deg
.50
UNIT LEVELING TOLERANCES
*From edge of unit to horizontal.
Fig. N — Condenser Section Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY, Size 074
in.
.75
NOTES:
1. Sizes 034-048: Rig with 4 cables and spread with two 95 in. (2413 mm) and
2 8A 1 A8 long spreader bars.
Sizes 054-074: Rig with 4 cables and spread with two 95 in. (2413 mm) and
2 8A 1 A8 long spreader bars.
2. Center of gravity includes economizer.
1. All panels must be in place when rigging.
2. Unit is not designed for handling by forklift truck.
RIGGING WEIGHTS AND DIMENSIONS
MODEL NO.
(EXTENDED CHASSIS UNITS)
50FJX,FJY,FKX,FKY,FPX,FPY034
50FJX,FJY,FKX,FKY,FPX,FPY038
50FJX,FJY,FKX,FKY,FPX,FPY044
50FJX,FJY,FKX,FKY,FPX,FPY048
50FJX,FJY,FKX,FKY,FPX,FPY054
50FJX,FJY,FKX,FKY,FPX,FPY064
50FJX,FJY,FKX,FKY,FPX,FPY074
50JJX,JJY,JKX,JKY,JPX,JPY034
50JJX,JJY,JKX,JKY,JPX,JPY038
50JJX,JJY,JKX,JKY,JPX,JPY044
50JJX,JJY,JKX,JKY,JPX,JPY048
50JJX,JJY,JKX,JKY,JPX,JPY054
50JJX,JJY,JKX,JKY,JPX,JPY064
WEIGHT
Lb
Kg
5970
2714
6150
2790
6620
3009
6740
3057
8250
3750
8550
3886
8970
4077
6470
2934
6650
3016
7120
3229
7240
3284
8800
3990
9100
4127
A
in.
83.23
83.23
92.64
92.64
126.50
126.50
109.50
95.83
95.83
105.24
105.24
136.61
136.61
B
mm
2114
2114
2353
2353
3213
3213
2782
2434
2434
2673
2673
3470
3470
Fig. O — Rigging Label
19
in.
159.21
161.02
189.88
190.98
238
238
255
173.94
176.14
205.16
206.26
251.70
251.70
mm
4044
4090
4823
4851
6045
6045
6477
4418
4474
5211
5239
6393
6393
ECONOMIZER
Lb
Kg
300
136
300
136
300
136
300
136
530
240.9
530
240.9
530
240.9
300
136
300
136
300
136
300
136
530
240.9
530
240.9
3
4
2
1
B
A
UNIT CORNER WEIGHTS (lbs)
UNIT
50FJX,FJY
50FKX,FKY
50FPX,FPY
50JJX,JJY
50JKX,JKY
50JPX,JPY
034
038
044
048
054
064
074
034
038
044
048
054
064
1
2
3
4
Total
1864
1922
2070
2115
2381
2461
2551
1989
2043
2195
2240
2518
2598
1268
1287
1387
1412
2005
2074
2194
1393
1413
1512
1537
2143
2212
1271
1290
1389
1414
2009
2078
2199
1396
1417
1514
1539
2146
2215
1867
1951
2074
2099
2385
2467
2556
1992
2077
2199
2224
2523
2605
6270
6450
6920
7040
8780
9080
9500
6770
6950
7420
7540
9330
9630
CENTER OF GRAVITY
A
B
ft-in.
ft-in.
13- 31⁄4
3-913⁄16
13- 5
3-913⁄16
15- 97⁄8
3-913⁄16
15-11
3-913⁄16
19-10
3-913⁄16
19-10
3-913⁄16
21- 3
3-913⁄16
3-913⁄16
14- 515⁄16
14- 81⁄8
3-913⁄16
17- 11⁄8
3-913⁄16
17- 21⁄4
3-913⁄16
20-1111⁄16
3-913⁄16
20-1111⁄16
3-913⁄16
NOTE: Weights include economizer.
Fig. P — Unit Center of Gravity and Corner Weights
Table B — Supply Fan Drive Data
SHAFT
DIA.
Sizes 034-048
7.5
13⁄8
10
13⁄8
15
15⁄8
20
15⁄8
Sizes 054-074
15
15⁄8
20
15⁄8
25
17⁄8
30
17⁄8
HP
SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
PITCH DIA.
WHEEL
SHEAVE
WHEEL
PITCH DIA.
QUANTITY
...BELT
438
549
626
703
2BK36
2B5V42
2B5V48
2B5V54
3.4
4.3
4.9
5.5
2B5V136
2B5V136
2B5V136
2B5V136
13.6
13.7
13.7
13.7
2...BX60
2...5VX630
2...5VX630
2...5VX630
575
651
703
711
2B5V44
2B5V50
2B5V54
2B5V62
4.5
5.1
5.5
5.9
2B5V136
2B5V136
2B5V136
2B5V154
13.7
13.7
13.7
15.5
2...5VX1230
2...5VX1230
2...5VX1230
2...5VX1250
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
PC 111
Catalog No. 565-008
Printed in U.S.A.
Form 50F,J-1SIS
Pg 20
1-99
Replaces: New