50FJX,FJY,FKX,FKY,FPX,FPY034-074 50JJX,JJY,JKX,JKY,JPX,JPY034-064 Single Package Electric Cooling Units with Extended Plenum Installation Instructions Supplement This book is a supplement to the 50FJ,FK,FP,JJ,JK,JP Installation, Start-Up and Service Instructions and is to be used with units with optional extended plenum. The following units are covered in this supplement: 50FJX,FJY,FKX,FKY,FPX,FPY034-074 and 50JJX, JJY, JKX, JKY, JPX, JPY034-064 units. Units with an X in the fifth position are extended plenum units. Units with a Y in the fifth position are extended plenum units with the unit disconnect option. GENERAL Units with the extended plenum option are a bottom supply, air arrangement design, intended for mounting on a roof curb. The unit supply fan is arranged to discharge horizontally into an outlet plenum. The supply air then exits the plenum through the basepan opening into the supply duct. The extended plenum option is available on standard length chassis units (units with a F in the third position) and extended length chassis units (units with a J in the third position). The following information is included in this supplement and should be used for all extended plenum units: • physical data tables (Table A) • base unit dimensional drawings (Fig. A-F) • roof curb dimensional drawings (Fig. G-N) • rigging data (Fig. O) • center of gravity and corner weights (Fig P) • fan drive data (Table B) Installation of these units follows all procedures described in the base unit installation instructions for curbmounted units. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 565-008 Printed in U.S.A. Form 50F,J-1SIS Pg 1 1-99 Replaces: New Tab 1b Table A — Physical Data — Extended Plenum Units 50FJ,FK,FP 034 BASE UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Base Unit With Economizer COMPRESSORS Quantity...Type Capacity Steps (%) CV Units VAV Units Number of Refrigerant Circuits REFRIGERANT Operating Charge (lb), Sys 1/Sys 2 Without Hot Gas Bypass With Hot Gas Bypass CONDENSER COILS Quantity Rows...Fins/in. Aluminum Copper (Optional) Total Face Area (sq ft) EVAPORATOR COILS Quantity Rows...Fins/in. Total Face Area (sq ft) Refrigerant Feed Device...No. per Circuit CONDENSER FANS Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm EVAPORATOR FAN Nominal Cfm Maximum Allowable Cfm Maximum Allowable Rpm Shaft Diameter at Pulley (in.) EVAPORATOR-FAN MOTOR AND DRIVE Motor Hp Motor Frame Size Efficiency at Full Load (%) High Efficiency Premium Efficiency* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Resulting Fan Rpm Maximum Allowable Rpm Belts Quantity...Model No. Center Distance Range (in.) OPTIONAL POWER EXHAUST Quantity...Motor Hp Motor Frame Size Efficiency at Full Load (%) High/Premium* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Shaft Diameter at Pulley (in.) Resulting Fan Rpm Maximum Allowable Rpm Belts Quantity...No. FILTERS Standard Efficiency Throwaway (Standard) Quantity...Size (in.) Medium Efficiency (30%) Pleated (Optional) Quantity...Size (in.) High Efficiency (90%) Bag Filters