Instruction Leaflet IL032005EN Effective December 2015 Version 2.0 105U-3 wireless extension I/O installation guide Figure 1. Antenna Installation Antenna* 1 Wavelength (minimum) Wavelengths: 360 MHz = 32.7" (83 cm) 512 MHz = 22.8" (58 cm) 869 MHz = 13.4" (34 cm) Stress Relief Loop Weatherproof Connections (recommended: 3M™ 23 selfbonding tape) CAUTION For continued protection against risk of fire, replace the module fuse only with the same type and rating. Surge Arrestor (optional) Coaxial Cable Statutory requirements Mast 105U-3 ELPRO 105U-3 Multi I/O EC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. GND Earth Conductor at least 5 AWG (16 mm2) Antenna installation Use Figure 1 as a guide for installing an antenna and attaching it to the module. * For maximum range, install above local obstructions. GND at least 11 AWG (4 mm2) Earth Stake Provide good ground connection to mast, module, and surge arrestor. If ground conditions are poor, use more than one stake. Instruction Leaflet IL032005EN 105U-3 wireless extension I/O installation guide EATON_105U-3 Install Guide Effective December 2015 Version 2.0 Installation Figure 2. Wiring Diagram Choose a power supply option: + - After choosing a power supply option, wire the module as shown in Figure 2. When the wiring is completed, connect the module to a computer (PC) and configure it using the configuration software. For details, refer to the user manual. 5 6 7 AO 8 +24V AO 7 AO 5 NNote: All I/O must be SELV. AO 6 BAT+ 2A +24V Solar panel with battery DO 7 11–15 Vdc, 1.5A • - + DO 8 • 11–15 Vdc Supply or Optional 12V Backup Battery to 12 Ah for AC/DC to 100 Ah for Solar DO 5 15–30 Vdc, 1.5A CSA certified Class 2 DO 6 • Analog Output Externally-Powered Loop is earthed/grounded (not floating). COM 12–24 Vac, 1.5A CSA certified Class 2 GND COM • 8 OUTPUTS ELPRO 105U-3 Multi I/O Before operating the module, read the sections on operation and configuration in the user manual to take advantage of all product features. WARNING EXPLOSION HAZARD Do not disconnect while circuit is live unless area is known to be non-hazardous. OUTPUTS +24V AO 4 AO 3 AO 1 4 COM DO 4 DO 3 DO 2 DO 1 SOL GND SUP2 SUP1 SOL GND SUP1 SUP2 3 AO 2 2 1 + + AC Supply 12–24 Vac Min. 15 Vac for Battery Charging 12V Solar Panel Supply; Max. 20 Vdc Max. 30 W Panel DC Supply 15–30 Vdc Min. 17 Vdc for Battery Charging Digital Output Max. 30 Vdc 500 mA DC Relay Supply Analog Output Loop-Powered Loop is earthed/grounded (not floating). Do not earth SUP1 or SUP2 connection. To Earth Stake Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s wireless business www.eaton.com/wireless © 2014 Eaton All Rights Reserved Printed in USA Publication No. IL032005EN December 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.