281300S41 ACCESS CONTROL - Central Host Head End Computer 1. LOCATION Host Computer located at 305 Euclid or as designated by Construction Administrator 2. HARDWARE MS DOS/Workgroups for Windows Based System (latest version) 1. IBM compatible PC 80486 66 Mhz. minimum Note: Complete PC and the cards in it must be industry standard off-the-shelf design with no proprietary modifications and must be manufactured by a recognized reputable manufacturer of national prominence. 2. Expansion slots - 8 min, 2-32 bit and 6-16 bit. 3. System Memory - 4 megabytes minimum, 640KB conventual,384KB Shadow/ext., 1 MB expanded, and 2 MB extended. 4. Hard Drive Provide 420 megabyte (formatted) minimum, 12 ms maximum access time. 5. Floppy Disk drives (2 minimum) 1. 3.5 inch 1.44 megabyte, TEAC or equivalent 2. 5.25 inch 1.2 megabyte TEAC or equivalent 6. I/O ports and adapters 1. Serial ports (COM), 3 minimum Dedicated to controller communication (listed in order of preference) 1. RS-485 hardwired 2. RS-232 Short haul modem 3. RS-232 UB (Ungermann-Bass)/LAN system 4. RS-232 dial up modem 2. RS-232 for modem. 3. RS-232 for Serial mouse 1. 2. Centronics parallel port (LPT) for Local printer (1 minimum) 3. Ethernet, IEEE 802.3 10 Base-T compatible, Western Digital 16 bit WD8003E or equal, subnetted. 4. VGA 15" non-interlaced monitor and 16 bit adapter, 1024x768 minimum. 3. INPUT/OUTPUT AND PERIPHERAL DEVICES 1. 2. 3. 4. NEC 2A Monitor or equal 101 enhanced Keyboard Epson LQ1050 Printer or equal Microsoft 3 button serial port mouse or equal 281300S41- ACCESS CONTROL - Central Host Head End Computer Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 1 of 2 281300S41 ACCESS CONTROL - Central Host Head End Computer 4. COMMUNICATIONS 1. Dedicated to Building Controller 1. Hardwired connections (default) RS-485 2. Short haul modem RS-232 3. UK's UB (Ungermann-Bass) LAN System RS-232 4. Dial up phone line modem 1. 9600 baud, RS-232, CCITT V.32V/V.22bis/V.22, Bell 212A and 103, Hayes and MNP-5 compatible modem 2. 2400 baud, RS-232, CCITT V.22bis/V.22, Bell 212A and 103, Hayes and MNP-5 compatible 2. Communications with other computers 1. UK's UB (Ungermann-Bass) LAN system 1. UTP (default) 2. ThinNet (optional) 2. Dial-up phone line modem, RS-232 1. 9600 baud 2. 2400 baud 5. SOFTWARE MS DOS based Host Computer and Remote Building Computer 1. Operating System - MS DOS/Workgroups for Windows (most current version) 2. Application Software 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Graphic display Compatible with operating system 256 controller capacity minimum 65,000 cards minimum 512 levels of access minimum 2048 alarm points minimum 1024 output control relays minimum 512,000 historic events minimum 32 time zones per controller minimum 32 holidays per controller minimum 2048 action messages minimum Ability to download data (nonstandard) from other systems Ability to uploaded to the controllers. English text help screen and alarm annunciation 281300S41- ACCESS CONTROL - Central Host Head End Computer Dated: 12/2015 Applies to: Med Center/Hospital Only University of Kentucky Page 2 of 2