with Prefilters (Optional) Quantity...Size (in.) 50JJ,JK,JP 034 50FJ,FK,FP 038 30 50JJ,JK,JP 038 35 5970 6270 6470 6770 6150 6450 6650 6950 Semi-Hermetic 2...06D 1...06D, 1...06E 50, 100 17, 33, 50, 66, 83, 100 2 43,100 14, 28, 43, 71, 86, 100 2 29.0/29.0 31.0/29.0 31.0/30.5 29.0/30.5 ⁄ -in. Tube Diameter 38 2 2 3...15.0 3...13.7 37.5 3...15.0 3...13.7 37.5 ⁄ -in. Tube Diameter 12 1 3...15.0 32.1 TXV...1 1 4...15.0 32.1 TXV...1 Propeller Type 2...30 18,600 1.0...1140 2...30 18,600 1.0...1140 Centrifugal 25 x 25 in. 10,500 15,000 900 111⁄16 12,250 15,000 900 111⁄16 (Any motor available on any unit) 10.0 15.0 215T 254T 7.5 213T 20.0 256T 88.5 89.5 91.0 91.0 91.7 91.7 93.0 93.6 13.6 13.7 13.7 13.7 3.4 4.3 4.9 5.5 438 549 626 703 900 900 900 900 2...BX60 2...5VX630 2...5VX630 2...5VX630 17.74...14.30 17.74...14.30 17.63...14.01 17.63...14.01 Centrifugal, 15 x 15 in. (Any motor available on any unit) 2...3.0 2...5.0 2...7.5 56HZ 184T 213T 81.0/88.5 87.5/89.5 88.5/91.7 6.9 6.9 6.9 3.35 4.12 5.0 13⁄16 13⁄16 13⁄16 843 1040 1264 1300 1300 1300 2...3VX670 2...3VX670 2...3VX710 12...20 4...16 12...20 4...16 6...20 6...20 LEGEND CV — Constant Volume TXV — Thermostatic Expansion Valve VAV — Variable Air Volume *Premium efficiency motors are not available on 380-v and 575-v units. 2 × × × × × × 25 20 25 20 24 20 × × × × × × 2 2 2 2 22 22 12...20 × 4...16 × 12...20 x 4...16 × 6...20 × 6...20 × 25 20 25 20 24 20 ×2 ×2 x2 ×2 × 22 × 22 Table A — Physical Data — Extended Plenum Units (cont) BASE UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Base Unit With Economizer COMPRESSORS Quantity...Type Capacity Steps (%) CV Units VAV Units Number of Refrigerant Circuits REFRIGERANT Operating Charge (lb), Sys 1/Sys 2 Without Hot Gas Bypass With Hot Gas Bypass CONDENSER COILS Quantity Rows...Fins/in. Aluminum Copper (Optional) Total Face Area (sq ft) EVAPORATOR COILS Quantity Rows...Fins/in. Total Face Area (sq ft) Refrigerant Feed Device...No. per Circuit CONDENSER FANS Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm EVAPORATOR FAN Nominal Cfm Maximum Allowable Cfm Maximum Allowable Rpm Shaft Diameter at Pulley (in.) EVAPORATOR-FAN MOTOR AND DRIVE Motor Hp Motor Frame Size Efficiency at Full Load (%) High Efficiency Premium Efficiency* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Resulting Fan Rpm Maximum Allowable Rpm Belts Quantity...Model No. Center Distance Range (in.) OPTIONAL POWER EXHAUST Quantity...Motor Hp Motor Frame Size Efficiency at Full Load (%) High/Premium* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Shaft Diameter at Pulley (in.) Resulting Fan Rpm Maximum Allowable Rpm Belts Quantity...No. FILTERS Standard Efficiency Throwaway (Standard) Quantity...Size (in.) Medium Efficiency (30%) Pleated (Optional) Quantity...Size (in.) High Efficiency (90%) Bag Filters with Prefilters (Optional) Quantity...Size (in.) 50FJ,FK,FP 044 50JJ,JK,JP 044 50FJ,FK,FP 048 50JJ,JK,JP 048 40 45 6620 6920 7120 7420 6740 7040 7240 7540 Semi-Hermetic 2...06E 2...06E 50, 100 25, 50, 75, 100 2 56, 100 18, 37, 56, 63, 81, 100 2 