Installation Instructions SuperSwitch® Ultrasonic Wall Switch Model # OSW-U-0721-MV-A Model # OSW-U-0721-MV-V Model # OSW-U-0721-MV-W 120/277 VAC Ultrasonic Activated P/N 9850-000408-00 Wiring • Notforusewheretemperaturesfallbelow32°For TheOSW-U-0721-MVisdesignedforofficesupto300squarefeet.Wallswitchesarenormallymountedoff-centerin exceed100°F aroomwhichreducesthecoverageattainable. • Forindooruseonly • NoleakagetoloadinOFFmode Specifications Technology:Ultrasonic Electrical Ratings: 120VAC: • Incandescent/Tungsten–Max.load:6.7amps, 800W,60Hz • Fluorescent/Ballast–Max.load:6.7amps,800W, 60Hz MotorLoad:¼HP@125VAC 277VAC: • Fluorescent/MagneticBallast–Max.load:4.3 amps,1200W,60Hz Ballast Compatibility:Compatiblewithmagneticballasts No Minimum Load Requirement Time Delays:15secondsto15minutes 24’ 24' (7.31m) 7.31m Sensor Coverage:Majormotion–500sq.ft. Minormotion–300sq.ft. Operating Environment: • Temperature:60°F–80°F(15°C–26°C) • RelativeHumidity:Lessthan95%non-condensing Forindooruseonly Housing:Durable,injectionmoldedhousing.ABSresin complieswithUL94V-O. Size: • MountingPlateDimensions: 4.15”Hx1.94”W(105.41mmx49.28mm) • ProductHousingDimensions: 2.73”Hx1.8”Wx1.8”D (69.34mmx45.72mmx45.72mm) LED Indicators:RedLEDforUltrasonicdetection Description OSW-U-0721-MVisaself-containedmotion-sensinglightingcontroldevicethatreplacesaconventionalwall switchforenergysavingsandconvenience.Built-insensorsproducelowintensity,inaudiblesoundanddetect changesinsoundwavescausedbymotion,suchaswalkingintotheroom,reachingforatelephone,turningina chair.Thesensordoesnotrespondtoaudiblesound.LightsturnOFFautomaticallyafteraroomisvacated. ThedeviceoffersachoiceofAutomaticONorManualONmodes.IntheAutomaticONmode,thelightsturn ONautomaticallywhenapersonenterstheroom.IntheManualONmode,lightsareturnedONbypressingthe touchplateONtheswitch.Modescanbechangedbyflippingtheconcealedswitchunderthetouchplate. (SeeCheckoutandAdjustment).Ineithermode,lightswillremainONaslongasmotionisdetectedintheroom. Whennomotionisdetected,thelightswillturnOFFautomaticallyafterthepre-settimedelay.Followingthis,a “graceperiod”ofapproximatelytensecondsallowslightstobeturnedONagainbymotion. Atanytime,lightsmaybeturnedOFFwhiletheroomisoccupiedbypressingthetouchplate.OSW-U-0721-MVis fullyself-resetting;lightsturnedOFFmanuallyinAutomaticONmodewillstayOFFwhiletheroomremainsoccupied. Aftertheroomisvacatedandthepre-settimedelayandgraceperiodhaveelapsed,thelightswillremainOFFuntil turnedONautomaticallythenexttimesomeoneenterstheroom. OSW-U-0721-MVcanbeusedwithastandardtoggleswitchtosplitthelightingloadforroomsthatarewiredfor twoswitchesasshownintheWiringDiagram. 15’ 10’ 20’ 20' 6.09m (6.09m) 25' 25’ (7.62m) 7.62m 30' 30’ (9.14m) 9.14m Location WheninstallingtheOSW-U-0721-MVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearlineof sightbetweentheOSW-U-0721-MVandtheareatobecovered.AvoidpointingtheOSW-U-0721-MVdirectlyintothe hallwaywhereitmaydetectpassers-by. Installation TheOSW-U-0721-MVcanreplaceoneswitchinanystandardsingleor doublegangbox.Itmaybeinstalledinthesamemannerasanordinarywall switch. Forsafetypurposesbeforeinstallingordoinganyserviceonthe OSW-U-0721-MV,thepowermustbeturnedOFFatthecircuitbreakerpanel. WiretheOSW-U-0721-MVasdescribedinthewiringsection. MounttheOSW-U-0721-MVinthejunctionbox. CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes. NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling. CAUTION: Model OSW-U-0721-MV is for use with either 120 VAC or 277 VAC only. For other voltages refer to product spec sheet. Do not wire to control receptacle circuits. VERIFYthattheconnectedloaddoesnotexceedtheOSW-U-0721-MVratings.Thereisnominimumload requirement.Usetwist-onwireconnectorsforallconnections.ModelOSW-U-0721-MVcanbewiredtocontrol bothanexhaustfanandlightingprovidedthetotalloaddoesnotexceedthemaximumloadrating(inAmps)forthe automaticwallswitch. 1.Connectthewhiteleadtotheneutral. 2.ConnecttheredleadtotheswtichlegforLoad1andtooneterminalofthetoggleswitch. 3.ConnecttheothertoggleswitchterminaltotheswitchlegforLoad2. 