Host Protocol Connection WARNING ! 105U-G EXPLOSION HAZARD Installation Guide DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON HAZARDOUS Statutory Requirements EC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. WIRELESS GATEWAY NOTES CAUTION! For continued protection against risk of fire, replace the module fuse only with the same type and rating 1m minimum DIO8 DIO7 DIO6 DIO5 DIO4 DIO3 DIO2 GND SUP1 SUP2 SUP2 DIO1 105U-G-xx BAT+ Aerial Installation All I/O must be SELV. GND Backup battery must be used if radio power over 2Watts. 2. GND 1 DIO channels can be wired as either inputs or outputs. SUP2 Power supply may be: (A) 12-24VAC 1 (B) 9-30VDC 1 (C) Supply battery 1. GND 105U-G Installation 2A - + -+ DC Supply 9-30VDC 16VA To Earth Connection AC Supply 12-24VAC Do not earth SUP1 or SUP2 connections Digital Input Voltage Free Contact OR Transistor Device Optional 12V Backup Battery up to 100 Amphour To Earth Connection + Digital Output Max 30VDC, 500mA DC Relay Supply 0885 N16 © ELPRO Technologies Pty. Ltd. 2003 Rev. 1.3