40.0/40.0 42.0/40.0 43.5/39.0 41.5/39.0 ⁄ -in. Tube Diameter 38 2 2 3...15.0 3...13.7 50.0 3...15.0 3...13.7 50.0 ⁄ -in. Tube Diameter 12 2 3...15.0 45.5 TXV...2 2 4...15.0 45.5 TXV...2 Propeller Type 3...30 26,000 1.0...1140 3...30 26,000 1.0...1140 Centrifugal 25 × 25 in. 14,000 20,000 900 111⁄16 15,750 20,000 900 111⁄16 (Any motor available on any unit) 10.0 15.0 215T 254T 7.5 213T 20.0 256T 88.5 89.5 91.0 91.0 91.7 91.7 93.0 93.6 13.6 13.7 13.7 13.7 3.4 4.3 4.9 5.5 438 549 626 703 900 900 900 900 2...BX60 2...5VX630 2...5VX630 2...5VX630 17.74...14.30 17.74...14.30 17.63...14.01 17.63...14.01 Centrifugal, 15 x 15 in. (Any motor available on any unit) 2...3.0 2...5.0 2...7.5 56HZ 184T 213T 81.0/88.5 87.5/89.5 88.5/91.7 6.9 6.9 6.9 3.35 4.12 5.0 13⁄16 13⁄16 13⁄16 843 1040 1264 1300 1300 1300 2...3VX670 2...3VX670 2...3VX710 12...20 4...16 12...20 4...16 6...20 6...20 LEGEND CV — Constant Volume TXV — Thermostatic Expansion Valve VAV — Variable Air Volume *Premium efficiency motors are not available on 380-v and 575-v units. 3 × × × × × × 25 20 25 20 24 20 × × × × × × 2 2 2 2 22 22 12...20 4...16 12...20 4...16 6...20 6...20 × × × × × × 25 20 25 20 24 20 × × × × × × 2 2 2 2 22 22 Table A — Physical Data — Extended Plenum Units (cont) BASE UNIT NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Base Unit With Economizer COMPRESSORS Quantity...Type Capacity Steps (%) CV Units VAV Units Number of Refrigerant Circuits REFRIGERANT Operating Charge (lb), Sys 1/Sys 2 Without Hot Gas Bypass With Hot Gas Bypass CONDENSER COILS Quantity Rows...Fins/in. Aluminum Copper (Optional) Total Face Area (sq ft) EVAPORATOR COILS Quantity Rows...Fins/in. Total Face Area (sq ft) Refrigerant Feed Device... No. per Circuit CONDENSER FANS Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm EVAPORATOR FAN Nominal Cfm Maximum Allowable Cfm Maximum Allowable Rpm Shaft Diameter at Pulley (in.) EVAPORATOR-FAN MOTOR AND DRIVE Motor Hp Motor Frame Size Efficiency at Full Load (%) High Efficiency Premium Efficiency* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Resulting Fan Rpm Maximum Allowable Rpm Belts Quantity...Model No. Center Distance Range (in.) OPTIONAL POWER EXHAUST Quantity...Motor Hp Motor Frame Size Efficiency at Full Load (%) High/Premium* Fan Pulley Pitch Diameter (in.) Motor Pulley Pitch Diameter (in.) Shaft Diameter at Pulley (in.) Resulting Fan Rpm Maximum Allowable Rpm FILTERS Standard Efficiency Throwaway (Standard) Quantity...Size (in.) Medium Efficiency (30%) Pleated (Optional) Quantity...Size (in.) High Efficiency (90%) Bag Filters with Prefilters (Optional) Quantity...Size (in.) 50FJ,FK,FP 054 50JJ,JK,JP 054 50FJ,FK,FP 064 50 50JJ,JK,JP 064 50FJ,FK,FP 074 75 60 8250 8780 8800 9330 2...06E 8550 9100 9080 9630 Semi-Hermetic 2...06E 2...06E 60, 100 20, 40, 60, 80, 100 2 50, 100 17, 33, 50, 66, 83, 100 2 43, 100 14, 28, 43, 71, 85, 100 2 59.0/44.5 62.0/44.5 4 2...17.0, 3...17.0 2...15.7, 3...15.7 72.4 2 3...17.0 61.5 TXV...2 15.0 254T 91.0 93.0 13.7 4.5 575 750 2...5VX1230 48.25...44.00 3...17.0 3...15.7 72.4 1⁄2-in. Tube Diameter 2 4...17.0 61.5 3...17.0 3...15.7 108.4 x x x x 2 2 2 2 15...20 5...16 15...20 5...16 6...20 x 24 x 22 6...24 x 24 x 22 LEGEND CV — Constant Volume TXV — Thermostatic Expansion Valve VAV — Variable Air Volume *Premium efficiency motors are not available on 380-v and 575-v units. 