Series M, CL, CK Contactors for connection of power transformers In this application it is essential to ascertain the no-load inrush current of the transformer Iμ, (magnetisation current) which in the majority of cases determines the size of the contactor. Motorstarters Two cases are illustrated in the table: – No-loap inrush current up to 20 times the rated transformer current – No-loap inrush current up to 40 times the rated transformer current. A B C D E F G H I X D.62 Selection table Iμ Iμ = 20 Ie = 40 Contactor Ie 230V 240V kVA 380V 400V kVA 2 2.75 4 5.75 5.75 7.25 9 10 12 15 20 25 30 35 40 45 50 80 100 127 160 3.5 5 7 10 10 12.5 15.5 17 21 25 35 40 50 55 60 75 85 150 170 215 280 230V 240V kVA 1 1.37 2 2.85 2.85 3.65 4.50 5 6 7.5 10 12.5 15 17 20 22 25 40 50 64 80 380V 400V kVA 1.75 2.5 3.5 5 5 6.25 7.75 8.5 10.5 12.5 16 20 25 27 30 35 42.5 75 85 107 140 CL00A CL01A CL02A CL25A CL03A CL04A CL45A CL05A CL06A CL07A CL08A CL09A CL10A CK75C CK08C CK85B CK09B CK10C CK11C CK12B CK13B The contactor should not cut out the short-circuit current; if the protective devices used are fuses, this condition will be intrinsically complied with. In the case however of devices with tripping contacts the general line circuit breaker will be driven rather than the contactor coil.