Room Controller - Private Patient Room

advertisement
Room Controller - Private Patient Room
w/Daylight Dimming and Pillow Speaker Integration
Entry
Lighting
All Off
Summary
Access to daylight and personal control of electric light improves the health and well being of patients, reduces anxiety and increases overall patient satisfaction.
Simple to use, labeled controls allow hospital staff to provide quality care. Including energy saving strategies such as daylighting, which provides up to 30% savings,
and code requirements like integral UL 924 relays qualifies the Room Controller as an outstanding solution for the private patient room.
Entry
Lighting
All Off
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings.
Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work
immediately as defined on this application guide.
RC3D
Entry
Lighting
All Off
Room Controller Sample room layout (12’ x 16’)
General
Exam
Room Controller QuicKit
RC3D
Reading
All Off
Half Lights
Full Lights
Raise
Lower
All Off
Half Lights
Full Lights
RCQK-HC3E-HC1-HC2-HC2-3ZD-D1-W
Raise
Lower
All Off
RC3D
TV
CHANNEL
VOLUME
cc
1
2
3
4
5
6
7
8
9
RC3DE
0
PREV
Half Lights
SLEEP
MUTE
OPTION
2
Full3 Lights
1
ALL
ON/OFF
Raise
Lower
All Off
General
RC-6TSB-HC2-*
Patient Station
RC-6TSB-HC2-*
Patient Station
Product Legend
Qty1: RC3Dehc
3 relay + 3 dimmer + 1 emergency relay
Half Lights
RC3DE
Full Lights
Raise
General
Exam
Exam
Reading
Reading
Raise
Raise
Lower
Lower
All Off
All Off
General
Lower
Exam
All Off
Reading
All Off
Entry
Lighting
Qty1: RC-4TSB-HC1-W
general, eXAM, rEADING, all off
All Off Half Lights
General
Emergency
Tracks with Load (1)
General
Load (1)
Full Lights
General
Load (1)
Raise
RC3DE
Lower
General
Exam
All Off
Reading
General
All Off
Whiteboard
Quiet Time •
A/V Mode
TV
CHANNEL
VOLUME
Raise
cc
Lower
1
2
4
3
5
6
RC3DE
7
8
9
0
PREV
SLEEP
Qty1: RC-6TSB-HC2-W
General, Exam, Reading, Raise, LoweR, All Off
MUTE
OPTION
2
1
3
ALL
ON/OFF
TV
CHANNEL
VOLUME
cc
1
Emergency power
connection
2
4
3
5
6
RC3DE
7
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
3
Qty1: GPCS-3Z-DIM
3 oN/OFF & 3 ZONE DIMMING PATIENT CONTROLS
ALL
ON/OFF
Daylight sensor
(DSRC-FMOIR)
RC3D
General
Whiteboard
Qty1: GG37P
37PIN CONNECTOR FOR GPCS-3Z-DIM MOUNTED ON HEADWALL
Quiet Time •
A/V Mode
Raise
Lower
Exam
Load (2)
Qty1: DSRC-FMOIR
DAYLIGHT SENSOR
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
CHANNEL
TV
cc
1
2
4
5
7
8
0
PREV
SLEEP
1
2
ALL
ON/OFF
RC-4TSB-HC1-*
Patient Station
General
Exam
Qty1: GGRJ45-10-G
qUICKCONNECT CABLE 10’
VOLUME
3
6
9
MUTE
OPTION
3
GPCS-3Z-DIM
Greengate Patient Control Station
3 switch zones
3 dimming zones
w/ All Zone button
General
Exam
Reading
All Off
Qty1: GGRJ45-50-G
QUICKCONNECT CABLE 50’
Reading
All Off
Reading - Load (3)
TV
CHANNEL
Entry
cc
Lighting
1
VOLUME
2
3
4
All Off5
7
8
6
MUTE
OPTION
2
1
Single box packaging with wiring detail
and installation
9
0
PREV
SLEEP
3
ALL
ON/OFF
Nurse Call System and
Entertainment System
(by others)
RC3DEHC
Downlight Fixtures
Normal power
connection
RC3DEHC
For Patient Rooms
(3 Relay + 3 Dimmer + 1 Emergency)
Recessed FixtureS
General
RC3D
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
For guaranteed compatibility refer to preferred Cooper
lighting fixture information below.