4 x x x x 25 20 25 20 4 2 4...17.0 61.5 TXV..2 91.0 91.7 93.6 93.6 13.7 13.7 5.1 5.5 651 703 750 750 2...5VX1230 2...5VX1230 48.25...44.00 48.50...44.25 Centrifugal, 18 x 15 in. (Any motor available on any unit) 2...7.5 213T 88.5/91.7 10.6 5.0 17⁄16 820 925 2...5.0 184T 87.5/89.5 10.6 4.5 17⁄16 740 925 25 20 25 20 70.5/64.5 73.5/64.5 Propeller Type 4...30 40,000 1.0...1140 Centrifugal 30 x 27 in. 21,000 30,000 750 111⁄16 (Any motor available on any unit) 20.0 25.0 256T 284T 17,500 25,000 750 111⁄16 x x x x 61.0/61.0 64.0/61.0 3⁄8-in. Tube Diameter 4 TXV...2 4...30 40,000 1.0...1140 15...20 5...16 15...20 5...16 8970 9500 x x x x 2 2 2 2 6...20 x 24 x 22 6...24 x 24 x 22 5...30 50,000 1.0...1140 24,500 30,000 750 111⁄16 30.0 286T 92.4 93.6 15.5 5.9 711 750 2...5VX1250 48.50...44.25 2...10.0 215T 89.5/91.7 10.6 5.6 17⁄16 920 925 15...20 5...16 15...20 5...16 x x x x 25 20 25 20 x x x x 2 2 2 2 6...20 x 24 x 22 6...24 x 24 x 22 NOTES: 1. Dimensions in [ 2. 3. 4. 5. 6. ] are in millimeters. UNIT SIZE Center of Gravity includes economizer. Unit weight does not include economizer. Unit clearances: Top — Do not restrict condenser fans Control Box End — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09) [3048] For smaller service and operating clearances, contact Carrier Application Engineering Department. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. Economizer side hoods are folded inside unit for shipping. 50FJX,FKX,FPX,FJY,FKY,FPY034 50FJX,FKX,FPX,FJY,FKY,FPY038 5 Fig. A — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY034,038 Units WEIGHT lb kg 5970 2714 6150 2770 A mm 4044 4090 ft-in. 13-31⁄4 13-5 NOTES: 1. Dimensions in [ 2. 3. 4. 5. 6. ] are in millimeters. Center of Gravity includes economizer. Unit weight does not include economizer. Unit clearances: Top — Do not restrict condenser fans Control Box End — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048]) For smaller service and operating clearances, contact Carrier Application Engineering Department. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. Economizer side hoods are folded inside unit for shipping. UNIT SIZE 50FJX,FKX,FPX,FJY,FKY,FPY044 50FJX,FKX,FPX,FJY,FKY,FPY048 6 Fig. B — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY044,048 Units WEIGHT lb 6620 6740 kg 3009 3027 A mm 4823 4851 ft.in. 15- 97⁄8 15-11 UNIT SIZE 50FJX,FJY,FKX,FKY,FPX,FPY054 50FJX,FJY,FKX,FKY,FPX,FPY064 50FJX,FJY,FKX,FKY,FPX,FPY074 WEIGHT lb kg 8250 3750 8550 3886 8970 4077 A mm 2830 2830 3694 ft-in. 9-33⁄4 9-33⁄4 12-13⁄4 B mm 6427 6427 5563 C ft-in. 21-1 21-1 18-3 mm 6045 6045 6477 ft-in. 19-10 19-10 21- 3 D mm 1163 1163 1163 ft-in. 3-913⁄16 3-913⁄16 3-913⁄16 E mm 11 140 11 140 12 049 F ft-in. 36-69⁄16 36-69⁄16 39-63⁄8 mm 11 524 11 524 12 433 ft-in. 37-911⁄16 37-911⁄16 40-91⁄2 NOTES: 1. Dimensions in [ 2. ] are in millimeters. Center of Gravity includes economizer. Unit weight does not include economizer. 