SION Vacuum Circuit-Breakers Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 · 2008 Answers for energy. R-HG11-172.tif SION Vacuum Circuit-Breakers 2 Siemens HG 11.02 · 2008 SION Vacuum Circuit-Breakers Contents Contents Page Description 5 General 6 Construction and mode of operation, standards 7 Ambient conditions, current carrying capacity and dielectric strength 10 Medium-Voltage Equipment Catalog HG 11.02 · 2008 Product range overview and basic equipment 11 Invalid: PDF version of Catalog HG 11.02 · 2006 Equipment Selection SION Vacuum Circuit-Breakers 1 13 Ordering data and configuration example 2 14 Selection of basic types, standard circuit-breakers 15 Secondary equipment for standard circuit-breakers 23 Selection of basic types, slide-in modules 28 Secondary equipment for slide-in modules 32 Accessories and spare parts 37 Technical Data 41 3 Electrical data, dimensions and weights: Voltage levels 7.2 kV, 12 kV, 17.5 kV 42 Voltage level 24 kV 56 Operating times, short-circuit protection of motors, consumption data of releases 59 Circuit diagrams 60 Annex 61 Inquiry form 62 Configuration instructions 63 Configuration aid 4 Foldout page Siemens HG 11.02 · 2008 3 R-HG11-173.tif SION Vacuum Circuit-Breakers 4 Siemens HG 11.02 · 2008 SION Vacuum Circuit-Breakers Description Contents Contents Page Description 5 General 6 1 R-HG11-174.tif Construction and mode of operation: Industrial application: Refinery Switching medium 7 Pole assemblies 7 Operating mechanism 7 Trip-free mechanism 7 Releases 8 Closing / Circuit-breaker tripping signal 8 Interlocking 8 Low-voltage interface 8 Slide-in module 9 Standards 9 Maintenance-free design 9 Ambient conditions 10 Current carrying capacity 10 Dielectric strength 10 Product range overview 11 Basic equipment 11 Siemens HG 11.02 · 2008 5 SION Vacuum Circuit-Breakers Description General SION vacuum circuit-breaker from 7.2 to 24 kV – The Innovative generators, capacitors, filter circuits, motors and reactors. The comprehensive installation accessories enable easy integration in the panel and form – maximally equipped as a slide-in module – almost the complete circuit-breaker compartment. SION standard circuit-breaker – the Variable SION slide-in module – the Complete Our comprehensive range of standard circuit-breakers offers a wide selection for pole-center distances and widths across flats as well as various installation accessory packages for voltage levels from 7.2 to 24 kV. The drawout element, contact arms, contact systems and bushings enable easy integration in all customary medium-voltage switchgear types. Identical dimensions and connection dimensions across several voltage levels reduce planning costs and the diversity of panel versions. High reliability and availability are just as much a matter of course as 10,000 maintenancefree operating cycles. 6 Siemens HG 11.02 · 2008 R-HG11-168.eps R-HG11-167.eps 1 SION vacuum circuit-breakers control all switching duties in medium-voltage distribution systems and are suitable for installation in all customary air-insulated medium-voltage switchgear types. They are applicable for operation of e.g. overhead lines, cables, transformers, The slide-in module contains all components required for the circuit-breaker compartment of a panel. It consists of the circuit-breaker on a drawout element with contact arms, fitted in a cartridge with side and rear walls. The module is equipped with bushings, fixed contacts, shutters and the shutter mechanism. The surfaces of the side and rear walls form the tested connection compartment. SION Vacuum Circuit-Breakers Description Construction and mode of operation Switching medium The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Pole assemblies 1 R-HG11-170.eps The pole assemblies consist of the vacuum interrupters and the pole shells. The vacuum interrupters are air-insulated and freely accessible. The pole assemblies are fixed on the mounting plate of the operating mechanism and supported by means of the pole shell. The vacuum interrupter (3) is mounted rigidly to the upper interrupter support. The lower part of the interrupter is guided in the lower interrupter support, allowing axial movement. The pole shell (4) absorbs the external forces resulting from switching operations and the contact pressure. Vacuum circuit-breaker 3AE12 17.5 kV / 25 kA / 1250 A 1 HG11-2500 eps Operating mechanism The whole operating mechanism is mounted on its mounting plate, including the motor, releases, indicators and actuating devices. Stored-energy operating mechanism 2 3 1 Separating shell to the operating mechanism 4 2 Upper connection 3 Interrupter 5 The operating mechanism is a stored-energy spring mechanism. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. The closing spring can be charged either electrically or manually and latches automatically in when charging is complete. The closing spring acts as a stored-energy mechanism. 4 Pole shell 5 Lower connection 6 6 Bell-type insulator Pole structure To close the breaker, the closing spring can be unlatched either mechanically by means of the local “ON” pushbutton or electrically by remote control. The closing spring charges the contact-pressure / opening springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor. 1 1 Cover of low-voltage interface 2 Central control board HG11-2501 eps The breaker is now capable of performing the OPEN – CLOSE – OPEN operating sequence that is required for an unsuccessful auto-reclosing operation on the system side. All storedenergy mechanisms perform the switching duties of synchronizing and rapid load transfer as well as auto-reclosing. 2 Front view Trip-free mechanism The motors for charging the closing spring operate in short-time duty. Therefore the voltage and power consumption might differ from the data of the rating plate. 1 2 3 1 Auxiliary switch 4 3 Terminal strip 5 4 Motor 6 HG11-2502 eps SION vacuum circuit-breakers have a trip-free mechanism according to IEC 62271-100. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible according to IEC 62271-100. 7 2 1st release 5 Closing solenoid 6 Closing spring 7 Gear Operating mechanism without cover Siemens HG 11.02 · 2008 7 SION Vacuum Circuit-Breakers Description Construction and mode of operation Releases 1 A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The releases are designed for short-time duty up to 1 minute and are reset internally. The various types of releases available are described in detail below: • The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. • Shunt releases are used for automatic tripping of vacuum circuit-breakers by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage) but, in special cases, may also be connected to a voltage transformer for manual operation. • Current-transformer operated releases comprise a stored-energy mechanism, an unlatching mechanism, and an electromagnetic system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrenttime protection) acting on the current-transformer operated release. • Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the vacuum circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the stored-energy mechanism. The maximum equipment are 2 freely selected releases. For release combinations, refer to page 23 or page 32. For consumption data, refer to page 59. Closing / Circuit-breaker tripping signal In the standard version, the vacuum circuit-breakers can be remote-closed electrically. In addition, they can be mechanically closed locally by direct unlatching of the closing spring. If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuitbreaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= “pumping”) is prevented. The charging status of the closing spring in the vacuum circuit-breaker can be interrogated electrically by means of the position switch. 8 Siemens HG 11.02 · 2008 During electrical opening, the NO contact S6 makes brief contact. This is often used to operate a hazard warning system which should respond to automatic tripping of the circuit-breaker. In case of local control, the NO contact S6 does not close. For the corresponding circuit diagrams, refer to page 60. Interlocking Mechanical interlocking At the interface of the mechanical interlocking of the vacuum circuit-breaker, sensors on the switchgear side can check the switch position and prevent the associated disconnector from being closed while the vacuum circuitbreaker is closed. The system also prevents the vacuum circuit-breaker from being closed while the associated disconnector is in a faulty position. Vacuum circuit-breakers mounted on drawout elements are mechanically interlocked, with the result that the handle for racking the drawout element can only be inserted in the “OPEN” position. The lock of the drawout element can only be released in the disconnected position by operating the pushing handles. If the vacuum circuit-breaker on the drawout element is in an intermediate position (neither in the service nor in the disconnected position), operation is not possible due to the mechanical interlocking. Electrical interlocking The auxiliary and signaling contacts which show the switch position of the vacuum circuit-breaker or the position of the drawout element can be integrated in the switchgear interlocking concept in order to exclude impermissible switching sequences. Low-voltage interface The separate cover enables easy access to the low-voltage interface. All possible customer-side control and signaling connections are concentrated here. SION Vacuum Circuit-Breakers Description Construction and mode of operation, standards Slide-in module Besides the circuit-breaker installation equipment available for standard circuit-breakers by means of the packages for the drawout element, contact arms, fixed contacts and bushings, it is also possible to supply a complete slide-in module. 1 The vacuum circuit-breaker on the drawout element is racked into the cartridge with the associated handle by the rotary movement of the spindle. The shutter mechanism is controlled by lateral gates, and the shutters are opened for contacting. Signals for the service and disconnected positions are transmitted to the module connector at the low-voltage interface of the vacuum circuit-breaker via the position switches of the drawout element. R-HG11-171.eps The slide-in module contains all necessary components for the circuit-breaker compartment of a panel. It consists of the circuit-breaker on a drawout element with contact arms, mounted in a cartridge with side and rear walls, equipped with bushings, fixed contacts, shutters and shutter mechanism. The surfaces of the side and rear walls form the tested connection compartment. Slide-in module 1 Contact system 2 Fixed contact 6 Contact arm 3 Shutter 7 Low-voltage interface 4 Bushing 8 Vacuum circuit-breaker 5 Cartridge 9 Drawout element Standards The vacuum circuit-breakers conform to the following standards: • IEC 62271-1 (former IEC 60694) • IEC 62271-100 (former IEC 60056) All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The slide-in modules have been tested according to • IEC 62271-200 regarding – Dielectric strength – Temperature rise – Switching capacity. Maintenance-free design SION vacuum circuit-breakers are maintenance-free: • Under normal ambient conditions according to IEC 62271-1 (former IEC 60694) • Up to 10,000 operating cycles, – no regreasing – no readjusting, the ratings are independent – within their tolerances – of the switching rate or standing times without switching. Siemens HG 11.02 · 2008 9 SION Vacuum Circuit-Breakers Description Ambient conditions, current carrying capacity and dielectric strength Ambient conditions The vacuum circuit-breakers are designed for the normal operating conditions defined in IEC 62271-100. Condensation can occasionally occur under the ambient conditions shown opposite. 