– Administrative 281300S42 ACCESS CONTROL Remote Building Computer Office

advertisement
281300S42 ACCESS CONTROL Remote Building Computer – Administrative
Office
1. LOCATION
Remote Building Computer located in the building with the card access system or at a remote
administrative office as designated by Construction Administrator
2. OPERATING SYSTEM
MS DOS/Workgroups for Windows Based System (default)
3. HARDWARE
1. IBM compatible PC 80486 66 Mhz. min (default for workstation)
IBM compatible PC Pentium (P-66) 66 Mhz. min. (default for server)
Note: Complete PC and the cards in it must be industry standard off-the-shelf design with no
proprietary modifications and must be manufactured by a recognized reputable manufacturer of
national prominence.
2. Expansion slots, 8 min, 2-32 bit and 6-16 bit.
3. MS-DOS System Memory, 8 megabytes minimum, 640K conv.,384K Shadow/ext., 1 MB
expanded, and 6 MB extended.
4. Hard drive
MS-DOS System, provide 420 megabyte (formatted) minimum, 12 ms maximum access time.
5. Floppy Disk drives, 2 minimum
1. 3.5 inch 1.44 megabyte, TEAC or equivalent
2. 5.25 inch 1.2 megabyte, TEAC or equivalent
6. I/O ports and adapters
1. Serial ports (COM), 3 minimum
1. Dedicated to controller communication (listed in order of preference)
1. RS-485 hardwired
2. RS-232 Short haul modem
3. RS-232 UB (Ungermann-Bass)/LAN system
4. RS-232 dial up modem
2. RS-232 for modem.
3. RS-232 for Serial mouse
2. Centronics parallel port (LPT) for Local printer, 1 minimum.
3. Ethernet, IEEE 802.3 10 Base-T compatible, Western Digital 16 bit WD8003E or equal.
4. SVGA 15" non-interlaced monitor and 16 bit adapter, 1024x768 minimum.
7. Input/Output and Peripheral Devices
1. NEC 4FGE Monitor or equal
2. 101 enhanced Keyboard
3. Epson LQ1050 Printer or equal
4. Microsoft 3 button serial port mouse or equal
281300S42 ACCESS CONTROL Remote Building Computer – Administrative Office Page 1 of 2
Dated: 12/2015
Applies to: Med Center/Hospital Only
University of Kentucky
281300S42 ACCESS CONTROL Remote Building Computer – Administrative
Office
4. COMMUNICATIONS TO HOST AND/OR BUILDING CONTROLLER
1. UK's UB (Ungermann-Bass) LAN system (default) RS-232/async
2. Dial-up phone line modem14,400 baud
5. SOFTWARE
MS-DOS Based Remote Building Computer
1. Operating System - Latest version of M-DOS
2. Application Software
01. Graphic display
02. Compatible with operating system
03. 256 controller capacity minimum
04. 65,000 cards minimum
05. 512 levels of access minimum
06. 2048 alarm points minimum
07. 1024 output control relays minimum
08. 512,000 historic events minimum
09. 32 time zones per controller minimum
10. 32 holidays per controller minimum
11. 2048 action messages minimum
12. Ability to download data (nonstandard) from other systems
13. Ability to uploaded to the controllers.
14. English text help screen and alarm annunciation