3. Unit clearances: Top — Do not restrict condenser fans Control Box End — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048]) For smaller service and operating clearances, contact Carrier Application Engineering Department. 4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. 5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. 6. Economizer side hoods are folded inside unit for shipping. 7 Fig. C — Base Unit Dimensions — 50FJX,FJY,FKX,FKY,FPX,FPY054-074 Units NOTES: 1. Dimensions in [ 2. 3. 4. 5. 6. 7. 8. 9. ] are in millimeters. Center of gravity includes economizer. Unit weight does not include economizer or heating coil. Unit Clearances Top — Do not restrict condenser fans Control Box End — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048]) For smaller service and operational clearances, contact Carrier Application Engineering Department. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. Auxiliary heating coil dimensions (maximum): Length (header included), 78-01⁄49 [2140] Width, 08-95⁄89 [244] Height, 48-515⁄169 [1370] Auxiliary heating coil field supplied and installed. Economizer side hoods are folded inside unit for shipping. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut. AUXILIARY COIL PIPE CHASES (See Note 9) WEIGHT A UNIT SIZE lb kg mm ft-in. 50JJX,JKX,JPX,JJY,JKY,JPY034 6470 2934 4618 14-515⁄16 50JJX,JKX,JPX,JJY,JKY,JPY038 6650 2991 4474 14-81⁄8 8 Fig. D — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY034,038 Units NOTES: 1. Dimensions in [ 2. 3. 4. 5. 6. 7. 8. 9. ] are in millimeters. Center of gravity includes economizer. Unit weight does not include economizer or heating coil. Unit Clearances Top — Do not restrict condenser fans Control Box End — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048]) For smaller service and operational clearances, contact Carrier Application Engineering Department. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. Auxiliary heating coil dimensions (maximum): Length — (header included), 78-01⁄49 [2140] Width, 08-95⁄89 [244] Height, 48-71⁄29 [1410] Auxiliary heating coil field supplied and installed. Economizer side hoods are folded inside unit for shipping. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut. AUXILIARY COIL PIPE CHASES (See Note 9) 9 Fig. E — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY044,048 Units WEIGHT A UNIT SIZE lb kg mm ft-in. 50JJX,JKX,JPX,JJY,JKY,JPY044 7120 3229 5211 17-11⁄8 50JJX,JKX,JPX,JJY,JKY,JPY048 7240 3247 5239 17-21⁄4 UNIT SIZE 50JJX,JKX,JPX,JJY,JKY,JPY054 50JJX,JKX,JPX,JJY,JKY,JPY064 WEIGHT lb kg 8800 3990 9100 4127 A mm 2959 2959 B C D E F ft-in. 9-81⁄2 mm 6940 ft-in. 22-93⁄4 mm 6393 ft-in. 20-1111⁄16 mm 1163 ft-in. 3-913⁄16 mm 11 780 ft-in. 38-713⁄16 mm 12 164 ft-in. 39-107⁄8 9-81⁄2 6940 22-93⁄4 6393 20-1111⁄16 1163 3-913⁄16 11 780 38-713⁄16 12 164 39-107⁄8 AUXILIARY COIL PIPE CHASES (See Note 9) NOTES: 1. Dimensions in [ ] are in millimeters. 