1 40°C max. 95% per day max. 90% per month HG11-2515_en eps -5°C SION vacuum circuit-breakers are suitable for use in the following climatic classes according to IEC 60721, Part 3-3: Climatic ambient conditions: Class 3K41) Biological ambient conditions: Class 3B1 Mechanical ambient conditions: Class 3M2 Chemically-active substances: Class 3C22) Mechanically-active substances: Class 3S23) 1) Low temperature limit: –5 °C 2) Without icing and wind-driven precipitation 3) Restriction: Clean insulation parts 3400 A 3000 5 2600 HG11-2516a_en eps Rated normal current Current carrying capacity 4 2200 Characteristics curve 1 = Rated normal current 800 A Characteristics curve 2 = Rated normal current 1250 A Characteristics curve 3 = Rated normal current 2000 A Characteristics curve 4 = Rated normal current 2500 A Characteristics curve 5 = Rated normal current 3150 A 1400 2 1000 600 1 10 20 30 40 50 60 °C 70 Ambient air temperature Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration powerfrequency withstand voltage specified in the chapter “Technical Data” apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. 1.50 1.40 1.30 The characteristic shown applies to both rated withstand voltages. 1.20 To select the devices, the following applies: HG11-2517c_en eps Altitude correction factor For enclosed switchgear the data of the switchgear manufacturer applies. At ambient air temperatures below + 40 °C, higher normal currents can be carried (see diagram): 3 1800 The rated normal currents specified in the diagram have been defined according to IEC 62271-100 for an ambient air temperature of + 40 °C and apply to open switchgear. 1.10 1.00 1000 1500 2000 2500 3000 3500 m 4000 Site altitude U W U0 x Ka U Rated withstand voltage under reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under reference atmosphere is required as a minimum: 90 kV W 75 kV x 1.2 10 Siemens HG 11.02 · 2008 SION Vacuum Circuit-Breakers Description Product range overview and basic equipment Type kV kA 3AE10 7.2 16 20 25 25 31.5 31.5 40 40 16 20 25 25 31.5 31.5 40 40 12.5 16 25 25 31.5 31.5 40 40 12.5 16 20 20 25 25 3AE11 3AE12 3AE13 12 17.5 24 Pole-center distance (in mm) Rated normal current Rated shortcircuit breaking current Rated voltage Product range overview 150 160 210 275 Width across flats (in mm) A 205 275 310 205 275 310 205 275 310 310 800/1250 800/1250 800/1250 2000 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000/2500 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000/2500 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250/2000 800/1250 2000/2500 800/1250 2000/2500 n n n no no no no no no n n n n n n n n n n n n no no no n no no n n n n no n n n no no no no no no n n n n n n n n n n n n no no no n no no n n n n no n n n no no no no no no n n n n n n n n n n n n no no no n no no n n n n no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no n Standard circuit-breaker (fixed-mounted/drawout version with installation accessories) o Slide-in module Basic equipment Features Minimum equipment Alternative equipment Remarks Operating mechanism Closing None None Also for manual operation – 1st release Electrical operating mechanism Closing solenoid and mechanical manual closing Shunt release – 2nd release Without Varistor circuit Installed with W 60 V DC Undervoltage release, c.t.-operated release Shunt release, undervoltage release, c.t.-operated release None Auxiliary switch Plug connection 6 NO + 6 NC 27-pole terminal strip Anti-pumping Circuit-breaker tripping signal Operations counter Position switches Mechanical interlocking Installation accessories Available Without Available 1 NO + 1 NC Available for slide-in module Fixed-mounted 12 NO + 12 NC 24-pole plug, 64-pole plug None Possible None None Mechanical interlocking for circuit-breaker With drawout element, contact arms, contact system, with fixed contacts and bushings, complete slide-in module – For limiting switching overvoltages – 12 NO + 12 NC not available with 24-pole plug – – – – Required for slide-in module – Siemens HG 11.02 · 2008 11 1 R-HG11-175.tif SION Vacuum Circuit-Breakers 12 Siemens HG 11.02 · 2008 SION Vacuum Circuit-Breakers Equipment Selection Contents Contents Page Equipment Selection Ordering data and configuration example 13 14 Selection of basic types, standard circuit-breakers: Voltage level 7.2 kV 15 Voltage level 12 kV 17 Voltage level 17.5 kV 20 Voltage level 24 kV 22 Secondary equipment for standard circuit-breakers 23 Additional equipment for standard circuit-breakers 27 2 R-HG11-176.eps Selection of basic types, slide-in modules: 28 Voltage level 12 kV 29 Voltage level 17.5 kV 30 Voltage level 24 kV 31 Secondary equipment for slide-in modules 32 Additional equipment for slide-in modules 36 Accessories and spare parts 37 R-HG11-168.eps Standard circuit-breaker Voltage level 7.2 kV Slide-in module Siemens HG 11.02 · 2008 13 SION Vacuum Circuit-Breakers Equipment Selection Ordering data and configuration example Order number structure Special versions («) The SION vacuum circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. In case of special versions, “-Z” is added to the order number and a descriptive order code follows. If several special versions are required, the suffix “-Z” is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department in the Switchgear Factory Berlin. Order codes Individual equipment versions, marked with 9 or Z in the 9th to 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence. 2 a: alphabetical Position: Order No.: 1st position n: numerical 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 3 A E n n n n – n a a n n n – a a n Order codes – « n n n Primary part Superior group Switching devices 2nd position Main group Circuit-breaker 3rd position Subgroup Circuit-breaker type series 4th to 8th position Basic equipment Design and ratings primary part 9th to 16th position 1 Secondary part Secondary equipment Operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Group of 3 after the Order No. Format: a n a Special versions («) Initiated with “-Z” Group of 3 after the Order No. Format: a n n Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find a configuration example on each page of the chapter “Equipment Selection”. For the selection of the secondary part, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (pages 27 and 36) a completely configured circuit-breaker results as an example. Example for Order No.: Order codes: 14 Siemens HG 11.02 · 2008 3 A On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your circuit-breaker. E 1 0 8 3 – 2 n n n n – n n n n SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers kV kV kV kA kA mm mm A 60 20 16 40/42 210 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 160 150 60 20 20 50/52 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 n n n See page 27 8 See page 26 – See page 26 7 See page 25 6 See page 25 5 Ir 7.2 7.2 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 7.2 kV 210 160 150 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 20 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: 3 A E 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 0 8 3 – 2 0 8 3 – 2 n n n n – n n n n 2 Order codes: Siemens HG 11.02 · 2008 15 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers kV kV kV kA kA mm mm A 60 20 25 63/65 210 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 800 1250 2000 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 160 150 7.2 60 20 31.5 80/82 210 160 150 7.2 60 20 40 100/104 210 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 40 kA Rated normal current Ir = 2000 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes: 16 Siemens HG 11.02 · 2008 9 10 11 12 – 13 14 15 16 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 3 A E 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 4 6 7 0 8 6 – 4 0 8 6 – 4 n n n n – n n n n Order codes See page 27 8 See page 26 – See page 26 7 See page 25 6 See page 25 5 Ir 7.2 2 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 7.2 kV n n n SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers 8 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 n n n See page 27 – See page 26 7 See page 26 6 See page 25 5 See page 25 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 12 kV Ir kV kV kV kA kA mm 12 75 28 16 40/42 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 12 75 28 20 50/52 210 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 800 A Pole-center distance = 160 mm, width across flats = 275 mm Rated short-duration power-frequency withstand voltage Ud = 42 kV Example for Order No.: Order codes: A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A 3 A E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 E E 3 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 – Z E 1 3 – Z E 1 3 1 n n n n – n n n n – Z 1 1 3 A 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 1 1 4 4 2 2 – – 1 Siemens HG 11.02 · 2008 17 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers 2 kV kV kV kA kA mm 75 28 25 63/65 210 mm 310 310 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 12 75 28 31.5 80/82 210 310 310 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 n n n See page 27 9 See page 26 8 See page 26 – See page 25 7 See page 25 6 A 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 31.5 kA Rated normal current Ir = 1250 A Pole-center distance = 150 mm, width across flats = 205 mm A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Order codes: 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 – 3 A Example for Order No.: Siemens HG 11.02 · 2008 5 Ir 12 18 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 12 kV 3 A E E 1 1 1 0 5 – 2 1 0 5 – 2 n n n n – n n n n Z E 1 3 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers kV kV kV kA kA mm 75 28 40 100/104 210 mm 310 310 310 310 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV 12 75 28 40 100/104 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 E E E E 1 1 1 1 n n n See page 27 8 See page 26 – See page 26 7 See page 25 6 See page 25 5 Ir 12 Circuit-breaker for installation in NXAIR 12 75 28 31.5 80/82 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 12 kV 210 160 210 275 275 275 275 275 275 275 A 1250 2000 2500 3150 1250 2500 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 A A A A A A A A A A A E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 5 5 5 5 5 5 5 8 8 8 8 7 7 4 7 7 7 7 6 6 6 6 5 5 5 6 6 6 6 – – – – – – – – – – – 2 4 6 7 3 A Example for Order No.: 3 A E E Z E 1 3 – Z E 1 3 2 6 2 2 4 6 7 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 40 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm – 1 1 1 8 6 – 2 1 8 6 – 2 n n n n – n n n n Order codes: Siemens HG 11.02 · 2008 19 2 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers kV kV kV kA kA mm mm A 95 38 12.5 31/33 210 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 160 150 17.5 95 38 16 40/42 210 160 150 17.5 95 38 25 63/65 210 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 275 mm Example for Order No.: Order codes: 20 Siemens HG 11.02 · 2008 9 10 11 12 – 13 14 15 16 