WARNING! 11-15VDC Supply or 12V Backup Battery Required EXPLOSION HAZARD Installation Guide IMPORTANT NOTICE o 12 Amphour for AC/DC o 100 Amphour for Solar DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON – HAZARDOUS Digital Output Max 30VDC, 500mA DC Relay Supply + - + DC Load +24V DOT AI 6+ AI 5+ AI 4+ COM AI 3+ BAT+ PLEASE REFER TO THE USER MANUAL FOR IMPORTANT REGULATORY AND SAFETY INFORMATION PRIOR TO INSTALLATION AND USE OF THIS PRODUCT GND 2A COM 105U-2-5W OUTPUT Aerial Installation 1m minimum xxxx-2 NOTES 1. All I/O must be SELV. COLINEAR ANTENNA WEATHERPROOF CONNECTORS WITH “3M 23” TAPE SURGE ARRESTOR (OPTIONAL) COAXIAL CABLE ANT 105U GND STRESS RELIEF LOOP CAUTION! For continued protection against risk of fire, replace the module fuse only with the same type and rating MAST PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR RADIO TELEMETRY MODULE INPUTS - +AI 2 +AI 1 - +24V DI 4 DI 3 DI 2 DI 1 4 COM 3 2 SOL GND SUP1 SUP2 SOL GND EARTH STAKE IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN SUP1 INSTALL AERIAL ABOVE LOCAL OBSTRUCTIONS SUP2 1 ANTENNA INSTALLATION Antennas should be installed by experienced contractors. + + - 105U-2-5W Installation Power supply: (A) 12-24VAC 2.0 Amp CSA Certified Class 2 (B) 15-30VDC 2.0 Amp CSA Certified Class 2 (C) Supply battery or 11-15VDC (D) Solar panel with solar battery Choose option and wire as shown + AC Supply 12-24VAC min 15VAC for Battery Charging. Do not earth SUP1 or SUP2 connections 12V Solar Panel Supply max 20VDC max 30W panel DC Supply 15-30VDC min 17VDC for Battery Charging Digital Input Voltage Free Contact OR Transistor Device Loop Powered Analog Transducer Ext. Powered AnalogTransducer To Earth Connection © ELPRO Technologies Pty. Ltd. 2006 Rev. 1.0