Installation Instructions SuperSwitch® Ultrasonic Wall Switch 120/277 VAC General Information

advertisement
Installation Instructions
SuperSwitch® Ultrasonic Wall Switch
Model # OSW-U-0721-MV-A
Model # OSW-U-0721-MV-V
Model # OSW-U-0721-MV-W
120/277 VAC
Ultrasonic
Activated
P/N 9850-000408-00
Wiring
• Notforusewheretemperaturesfallbelow32°For
TheOSW-U-0721-MVisdesignedforofficesupto300squarefeet.Wallswitchesarenormallymountedoff-centerin
exceed100°F
aroomwhichreducesthecoverageattainable.
• Forindooruseonly
• NoleakagetoloadinOFFmode
Specifications
Technology:Ultrasonic
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–Max.load:6.7amps,
800W,60Hz
• Fluorescent/Ballast–Max.load:6.7amps,800W,
60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/MagneticBallast–Max.load:4.3
amps,1200W,60Hz
Ballast Compatibility:Compatiblewithmagneticballasts
No Minimum Load Requirement
Time Delays:15secondsto15minutes
24’
24'
(7.31m)
7.31m
Sensor
Coverage:Majormotion–500sq.ft.
Minormotion–300sq.ft.
Operating Environment:
• Temperature:60°F–80°F(15°C–26°C)
• RelativeHumidity:Lessthan95%non-condensing
Forindooruseonly
Housing:Durable,injectionmoldedhousing.ABSresin
complieswithUL94V-O.
Size:
• MountingPlateDimensions:
4.15”Hx1.94”W(105.41mmx49.28mm)
• ProductHousingDimensions:
2.73”Hx1.8”Wx1.8”D
(69.34mmx45.72mmx45.72mm)
LED Indicators:RedLEDforUltrasonicdetection
Description
OSW-U-0721-MVisaself-containedmotion-sensinglightingcontroldevicethatreplacesaconventionalwall
switchforenergysavingsandconvenience.Built-insensorsproducelowintensity,inaudiblesoundanddetect
changesinsoundwavescausedbymotion,suchaswalkingintotheroom,reachingforatelephone,turningina
chair.Thesensordoesnotrespondtoaudiblesound.LightsturnOFFautomaticallyafteraroomisvacated.
ThedeviceoffersachoiceofAutomaticONorManualONmodes.IntheAutomaticONmode,thelightsturn
ONautomaticallywhenapersonenterstheroom.IntheManualONmode,lightsareturnedONbypressingthe
touchplateONtheswitch.Modescanbechangedbyflippingtheconcealedswitchunderthetouchplate.
(SeeCheckoutandAdjustment).Ineithermode,lightswillremainONaslongasmotionisdetectedintheroom.
Whennomotionisdetected,thelightswillturnOFFautomaticallyafterthepre-settimedelay.Followingthis,a
“graceperiod”ofapproximatelytensecondsallowslightstobeturnedONagainbymotion.
Atanytime,lightsmaybeturnedOFFwhiletheroomisoccupiedbypressingthetouchplate.OSW-U-0721-MVis
fullyself-resetting;lightsturnedOFFmanuallyinAutomaticONmodewillstayOFFwhiletheroomremainsoccupied.
Aftertheroomisvacatedandthepre-settimedelayandgraceperiodhaveelapsed,thelightswillremainOFFuntil
turnedONautomaticallythenexttimesomeoneenterstheroom.
OSW-U-0721-MVcanbeusedwithastandardtoggleswitchtosplitthelightingloadforroomsthatarewiredfor
twoswitchesasshownintheWiringDiagram.
15’
10’
20’
20'
6.09m
(6.09m)
25'
25’
(7.62m)
7.62m
30'
30’
(9.14m)
9.14m
Location
WheninstallingtheOSW-U-0721-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof
sightbetweentheOSW-U-0721-MVandtheareatobecovered.AvoidpointingtheOSW-U-0721-MVdirectlyintothe
hallwaywhereitmaydetectpassers-by.
Installation
TheOSW-U-0721-MVcanreplaceoneswitchinanystandardsingleor
doublegangbox.Itmaybeinstalledinthesamemannerasanordinarywall
switch.
Forsafetypurposesbeforeinstallingordoinganyserviceonthe
OSW-U-0721-MV,thepowermustbeturnedOFFatthecircuitbreakerpanel.
WiretheOSW-U-0721-MVasdescribedinthewiringsection.
MounttheOSW-U-0721-MVinthejunctionbox.
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at
the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch
for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in
compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
CAUTION: Model OSW-U-0721-MV is for use with either 120 VAC or 277 VAC only. For other voltages refer to
product spec sheet. Do not wire to control receptacle circuits.
VERIFYthattheconnectedloaddoesnotexceedtheOSW-U-0721-MVratings.Thereisnominimumload
requirement.Usetwist-onwireconnectorsforallconnections.ModelOSW-U-0721-MVcanbewiredtocontrol
bothanexhaustfanandlightingprovidedthetotalloaddoesnotexceedthemaximumloadrating(inAmps)forthe
automaticwallswitch.
1.Connectthewhiteleadtotheneutral.
2.ConnecttheredleadtotheswtichlegforLoad1andtooneterminalofthetoggleswitch.
3.ConnecttheothertoggleswitchterminaltotheswitchlegforLoad2.
4.Connecttheblackwiretothehotlead.
Note: Connectionsarepolaritysensitive.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one
circuit to the OSW-U-0721-MV. Split one circuit into two switch legs and cap the unused hot lead inside the box.