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 3 A E 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 2 7 2 – 2 2 7 2 – 2 n n n n – n n n n Order codes See page 27 8 See page 26 – See page 26 7 See page 25 6 See page 25 5 Ir 17.5 2 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 17.5 kV n n n SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers kV kV kV kA kA mm mm A 95 38 25 63/65 210 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 160 150 95 38 31.5 80/82 210 160 150 17.5 95 38 40 100/104 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 n n n See page 27 8 See page 26 – See page 26 7 See page 25 6 See page 25 5 Ir 17.5 17.5 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 17.5 kV 210 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 31.5 kA Rated normal current Ir = 2500 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: 3 A E 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 4 6 7 2 8 5 – 6 2 8 5 – 6 n n n n – n n n n 2 Order codes: Siemens HG 11.02 · 2008 21 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, standard circuit-breakers 2 kV kV kV kA kA mm 125 50 12.5 31/33 210 mm 310 310 24 125 50 16 40/42 210 310 310 310 275 310 310 310 24 125 50 20 50/52 210 310 310 310 310 275 310 310 310 310 24 125 50 25 63/65 210 310 310 310 310 275 310 310 310 310 Special versions (available for all 24 kV standard circuit-breakers) Ud = 55 kV Ud = 65 kV 320 320 320 275 320 Special versions (available for all 24 kV standard circuit-breakers) Ud = 55 kV Ud = 65 kV 210 1250 2000 2500 2500 10 11 12 – 13 14 15 16 Order codes E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 n n n See page 27 9 See page 26 8 See page 26 – See page 25 7 See page 25 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A 3 A Example for Order No.: Order codes: Siemens HG 11.02 · 2008 6 A 800 1250 800 1250 2000 800 1250 2000 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 24 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 125 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 2000 A Pole-center distance = 275 mm, width across flats = 310 mm 22 5 Ir 24 Circuit-breaker for installation in NXAIR 24 125 50 25 63/65 4 1 n n n – n n n n n – n n n n – « See page 24 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 24 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 23 Position: Order No.: 50/60 Hz See page 23 24 kV 3 A E E E E E E 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 7 7 7 7 2 2 2 2 2 5 5 5 2 2 2 2 5 5 5 5 2 2 2 2 5 5 5 5 2 2 2 5 1 1 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 4 1 2 4 1 2 4 6 1 2 4 6 1 2 4 6 1 2 4 6 Z Z E E 5 6 5 5 – – Z Z E E 5 6 5 5 2 4 6 6 1 1 – – 3 5 4 – 4 3 5 4 – 4 n n n n – n n n n SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for standard circuit-breakers n n n n n n 7 – 8 10 11 12 – See page 24 13 14 15 16 Order codes n n n A B C G H F E N P Q J L M n n n n n n n n n 9 See page 27 6 See page 26 5 See page 26 4 1 n n n – n n n n n – n n n n – « See page 25 3 E See page 25 1 C.t.-operated release with tripping pulse W 0.1 Ws (20 O) C.t.-operated release 1.0 A C.t.-operated release 0.5 A 2 3 A See page 24 Position: Order No.: Undervoltage release 2nd shunt release 1st shunt release 9th position Release combination n n n n n n 2 10th position Operating voltage of the closing solenoid Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC Special voltages B C D E F H J K M N P Q R S U V W 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 1st shunt release Operating voltage of the closing solenoid 48 V DC 3 A E 1 3 5 4 – 4 A C Example for Order No.: 3 A E 1 3 5 4 – 4 A C n n – n n n n Order codes: Siemens HG 11.02 · 2008 23 SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for standard circuit-breakers 4 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – Special voltages C.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 2 13 14 15 16 0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) Order codes n n n See page 27 3 E See page 26 1 See page 26 2 3 A See page 25 Standard voltages Position: Order No.: See page 25 11th position Operating voltage of the 1st release With order code With order code With order code With order code With order code With order code With order code With order code With order code L L L L L L L L L 1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M With order code With order code With order code With order code With order code With order code With order code With order code With order code M M M M M M M M M 1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M L 1 12th position Operating voltage of the 2nd release Standard voltages Special voltages Without, or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Operating voltage of the 1st release 32 V DC Without 2nd release 3 A 5 4 – 4 A C 9 0 Order codes: Siemens HG 11.02 · 2008 1 3 Example for Order No.: 24 E 3 A E L B 1 1 3 5 4 – 4 A C 9 0 – n n n n B SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for standard circuit-breakers 1 3 4 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 See page 26 2 3 A Options Without circuit-breaker installation accessories, fixed-mounted circuit-breaker With drawout element With drawout element, contact arms and contact system With drawout element, contact arms and contact system, fixed contacts and bushings Order codes n n n See page 27 Position: Order No.: See page 26 13th position Circuit-breaker installation accessories 0 1 2 3 14th position Operating voltage of the motor operating mechanism Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC Special voltages 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 2 B C D E F H J K M N P Q R S U V W 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Fixed-mounted circuit-breaker Operating voltage of the motor operating mechanism 230 V AC Example for Order No.: Order codes: 3 A E 1 3 5 4 – 4 A C 9 0 – 0 K 3 A E L B 1 1 3 5 4 – 4 A C 9 0 – 0 K n n Siemens HG 11.02 · 2008 25 SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for standard circuit-breakers 15th position Interlocking, auxiliary switch, circuit-breaker tripping signal and control cable connection n 1 3 4 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 n n n n n n n n n n n n n n n n n See page 27 n n n n n n n B D F H K M R Q A C E G J L N P n n n n n n n Special versions Auxiliary switch contacts 12 NO + 12 NC and pins of the 64-pole plug connector gold-plated – Z A 2 1 Key-interlocking (RONIS-lock at the vacuum circuit-breaker) Only for circuit-breakers without mechanical interlocking – Z J 6 0 16th position AC frequency of operating voltages Languages of operating instructions and rating plate n n Other languages on request 50 Hz and DC n n n n n n n n n n n 60 Hz and DC n n n 60 Hz n n 50 Hz n n DC Frequency selection Spanish French English German Language selection n n n n n n n n 0 1 2 3 4 5 6 7 Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in German Example for Order No.: Order codes: 26 Order codes 64-pole plug 24-pole plug n n n n n n n n n n n n n n n 27-pole terminal strip Circuit-breaker tripping signal 6 NO + 6 NC Mechanical interlocking n n n n 2 2 3 A Control cable connection 12 NO + 12 NC Auxiliary switch Position: Order No.: Siemens HG 11.02 · 2008 3 A E L B 1 1 3 5 4 – 4 A C 9 0 – 0 K N 0 4 – 4 A C 9 0 – 0 K N 0 SION Vacuum Circuit-Breakers Equipment Selection Additional equipment for standard circuit-breakers Additional equipment Position: Order No.: 2 3 4 3 A 1 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes n n n Options Wiring cables, halogen-free and flame-retardant Condensation protection, heating for 230 V AC, 50 W Silicone-free design For circuit-breaker operation at ambient air temperatures down to –25° C Electrical closing lock-out Additional rating plate, loose delivery Separating shell towards contact arm side (standard version) Separating shell towards contact arm side (short version, for 24 kV only) Routine test certificate (enclosed with delivery) Routine test certificate (with stamp and signature) Routine test certificate (to orderer) Special operating sequence (up to 31.5 kA): O - 0.3 s - CO - 15 s - CO Hand crank (for manual charging of the closing spring) Hand crank, long version Handle for drawout element (for racking the circuit-breaker on the drawout element) Key interlocking (only for designs with mechanical interlocking) Indication of disconnected position of the circuit-breaker (circuit-breaker with drawout element) Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 1st shunt release Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release Fixed-mounted circuit-breaker Operating voltage of the motor operating mechanism 230 V AC With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in German Hand crank Example for Order No.: Order codes: 3 A E 1 3 5 4 L B + F 3 0 1 – 4 – – – – – – – – – – – – – – Z Z Z Z Z Z Z Z Z Z Z Z Z Z A A A A A B D D F F F F F F 1 3 3 4 4 0 9 9 2 2 2 2 3 3 0 0 1 0 7 0 0 1 0 1 3 8 0 1 – – Z Z F J 3 6 2 0 – Z J 6 1 L 1 B F 3 0 A C 9 0 – 0 K N 0 A C 9 0 – 0 K N 0 – Z – Z Siemens HG 11.02 · 2008 27 2 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, slide-in modules kV kV kV kA kA mm mm A 60 20 16 40/42 210 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 150 2 60 20 20 50/52 210 150 7.2 60 20 25 63/65 210 150 7.2 60 20 31.5 80/82 210 150 7.2 60 20 40 100/104 210 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 20 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes: 28 Siemens HG 11.02 · 2008 9 10 11 12 – 13 14 15 16 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 3 A E 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7 0 8 3 – 2 0 8 3 – 2 n n n n – n n n n Order codes See page 36 8 See page 35 – See page 35 7 See page 34 6 See page 34 5 Ir 7.2 7.2 4 1 n n n – n n n n n – n n n n – « See page 33 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 33 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 32 Position: Order No.: 50/60 Hz See page 32 7.2 kV n n n SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, slide-in modules kV kV kV kA kA mm mm A 75 28 16 40/42 210 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 150 75 28 20 50/52 210 150 12 75 28 25 63/65 210 150 12 75 28 31.5 80/82 210 150 12 75 28 40 100/104 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 n n n See page 36 8 See page 35 – See page 35 7 See page 34 6 See page 34 5 Ir 12 12 4 1 n n n – n n n n n – n n n n – « See page 33 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 33 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 32 Position: Order No.: 50/60 Hz See page 32 12 kV 210 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7 Special version (available for all 12 kV slide-in modules) Ud = 42 kV Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 800 A Pole-center distance = 150 mm, width across flats = 275 mm Rated short-duration power-frequency withstand voltage Ud = 42 kV Example for Order No.: Order codes: 3 A E E E 3 1 – Z E 1 3 – Z E 1 3 1 n n n n – n n n n – Z 1 1 3 A 2 1 1 1 1 4 4 – – 1 Siemens HG 11.02 · 2008 29 SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, slide-in modules kV kV kV kA kA mm mm A 95 38 12.5 31/33 210 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 150 2 95 38 16 40/42 210 150 17.5 95 38 25 63/65 210 150 17.5 95 38 31.5 80/82 210 150 17.5 95 38 40 100/104 210 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 275 mm Example for Order No.: Order codes: 30 Siemens HG 11.02 · 2008 9 10 11 12 – 13 14 15 