Technical Data Effective November 5, 2014 OEF-P – High-Bay Fixture Mount Catalog# Prepared by Project Date Comments Type Overview The OEF-P sensor controls fluorescent fixtures and can be mounted directly to the fixtures via a 1/2” knock out. The nipple on the sensor attaches with a lock nut through a 1/2” knockout on the fixture or on a junction box and all wiring passes through the same knockout. Features Applications up to 40 feet in height Coverage diameter of twice the mounting height (2MH) Built in power supply, relay and light level sensor Zero-Crossing Technology prolongs relay life by switching highinrush equipment at close to zero power Compatible with electronic ballasts, incandescent lighting or motor loads No minimum load required Direct installation to fixture; fits standard 1/2” knockout PIR Activated Technical Data OEF-P – High-Bay Fixture Mount November 2014 Specifications Technology Electrical Ratings Input Light Level Sensing Operating Environment Housing Size Standards 2 Passive Infrared (PIR) Contacts: 800 VA @ 120 VAC Tungsten 800 VA @ 120 VAC Ballast 1200 VA @ 240-277 VAC Ballast 120/277 VAC +/- 10% 60Hz 0 to 200 foot-candles Temperature: 32°F - 104°F (0°C - 40°C) Relative humidity: Less than 95%, non-condensing For indoor use only Durable, injection molded housing. Polycarbonate resin complies with UL 94V-0 3.08"H x 3.08"W x 1.70"D (78.232mm x 78.232mm x 43.180mm) FCC Compliant UL Listed www.coopercontrol.com Description/Operation The OEF-P, High-bay sensors are designed to detect motion from a heat-emitting source (such as a person entering a space) within its field-of-view and automatically switch lights ON. Lights will remain ON until no motion is detected and a preset time delay has expired. If no motion is detected during the time delay, the relay is opened, turning the load off. No adjustments are needed at installation. After the installer test, the sensor will automatically set itself to the default 10-minute time delay. At installation, the sensor will scan the coverage area to determine the optimum sensitivity setting. Applications Warehouses Manufacturing Garages High Ceilings Technical Data OEF-P – High-Bay Fixture Mount November 2014 Wiring Diagrams HOT LINE NOTE: 120 VAC INCANDESCENT/TUNGSTEN; MAX. LOAD: 6.7 AMPS, 800VA, 60HZ 120 VAC FLUORESCENT/BALLAST; MAX. LOAD: 6.7 AMPS, 800VA, 60HZ NEUTRAL BLACK WHITE 120-277 VAC** BLUE LOAD 240-277 VAC FLUORESCENT/BALLAST; MAX. LOAD: 4.3 AMPS, 1200VA, 60HZ Coverage Mounting OEF-P-2MH0-MV-S NNote: Sensor needs to be mounted on fixture so that fixture does not block sensor field of view. www.coopercontrol.com 3 Technical Data OEF-P – High-Bay Fixture Mount November 2014 Coverage Hoods Comes with each sensor 180 Degree Aisle Custom NNote: Custom hood sections can be broken off to create custom pattern. Ordering Catalog # Mounting Photocell Wire Lead Length OEF-P-2MH0-MV-S Side Yes 36 inces Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, GA 30269 coopercontrol.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. ACC141017 November 5, 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners.