Instruction Leaflet IL032008EN Effective December 2015 Version 2.0 105U-4-5W wireless extension I/O installation guide Figure 1. Antenna Installation Antenna* 1 Wavelength (minimum) Wavelengths: 360 MHz = 32.7" (83 cm) 512 MHz = 22.8" (58 cm) Stress Relief Loop Weatherproof Connections (recommended: 3M™ 23 selfbonding tape) CAUTION For continued protection against risk of fire, replace the module fuse only with the same type and rating. Surge Arrestor (optional) Coaxial Cable Statutory requirements Mast 105U-4 ELPRO 105U-4 Multi I/O EC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. GND Earth Conductor at least 5 AWG (16 mm2) Antenna installation Use Figure 1 as a guide for installing an antenna and attaching it to the module. * For maximum range, install above local obstructions. GND at least 11 AWG (4 mm2) Earth stake Provide good ground connection to mast, module, and surge arrestor. If ground conditions are poor, use more than one stake. Instruction Leaflet IL032008EN 105U-4-5W wireless extension I/O installation guide EATON_105U-4-5W Install Guide Effective December 2015 Version 2.0 Installation Figure 2. Wiring Diagram Choose a power supply option: NNote: All I/O must be SELV. DIO channels can be wired as inputs or outputs. OUTPUTS DIO11 DIO12 DIO10 DIO 8 DIO 9 DIO 7 DO 4 DC Load COM After choosing a power supply option, wire the module as shown in Figure 2. 2A DO 2 Solar panel with battery DO 3 • Digital Output Max. 30 Vdc, 500 mA DC Relay Supply + - DO 1 11–15 Vdc, 2.0A SOL • GND 15–30 Vdc, 1.5A CSA certified Class 2 * 11–15 Vdc Supply or 12V Backup Battery Required 12 Ah for AC/DC 100 Ah for Solar BAT+ • 12V Solar Panel Supply; Max. 20 Vdc Max. 30W Panel SOL 12–24 Vac, 1.5A CSA certified Class 2 * GND • I/O *Backup battery must be used if radio power is set to 2W or higher. ELPRO 105U-4 Multi I/O When the wiring is completed, connect the module to a computer (PC) and configure it using the configuration software. For details, refer to the user manual. Before operating the module, read the sections on operation and configuration in the user manual to take advantage of all product features. DIO 6 DIO 5 DIO 4 DIO 3 DIO 2 DIO 1 COM DI 4 I/O DI 3 DI 2 DI 1 GND SUP2 SUP1 SUP2 Do not disconnect while circuit is live unless area is known to be non-hazardous. INPUTS SUP1 WARNING EXPLOSION HAZARD + AC Supply 12–24 Vac Min. 15 Vac for Battery Charging DC Supply 15–30 Vdc Min. 17 Vdc for Battery Charging Digital Input Voltage-Free Contact or Transistor Device Do not earth SUP1 or SUP2 connections. To Earth Stake Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s wireless business www.eaton.com/wireless © 2014 Eaton All Rights Reserved Printed in USA Publication No. IL032008EN December 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.