16 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 3 A E 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7 2 7 2 – 2 2 7 2 – 2 n n n n – n n n n Order codes See page 36 8 See page 35 – See page 35 7 See page 34 6 See page 34 5 Ir 17.5 17.5 4 1 n n n – n n n n n – n n n n – « See page 33 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 32 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 33 Position: Order No.: 50/60 Hz See page 32 17.5 kV n n n SION Vacuum Circuit-Breakers Equipment Selection Selection of basic types, slide-in modules kV kV kV kA kA mm mm 125 50 12.5 31/33 210 24 125 50 16 40/42 210 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 275 125 50 20 50/52 210 275 24 125 50 25 63/65 9 10 11 12 – 13 14 15 16 Order codes 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 A E 1 n n n See page 36 8 See page 35 – See page 35 7 See page 34 6 See page 34 5 Ir 24 24 4 1 n n n – n n n n n – n n n n – « See page 33 Rated short-circuit making current (at 50/60 Hz) Ima 3 E See page 33 Rated short-circuit breaking current at 36 % DC component Isc 1 Rated normal current Rated short-duration power-frequency withstand voltage Ud Width across flats Rated lightning impulse withstand voltage Up Pole-center distance Rated voltage Ur 2 3 A See page 32 Position: Order No.: 50/60 Hz See page 32 24 kV 210 275 A 800 1250 800 1250 2000 800 1250 2000 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 Configuration example SION vacuum circuit-breaker Rated voltage Ur = 24 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 125 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 2000 A Pole-center distance = 275 mm, width across flats = 310 mm Example for Order No.: 3 A E 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 5 5 5 2 2 2 2 5 5 5 5 2 2 2 2 5 5 5 5 1 1 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 – – – – – – – – – – – – – – – – – – – – – – – – 1 2 1 2 4 1 2 4 1 2 4 6 1 2 4 6 1 2 4 6 1 2 4 6 3 5 4 – 4 3 5 4 – 4 n n n n – n n n n 2 Order codes: Siemens HG 11.02 · 2008 31 SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for slide-in modules n n n n n n 7 – 8 2 10 11 12 – See page 33 13 14 15 16 A B C G H F E N P Q J L M n n n n n n n n n 9 n n n n n n 10th position Operating voltage of the closing solenoid Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC Special voltages B C D E F H J K M N P Q R S U V W 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 1st shunt release Operating voltage of the closing solenoid 48 V DC 3 A 5 4 – 4 A C Order codes: Siemens HG 11.02 · 2008 1 3 Example for Order No.: 32 E 3 A E 1 3 5 4 – 4 A C n n – n n n n Order codes See page 36 6 See page 35 5 See page 35 4 1 n n n – n n n n n – n n n n – « See page 34 3 E See page 34 1 C.t.-operated release with tripping pulse W 0.1 Ws (20 O) C.t.-operated release 1.0 A C.t.-operated release 0.5 A 2 3 A See page 33 Position: Order No.: Undervoltage release 2nd shunt release 1st shunt release 9th position Release combination n n n SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for slide-in modules 4 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – Special voltages C.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 13 14 15 16 0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) Order codes n n n See page 36 3 E See page 35 1 See page 35 2 3 A See page 34 Standard voltages Position: Order No.: See page 34 11th position Operating voltage of the 1st release With order code With order code With order code With order code With order code With order code With order code With order code With order code L L L L L L L L L 1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M With order code With order code With order code With order code With order code With order code With order code With order code With order code M M M M M M M M M 1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M L 1 12th position Operating voltage of the 2nd release Standard voltages Special voltages Without, or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Operating voltage of the 1st release 32 V DC Without 2nd release 3 A E 1 3 5 4 – 4 A C 9 B 0 Example for Order No.: Order codes: 3 A E L B 1 1 3 5 4 – 4 A C 9 0 – n n n n Siemens HG 11.02 · 2008 33 2 SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for slide-in modules 1 3 4 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 See page 35 2 3 A Options On cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters On cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings, shutters and earthing switch with short-circuit making capacity Drawings of the fully equipped slide-in-module. Scope of supply includes fixed-mounted circuit-breaker 5 6 8 14th position Operating voltage of the motor operating mechanism 2 Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC Special voltages B C D E F H J K M N P Q R S U V W 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC 50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35) Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Circuit-breaker on cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters Operating voltage of the motor operating mechanism 240 V DC Example for Order No.: Order codes: 34 Siemens HG 11.02 · 2008 3 A E 1 3 5 4 – 4 A C 9 0 – 5 S 3 A E L B 1 1 3 5 4 – 4 A C 9 0 – 5 S n n Order codes See page 36 Position: Order No.: See page 35 13th position Circuit-breaker installation accessories n n n SION Vacuum Circuit-Breakers Equipment Selection Secondary equipment for slide-in modules 15th position Interlocking, auxiliary switch, circuit-breaker tripping signal and control cable connection 1 3 4 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes n n n n n n n n See page 36 64-pole plug 27-pole terminal strip n n Circuit-breaker tripping signal 6 NO + 6 NC n n n n n n 2 3 A Control cable connection 12 NO + 12 NC Mechanical interlocking Auxiliary switch Position: Order No.: n n n n n n A C J L N P n n Special versions Auxiliary switch contacts 12 NO + 12 NC and pins of the 64-pole plug connector gold-plated – Z A 2 1 – Z A 2 1 – Z 16th position AC frequency of operating voltages Languages of operating instructions and rating plate n n Other languages on request 50 Hz and DC n n n n n n n n n n n 60 Hz and DC n n n 60 Hz n n 50 Hz n n DC Frequency selection Spanish French English German Language selection n n n n n n n n 0 1 2 3 4 5 6 7 Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage DC, operating instruction and rating plate in Spanish Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated Example for Order No.: Order codes: 3 A E 1 3 5 4 L B + A 2 1 1 – 4 A C 9 0 – 5 S N 6 A C 9 0 – 5 S N 6 Siemens HG 11.02 · 2008 35 2 SION Vacuum Circuit-Breakers Equipment Selection Additional equipment for slide-in modules Additional equipment Position: Order No.: 2 3 4 3 A 1 E 1 n n n – n n n n n – n n n n – « 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes n n n Options Wiring cables, halogen-free and flame-retardant Condensation protection, heating for 230 V AC, 50 W Silicone-free design For circuit-breaker operation at ambient air temperatures down to –25° C Electrical closing lock-out Additional rating plate, loose delivery Routine test certificate (enclosed with delivery) Routine test certificate (with stamp and signature) Routine test certificate (to orderer) Special operating sequence (up to 31.5 kA): O - 0.3 s - CO - 15 s - CO Hand crank (for manual charging of the closing spring) Hand crank, long version Handle for drawout element (for racking the circuit-breaker on the drawout element) Handle for earthing switch (for operating the earthing switch at the module) Key interlocking (only for designs with mechanical interlocking) 2 Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 – 4 1st shunt release Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release Circuit-breaker on cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters Operating voltage of the motor operating mechanism 240 V DC With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage DC, operating instructions and rating plate in Spanish Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated Wiring cables halogen-free and flame-retardant Silicone-free design Electrical closing lock-out Example for Order No.: Order codes: 36 Siemens HG 11.02 · 2008 3 A E 1 3 5 4 – L B + A 2 1 + A 1 4 – – – – – – – – – – – – Z Z Z Z Z Z Z Z Z Z Z Z A A A A A B F F F F F F 1 3 3 4 4 0 2 2 2 2 3 3 0 0 1 0 7 0 0 1 3 8 0 1 – Z F 3 2 – – Z Z F J 3 6 4 0 L 1 B A A A A 2 1 3 4 1 0 1 7 A C 9 0 – 5 S N 6 – – – – Z Z Z Z Z A C 9 0 – 5 S N 6 – 1 + A 3 1 + 7 0 A 4 SION Vacuum Circuit-Breakers Equipment Selection Accessories and spare parts Retrofitting Accessories for the plug connector When releases/solenoids are retrofitted, the order numbers of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included in the delivery. Included in the scope of supply of the basic equipment for SION vacuum circuit-breakers: Spare parts When releases/solenoids are required as spare parts, the order number and the type of construction of the associated circuit-breaker type must also be specified. Remark for orders The order numbers are applicable to vacuum circuitbreakers of current manufacture. When mounting parts or spare parts are being ordered for an existing vacuum circuit-breaker, always quote the type designation, serial number, design code and the year of manufacture of the circuit-breaker to be sure to get the correct delivery. For 24-pole plug connector – Lower part of plug – Crimp sockets according to number of contacts – Upper part of plug with screwed contacts (no crimp sockets required) For 64-pole plug connector – Lower part of plug – Upper part of plug – Crimp sockets according to number of contacts Vacuum interrupters and other spare parts must only be replaced by instructed personnel. Designation Remarks Handles Hand crank for circuit-breaker Long hand crank for circuit-breaker Handle for drawout element Handle for earthing switch (for modules up to 31.5 kA) Handle for earthing switch (for 40 kA modules) 180 g of Klüber-Isoflex Topas L32N 1 kg of Klüber-Isoflex Topas L32N 1 kg of Molykote grease Used as closing solenoid or 1st shunt release Lubricant Operating solenoid Mounting parts Operating voltage Order No. For 2nd shunt release For rated normal current 0.5 A 3AX15 30-2B 3AX14 30-2B 3AX14 30-2C 3AX14 30-2D 3AX14 30-3D 3AX11 33-3H 3AX11 33-3E 3AX11 33-2L 3AY15 10-5B 3AY15 10-5M 3AY15 10-5C 3AY15 10-5D 3AY15 10-5E 3AY15 10-5N 3AY15 10-5F 3AY15 10-5E 3AY15 10-5F 3AX11 01-2B 3AX11 01-2C 3AX11 01-2E 3AX11 01-2F 3AX11 01-2G 3AX11 01-2J 3AX11 01-3G 3AX11 01-3J 3AX14 11-2A 3AX11 02-2A For rated normal current 1 A For tripping pulse W 0.1 Ws, 20 O for protection relay 7SJ45 For current-transformer operated release 3AX11 02-2B 3AX11 04-2B 3AX14 11-2A 2nd shunt release Mounting parts Current-transformer operated release 2 24 V DC 30/32 V DC 48 V DC 60 V DC 100/124 V DC 125/144 V DC 220/250 V DC 100/125 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 24 – 32 V DC 48 – 60 V DC 110 – 127 V DC 220 – 240 V DC 100 – 125 V AC, 50 Hz 230 – 240 V AC, 50 Hz 100 – 125 V AC, 60 Hz 230 – 240 V AC, 60 Hz Siemens HG 11.02 · 2008 37 SION Vacuum Circuit-Breakers Equipment Selection Accessories and spare parts Designation Remarks Undervoltage release 2 Mounting parts Drive motor For undervoltage release Auxiliary contactor Type 3RH11 22 for anti-pumping Position switch Auxiliary switch (-S1) Mechanical interlocking Key-operated