281300S44 ACCESS CONTROL Building PC For Local Control (optional)

advertisement
281300S44 ACCESS CONTROL
Building PC For Local Control (optional)
1.
Location
Building PC for Local Control to be located in the building with the Controller or any other building as
designated by Construction Administrator
2.
Hardware
MS-DOS Based System (default)
1.
IBM compatible PC 80486SX 33 Mhz. minimum (default)
Note:
Complete PC and cards in it must be industry standard off-the-shelf design with no
proprietary modifications and must be manufactured by a recognized reputable manufacturer
of national prominence.
2.
Expansion slots, 8 minimum, 2-8 bit and 6-16 bit.
3.
MS-DOS System Memory, 8 megabytes min., 640K conv.,384K Shadow/ext., 1 MB expanded,
and 6 MB extended.
4.
Hard drive
MS-DOS System, provide 120 megabyte (formatted) minimum, 15 ms maximum access time.
5.
Floppy Disk drives, 2 minimum
1.
2.
6.
3.5 inch 1.44 megabyte, TEAC or equivalent
5.25 inch 1.2 megabyte TEAC or equivalent
I/O ports and adapters
1.
Serial ports (COM), 3 minimum
Dedicated to controller communication
(listed in order of preference)
1.
RS-485 hardwired
2.
RS-232 Short haul modem
3.
RS-232 UB (Ungermann-Bass)/LAN system
4.
RS-232 dial up modem
2.
RS-232 for modem.
3.
RS-232 for Serial mouse
1.
3.
2.
Centronics parallel port (LPT) for Local printer, 1 minimum.
3.
Ethernet, IEEE 802.3 10 Base-T compatible, Western Digital 16 bit WD8003E or equal.
4.
VGA 14" non-interlaced monitor and 16 bit adapter, 1024x768 minimum.
INPUT/OUTPUT AND PREPHRIAL DEVICES
1.
2.
3.
4.
NEC 2A Monitor or equal
101 enhanced Keyboard
Epson LQ1050 Printer or equal
Microsoft 3 button serial port mouse or equal
281300S44 ACCESS CONTROL Building PC For Local Control (optional)
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 1 of 2
281300S44 ACCESS CONTROL
Building PC For Local Control (optional)
4.
COMMUNICATIONS
1.
Building Controller
1.
Dedicated to Host (listed in order of preference)
Hardwired connections
1. RS-485
2.
Short haul modem
1. RS-232
3.
UK's UB (Ungermann-Bass) LAN System
1. RS-232
4.
Dial up phone line modem
14400 baud, RS-232, CCITT V.32V/V.22bis/V.22, Bell 212A and 103, Hayes and MNP-5
compatible modem
1.
2.
1.
2.
3.
2.
1.
To Silent Knight 9000
RS-232, Digital dialer (refer to UK Standard 16720S01).
Building PC for local control
Hardwired to Building Controller
1.
RS-232
2.
RS-485
2.
1.
5.
UK's UB (Ungermann-Bass) LAN system
RS-232
SOFTWARE
1.
Operating system for Building PC for local control (optional) is to be the latest version of MS
DOS (v6.2 or later).
2.
1.
2.
3.
4.
5.
6.
7.
6.
Hardwired to Local Control PC
RS-232
RS-485
Application for Building PC for local control (optional)
Multitasking
Compatible with operating system
2048 action messages minimum
Graphic display
Ability to download data (nonstandard) from other systems
Ability to uploaded to the controllers.
English text help screen and alarm annunciation
FIRMWARE
EEPROMS in the controllers used as a memory storage device for card numbers and related
information so that that information can be downloaded from the host computer, a remote computer, or
a hand held programmer.
281300S44 ACCESS CONTROL Building PC For Local Control (optional)
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
Page 2 of 2