Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration Entry Lighting All Off Summary Access to daylight and personal control of electric light improves the health and well being of patients, reduces anxiety and increases overall patient satisfaction. Simple to use, labeled controls allow hospital staff to provide quality care. Including energy saving strategies such as daylighting, which provides up to 30% savings, and code requirements like integral UL 924 relays qualifies the Room Controller as an outstanding solution for the private patient room. Entry Lighting All Off The Room Controller QuicKit is shipped preconfigured to work out-of-the-box, minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide. RC3D Entry Lighting All Off Room Controller Sample placement layout (12’ x 16’) General Exam Room Controller QuicKit RC3D Reading All Off Half Lights Full Lights Raise Lower Half Lights Full Lights RCQK-HC3E-HC1-HC2-HC2-3ZD-D1-P-W Raise Lower All Off RC3D TV CHANNEL 1 2 3 4 5 6 7 Qty1: RC3DEhc 3 relay + 3 dimmer + 1 emergency relay VOLUME cc 8 9 RC3DE 0 PREV Half Lights SLEEP MUTE OPTION 2 Full3 Lights 1 ALL ON/OFF Normal power (3 Relay + 3 Dimmer + 1 Emergency) RC3DEHC GPCS-3Z-DIM Greengate Patient Control Station 3 switch zones 3 dimming zones w/ All Zone button VOLUME 3 6 9 Half Lights RC3DE Full Lights Qty1: RC-4TSB-HC1-W general, eXAM, rEADING, all off Raise General Lower Exam All Off Reading All Off Entry Lighting All Off Half Lights Full Lights Raise RC3DE Lower General Exam Qty1: RC-6TSB-HC2-W General, Exam, Reading, Raise, LoweR, All Off All Off Reading General All Off Whiteboard Quiet Time • A/V Mode TV CHANNEL VOLUME Raise cc Lower 1 2 4 3 5 6 RC3DE 7 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 Reading - Load (3) ALL ON/OFF TV CHANNEL Qty1: GPCS-3Z-DIM 3 oN/OFF & 3 ZONE DIMMING PATIENT CONTROLS VOLUME cc 1 2 4 3 5 6 RC3DE 7 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 ALL ON/OFF Qty1: GG37P 37PIN CONNECTOR FOR GPCS-3Z-DIM MOUNTED ON HEADWALL 3 OPTION MUTE 2 5 8 0 2 TV cc All Off ALL ON/OFF 1 4 7 Lower 1 PREV SLEEP CHANNEL connection RC3DEHC For Patient Rooms Daylight sensor (DSRC-FMOIR) General Load (1) (Tracks with Load (1) 1 CHANNEL PREV 7 1 SLEEP 4 2 0 8 cc ALL ON/OFF 5 2 TV General Emergency 3 9 6 MUTE 3 OPTION VOLUME (Tracks with Load (1) Exam Load (2) Emergency power connection Raise Exam Lower All Off General Reading Exam Raise Lower All Off General RC-6TSB-HC2-* Patient Station General Load (1) Reading RC-6TSB-HC2-* Patient Station General Emergency Daylight sensor (DSRC-FMOIR) Exam Load (2) Reading - Load (3) GPCS-3Z-DIM Greengate Patient Control Station 3 switch zones 3 dimming zones w/ All Zone button RC3DEHC Emergency power connection Raise Normal power connection RC3DEHC For Patient Rooms (3 Relay + 3 Dimmer + 1 Emergency) Product Legend (per patient bed) All Off RC3D General Whiteboard Quiet Time • A/V Mode Raise General Load (1) General Load (1) RC-6TSB-HC2-* Patient Station Nurse Call System and Entertainment System (by others) Raise Lower All Off Exam Reading General Exam Raise Lower All Off General Reading Nurse Call System and Entertainment System (by others) Lower RC-6TSB-HC2-* Patient Station Qty1: DSRC-FMOIR DAYLIGHT SENSOR General Whiteboard Quiet Time • A/V Mode Raise Lower Qty1: GGRJ45-10-G qUICKCONNECT CABLE 10’ General Exam Reading All Off General RC-4TSB-HC1-* Patient Station Qty1: GGRJ45-50-G QUICKCONNECT CABLE 50’ General Exam Exam Reading Reading All Off All Off RC-4TSB-HC1-* Patient Station TV CHANNEL Entry cc Lighting 1 VOLUME 2 3 4 All Off5 7 8 6 MUTE OPTION 2 1 Single box packaging with wiring detail and installation 9 0 PREV SLEEP 3 ALL ON/OFF dOWNLIGHT fIXTURES Recessed FixtureS General RC3D Whiteboard Quiet Time • A/V Mode Raise Lower For guaranteed compatibility refer to preferred Cooper lighting fixture information below. Entry Lighting All Off Entry Lighting General Exam Reading All Off All Off Control sequence Entry Lighting All Off • Manual On TV CHANNEL VOLUME cc 1 2 4 3 5 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 ALL ON/OFF Entry Lighting • Patient personal control from pillow speaker, 3 relay On/Off