interlocking Module connector Accessories for plug connector Siemens HG 11.02 · 2008 Order No. 24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240 V DC 100 V AC, 50 Hz 110/125 V AC, 50 Hz 230 V AC, 50 Hz 240 V AC, 50 Hz 100 V AC, 60 Hz 110/125 V AC, 60 Hz 230 V AC, 60 Hz 240 V AC, 60 Hz 3AX11 03-2B 3AX11 03-2L 3AX11 03-2C 3AX11 03-2D 3AX11 03-2E 3AX11 03-2N 3AX11 03-2F 3AX11 03-2P 3AX11 03-2G 3AX11 03-2H 3AX11 03-2J 3AX11 03-2M 3AX11 03-3G 3AX11 03-3H 3AX11 03-3J 3AX11 03-3M 3AX14 13-2A 3AY17 11-2B 3AY17 11-2C 3AY17 11-2D 3AY17 11-2E 3AY17 11-2F 24/30/32 V DC 48 V DC 60 V DC 100/110/125 V DC/AC 220 V DC/230 V AC Type SE4 without installation accessories Used for: – Electrical anti-pumping (-S3) – Electrical interlocking (-S12) – Motor control (-S21, -S22) – Closing spring charged (-S4) – Circuit-breaker tripping signal (-S6) – Electrical closing lock-out (-S5) – Drawout element (-S1.0 to - S1.9) 6 NO + 6 NC 12 NO + 12 NC State position indicator of drawout element (for conductor cross-section 1.5 mm) Crimp pins (for lower part of plug) Crimp sockets (for upper part of plug) Crimping pliers Disassembly tool Plug connector, complete 38 Operating voltage 24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240/250 V DC 110 V AC, 50/60 Hz 120 V AC, 50/60 Hz 125 V AC, 50/60 Hz 230 V AC, 50/60 Hz 240 V AC, 50/60 Hz SWB: 55656 SWB: 55658 SWB: 55659 SWB: 55660 SWB: 55661 SWB: 55662 SWB: 55663 SWB: 55665 SWB: 55666 SWB: 55667 SWB: 55668 SWB: 55669 SWB: 55670 SWB: 46677 Nos. 1 1 2 1 2 1 10 3SV92 73-2AA0 3SV92 74-2AA0 3AX14 20-2A 3AX14 37-2A 3AX14 60-2A 24-pole 64-pole 64-pole 24-pole 64-pole 3AX11 34-3A 3AX11 34-4B 3AX11 34-4C 3AX11 34-4D 3AX11 34-4G 3AX11 34-7A 3AX11 34-6A SION Vacuum Circuit-Breakers Equipment Selection Accessories and spare parts Designation Remarks Electrical closing lock-out Mounting parts Bushing For electrical closing lock-out Separating shell towards contact arm side, for standard circuit-breakers only Additional shielding for narrow mounting conditions Standard version, width across flats 310 mm Standard version, width across flats 275 mm Standard version, width across flats 205 mm Standard version, width across flats 310 mm Short version, width across flats 310 mm Short version Gate for cartridge Contact system Order No. 24 V DC 30/32 V DC 48 V DC 60 V DC 110/127 V DC 220/240 V DC 100 V AC, 50/60 Hz 110/125 V AC, 50/60 Hz 220/240 V AC, 50/60 Hz 3AX14 05-2B 3AX14 05-2K 3AX14 05-2C 3AX14 05-2D 3AX14 05-2E 3AX14 05-2F 3AX14 05-2G 3AX14 05-2H 3AX14 05-2J 3AX14 15-2A 3AX14 51-2A 3AX14 51-2B 3AX14 51-2B 7.2 to 17.5 kV to 1250 A 7.2 to 17.5 kV to 3150 A 24 kV to 2500 A Contact arm, complete with contact system Fixed contact Conductor bars (1 set each) for earthing switch connection Operating voltage 150/210 mm pole-center distance, 275 mm width across flats 150 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats 7.2 to 17.5 kV 7.2 to 17.5 kV 7.2 to 17.5 kV 24 kV 24 kV 7.2/12/24 kV, 800 to 1250 A 17.5 kV, 800 to 1250 A 7.2/12/24 kV, to 3150 A 17.5 kV, to 3150 A 7.2/12 kV, up to 31.5 kA, up to 1250 A 7.2/12 kV, up to 31.5 kA, up to 2500 A 17.5 kV, up to 31.5 kA, up to 1250 A 17.5 kV, up to 31.5 kA, up to 2500 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 2500 A 7.2/12 kV, 40 kA, up to 1250 A 7.2/12 kV, 40 kA, up to 3150 A 17.5 kV, 40 kA, up to 1250 A 17.5 kV, 40 kA, up to 3150 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 2500 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 2500 A 24 kV, up to 25 kA, up to 2500 A 3AX14 38-2A 3AX14 38-2C 3AX14 38-2D 3AX14 38-2B 3AX14 38-3B 3AX14 52-2B 3AX14 42-2A 3AX14 42-2B 3AX14 42-2C 3AX14 42-2D 3AX14 43-2A 3AX14 43-2B 3AX14 43-2C 3AX14 43-2D 3AX14 43-2E 3AX14 43-2F 3AX14 43-2G 3AX14 43-2H 3AX14 43-2J 3AX14 43-2K 3AX14 44-2A 3AX14 44-2B 3AX14 44-2A 3AX14 44-2C 3AX14 55-2A 3AX14 55-2A 3AX14 55-2B 3AX14 55-2C 3AX14 55-2D 3AX14 55-2E 3AX14 55-2F 3AX14 55-2G 3AX14 55-2H HG11-2518_en eps Data on the rating plate Note: For any query regarding spare parts, subsequent deliveries, etc., the following four details are necessary: – Type designation – Serial No. – Design code – Year of manufacture Siemens HG 11.02 · 2008 39 2 R-HG11-177.tif SION Vacuum Circuit-Breakers 40 Siemens HG 11.02 · 2008 SION Vacuum Circuit-Breakers Technical Data Contents Contents Page Technical Data 41 Electrical data, dimensions and weights: Voltage level 7.2 kV 42 Voltage level 12 kV 46 Voltage level 17.5 kV 50 Voltage level 24 kV 56 R-HG11-178.eps Dimension drawings: Voltage levels 7.2 to 17.5 kV 54 Voltage level 24 kV 58 Operating times 59 Short-circuit protection of motors 59 Consumption data of releases 59 Circuit diagrams 60 SION vacuum circuit-breaker with drawout element, contact arms and contact system R-HG11-179.eps 3 SION vacuum circuit-breaker with drawout element, contact arms and contact system Siemens HG 11.02 · 2008 41 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 60 20 2.1 129 140 105 75 80/ – 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 800 205 150 n 3 16 36 17.9 3AE1 002-2 ... 1250 205 150 n 3 16 36 17.9 3AE1 003-1 ... 800 205 150 n 3 20 36 22.4 3AE1 003-2 ... 1250 205 150 n 3 20 36 22.4 3AE1 004-1 ... 800 205 150 n 3 25 36 28 3AE1 004-2 ... 1250 205 150 n 3 25 36 28 3AE1 005-1 ... 800 205 150 n 3 31.5 36 35.4 3AE1 005-2 ... 1250 205 150 n 3 31.5 36 35.4 3AE1 012-1 ... 800 275 150 n 3 16 36 17.9 3AE1 012-2 ... 1250 275 150 n 3 16 36 17.9 3AE1 013-1 ... 800 275 150 n 3 20 36 22.4 3AE1 013-2 ... 1250 275 150 n 3 20 36 22.4 3AE1 014-1 ... 800 275 150 n 3 25 36 28 3AE1 014-2 ... 1250 275 150 n 3 25 36 28 3AE1 015-1 ... 800 275 150 n 3 31.5 36 35.4 3AE1 015-2 ... 1250 275 150 n 3 31.5 36 35.4 3AE1 022-1 ... 800 310 150 n 3 16 36 17.9 3AE1 022-2 ... 1250 310 150 n 3 16 36 17.9 3AE1 023-1 ... 800 310 150 n 3 20 36 22.4 3AE1 023-2 ... 1250 310 150 n 3 20 36 22.4 3AE1 024-1 ... 800 310 150 n 3 25 36 28 3AE1 024-2 ... 1250 310 150 n 3 25 36 28 3AE1 025-1 ... 800 310 150 n 3 31.5 36 35.4 3AE1 025-2 ... 1250 310 150 n 3 31.5 36 35.4 42 Siemens HG 11.02 · 2008 Possible 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 105 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 60 20 2.1 129 140 100 75 – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 002-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 45) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 7.2 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 1 K/– 1 K/– 2 K/– 2 K/– 3 K/– 3 K/– 4 K/– 4 K/– 1 I/J 1 I/J 2 I/J 2 I/J 3 I/J 3 I/J 4 I/J 4 I/J 1 H/J 1 H/J 2 H/J 2 H/J 3 H/J 3 H/J 4 H/J 4 H/J kg 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm kg 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 115 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 110 75 80/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 800 205 160 n 3 16 36 17.9 3AE1 032-2 ... 1250 205 160 n 3 16 36 17.9 3AE1 033-1 ... 800 205 160 n 3 20 36 22.4 3AE1 033-2 ... 1250 205 160 n 3 20 36 22.4 3AE1 034-1 ... 800 205 160 n 3 25 36 28 3AE1 034-2 ... 1250 205 160 n 3 25 36 28 3AE1 035-1 ... 800 205 160 n 3 31.5 36 35.4 3AE1 035-2 ... 1250 205 160 n 3 31.5 36 35.4 3AE1 042-1 ... 800 275 160 n 3 16 36 17.9 3AE1 042-2 ... 1250 275 160 n 3 16 36 17.9 3AE1 043-1 ... 800 275 160 n 3 20 36 22.4 3AE1 043-2 ... 1250 275 160 n 3 20 36 22.4 3AE1 044-1 ... 800 275 160 n 3 25 36 28 3AE1 044-2 ... 1250 275 160 n 3 25 36 28 3AE1 045-1 ... 800 275 160 n 3 31.5 36 35.4 3AE1 045-2 ... 1250 275 160 n 3 31.5 36 35.4 3AE1 052-1 ... 800 310 160 n 3 16 36 17.9 3AE1 052-2 ... 1250 310 160 n 3 16 36 17.9 3AE1 053-1 ... 800 310 160 n 3 20 36 22.4 3AE1 053-2 ... 1250 310 160 n 3 20 36 22.4 3AE1 054-1 ... 800 310 160 n 3 25 36 28 3AE1 054-2 ... 1250 310 160 n 3 25 36 28 3AE1 055-1 ... 800 310 160 n 3 31.5 36 35.4 3AE1 055-2 ... 1250 310 160 n 3 31.5 36 35.4 3AE1 062-1 ... 800 205 210 n 3 16 36 17.9 3AE1 062-2 ... 1250 205 210 n 3 16 36 17.9 Possible – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 032-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02022 001 3M 442 02022 001 Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see page 45) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 7.2 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 1 G/– 1 G/– 2 G/– 2 G/– 3 G/– 3 G/– 4 G/– 4 G/– 1 F/– 1 F/– 2 F/– 2 F/– 3 F/– 3 F/– 4 F/– 4 F/– 1 E/– 1 E/– 2 E/– 2 E/– 3 E/– 3 E/– 4 E/– 4 E/– 1 D/– 1 D/– 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 · 2008 43 3 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 90/ – 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 165 75 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 1.5 129 265 130 130 60 20 2.1 129 140 160 75 60 20 2.1 129 140 160 75 60 20 1.5 129 265 130 130 60 20 1.5 129 265 130 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 800 205 210 n 3 20 36 22.4 3AE1 063-2 ... 1250 205 210 n 3 20 36 22.4 3AE1 064-1 ... 800 205 210 n 3 25 36 28 3AE1 064-2 ... 1250 205 210 n 3 25 36 28 3AE1 065-1 ... 800 205 210 n 3 31.5 36 35.4 3AE1 065-2 ... 1250 205 210 n 3 31.5 36 35.4 3AE1 072-1 ... 800 275 210 n 3 16 36 17.9 3AE1 072-2 ... 1250 275 210 n 3 16 36 17.9 3AE1 073-1 ... 800 275 210 n 3 20 36 22.4 3AE1 073-2 ... 1250 275 210 n 3 20 36 22.4 3AE1 074-1 ... 800 275 210 n 3 25 36 28 3AE1 074-2 ... 1250 275 210 n 3 25 36 28 3AE1 075-1 ... 800 275 210 n 3 31.5 36 35.4 3AE1 075-2 ... 1250 275 210 n 3 31.5 36 35.4 3AE1 082-1 ... 800 310 210 n 3 16 36 17.9 3AE1 082-2 ... 1250 310 210 n 3 16 36 17.9 3AE1 083-1 ... 800 310 210 n 3 20 36 22.4 3AE1 083-2 ... 1250 310 210 n 3 20 36 22.4 3AE1 084-1 ... 800 310 210 n 3 25 36 28 3AE1 084-2 ... 1250 310 210 n 3 25 36 28 3AE1 084-4 ... 2000 310 210 n 3 25 36 28 3AE1 085-1 ... 800 310 210 n 3 31.5 36 35.4 3AE1 085-2 ... 1250 310 210 n 3 31.5 36 35.4 3AE1 085-4 ... 2000 310 210 n 3 31.5 36 35.4 3AE1 085-6 ... 2500 310 210 n 3 31.5 36 35.4 44 Siemens HG 11.02 · 2008 Possible – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 063-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 45) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 7.2 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 2 D/– 2 D/– 3 D/– 3 D/– 4 D/– 4 D/– 1 B/C 1 B/C 2 B/C 2 B/C 3 B/C 3 B/C 4 B/C 4 B/C 1 A/C 1 A/C 2 A/C 2 A/C 3 A/C 3 A/C 3 L/C 4 A/C 4 A/C 4 L/C 4 L/C kg 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % 3AE1 086-2 ... 1250 310 210 n 3 40 36 44.9 3AE1 086-4 ... 2000 310 210 n 3 40 36 44.9 3AE1 086-6 ... 2500 310 210 n 3 40 36 44.9 3AE1 086-7 ... 3150 310 210 n 3 40 36 44.9 n Standard acc. to IEC 62271-100 Possible mV mm mm mm mm kg 120/ 160 160/ 210 160/ 210 160/ 210 60 20 1.7 145 155 169 140 60 20 1.0 145 249 149 140 60 20 1.0 145 249 149 140 60 20 1.0 145 249 149 140 – Not available as slide-in module Detailed dimension drawing (has to be ordered) Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 100/ 104 100/ 104 100/ 104 100/ 104 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see below) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 7.2 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 5 M/C 5 M/C 5 M/C 5 M/C 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 3 Operating cycle diagrams for 7.2 kV electrical operating cycles 20 000 10 000 is shown as a function of 10 000 the breaking current 2 000 vacuum circuit-breakers 1 000 fulfil the endurance classes (r.m.s. value). All SION 200 curve shape beyond the 100 parameters defined in 20 10 0.5 1 000 500 to IEC 62271-100. The 1 1 2 3 5 kA 10 16 20 25 Breaking current (r.m.s. value) 5 HG11-2539b_en eps 80 50 2 000 E2, M2 and C2 according 500 180 5 000 40 50 IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respec- 200 130 100 50 20 10 0.5 2 1 2 4 HG11-2540a_en eps 5 000 Operating cycle No. Operating cycle No. The permissible number of 20 000 20 31.5 50 5 kA 10 Breaking current (r.m.s. value) tive application. Siemens HG 11.02 · 2008 45 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 75 28 2.1 129 140 105 75 80/ – 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 800 205 150 n 3 16 36 17.9 3AE1 102-2 ... 