2. Center of gravity includes economizer. Does not include heating coil. Unit weight does not include economizer or heating coil. 3. Unit Clearances Top — Do not restrict condenser fans Control box end — 68-09 [1829] Sides — 68-09 [1829] Economizer End — 68-09 [1829] (except power exhaust units 108-09 [3048]) For smaller service and operational clearances, contact Carrier Application Engineering Department. 4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb. 5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes. 6. Auxiliary heating coil dimensions (maximum): Length (header included), 78-01⁄49 [2140] Width, 08-95⁄89 [244] Height, 58-69 [1676] 7. Auxiliary heating coil field supplied and installed. 8. Economizer side hoods are folded inside unit for shipping. 9. Pipe chases for auxiliary coil are not provided with unit. Chases must be fieldcut. 10 Fig. F — Base Unit Dimensions — 50JJX,JJY,JKX,JKY,JPX,JPY054,064 Units DIMENSIONS* (degrees and inches) A 11 Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. G — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY034,038 in. .75 12 DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. H — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY044,048 in. .75 13 DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. I — Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY054-074 in. .75 DIMENSIONS* (degrees and inches) A 14 Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. NOTES: 1. Roof curb is shipped disassembled. 2. Roof curb: 14 gage (VA03-56) steel. 3. Dimensions in [ ] are millimeters. 4. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut. Fig. J — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY034,038 in. .75 NOTES: 1. Roof curb is shipped disassembled. 2. Roof curb: 14 ga. [VA03-56] stl. 3. Dimensions in [ ] are millimeters. 4. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut. 15 DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. K — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY044,048 in. .75 NOTES: 1. Roof curb is shipped disassembled. 2. Roof curb: 14 ga. [VA03-56] stl. 3. Dimensions in [ ] are millimeters. 4. Suggested hole location for field wiring through roof curb (holes to be supplied by field). 5. Pipe chases for auxiliary coil are not provided with unit. Chases must be field-cut. 16 DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. L — Roof Curb — 50JJX,JJY,JKX,JKY,JPX,JPY054,064 in. .75 NOTES: 1. Roof curb is shipped disassembled. 2. Roof curb: 14 gage (VA03-56) steel. 3. Dimensions in [ ] are millimeters. DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 17 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. M — Condenser Section Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY,JJX,JJY,JKX,JKY,JPX,JPY, Sizes 054 and 064 in. .75 NOTES: 1. Roof curb is shipped disassembled. 2. Dimensions in [ ] are millimeters. 3. Roof curb: 14 gage (VA03-56) steel. Roof curb pans, 16 gage (VA03-56) steel. 