Entry
Lighting
All Off
Entry
Lighting
General
Exam
Reading
All Off
All Off
Control sequence
Entry
Lighting
All Off
• Manual On
TV
CHANNEL
VOLUME
cc
1
2
4
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
3
ALL
ON/OFF
Entry
Lighting
• Patient personal control from pillow speaker, 3 relay On/Off
and 3 dimming zones
• Direct integration with most major Nurse Call Systems
2. Toggle Load 2
General
General
3. Toggle Load 3
Whiteboard
Quiet Time •
A/V Mode
RC3D
Lower
Reading
Exam
4. Load 1, 2, 3 Off
Raise
RC3D
4. Raise Dimmer 5%
Lower
All Off
5. Lower Dimmer 5%
General
Exam
Reading
RC3D
All Off
• BMS integration for HVAC control based on Occupancy
3. Toggle Load 3
Reading
All Off
• Automatic multi-zone daylight dimming out-of-the-box
• High-end
UL924 trim/tuning to define target light levels guarantees
energy
savings
UL924
2. Toggle Load 2
General
Exam
Raise
• Providing users with well-based dimming controls to adjust
the lighting levels to meet their needs
1. Toggle Load 1
1. Toggle Load 1
All Off
RC3D
RC-4TSB-HC1
6. Load 1, 2, 3 Off
RC-6TSB-HC2
General
Exam
Reading
All Off
TV
CHANNEL
VOLUME
cc
1
2
4
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
General
3
ALL
ON/OFF
Exam
Reading
All Off
Integrated capabilities
TV
CHANNEL
VOLUME
cc
1
2
4
7
3
5
6
8
9
General
0
PREV
Cooper Lighting Guaranteed Compatible Fixtures
MUTE
Exam
SLEEP
OPTION
2
1 Reading3
ALL
ON/OFF
All Off
CHANNEL
TV
2
4
1
3
5
7
6
8
9
0
PREV
SLEEP
Fail-Safe
VOLUME
cc
1
MUTE
OPTION
2
Room Controller Patient Room Lighting Layouts
3
ALL
ON/OFF
UL924
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower TV
CHANNEL
VOLUME
cc
1
2
4
3
5
7
6
8
0
PREV
SLEEP
2
1
9
MUTE
OPTION
3
ALL
ON/OFF
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Daylighting
Control
Manual
Control
Integration
Emergency
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
www.coopercontrol.com
1
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance
value information.
Room Controller - Private Patient Room
w/Daylight Dimming and Pillow Speaker Integration
Pillow speaker control functionality
In developing a patient room lighting control solution, Cooper Controls found existing methods for providing patients control over natural and electric lighting levels
to be inadequate. Control solutions that rely on existing off-the-shelf pillow speakers and nurse call station interfaces are severely limited in functionality. On/Off only
control of a limited number of lighting zones is typical for these systems.
To adress this issue, Cooper Controls developed a line of proprietary pillow speakers designed specifically to support the control of natural and electric light.
These units offer the following features:
• Support for up to three zones of electric lighting control
• An all zones On/all zones Off function
• Independent Raise/Lower control of each zone
• Shade Raise/Lower function
• Standard pillow speaker functionality including nurse call and television control
• Sealed design reduces potential risk of infectious fluids or solids settling into the unit, even in the speaker area
• High-impact case material is designed to withstand over 100 drops onto a concrete floor without impacting its functionality
• Standard interface to leading nurse call stations
These exceptionally functional control devices interface with a state of art, small form factor lighting control panel. This panel is capable of supporting a digital
switch network. Multiple digital switch stations maybe used in conjunction with the pillow speaker to provide additional control points for staff and visitors.