1250 205 150 n 3 16 36 17.9 3AE1 103-1 ... 800 205 150 n 3 20 36 22.4 3AE1 103-2 ... 1250 205 150 n 3 20 36 22.4 3AE1 104-1 ... 800 205 150 n 3 25 36 28 3AE1 104-2 ... 1250 205 150 n 3 25 36 28 3AE1 105-1 ... 800 205 150 n 3 31.5 36 35.4 3AE1 105-2 ... 1250 205 150 n 3 31.5 36 35.4 3AE1 112-1 ... 800 275 150 n 3 16 36 17.9 3AE1 112-2 ... 1250 275 150 n 3 16 36 17.9 3AE1 113-1 ... 800 275 150 n 3 20 36 22.4 3AE1 113-2 ... 1250 275 150 n 3 20 36 22.4 3AE1 114-1 ... 800 275 150 n 3 25 36 28 3AE1 114-2 ... 1250 275 150 n 3 25 36 28 3AE1 115-1 ... 800 275 150 n 3 31.5 36 35.4 3AE1 115-2 ... 1250 275 150 n 3 31.5 36 35.4 3AE1 122-1 ... 800 310 150 n 3 16 36 17.9 3AE1 122-2 ... 1250 310 150 n 3 16 36 17.9 3AE1 123-1 ... 800 310 150 n 3 20 36 22.4 3AE1 123-2 ... 1250 310 150 n 3 20 36 22.4 3AE1 124-1 ... 800 310 150 n 3 25 36 28 3AE1 124-2 ... 1250 310 150 n 3 25 36 28 3AE1 125-1 ... 800 310 150 n 3 31.5 36 35.4 3AE1 125-2 ... 1250 310 150 n 3 31.5 36 35.4 3AE1 132-1 ... 800 205 160 n 3 16 36 17.9 3AE1 132-2 ... 1250 205 160 n 3 16 36 17.9 46 Siemens HG 11.02 · 2008 Possible 6 K/– 6 K/– 7 K/– 7 K/– 8 K/– 8 K/– 9 K/– 9 K/– 6 I/J 6 I/J 7 I/J 7 I/J 8 I/J 8 I/J 9 I/J 9 I/J 6 H/J 6 H/J 7 H/J 7 H/J 8 H/J 8 H/J 9 H/J 9 H/J 6 G/– 6 G/– kg 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 105 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 100 75 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 102-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 49) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 12 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02016 001 3M 442 02016 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 115 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 110 75 80/ – 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 800 205 160 n 3 20 36 22.4 3AE1 133-2 ... 1250 205 160 n 3 20 36 22.4 3AE1 134-1 ... 800 205 160 n 3 25 36 28 3AE1 134-2 ... 1250 205 160 n 3 25 36 28 3AE1 135-1 ... 800 205 160 n 3 31.5 36 35.4 3AE1 135-2 ... 1250 205 160 n 3 31.5 36 35.4 3AE1 142-1 ... 800 275 160 n 3 16 36 17.9 3AE1 142-2 ... 1250 275 160 n 3 16 36 17.9 3AE1 143-1 ... 800 275 160 n 3 20 36 22.4 3AE1 143-2 ... 1250 275 160 n 3 20 36 22.4 3AE1 144-1 ... 800 275 160 n 3 25 36 28 3AE1 144-2 ... 1250 275 160 n 3 25 36 28 3AE1 145-1 ... 800 275 160 n 3 31.5 36 35.4 3AE1 145-2 ... 1250 275 160 n 3 31.5 36 35.4 3AE1 152-1 ... 800 310 160 n 3 16 36 17.9 3AE1 152-2 ... 1250 310 160 n 3 16 36 17.9 3AE1 153-1 ... 800 310 160 n 3 20 36 22.4 3AE1 153-2 ... 1250 310 160 n 3 20 36 22.4 3AE1 154-1 ... 800 310 160 n 3 25 36 28 3AE1 154-2 ... 1250 310 160 n 3 25 36 28 3AE1 155-1 ... 800 310 160 n 3 31.5 36 35.4 3AE1 155-2 ... 1250 310 160 n 3 31.5 36 35.4 3AE1 162-1 ... 800 205 210 n 3 16 36 17.9 3AE1 162-2 ... 1250 205 210 n 3 16 36 17.9 3AE1 163-1 ... 800 205 210 n 3 20 36 22.4 3AE1 163-2 ... 1250 205 210 n 3 20 36 22.4 Possible – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 133-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see page 49) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 12 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 7 G/– 7 G/– 8 G/– 8 G/– 9 G/– 9 G/– 6 F/– 6 F/– 7 F/– 7 F/– 8 F/– 8 F/– 9 F/– 9 F/– 6 E/– 6 E/– 7 E/– 7 E/– 8 E/– 8 E/– 9 E/– 9 E/– 6 D/– 6 D/– 7 D/– 7 D/– kg 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 · 2008 47 3 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 75 28 2.1 129 140 165 75 90/ – 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 800 205 210 n 3 25 36 28 3AE1 164-2 ... 1250 205 210 n 3 25 36 28 3AE1 165-1 ... 800 205 210 n 3 31.5 36 35.4 3AE1 165-2 ... 1250 205 210 n 3 31.5 36 35.4 3AE1 172-1 ... 800 275 210 n 3 16 36 17.9 3AE1 172-2 ... 1250 275 210 n 3 16 36 17.9 3AE1 173-1 ... 800 275 210 n 3 20 36 22.4 3AE1 173-2 ... 1250 275 210 n 3 20 36 22.4 3AE1 174-1 ... 800 275 210 n 3 25 36 28 3AE1 174-2 ... 1250 275 210 n 3 25 36 28 3AE1 175-1 ... 800 275 210 n 3 31.5 36 35.4 3AE1 175-2 ... 1250 275 210 n 3 31.5 36 35.4 3AE1 182-1 ... 800 310 210 n 3 16 36 17.9 3AE1 182-2 ... 1250 310 210 n 3 16 36 17.9 3AE1 183-1 ... 800 310 210 n 3 20 36 22.4 3AE1 183-2 ... 1250 310 210 n 3 20 36 22.4 3AE1 184-1 ... 800 310 210 n 3 25 36 28 3AE1 184-2 ... 1250 310 210 n 3 25 36 28 3AE1 184-4 ... 2000 310 210 n 3 25 36 28 3AE1 184-6 ... 2500 310 210 n 3 25 36 28 3AE1 185-1 ... 800 310 210 n 3 31.5 36 35.4 3AE1 185-2 ... 1250 310 210 n 3 31.5 36 35.4 3AE1 185-4 ... 2000 310 210 n 3 31.5 36 35.4 3AE1 185-6 ... 2500 310 210 n 3 31.5 36 35.4 48 Siemens HG 11.02 · 2008 Possible 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 165 75 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 1.5 129 265 130 130 75 28 1.5 129 265 130 130 75 28 2.1 129 140 160 75 75 28 2.1 129 140 160 75 75 28 1.5 129 265 130 130 75 28 1.5 129 265 130 130 – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 164-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 49) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 12 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 8 D/– 8 D/– 9 D/– 9 D/– 6 B/C 6 B/C 7 B/C 7 B/C 8 B/C 8 B/C 9 B/C 9 B/C 6 A/C 6 A/C 7 A/C 7 A/C 8 A/C 8 A/C 8 L/C 8 L/C 9 A/C 9 A/C 9 L/C 9 L/C kg 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % 3AE1 186-2 ... 1250 310 210 n 3 40 36 44.9 3AE1 186-4 ... 2000 310 210 n 3 40 36 44.9 3AE1 186-6 ... 2500 310 210 n 3 40 36 44.9 3AE1 186-7 ... 3150 310 210 n 3 40 36 44.9 3AE1 545-2 ... 1250 275 160 n 3 31.5 36 35.4 3AE1 575-2 ... 1250 275 210 n 3 31.5 36 35.4 3AE1 575-6 ... 2500 275 210 n 3 31.5 36 35.4 3AE1 576-2 ... 1250 275 210 n 3 40 36 44.9 3AE1 576-4 ... 2000 275 210 n 3 40 36 44.9 3AE1 576-6 ... 2500 310 210 n 3 40 36 44.9 3AE1 576-7 ... 3150 310 210 n 3 40 36 44.9 n Standard acc. to IEC 62271-100 Possible mV Weight 1) (fixed-mounted circuit-breaker/slide-in module) mm mm mm mm kg 120/ 160 160/ 210 160/ 210 160/ 210 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 10 M/C 10 M/C 10 M/C 10 M/C Detailed dimension drawing (has to be ordered) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 100/ 104 100/ 104 100/ 104 100/ 104 80/ 82 80/ 82 80/ 82 100/ 104 100/ 104 100/ 104 100/ 104 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see pages 54) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see below) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 12 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 75 28 1.7 145 155 169 140 75 28 1.0 145 249 149 140 75 28 1.0 145 249 149 140 75 28 1.0 145 249 149 140 75 28 2.1 129 140 115 75 80/ – – 9 –/– 75 28 2.1 129 140 160 75 90/ – – 9 –/– 75 28 1.5 129 265 130 130 110/ – – 9 –/– 75 28 1.7 145 155 169 140 120/ – – 10 –/– 75 28 1.0 145 249 149 140 160/ – – 10 –/– 75 28 1.0 145 249 149 140 160/ – – 10 –/– 75 28 1.0 145 249 149 140 160/ – – 10 –/– – Not available as slide-in module 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Operating cycle diagrams for 12 kV electrical operating cycles 20 000 10 000 is shown as a function of 10 000 5 000 (r.m.s. value). All SION 2 000 vacuum circuit-breakers 1 000 fulfil the endurance classes E2, M2 and C2 according 500 80 50 200 1 000 500 200 curve shape beyond the parameters defined in 100 20 10 0.5 2 000 to IEC 62271-100. The 6 1 2 8 5 kA 10 16 20 25 Breaking current (r.m.s. value) 10 HG11-2734_en eps 180 5 000 40 50 130 IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respec- 100 50 20 10 0.5 7 1 2 9 HG11-2735_en eps the breaking current Operating cycle No. Operating cycle No. The permissible number of 20 000 20 31.5 50 5 kA 10 Breaking current (r.m.s. value) tive application. Siemens HG 11.02 · 2008 49 3 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm kg 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 95 38 2.1 129 275 237 150 80/ – 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 800 205 150 n 3 12.5 36 14.9 3AE1 201-2 ... 1250 205 150 n 3 12.5 36 14.9 3AE1 202-1 ... 800 205 150 n 3 16 36 17.9 3AE1 202-2 ... 1250 205 150 n 3 16 36 17.9 3AE1 204-1 ... 800 205 150 n 3 25 36 28 3AE1 204-2 ... 1250 205 150 n 3 25 36 28 3AE1 205-1 ... 800 205 150 n 3 31.5 36 35.4 3AE1 205-2 ... 1250 205 150 n 3 31.5 36 35.4 3AE1 211-1 ... 800 275 150 n 3 12.5 36 14.9 3AE1 211-2 ... 1250 275 150 n 3 12.5 36 14.9 3AE1 212-1 ... 800 275 150 n 3 16 36 17.9 3AE1 212-2 ... 1250 275 150 n 3 16 36 17.9 3AE1 214-1 ... 800 275 150 n 3 25 36 28 3AE1 214-2 ... 1250 275 150 n 3 25 36 28 3AE1 215-1 ... 800 275 150 n 3 31.5 36 35.4 3AE1 215-2 ... 1250 275 150 n 3 31.5 36 35.4 3AE1 221-1 ... 800 310 150 n 3 12.5 36 14.9 3AE1 221-2 ... 1250 310 150 n 3 12.5 36 14.9 3AE1 222-1 ... 800 310 150 n 3 16 36 17.9 3AE1 222-2 ... 1250 310 150 n 3 16 36 17.9 3AE1 224-1 ... 800 310 150 n 3 25 36 28 3AE1 224-2 ... 1250 310 150 n 3 25 36 28 3AE1 225-1 ... 800 310 150 n 3 31.5 36 35.4 3AE1 225-2 ... 1250 310 150 n 3 31.5 36 35.4 3AE1 231-1 ... 800 205 160 n 3 12.5 36 14.9 3AE1 231-2 ... 1250 205 160 n 3 12.5 36 14.9 50 Siemens HG 11.02 · 2008 Possible 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 214 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 190 150 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 201-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02019 001 3M 442 02019 001 Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 53) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 17.5 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 11 K/– 11 K/– 12 K/– 12 K/– 13 K/– 13 K/– 14 K/– 14 K/– 11 I/J 11 I/J 12 I/J 12 I/J 13 I/J 13 I/J 14 I/J 14 I/J 11 H/J 11 H/J 12 H/J 12 H/J 13 H/J 13 H/J 14 H/J 14 H/J 11 G/– 11 G/– 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm kg 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 247 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 224 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 200 150 80/ – 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 800 205 160 n 3 16 36 17.9 3AE1 232-2 ... 1250 205 160 n 3 16 36 17.9 3AE1 234-1 ... 800 205 160 n 3 25 36 28 3AE1 234-2 ... 1250 205 160 n 3 25 36 28 3AE1 235-1 ... 800 205 160 n 3 31.5 36 35.4 3AE1 235-2 ... 1250 205 160 n 3 31.5 36 35.4 3AE1 241-1 ... 800 275 160 n 3 12.5 36 14.9 3AE1 241-2 ... 1250 275 160 n 3 12.5 36 14.9 3AE1 242-1 ... 800 275 160 n 3 16 36 17.9 3AE1 242-2 ... 1250 275 160 n 3 16 36 17.9 3AE1 244-1 ... 800 275 160 n 3 25 36 28 3AE1 244-2 ... 1250 275 160 n 3 25 36 28 3AE1 245-1 ... 800 275 160 n 3 31.5 36 35.4 3AE1 245-2 ... 1250 275 160 n 3 31.5 36 35.4 3AE1 251-1 ... 800 310 160 n 3 12.5 36 14.9 3AE1 251-2 ... 1250 310 160 n 3 12.5 36 14.9 3AE1 252-1 ... 800 310 160 n 3 16 36 17.9 3AE1 252-2 ... 1250 310 160 n 3 16 36 17.9 3AE1 254-1 ... 800 310 160 n 3 25 36 28 3AE1 254-2 ... 1250 310 160 n 3 25 36 28 3AE1 255-1 ... 800 310 160 n 3 31.5 36 35.4 3AE1 255-2 ... 1250 310 160 n 3 31.5 36 35.4 3AE1 261-1 ... 800 205 210 n 3 12.5 36 14.9 3AE1 261-2 ... 1250 205 210 n 3 12.5 36 14.9 3AE1 262-1 ... 800 205 210 n 3 16 36 17.9 3AE1 262-2 ... 