18 DIMENSIONS* (degrees and inches) A Deg 1.0 B in. 2.0 Deg .50 UNIT LEVELING TOLERANCES *From edge of unit to horizontal. Fig. N — Condenser Section Roof Curb — 50FJX,FJY,FKX,FKY,FPX,FPY, Size 074 in. .75 NOTES: 1. Sizes 034-048: Rig with 4 cables and spread with two 95 in. (2413 mm) and 2 8A 1 A8 long spreader bars. Sizes 054-074: Rig with 4 cables and spread with two 95 in. (2413 mm) and 2 8A 1 A8 long spreader bars. 2. Center of gravity includes economizer. 1. All panels must be in place when rigging. 2. Unit is not designed for handling by forklift truck. RIGGING WEIGHTS AND DIMENSIONS MODEL NO. (EXTENDED CHASSIS UNITS) 50FJX,FJY,FKX,FKY,FPX,FPY034 50FJX,FJY,FKX,FKY,FPX,FPY038 50FJX,FJY,FKX,FKY,FPX,FPY044 50FJX,FJY,FKX,FKY,FPX,FPY048 50FJX,FJY,FKX,FKY,FPX,FPY054 50FJX,FJY,FKX,FKY,FPX,FPY064 50FJX,FJY,FKX,FKY,FPX,FPY074 50JJX,JJY,JKX,JKY,JPX,JPY034 50JJX,JJY,JKX,JKY,JPX,JPY038 50JJX,JJY,JKX,JKY,JPX,JPY044 50JJX,JJY,JKX,JKY,JPX,JPY048 50JJX,JJY,JKX,JKY,JPX,JPY054 50JJX,JJY,JKX,JKY,JPX,JPY064 WEIGHT Lb Kg 5970 2714 6150 2790 6620 3009 6740 3057 8250 3750 8550 3886 8970 4077 6470 2934 6650 3016 7120 3229 7240 3284 8800 3990 9100 4127 A in. 83.23 83.23 92.64 92.64 126.50 126.50 109.50 95.83 95.83 105.24 105.24 136.61 136.61 B mm 2114 2114 2353 2353 3213 3213 2782 2434 2434 2673 2673 3470 3470 Fig. O — Rigging Label 19 in. 159.21 161.02 189.88 190.98 238 238 255 173.94 176.14 205.16 206.26 251.70 251.70 mm 4044 4090 4823 4851 6045 6045 6477 4418 4474 5211 5239 6393 6393 ECONOMIZER Lb Kg 300 136 300 136 300 136 300 136 530 240.9 530 240.9 530 240.9 300 136 300 136 300 136 300 136 530 240.9 530 240.9 3 4 2 1 B A UNIT CORNER WEIGHTS (lbs) UNIT 50FJX,FJY 50FKX,FKY 50FPX,FPY 50JJX,JJY 50JKX,JKY 50JPX,JPY 034 038 044 048 054 064 074 034 038 044 048 054 064 1 2 3 4 Total 1864 1922 2070 2115 2381 2461 2551 1989 2043 2195 2240 2518 2598 1268 1287 1387 1412 2005 2074 2194 1393 1413 1512 1537 2143 2212 1271 1290 1389 1414 2009 2078 2199 1396 1417 1514 1539 2146 2215 1867 1951 2074 2099 2385 2467 2556 1992 2077 2199 2224 2523 2605 6270 6450 6920 7040 8780 9080 9500 6770 6950 7420 7540 9330 9630 CENTER OF GRAVITY A B ft-in. ft-in. 13- 31⁄4 3-913⁄16 13- 5 3-913⁄16 15- 97⁄8 3-913⁄16 15-11 3-913⁄16 19-10 3-913⁄16 19-10 3-913⁄16 21- 3 3-913⁄16 3-913⁄16 14- 515⁄16 14- 81⁄8 3-913⁄16 17- 11⁄8 3-913⁄16 17- 21⁄4 3-913⁄16 20-1111⁄16 3-913⁄16 20-1111⁄16 3-913⁄16 NOTE: Weights include economizer. Fig. P — Unit Center of Gravity and Corner Weights Table B — Supply Fan Drive Data SHAFT DIA. Sizes 034-048 7.5 13⁄8 10 13⁄8 15 15⁄8 20 15⁄8 Sizes 054-074 15 15⁄8 20 15⁄8 25 17⁄8 30 17⁄8 HP SPEED (rpm) MOTOR SHEAVE MOTOR PITCH DIA. WHEEL SHEAVE WHEEL PITCH DIA. QUANTITY ...BELT 438 549 626 703 2BK36 2B5V42 2B5V48 2B5V54 3.4 4.3 4.9 5.5 2B5V136 2B5V136 2B5V136 2B5V136 13.6 13.7 13.7 13.7 2...BX60 2...5VX630 2...5VX630 2...5VX630 575 651 703 711 2B5V44 2B5V50 2B5V54 2B5V62 4.5 5.1 5.5 5.9 2B5V136 2B5V136 2B5V136 2B5V154 13.7 13.7 13.7 15.5 2...5VX1230 2...5VX1230 2...5VX1230 2...5VX1250 Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 PC 111 Catalog No. 565-008 Printed in U.S.A. Form 50F,J-1SIS Pg 20 1-99 Replaces: New Tab 1b