EMERGENCY NEUTRAL
Emergency Lighting Load
YELLOW
Emergency Power OUT (Tracks with normal
lighting YELLOW load)
YELLOW
Lighting Load (1)
General
WHT/ORG or WHT/BLK
Neutral
RED
BLACK - Hot
(120/277 VAC)
Lighting Load (2)
Exam
BLUE - Relay In
(120/277 VAC)
Lighting Load (3)
Reading
PURPLE
BLUE - Emergency Power In
(120/277 VAC)
Requires 0-10V
dimming ballasts
Violet - Dimmer 1
Gray - Dimmer 1
Violet - Dimmer 2
Gray - Dimmer 2
Emergency Note:
Violet - Dimmer 3
Gray - Dimmer 3
Emergency load tracks with normal lighting
YELLOW load for On/OFF. If dimming it will be
adjusted with the dimming zone it is connected to.
Upon loss of normal power to the RC3DE, the
emergency load will be forced On and full bright to
100%.
0-10V Dimming Zone Note:
The 0-10V dimming zones within the
Room Controller can be wired and
controlled independent of the connected
loads. This allows a each load to have a
dedicated 0-10V dimming zone or a single
load to have up to three 0-10V dimming zones.
In room ladderless testing is done by pressing the
"All Off" button four times, within 3 seconds.
The RC3DE is UL 924 listed.
QuickConnect coupler
(GGRC-COUPLER)
Lower
All Off
GG37P
Greengate 37 Pin Receptacle
Provided by Cooper Controls for
pillow speaker connection
RC-6TSB-HC2-*
Wallstation
6
9
2
0
4
8
1
CHA
5
NNE
L
cc
3
TV
RC-4TSB-HC1-*
Wallstation
Connect up to four
wallstations per Room
Controller
Button 1: Toggle Load (1)
Button 2: Toggle Load (2)
Button 3: Toggle Load (3)
Button 4: Press and hold increase zone 5%
Button 5: Press and hold decrease zone 5%
Button 6: Load (1), (2), (3) Off
E
Raise
MUT
Exam
Reading
ION
General
Exam
All Off
To Nurse Call System and
Entertainment System
(by others)
OPT
General
Reading
Daylight sensor
(DSRC-FMOIR)
*Immediately provides multi-zone
daylight dimming upon powerup
EP
ALL
ON/
OFF
1
SLE
PRE
V
2
7
3
Button 1: Toggle Load (1)
Button 2: Toggle Load (2)
Button 3: Toggle Load (3)
Button 4: Load (1),(2),(3) Off
Adjustable daylight
sensor dome
Eight conductors of the 37 conductor
healthcare cable.
VOL
UME
Quick connect cables are
pre-terminated and included
in the Room Controller
QuicKit and measured to fit
typical room layouts
GPCS
Greengate Patient Control Station
Provided by Cooper Controls
Note:
Use only wiring supplied with the GG37P receptacle.
Only the Greengate Patient Control Station sall be connected to a
GG37P Receptacle
Cooper Controls
203 Cooper Circle
Peachtree City,
GA 30269. USA
Tel: +1-800-553-3879
Fax: +1-800-954-7016
Email: controls@cooperindustries.com
Website: www.coopercontrol.com
Room Controller - RC3DEHC
Three Relay + Three Dimmers Wiring Diagram + One Emergency Relay
Drawing Name:
RC3DEHC-PatientRoomWiring.dwg
www.coopercontrol.com
2
Drawing Date:
1/10/2013
Room Controller - Private Patient Room
w/Daylight Dimming and Pillow Speaker Integration
Mounting The Room Controller
The Room Controller mounts above the ceiling in the space it is controlling, typically above the headwall so it can be easily wired to the 37pin connector and Nurse
Call System. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller
using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller.