1250 205 210 n 3 16 36 17.9 Possible – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 232-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see page 53) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 17.5 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 12 G/– 12 G/– 13 G/– 13 G/– 14 G/– 14 G/– 11 F/– 11 F/– 12 F/– 12 F/– 13 F/– 13 F/– 14 F/– 14 F/– 11 E/– 11 E/– 12 E/– 12 E/– 13 E/– 13 E/– 14 E/– 14 E/– 11 D/– 11 D/– 12 D/– 12 D/– 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 · 2008 51 3 SION Vacuum Circuit-Breakers Technical Data % mm mm mm mm kg 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 95 38 2.1 129 275 165 150 90/ – 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 800 205 210 n 3 25 36 28 3AE1 264-2 ... 1250 205 210 n 3 25 36 28 3AE1 265-1 ... 800 205 210 n 3 31.5 36 35.4 3AE1 265-2 ... 1250 205 210 n 3 31.5 36 35.4 3AE1 271-1 ... 800 275 210 n 3 12.5 36 14.9 3AE1 271-2 ... 1250 275 210 n 3 12.5 36 14.9 3AE1 272-1 ... 800 275 210 n 3 16 36 17.9 3AE1 272-2 ... 1250 275 210 n 3 16 36 17.9 3AE1 274-1 ... 800 275 210 n 3 25 36 28 3AE1 274-2 ... 1250 275 210 n 3 25 36 28 3AE1 275-1 ... 800 275 210 n 3 31.5 36 35.4 3AE1 275-2 ... 1250 275 210 n 3 31.5 36 35.4 3AE1 281-1 ... 800 310 210 n 3 12.5 36 14.9 3AE1 281-2 ... 1250 310 210 n 3 12.5 36 14.9 3AE1 282-1 ... 800 310 210 n 3 16 36 17.9 3AE1 282-2 ... 1250 310 210 n 3 16 36 17.9 3AE1 284-1 ... 800 310 210 n 3 25 36 28 3AE1 284-2 ... 1250 310 210 n 3 25 36 28 3AE1 284-4 ... 2000 310 210 n 3 25 36 28 3AE1 284-6 ... 2500 310 210 n 3 25 36 28 3AE1 285-1 ... 800 310 210 n 3 31.5 36 35.4 3AE1 285-2 ... 1250 310 210 n 3 31.5 36 35.4 3AE1 285-4 ... 2000 310 210 n 3 31.5 36 35.4 3AE1 285-6 ... 2500 310 210 n 3 31.5 36 35.4 52 Siemens HG 11.02 · 2008 Possible 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 165 150 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 1.5 129 265 130 130 95 38 1.5 129 265 130 130 95 38 2.1 129 275 160 150 95 38 2.1 129 275 160 150 95 38 1.5 129 265 130 130 95 38 1.5 129 265 130 130 – Not available as slide-in module Detailed dimension drawing (has to be ordered) mV 3AE1 264-1 ... n Standard acc. to IEC 62271-100 Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02029 001 3M 442 02029 001 3M 442 02027 001 3M 442 02027 001 3M 442 02029 001 3M 442 02029 001 Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) 3 mm mm Ima Operating cycle diagram no. (see page 53) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 17.5 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 13 D/– 13 D/– 14 D/– 14 D/– 11 B/C 11 B/C 12 B/C 12 B/C 13 B/C 13 B/C 14 B/C 14 B/C 11 A/C 11 A/C 12 A/C 12 A/C 13 A/C 13 A/C 13 L/C 13 L/C 14 A/C 14 A/C 14 L/C 14 L/C 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 SION Vacuum Circuit-Breakers Technical Data % 3AE1 286-2 ... 1250 310 210 n 3 40 36 44.9 3AE1 286-4 ... 2000 310 210 n 3 40 36 44.9 3AE1 286-6 ... 2500 310 210 n 3 40 36 44.9 3AE1 286-7 ... 3150 310 210 n 3 40 36 44.9 n Standard acc. to IEC 62271-100 Possible mV mm mm mm mm kg 120/ 160 160/ 210 160/ 210 160/ 210 95 38 1.7 145 249 169 140 95 38 1.0 145 249 149 140 95 38 1.0 145 249 149 140 95 38 1.0 145 249 149 140 – Not available as slide-in module Detailed dimension drawing (has to be ordered) Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 100/ 104 100/ 104 100/ 104 100/ 104 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see below) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 17.5 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 15 M/C 15 M/C 15 M/C 15 M/C 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 3 Operating cycle diagrams for 17.5 kV electrical operating cycles 20 000 10 000 is shown as a function of 10 000 5 000 (r.m.s. value). All SION 2 000 vacuum circuit-breakers 1 000 fulfil the endurance classes to IEC 62271-100. The 180 200 20 12 13 1 2 5 kA 10 16 20 25 Breaking current (r.m.s. value) 15 HG11-2537b_en eps 100 10 0.5 2 000 1 000 E2, M2 and C2 according 500 80 50 5 000 40 50 350 500 curve shape beyond the 200 parameters defined in 100 IEC 62271-100 is based on average experience data. 50 The number of operating 20 cycles that can actually be 10 0.5 reached can be different depending on the respec- 11 1 2 14 HG11-2541a_en eps the breaking current Operating cycle No. Operating cycle No. The permissible number of 20 000 5 kA 10 12.5 20 31.5 50 Breaking current (r.m.s. value) tive application. Siemens HG 11.02 · 2008 53 SION Vacuum Circuit-Breakers Technical Data Dimensions drawings for voltage levels 7.2 kV to 17.5 kV Dimension drawings for 7.2 to 17.5 kV 565 210 217.5 20 279 Dimension drawing A 310 380 279 Dimension drawing B 472/5221) 794 210 102 100 210 187 30 HG11-2521a_en eps 310 380 210 562.5 275 540 517.5 562.5 237.5 540 572.5 517.5 20 HG11-2520_en eps 370 ca.93 210 310 210 HG11-2519_en eps 565 ca.93 370 b a Width across flats mm Height mm a b 310 905 275 850 27.5 27.5 43 Dimension drawing C 310 237.5 20 279 20 310 380 279 Dimension drawing F 54 Siemens HG 11.02 · 2008 217.5 562.5 205 160 20 310 380 279 Dimension drawing G 160 HG11-2525_en eps 465 ca.93 217.5 562.5 275 540 370 540 465 160 160 ca.93 370 279 Dimension drawing E HG11-2524_en eps Dimension drawing D 310 380 517.5 310 380 562.5 540 572,5 517.5 217.5 20 465 160 160 HG11-2523_en eps 370 ca.93 210 562.5 205 540 517.5 210 HG11-2522_en eps 565 ca.93 370 517.5 3 688/7381) 286.5 345 1) for 40 kA SION Vacuum Circuit-Breakers Technical Data Dimensions drawings for voltage levels 7.2 kV to 17.5 kV Dimension drawings for 7.2 to 17.5 kV 540 517.5 562.5 275 310 562.5 20 279 Dimension drawing H 310 380 279 Dimension drawing I 472 150 102 100 30 594 150 147 HG11-2528a_en eps 310 380 217.5 237.5 540 572.5 517.5 20 HG11-2527_en eps 445 150 150 ca.93 370 HG11-2526_en eps 445 150 150 ca.93 370 a b 310 905 275 850 27.5 27.5 43 688 710 Height mm 266.5 341 b a Width across flats mm 3 565 ca.93 237.5 217.5 310 380 20 279 210 210 a 350 450 107 c 279 Dimension drawing M d HG11-2589 eps 237.5 50 PCD a c d Weight 150 529 500 470 ca. 15 kg 160 529 500 470 ca. 15 kg 210 679 650 620 ca. 20 kg Height of drawout element: 60 540 600 310 ca.93 420 279 Dimension drawing L HG11-2531_en eps Dimension drawing K 310 380 424 20 210 310 210 562.5 540 581 517.5 562.5 205 540 517.5 370 HG11-2529_en eps 445 150 150 ca.93 370 HG11-2530_en eps Dimension drawing J PCD a c d Pole-center distance Width of drawout elements Total width across wheels Distance between wheels Dimension drawing of slide-in module Siemens HG 11.02 · 2008 55 SION Vacuum Circuit-Breakers Technical Data kA kV kV 31/ 33 31/ 33 40/ 42 40/ 42 40/ 42 50/ 52 50/ 52 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 40/ 42 40/ 42 40/ 42 3AE1 321-1 ... 800 310 210 n 3 12.5 36 14.9 3AE1 321-2 ... 1250 310 210 n 3 12.5 36 14.9 3AE1 322-1 ... 800 310 210 n 3 16 36 17.9 3AE1 322-2 ... 1250 310 210 n 3 16 36 17.9 3AE1 322-4 ... 2000 310 210 n 3 16 36 17.9 3AE1 323-1 ... 800 310 210 n 3 20 36 22.4 3AE1 323-2 ... 1250 310 210 n 3 20 36 22.4 3AE1 323-4 ... 2000 310 210 n 3 20 36 22.4 3AE1 323-6 ... 2500 310 210 n 3 20 36 22.4 3AE1 324-1 ... 800 310 210 n 3 25 36 28 3AE1 324-2 ... 1250 310 210 n 3 25 36 28 3AE1 324-4 ... 2000 310 210 n 3 25 36 28 3AE1 324-6 ... 2500 310 210 n 3 25 36 28 3AE1 352-1 ... 800 310 275 n 3 16 36 17.9 3AE1 352-2 ... 1250 310 275 n 3 16 36 17.9 3AE1 352-4 ... 2000 310 275 n 3 16 36 17.9 n Standard acc. to IEC 62271-100 56 Siemens HG 11.02 · 2008 Possible mV mm mm mm mm kg 120/ 160 120/ 160 120/ 160 120/ 160 140/ 180 120/ 160 120/ 160 140/ 180 140/ 180 120/ 160 120/ 160 140/ 180 140/ 180 130/ 180 130/ 180 150/ 200 125 50 2.6 200 350 200 210 125 50 2.6 200 350 200 210 125 50 2.6 200 350 200 210 125 50 2.6 200 350 200 210 125 50 2.0 200 340 200 205 125 50 2.6 200 350 200 210 125 50 2.6 200 350 200 210 125 50 2.0 200 340 200 205 125 50 2.0 200 340 200 205 125 50 2.6 200 350 200 210 125 50 2.6 200 350 200 210 125 50 2.0 200 340 200 205 125 50 2.0 200 340 200 205 125 50 2.6 200 350 265 210 125 50 2.6 200 350 265 210 125 50 2.0 200 340 265 205 – Not available as slide-in module Detailed dimension drawing (has to be ordered) kA 3M 442 02050 001 3M 442 02050 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02051 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02051 001 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 Catalog dimension drawings (see page 58) (fixed-mounted circuit-breaker/slide-in module) % Weight 1) (fixed-mounted circuit-breaker/slide-in module) kA Minimum clearance, phase-to-earth Ud Minimum clearance, phase-to-phase Up Asymmetrical breaking current s DC component in % of the rated short-circuit breaking current Isc Operating cycle diagram no. (see page 57) 3 mm mm tk Minimum creepage distance, phase-to-earth Rated short-duration power-frequency withstand voltage A Rated short-circuit breaking current Ir Rated duration of short-circuit O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. 50/60 Hz Minimum creepage distance, interrupter Rated lightning impulse withstand voltage Ima 24 kV Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) Rated short-circuit making current (at 50/60 Hz) Electrical data, dimensions and weights 16 N/P 16 N/P 17 N/P 17 N/P 17 N/P 18 N/P 18 N/P 18 N/P 18 N/P 19 N/P 19 N/P 19 N/P 19 N/P 17 R/T 17 R/T 17 S/T 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 58 SION Vacuum Circuit-Breakers Technical Data % 3AE1 353-1 ... 800 310 275 n 3 20 36 22.4 3AE1 353-2 ... 1250 310 275 n 3 20 36 22.4 3AE1 353-4 ... 2000 310 275 n 3 20 36 22.4 3AE1 353-6 ... 2500 310 275 n 3 20 36 22.4 3AE1 354-1 ... 800 310 275 n 3 25 36 28 3AE1 354-2 ... 1250 310 275 n 3 25 36 28 3AE1 354-4 ... 2000 310 275 n 3 25 36 28 3AE1 354-6 ... 2500 310 275 n 3 25 36 28 3AE1 724-2 ... 1250 320 210 n 3 25 36 28 3AE1 754-6 ... 2500 320 275 n 3 25 36 28 n Standard acc. to IEC 62271-100 Possible mV 18 R/T 18 R/T 18 S/T 18 S/T 19 R/T 19 R/T 19 S/T 19 S/T 200 350 200 210 120/ – – 19 –/– 200 340 200 205 150/ – – 19 –/– kg 130/ 180 130/ 180 150/ 200 150/ 200 130/ 180 130/ 180 150/ 200 150/ 200 50 2.6 200 350 265 210 125 50 2.6 200 350 265 210 125 50 2.0 200 340 265 205 125 50 2.0 200 340 265 205 125 50 2.6 200 350 265 210 125 50 2.6 200 350 265 210 125 50 2.0 200 340 265 205 125 50 2.0 200 340 265 205 125 50 2.6 125 50 2.0 Detailed dimension drawing (has to be ordered) 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 3M 442 02053 001 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 3M 442 02053 001 mm mm mm mm 125 – Not available as slide-in module Weight 1) (fixed-mounted circuit-breaker/slide-in module) kV Minimum clearance, phase-to-earth kV Minimum clearance, phase-to-phase kA 50/ 52 50/ 52 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 63/ 65 63/ 65 Minimum creepage distance, phase-to-earth kA Minimum creepage distance, interrupter kA Ud Voltage drop ΔU between connections (according to IEC 60694 at DC 100 A) s Up Catalog dimension drawings (see page 58) (fixed-mounted circuit-breaker/slide-in module) mm mm Ima Operating cycle diagram no. (see below) A Rated short-duration power-frequency withstand voltage Isc Rated lightning impulse withstand voltage O - 0.3 s - CO - 15 s - CO O - 0.3 s - CO - 3 min - CO Rated operating sequence: O - 3 min - CO - 3 min - CO Pole-center distance Width across flats Rated normal current Order No. Ir Rated short-circuit making current (at 50/60 Hz) Rated short-circuit breaking current tk 50/60 Hz Asymmetrical breaking current Rated duration of short-circuit 24 kV DC component in % of the rated short-circuit breaking current Electrical data, dimensions and weights 1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 