and 3 dimming zones • Direct integration with most major Nurse Call Systems 1. Toggle Load 1 1. Toggle Load 1 RC3D All Off General 2. Toggle Load 2 General 3. Toggle Load RC3D 3 Whiteboard Quiet Time • A/V Mode Raise Exam Lower • Providing users with wall-based dimming controls to adjust the lighting levels to meet their needs Reading All Off 4. Load 1, 2, 3 Off RC3D Raise 4. Raise Dimmer 5% Lower All Off 5. Lower Dimmer 5% General Exam Reading RC3D All Off • BMS integration for HVAC control based on Occupancy 3. Toggle Load 3 Reading • Automatic multi-zone daylight dimming out-of-the-box • High-end UL924 trim/tuning to define target light levels guarantees energy savings UL924 2. Toggle Load 2 General Exam RC-4TSB-HC1 6. Load 1, 2, 3 Off RC-6TSB-HC2 General Exam Reading All Off TV CHANNEL VOLUME cc 1 2 4 3 5 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 1 General 3 ALL ON/OFF Exam Reading All Off Integrated capabilities TV CHANNEL VOLUME cc 1 2 4 7 3 5 6 8 9 General 0 PREV Cooper Lighting Guaranteed Compatible Fixtures MUTE Exam SLEEP OPTION 2 1 Reading3 ALL ON/OFF All Off CHANNEL TV 2 4 1 3 5 7 6 8 9 0 PREV SLEEP Fail-Safe VOLUME cc 1 MUTE OPTION 2 Room Controller Patient Room Lighting Layouts 3 ALL ON/OFF UL924 General Whiteboard Quiet Time • A/V Mode Raise Lower TV CHANNEL VOLUME cc 1 2 4 3 5 7 6 8 0 PREV SLEEP 2 1 9 MUTE OPTION 3 ALL ON/OFF General Whiteboard Quiet Time • A/V Mode Raise Lower Daylighting Control Manual Control Integration Emergency General Whiteboard Quiet Time • A/V Mode Raise Lower General Whiteboard Quiet Time • A/V Mode Raise Lower www.coopercontrol.com 1 Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information. Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration Pillow speaker control functionality In developing a patient room lighting control solution, Cooper Controls found existing methods for providing patients control over natural and electric lighting levels to be inadequate. Control solutions that rely on existing off-the-shelf pillow speakers and nurse call station interfaces are severely limited in functionality. On/Off only control of a limited number of lighting zones is typical for these systems. To adress this issue, Cooper Controls developed a line of proprietary pillow speakers designed specifically to support the control of natural and electric light. These units offer the following features: • Support for up to three zones of electric lighting control • An all zones On/all zones Off function • Independent Raise/Lower control of each zone • Shade Raise/Lower function • Standard pillow speaker functionality including nurse call and television control • Sealed design reduces potential risk of infectious fluids or solids settling into the unit, even in the speaker area • High-impact case material is designed to withstand over 100 drops onto a concrete floor without impacting its functionality • Standard interface to leading nurse call stations These exceptionally functional control devices interface with a state of art, small form factor lighting control panel. This panel is capable of supporting a digital switch network. Multiple digital switch stations maybe used in conjunction with the pillow speaker to provide additional control points for staff and visitors. EMERGENCY NEUTRAL Emergency Lighting Load YELLOW Emergency Power OUT (Tracks with normal lighting YELLOW load) YELLOW Lighting Load (1) General WHT/ORG or WHT/BLK Neutral RED BLACK - Hot (120/277 VAC) Lighting Load (2) Exam BLUE - Relay In (120/277 VAC) Lighting Load (3) Reading PURPLE BLUE - Emergency Power In (120/277 VAC) Requires 0-10V dimming ballasts Violet - Dimmer 1 Gray - Dimmer 1 Violet - Dimmer 2 Gray - Dimmer 2 Emergency Note: Violet - Dimmer 3 Gray - Dimmer 3 Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%. 