Model # G5-W
Model # G5-D-W
Model # G5-D-V
Model # G5T-W
Model # G5T-D-W
Model # G5T-D-V
Installation Instructions
Model # G20-W
Model # G20-D-W
Model # G20-D-V
Model # G20T-W
Model # G20T-D-W
Model # G20T-D-V
INS #
Line Voltage Automatic Turn-OFF Switch – 120/277 VAC
General Information
Installation
Line Voltage Automatic Turn-OFF Switches allow the
disconnection of lighting loads from a remote location
while retaining ON/OFF control at the switch.
3-Way Installations
The G5 switch provides greater sensitivity at low currents
and MUST be specified if the load current is less than 0.8
Amps. Its maximum load is 5.0 Amps. The G20 model is
for use on loads from 1-20 Amps and MUST be specified
if the load current is greater than 5.0 Amps. These models
are SPST two-wire switches and are not polarity sensitive.
All models are 120/240/277/347 VAC 60 Hz.
For Models G5T and G20T, 5 Amp and 20 Amp, SPDT
Switches To turn lights ON, move either switch to the ON
(up) position. To turn lights OFF move the on (up) switch
back to the OFF (down) position. For lights to remain OFF,
both switches need to be in the OFF (down) position.
If a different switch is used to turn OFF lights than
was initially used to turn them ON, the circuit will have
two switches in the ON (up) position, one of these will
automatically release and the lights will turn ON again.
Features
OO
OO
Standard wall switch ON/OFF operation
Mechanically resets to “OFF” automatically when input
power to the unit is interrupted for five seconds or
longer
OO
Toggle or Decorator (Rocker)
OO
Uses standard wallplates (not included with unit)
OO
OO
Eliminates false triggering when used with occupancy
sensors
347 VAC available by special order
Ratings
Switch
Rating
Type
G5, G5-D-*, G5T,
G5T-D-*
5A, 120/240/277
VAC, 60hz
Two-wire connection,
SPST
G20, G20-D-*, G20T,
G20T-D-*
20A, 120/240/277
VAC, 60hz
Three-wire connection,
SPDT - three-way
In order to perform an OFF sweep of Line Voltage
Automatic Turn-OFF Switches a time schedule must be
programmed and linked to the appropriate relays in the
lighting control panel. The relays must be programmed
to perform a Sentry Warn function. Refer to the
corresponding lighting control panel programming guide
for more information.
Typical Line Voltage Automatic Turn-OFF Switch Installation
WARRANTIES AND LIMITATION OF LIABILITY
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
CooperControl.com
Eaton est une marque de commerce
déposée. Toutes les autres marques
de commerce sont la propriété de leur
propriétaire respectif.
© 2014 Eaton
All Rights Reserved
Printed in USA
P/N: 9850-000472-00
Eaton es una marca comercial
registrada. Todas las marcas
comerciales son propiedad de sus
respectivos propietarios.