58 Operating cycle diagrams for 24 kV electrical operating cycles 20 000 10 000 is shown as a function of 10 000 (r.m.s. value). All SION vacuum circuit-breakers 2 000 fulfil the endurance classes 1 000 E2, M2 and C2 according 500 1 000 500 curve shape beyond the 200 200 parameters defined in 100 IEC 62271-100 is based on 50 20 10 0.5 2 000 to IEC 62271-100. The 16 1 2 18 5 10 12.5 20 kA Breaking current (r.m.s. value) HG11-2538b_en eps 150 5 000 50 average experience data. The number of operating cycles that can actually be reached can be different depending on the respec- 90 100 50 30 20 10 0.5 17 1 2 19 HG11-2542a_en eps the breaking current 5 000 Operating cycle No. Operating cycle No. The permissible number of 20 000 5 10 16 25 kA 50 Breaking current (r.m.s. value) tive application. Siemens HG 11.02 · 2008 57 3 SION Vacuum Circuit-Breakers Technical Data Dimensions drawings for voltage level 24 kV Dimension drawings for 24 kV a 570 210 424 ca.93 210 HG11-2532 eps 420 107 739 310 269 d Dimension drawing N 794 210 210 187 850 820 ca. 25 kg PCD a c d Pole-center distance Width of drawout element Total width across wheels Distance between wheels 310 700 275 739 310 540 739 283 283 58 269 788 810 41.5 27.5 346 485.5 1013 1040.5 30 275 222 310 994 275 332 532 112 100 HG11-2536b_en eps Dimension drawing S 27.5 Dimension drawing R 360 468 275 HG11-2535 eps 420 540 739 739 310 ca.93 275 269 Siemens HG 11.02 · 2008 879 27.5 700 275 58 275 ca.93 420 HG11-2534 eps 41.5 788 810 27.5 Dimension drawing P Dimension drawing T ca. 20 kg 332 346 485.5 1013 1040.5 30 360 468 Weight 620 HG11-2533b_en eps 532 58 d 650 Dimension drawing of slide-in module 112 100 3 c 679 HG11-2590 eps c 283 360 468 a 210 Height of drawout element: 60 540 739 58 PCD SION Vacuum Circuit-Breakers Technical Data Operating times, short-circuit protection of motors, consumption data of releases Operating times at rated voltage of the secondary circuit Vacuum circuit-breaker equipment Equipment of circuit-breaker Closing time Opening time – 1st shunt release 2nd release – 1st shunt release 2nd release – 1st shunt release 2nd release Closing solenoid 1st shunt release 2nd release 1st shunt release 2nd release Arcing time Break time Dead time CLOSE/OPEN contact time Minimum command duration Pulse time for circuit-breaker tripping signal Operating time < 75 ms < 65 ms < 50 ms < 15 ms < 80 ms < 65 ms 300 ms < 75 ms < 60 ms 45 ms 40 ms 20 ms > 15 ms > 10 ms < 10 s 2 ms Charging time for electrical operation Synchronism error between the poles Short-circuit protection of motors (fuse protection of drive motors) Rated voltage of the motor V 24 DC 48 DC 60 DC 110 DC 220 DC 110 AC 230 AC Operating voltage max. V 26 53 66 121 242 121 244 Power consumption of the motor min. V 20 41 51 93 187 93 187 W (at DC) 350 350 350 350 350 – – Smallest possible rated current1) of the m.c.b. (miniature circuit-breaker) with C-characteristic VA (at AC) – – – – – 400 400 3 A 8 6 4 2 1.6 2 1.6 1) The current inrush in the drive motor can be neglected due to its very short presence Consumption data of releases Release Power consumption Tripping ranges Operation at Closing solenoid 3AY15 10 1st shunt release (without energy store) 3AY15 10 2nd shunt release (with energy store) 3AY11 01 Undervoltage release 3AY11 03 Current-transformer operated release 3AX11 02 (rated normal current 0.5 A or 1 A) Current-transformer operated release 3AX11 04 (tripping pulse W 0.1 Ws) Tripping voltage DC approx. W 140 140 AC 50/60 Hz approx. VA 140 140 at DC Tripping voltage or tripping current at AC 50/60 Hz 85 to 110 % U 70 to 110 % U 85 to 110 % U 85 to 110 % U 70 50 70 to 110 % U 85 to 110 % U 20 – 20 10 2) 35 to 35 to 0 % U 90 to 110 % Ia – – 0%U – – – 2) Consumption at pickup current (90 % of the rated normal current) and open armature Siemens HG 11.02 · 2008 59 SION Vacuum Circuit-Breakers Technical Data Circuit diagrams Basic equipment X1 21 -K1 22 -K1 A1 -M1 M 1= 22 31 14 32 -K1 A1 -Y9 D2 13 21 22 A1 A2 -S1 A2 23 11 -S4 12 22 -S22 13 21 14 22 -Y1 A1 -S1 -S1 24 11 13 21 23 31 33 41 43 51 53 61 63 12 14 22 24 32 34 42 44 52 54 62 64 HG11-2506 eps A2 21 HG11-2505 eps -S21 -S3 21 X1 Motor Closing and anti-pumping Signal “closing 1st shunt operating for motor operating spring charged“ release mechanism stored-energy mechanism Auxiliary switch 6 NO + 6 NC Additional equipment X0 X1 X0 X1 -K1 -Y9 -S5 13 22 31 14 32 A1 -K1 22 13 -S6 A1 A2 -S1 A2 13 -S1 12 HG11-2507 eps HG11-2508a eps 14 -S12 13 14 X1 X0 14 11 Closing and anti-pumping for motor operating stored-energy mechanism X1 X0 11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123 12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124 -X0 Circuit-breaker tripping signal Auxiliary switch 12 NO + 12 NC Additional equipment: Releases (for possible combinations see chapter 2 under “Secondary equipment“) X0 X1 X0 X1 X0 X1 X0 X1 -Y7 D2 34 A2 X1 X0 2nd shunt release X1 X0 -Y6 A2 X1 X0 Current-transformer operated release 0.5 A or 1 A -S1 A1 43 44 A2 Low-energy currenttransformer operated release 0.1 Ws -R1 1 2 X1 X0 HG11-2513 eps -Y4 A1 HG11-2512 eps -Y2 D1 33 HG11-2511 eps -S1 A1 HG11-2510 eps 3 -S3 21 HG11-2509 eps -K1 -X0 21 Undervoltage release Legend K1 M1 R1 S1 S12 S21 S22 Contactor (anti-pumping) Motor operating mechanism Resistance Auxiliary switch Mechanical interlocking Position switches (to de-energize the motor operating mechanism after charging S3 S4 S5 S6 X0 Position switch (anti-pumping) Position switch (for closing spring charged) Electrical closing lock-out Circuit-breaker tripping signal Plug connector, 24-pole or 64-pole X1 Y1 Y2 Y4 Y6 Terminal strip, 27-pole 1st shunt release 2nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Current-transformer operated release (tripping pulse W W 0.1 Ws) The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring 60 Siemens HG 11.02 · 2008 Y7 Y9 Undervoltage release Closing solenoid Abbreviations: NC Normally closed NO Normally open SION Vacuum Circuit-Breakers Annex Contents Contents Page Annex 61 Inquiry form 62 Configuration instructions 63 Foldout page R-HG11-181.tif Configuration aid Brandenburg Gate, Berlin, Germany R-HG11-180.eps 4 Switchgear Factory in Berlin, Germany Siemens HG 11.02 · 2008 61 SION Vacuum Circuit-Breakers Annex Inquiry form Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/SION Inquiry concerning o SION standard circuit-breaker o SION slide-in module Technical data o 7.2 kV o 24 kV o 12 kV Rated lightning impulse withstand voltage o 60 kV o 125 kV o 75 kV Rated short-duration power-frequency withstand voltage o 20 kV o 42 kV o 28 kV o 50 kV o 38 kV o 55 kV o _ _ _ kV Rated short-circuit breaking current o 12.5 kA o 25 kA o 16 kA o 31.5 kA o 20 kA o 40 kA o _ _ _ kA Rated normal current o 800 A o 2500 A o 1250 A o 3150 A o 2000 A Pole-center distance o 150 mm o 160 mm o 210 mm Width across flats o 205 mm o 275 mm o 310 mm Rated voltage Please o Submit an offer o Call us o Visit us Other values o 17.5 kV o _ _ _ kV o 95 kV o _ _ _ kV o _ _ _ kA o 275 mm Your address Secondary equipment Company Dept. For possible combinations see pages 23 to 26 or 32 to 35 Circuit-breaker equipment (only for standard circuit-breaker) o Fixed mounting o With drawout element o Drawout element, contact arms o Drawout element, contact arms, bushings Motor operating mechanism o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz Closing solenoid o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz st shunt release 1 o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz 2nd shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz Current-transformer operated release o Undervoltage release o _ _ _ V DC o AC _ _ _ V, _ _ _ Hz Auxiliary switch o 6 NO + 6 NC o 12 NO + 12 NC Low-voltage connection o 27-pole terminal strip o 24-pole plug o 64-pole plug o French o Spanish Name Street Postal code/city Phone Fax E-mail 4 Siemens AG o Mechanical interlocking o Circuit-breaker tripping signal o Electrical closing lock-out Dept. o Operating instructions o English o German Name Street Application and other requirements Postal code/city Fax o Please check off 62 Siemens HG 11.02 · 2008 _ _ _ Please fill in For configuration of your SION vacuum circuit-breaker 1 3 4 5 9 10 11 12 – 13 14 15 16 – – + + + + + + + + These ratings define the positions 5 to 8 of the order number 3 A E 1 2nd step: Definition of the secondary equipment (see pages 23 to 26 and pages 32 to 35) 3 A E Please specify the following equipment features: Possible options: Release combination (position 9) Closing solenoid (position 10) Operating voltage of the releases (positions 11 / 12) Installation accessories (position 13) Motor operating mechanism (position 14) Number of auxiliary contacts (position 15) Design of the control cable connection (position 15) Mechanical interlocking, circuit-breaker tripping signal (position 15) Language of the documentation (position 16) Frequency of the operating voltage of the secondary equipment at AC (position 16) Shunt release, current-transformer operated release and undervoltage release Operating voltages from 24 V DC to 240 V AC Operating voltages from 24 V DC to 240 V AC 3 A E – + + + + + + + + 1 – – + + + + + + + + 1 Fixed mounting; with drawout element, contact arms, contact system; slide-in module Operating voltages from 24 V DC to 240 V AC – – – + + + + + + + + 6 NO + 6 NC, 12 NO + 12 NC 3 A E 1 – – 27-pole terminal strip, 24-pole plug connector 64-pole plug connector With or without + + + + English, German, French, Spanish + + + + 50 Hz/60 Hz 3 A E 1 These equipment features define the positions 9 to 16 of the order number 3 A E Should you still need more options than the possible special equipment like halogen-free and flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc., please contact your responsible sales partner. 3 A E Siemens HG 11.02 · 2008 63 – + + + + + + + + 1 3rd step: Do you have any further requirements concerning the equipment? (Please refer to pages 27 and 36) 3 A E – – – + + + + + + + + 1 – – + + + + + + + + 1 – – + + + + + + + + See page 27 or 36 See page 26 or 35 1 See page 25 or 34 See page 26 or 35 7.2 kV to 24 kV 60 kV to 125 kV 20 kV to 55 kV 12.5 kA to 40 kA 800 A to 3150 A 150 mm to 275 mm 205 mm to 310 mm 8 See page 25 or 34 Ur: Up: Ud: Isc: Ir: – See page 24 or 33 Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (Isc) Rated normal current (Ir) Pole-center distance Width across flats See page 15 or 28 to Possible options: 7 3 A E 1st step: Definition of the primary part (see pages 15 to 22 and pages 28 to 31) Please specify the following ratings: 6 1 n n n – n n n n n – n n n n – Z See page 24 or 33 Instruction for configuration of the SION vacuum circuit-breaker 2 3 A E See page 23 or 32 See page 23 or 32 Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use our prompted online configurator under www.siemens.com/SION. page 22 or 31 You prefer to configure your SION vacuum circuit-breaker on your own? Published by and copyright © 2008: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Medium Voltage Nonnendammallee 104 13623 Berlin, Germany www.siemens.com/SION For more information, please contact our Customer Support Center. Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com KG 08.08 0.0 66 En 6101/13187 103217 All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. Responsible for General editing: Siemens AG, E CC MCC R Erlangen www.siemens.com/energy R-HG11-182.tif Technical contents: Siemens AG, E D MV C Berlin