0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones. In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds. The RC3DE is UL 924 listed. QuickConnect coupler (GGRC-COUPLER) Lower All Off GG37P Greengate 37 Pin Receptacle Provided by Cooper Controls for pillow speaker connection RC-6TSB-HC2-* Wallstation 6 9 2 0 4 8 1 CHA 5 NNE L cc 3 TV RC-4TSB-HC1-* Wallstation Connect up to four wallstations per Room Controller Button 1: Toggle Load (1) Button 2: Toggle Load (2) Button 3: Toggle Load (3) Button 4: Press and hold increase zone 5% Button 5: Press and hold decrease zone 5% Button 6: Load (1), (2), (3) Off E Raise MUT Exam Reading ION General Exam All Off To Nurse Call System and Entertainment System (by others) OPT General Reading Daylight sensor (DSRC-FMOIR) *Immediately provides multi-zone daylight dimming upon powerup EP ALL ON/ OFF 1 SLE PRE V 2 7 3 Button 1: Toggle Load (1) Button 2: Toggle Load (2) Button 3: Toggle Load (3) Button 4: Load (1),(2),(3) Off Adjustable daylight sensor dome Eight conductors of the 37 conductor healthcare cable. VOL UME Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts GPCS Greengate Patient Control Station Provided by Cooper Controls Note: Use only wiring supplied with the GG37P receptacle. Only the Greengate Patient Control Station sall be connected to a GG37P Receptacle Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: controls@cooperindustries.com Website: www.coopercontrol.com Room Controller - RC3DEHC Three Relay + Three Dimmers Wiring Diagram + One Emergency Relay Drawing Name: RC3DEHC-PatientRoomWiring.dwg www.coopercontrol.com 2 Drawing Date: 1/10/2013 Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration Mounting The Room Controller For semi-private rooms where you would need multiple Room Controllers, each would mount above the ceiling in the space it is controlling, typically above the headwall so it can be easily wired to the 37pin connector and Nurse Call System. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller. Sample Placement Diagram Sample Load Zoning (for example purposes only) (for example purposes only) Daylight Sensor 1 CHANNEL PREV 7 SLEEP 1 4 2 0 8 cc 5 2 TV ALL ON/OFF 3 9 6 3 MUTE 6 3 9 OPTION MUTE VOLUME 2 Reading Light Load 3 Dimmer 3 Exam Lighting Load 2 Dimmer 2 General Lighting Exam All Off General Reading General Lighting Exam Lighting Reading Light GPCS Load 3 Dimmer 3 Greengate Patient Control Station GPCS Greengate Patient Control Station Load 2 Dimmer 2 VOLUME 5 3 8 OPTION 0 2 TV cc Exam All Off General Reading Patient Wallstation Load 1 Dimmer 1 1 4 7 1 PREV SLEEP CHANNEL ALL ON/OFF Room Controller (above ceiling over headwall) Window Load 1 Dimmer 1 GG37P GG37P Daylight Sensor Room Controller (above ceiling over headwall) Window Window Window Patient Wallstation Patient Wallstation Patient Wallstation General General Exam Exam Reading Reading Raise Raise Lower Lower All Off All Off Wiring Diagram Daylight Sensor ceiling location Room Controller (Above Ceiling Over Headwall) Normal Power (Line In & Load Out) 1. Mount the daylight sensor one to two times the window height from the window wall. 2. Position the sensor so its arrow is pointed toward the nearest window. 3. Ensure the daylight sensor is not obstructed or looking directly at electric light. 4. For narrow spaces mount the daylight sensor near the window facing into the space. DSRC-FMOIR (Multi-zone daylight sensor) Emergency Power General General Exam Exam Reading (Line In & Load Out) Reading All Off Raise Lower All Off 0-10V Dimmer Wiring Wallstation Wallstation 60° (low voltage, class 2) UME VOL Connections to Room Controller TV 3 cc 6 1 3 0 4 ION 8 OPT E MUT 5 L NNE CHA 2 9 7 EP ALL OFF SLE V ON/ PRE 2 1 Connections to Nurse Call Stations and Entertainment System GPCS (Greengate Patient Control Station) Area viewed by daylight sensor GG37P (Greengate 37 Pin Receptacle for GPCS control station connection) Connections Room Controller and Smart Devices use Click & Go Connections Room Controller 0-10V Dimming Connections Dimmer 1: Near the Window Dimmer 2: Middle of Room Dimmer 3: Far from Window - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + The daylight sensor will automaticallyprovide multi-zone daylight dimming based on this wiring configuration. 