4.Connecttheblackwiretothehotlead. Note: Connectionsarepolaritysensitive. CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit to the OSW-U-0721-MV. Split one circuit into two switch legs and cap the unused hot lead inside the box. The OSW-U-0721-MV must always control Load 1, while its control of Load 2 is selected manually by opening and closing the toggle switch. Wiring Diagram 1: Single Level Switching *HOT - 120/277VAC *HOT RED BLACK LIGHTING LOAD WHITE • Readallinstructionsonbothsidesofthissheet first • Planallcomponentlocationscarefully • Installinaccordancewithalllocalcodes • Onemodelforeither120VACor277VAC Coverage NEUTRAL Wiring Diagram 2: Dual Level Switching using additional toggle switch *HOT - 120/277VAC *HOT RED BLACK LIGHTING LOAD NEUTRAL LIGHTING LOAD WHITE General Information Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com Wiring Diagram 3: For Three-Way Wiring 4.Leavetheroom.Thelightsshouldgooutinapproximately15seconds.Waitatleast12secondsafterthelights goout.WalknormallybackintotheroomandverifythatthelightsturnONautomatically.Ifnot,the“EntryRange” shouldbeincreasedslightly.Donotsethigherthannecessary. 5.IftheLEDblinksorstaysONwhenthereisnomovementintheroom,itispossiblethatthesensorisbeing activatedbyairflowfromtheHVACsystem.Reducethe“AreaRange”settinguntiltheLEDgoesOFFandstaysOFF withnomotion. 6.Ifthesensorisactivatedbypassers-byinthehallway,reducethe“EntryRange”setting. 7.Set“TimeDelay”tothedesiredsettingfornormaluse.Iflightsgooutwhiletheroomisoccupied,increasesetting slightlyuntilanoptimumintervalisobtained.Recommendedtimedelayisusually6-8minutes(approximately12 o’clockto1o’clock).Peoplewhoremainverystillforlongperiodsmayneedalongertimedelay. 8.Ifpreferred,ModelOSW-U-0721-MVcanbesettoManualONformaximumenergysavingsbymovingthe“Mode” switchtothe“M”position.Inthissetting,occupantmustpushthetouchplatetoturnONlightsuponenteringthe room. 120 VAC or 277 VAC TRAVELLERS BLACK RED WHITE BLACK RED WHITE LOAD NEUTRAL Override AnoverridejumperislocatedunderneaththeOSW-U-0721-MVtouchplate.Thisjumpershouldremaininplaceatall times,exceptintheeventofunitmalfunction.RemovethejumpertobypassthesensorandturnthelightsON. NEUTRAL Checkout and Adjustment Onceinstallationiscomplete,restorepowertothelightingcircuit.ProperoperationoftheOSW-U-0721-MVmust beverified.Controlscanthenbeadjustedfortheindividualuser.AdjustmentsshouldbemadewiththeHVACsystem ON. Note:Useonlyinsulatedtoolstomakeadjustments. LED will not turn ON Verifythatthelightingcircuithaspower.VerifythattheOSW-U-0721-MVisproperlyadjusted.Pressthe touchplatetomanuallyturnONthelights.IfLEDdoesnotlight,replaceOSW-U-0721-MV. Lights will not turn ON IfthelightswillnotturnONautomaticallyaftersomeoneenterstheroom,pressthetouchplatetoseeiflights willturnON.Ifso,theOSW-U-0721-MVcouldbesettotheManualONmode.Checkunderthetouchplatetoverify thesetting.IfOSW-U-0721-MVissettoAutomaticONmode,itmayhavebeenoverriddenbysomeonepressing thetouchplate;allowtheOSW-U-0721-MVtotimeouttoverifynormaloperation.IfthelightsdonotturnONafter pressingthetouchplate,confirmthatnootherswitchesorequipmentareinterruptingorbypassingpowertothe OSW-U-0721-MVortheload.IflightsstilldonotturnON,replacetheOSW-U-0721-MV. Lights will not turn OFF IfthelightswillnotturnOFFafterthetimedelayset,andtheLEDhasnotlitduringthetimeperiod,pressthe touchplatetomanuallyturnOFFthelights.IflightsturnOFF,refertoitems5and6aboveunder“Checkoutand Adjustment.”IflightsdonotturnOFF,verifythattheoverridejumperunderthetouchplatehasnotbeenremoved. ConfirmthatnootherswitchesorequipmentareinterruptingorbypassingpowertotheOSW-U-0721-MVorthe load.IflightsstilldonotturnOFF,replacetheOSW-U-0721-MV. Warranties and Limitation of Liability Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions. M Area 3 50 Range Entry A Time Delay 50 3 503 1.Adjustmentcontrolsareunderthetouchplate.“TimeDelay”ranges from1/4minute(15seconds),forinstallertesting,to15minutes. Usingasmallscrewdriver,set“TimeDelay”to1/4minutebyturning thecontrolcompletelycounterclockwiseuntilitstopsatminimum setting(approximately8o’clock).Turncontrolfor“AreaRange”until flatedgeofcontrolisat10o’clock.Turn“EntryRange”untilflat edgeofcontrolisat9o’clock. 2.Movethe“Mode”switchtothe“Auto”or“A”position. 3.Theareaofcoveragecanbedeterminedbywatchingthe LEDindicatoronthefrontofOSW-U-0721-MVwhilemoving aroundtheroom.TheLEDlightsonlywhenthesensoris detectingmotion.Adjustthe“AreaRange”controltothe lowestsettingthatprovidesadequatemotiondetection ofapersonworkingintheroom.Donotsethigherthannecessary. Troubleshooting 1/4 15 Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, Georgia 30269 www.coopercontrol.com