The OSW-U-0721-MV must always control Load 1, while its control of Load 2 is selected manually by opening and
closing the toggle switch.
Wiring Diagram 1: Single Level Switching
*HOT - 120/277VAC
*HOT
RED
BLACK
LIGHTING
LOAD
WHITE
• Readallinstructionsonbothsidesofthissheet
first
• Planallcomponentlocationscarefully
• Installinaccordancewithalllocalcodes
• Onemodelforeither120VACor277VAC
Coverage
NEUTRAL
Wiring Diagram 2: Dual Level Switching using additional toggle switch
*HOT - 120/277VAC
*HOT
RED
BLACK
LIGHTING
LOAD
NEUTRAL
LIGHTING
LOAD
WHITE
General Information
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Wiring Diagram 3: For Three-Way Wiring
4.Leavetheroom.Thelightsshouldgooutinapproximately15seconds.Waitatleast12secondsafterthelights
goout.WalknormallybackintotheroomandverifythatthelightsturnONautomatically.Ifnot,the“EntryRange”
shouldbeincreasedslightly.Donotsethigherthannecessary.
5.IftheLEDblinksorstaysONwhenthereisnomovementintheroom,itispossiblethatthesensorisbeing
activatedbyairflowfromtheHVACsystem.Reducethe“AreaRange”settinguntiltheLEDgoesOFFandstaysOFF
withnomotion.
6.Ifthesensorisactivatedbypassers-byinthehallway,reducethe“EntryRange”setting.
7.Set“TimeDelay”tothedesiredsettingfornormaluse.Iflightsgooutwhiletheroomisoccupied,increasesetting
slightlyuntilanoptimumintervalisobtained.Recommendedtimedelayisusually6-8minutes(approximately12
o’clockto1o’clock).Peoplewhoremainverystillforlongperiodsmayneedalongertimedelay.
8.Ifpreferred,ModelOSW-U-0721-MVcanbesettoManualONformaximumenergysavingsbymovingthe“Mode”
switchtothe“M”position.Inthissetting,occupantmustpushthetouchplatetoturnONlightsuponenteringthe
room.
120 VAC or 277 VAC
TRAVELLERS
BLACK
RED
WHITE
BLACK
RED
WHITE
LOAD
NEUTRAL
Override
AnoverridejumperislocatedunderneaththeOSW-U-0721-MVtouchplate.Thisjumpershouldremaininplaceatall
times,exceptintheeventofunitmalfunction.RemovethejumpertobypassthesensorandturnthelightsON.
NEUTRAL
Checkout and Adjustment
Onceinstallationiscomplete,restorepowertothelightingcircuit.ProperoperationoftheOSW-U-0721-MVmust
beverified.Controlscanthenbeadjustedfortheindividualuser.AdjustmentsshouldbemadewiththeHVACsystem
ON.
Note:Useonlyinsulatedtoolstomakeadjustments.
LED will not turn ON
Verifythatthelightingcircuithaspower.VerifythattheOSW-U-0721-MVisproperlyadjusted.Pressthe
touchplatetomanuallyturnONthelights.IfLEDdoesnotlight,replaceOSW-U-0721-MV.
Lights will not turn ON
IfthelightswillnotturnONautomaticallyaftersomeoneenterstheroom,pressthetouchplatetoseeiflights
willturnON.Ifso,theOSW-U-0721-MVcouldbesettotheManualONmode.Checkunderthetouchplatetoverify
thesetting.IfOSW-U-0721-MVissettoAutomaticONmode,itmayhavebeenoverriddenbysomeonepressing
thetouchplate;allowtheOSW-U-0721-MVtotimeouttoverifynormaloperation.IfthelightsdonotturnONafter
pressingthetouchplate,confirmthatnootherswitchesorequipmentareinterruptingorbypassingpowertothe
OSW-U-0721-MVortheload.IflightsstilldonotturnON,replacetheOSW-U-0721-MV.
Lights will not turn OFF
IfthelightswillnotturnOFFafterthetimedelayset,andtheLEDhasnotlitduringthetimeperiod,pressthe
touchplatetomanuallyturnOFFthelights.IflightsturnOFF,refertoitems5and6aboveunder“Checkoutand
Adjustment.”IflightsdonotturnOFF,verifythattheoverridejumperunderthetouchplatehasnotbeenremoved.
ConfirmthatnootherswitchesorequipmentareinterruptingorbypassingpowertotheOSW-U-0721-MVorthe
load.IflightsstilldonotturnOFF,replacetheOSW-U-0721-MV.
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
M
Area
3
50
Range
Entry
A
Time
Delay
50
3
503
1.Adjustmentcontrolsareunderthetouchplate.“TimeDelay”ranges
from1/4minute(15seconds),forinstallertesting,to15minutes.
Usingasmallscrewdriver,set“TimeDelay”to1/4minutebyturning
thecontrolcompletelycounterclockwiseuntilitstopsatminimum
setting(approximately8o’clock).Turncontrolfor“AreaRange”until
flatedgeofcontrolisat10o’clock.Turn“EntryRange”untilflat
edgeofcontrolisat9o’clock.
2.Movethe“Mode”switchtothe“Auto”or“A”position.
3.Theareaofcoveragecanbedeterminedbywatchingthe
LEDindicatoronthefrontofOSW-U-0721-MVwhilemoving
aroundtheroom.TheLEDlightsonlywhenthesensoris
detectingmotion.Adjustthe“AreaRange”controltothe
lowestsettingthatprovidesadequatemotiondetection
ofapersonworkingintheroom.Donotsethigherthannecessary.
Troubleshooting
1/4
15
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com