0-10V Dimming 1 0-10V Gray (-) 0-10V Violet (+) www.coopercontrol.com 3 2 5 34 6 1. Wallstations (up to four) 2. Slider Station Connection (one) 3. Occupancy Sensors (up to two) 4. Daylight Sensor (one) 5. Receptacle Control or BMS Output 6. Switchpack (controlled with Load 1 for alternate voltage) Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration Ordering (per patient bed) RCQK - HC3E - HC1-HC2 - 3ZD Room Controller Patient Stations (Choose up to 4) QuicKit HC1 - General, Exam, Reading, All Off HC2 - General, Exam, Reading, Raise, Lower, All Off - D1 - P W Daylight Station Color D1 - Multi-zone Daylight Sensor DH - Multi-zone Daylight Sensor w/ Handheld Remote W - White G - Gray V - Ivory B - Black Options P - Plug Load B - BMS/Egress Types of Space and Control HC3E - Healthcare Patient Room (RC3DEHC) - Pillow Speaker 3Z - 3 Relay On/Off control 3ZD - 3 Relay On/Off, 3 zone dimming control 2Z - 2 Relay On/Off control 2ZD - 2 Relay On/Off, 2 zone dimming conrtol *Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration. Pre-defined wallstations and Pillow speaker Model numbers General General LIGHT DIM LIGHT DIM Exam Exam Reading Reading All Off Raise 1 2 3 1 2 3 1 2 3 1 2 Lower 4 5 6 4 5 6 4 5 6 4 5 7 8 9 7 8 9 7 8 9 7 8 9 PREV 0 MUTE PREV 0 MUTE PREV 0 MUTE PREV 0 MUTE OPTION SLEEP OPTION SLEEP OPTION SLEEP TV TV POWER CHANNEL All Off SLEEP TV POWER VOLUME CHANNEL TV POWER VOLUME CHANNEL POWER VOLUME CHANNEL VOLUME RC-4TsB-hc1 RC-6TSB-hc2 LIGHTS 3 1 LIGHTS 3 1 LIGHTS 2 3 1 3 ALL ON/OFF ALL ON/OFF ALL ON/OFF Gen4 Gen4 Gen4 Gen4 gpcs-2z-DIM gpcs-3z gpcs-3z-dim gpcs-2z Button Text Control Type 1 General Toggle Load 1 (yellow) ON and OFF 2 Exam Toggle Load 2 (red) ON and OFF 3 Reading Toggle Load 3 (purple) ON and OFF 6 Raise Raise Raise All Dimmers† 7 Lower Lower Lower All Dimmers† 16 All On Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON Preset Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF *For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website Pillow Speaker Functionality Function (Unless a target level is indicated, the dimmer output will default to daylight sensor control) Program No. All Off LIGHTS ALL ON/OFF Healthcare Application Button Functionality 8 6 OPTION 2 1 3 Input Button Icon 1 (General) Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks will always track with Load 1 (yellow lead). Toggle Load 1 (yellow) ON and OFF, Sets Raise/Lower control action to control Dimmer 1 2 2 2 2 Toggle Load 2 (red) ON and OFF, Sets Raise/Lower control action to control Dimmer 2 3 (Reading) 3 3 3 3 Toggle Load 3 (purple) ON and OFF, Sets Raise/Lower control action to control Dimmer 3 Toggle Load 1 (yellow), Load 2 (red), Load 3 (purple) ON and OFF, Sets Raise/Lower control action to control dimmers 1, 2 and 3 Raise Raise the selected dimmer zone.† Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones. Lower Lower the selected dimmer zone. Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones. † Additional Information: Emergency relay will always work under normal conditions with Load 1 (yellow lead). Function (Unless a target level is indicated, the dimmer output will default to daylight sensor control) 2 (Exam) 6 (All) Final dimmer output level is determined by the following combination: • High end trim level • Daylighting contribution If enough natural light is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station will not override or raise the lighting above the target threshold implemented by these advanced energy savings methods. 1 1 1 1 Control Type Raise ALL 1 ALL ON/OFF ALL ON/OFF ON/OFF ALL ON/OFF 2 3 ALL ON/OFF Lower Final dimmer output level is determined by the following combination: • High end trim level • Daylighting contribution If enough natural light is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station will not override or raise the lighting above the target threshold implemented by these advanced energy savings methods. † Additional Information: Emergency relay will always work under normal conditions with Load 1 (yellow lead). Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks will always track with Load 1 (yellow lead). Catalog # † Project These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE) Comments †† Slider stations can not be used if a wallstation with Raise/Lower buttons are used Prepared by www.coopercontrol.com 4 ACC130085 Type Date