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout
openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Sample Placement Diagram
Sample Load Zoning
(for example purposes only)
(for example purposes only)
Load 1
Dimmer 1
Patient
Wallstation
General
Exam
Reading
Raise
Lower
All Off
Window
Window
Daylight
Sensor
GPCS
CHANNEL
TV
cc
1
2
VOLUME
3
4
5
6
7
8
9
PREV
SLEEP
1
0
2
ALL
ON/OFF
MUTE
OPTION
3
Greengate
Patient
Control
Station
General
Exam
Reading
All Off
GG37P
General Lighting
Load 2
Dimmer 2
Exam
Lighting
Patient
Wallstation
Reading Light
Load 3
Dimmer 3
Room Controller
(above ceiling
over headwall)
Wiring Diagram
Daylight Sensor ceiling location
Room Controller
(Above Ceiling
Over Headwall)
Normal Power
(Line In & Load Out)
1. Mount the daylight sensor one to two times the window height from the
window wall.
2. Position the sensor so its arrow is pointed toward the nearest window.
3. Ensure the daylight sensor is not obstructed or looking directly at electric
light.
4. For narrow spaces mount the daylight sensor near the window facing into
the space.
DSRC-FMOIR
(Multi-zone
daylight sensor)
Emergency Power
General
General
Exam
Exam
Reading
(Line In & Load Out)
Reading
All Off
Raise
Lower
All Off
0-10V Dimmer Wiring
Wallstation Wallstation
60°
(low voltage, class 2)
UME
VOL
Connections to
Room Controller
TV
3
cc
6
1
3
0
4
ION
8
OPT
E
MUT
5
L
NNE
CHA
2
9
7
EP
ALL
OFF
SLE
V
ON/
PRE
2
1
Connections to Nurse Call Stations
and Entertainment System
GPCS
(Greengate Patient
Control Station)
Area viewed by
daylight sensor
GG37P
(Greengate 37 Pin Receptacle
for GPCS control station
connection)
Connections
Room Controller and Smart Devices
use Click & Go Connections
Room Controller 0-10V Dimming Connections
Dimmer 1: Near the Window
Dimmer 2: Middle of Room
Dimmer 3: Far from Window
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
The daylight sensor will automatically provide multi-zone
daylight dimming based on this wiring configuration.
0-10V Dimming
1
0-10V Gray (-)
0-10V Violet (+)
www.coopercontrol.com
3
2
5
34
6
1. Wallstations (up to four)
2. Slider Station Connection (one)
3. Occupancy Sensors (up to two)
4. Daylight Sensor (one)
5. Receptacle Control or BMS Output
6. Switchpack (controlled with Load 1 for
alternate voltage)
Room Controller - Private Patient Room
w/Daylight Dimming and Pillow Speaker Integration
Ordering
RCQK
-
HC3E
-
HC1-HC2
-
3ZD
Room Controller
Patient Stations (Choose up to 4)
QuicKit
HC1 - General, Exam, Reading, All Off
HC2 - General, Exam, Reading, Raise, Lower, All Off
Types of Space
and Control
-
D1
-
P
W
Daylight
Station Color
D1 - Multi-zone Daylight Sensor
DH - Multi-zone Daylight Sensor w/
Handheld Remote
W - White
G - Gray
V - Ivory
B - Black
Options
P - Plug Load
B - BMS/Egress
Pillow Speaker
HC3E - Healthcare Patient Room (RC3DEHC)
-
3Z - 3 Relay On/Off control
3ZD - 3 Relay On/Off, 3 zone dimming control
2Z - 2 Relay On/Off control
2ZD - 2 Relay On/Off, 2 zone dimming conrtol
*Catalog number automatically includes low voltage
connection cable, wallplates and connectors based on room
type and configuration.
Pre-defined Wallstation Model numbers
General
General
LIGHT
DIM
LIGHT
DIM
Exam
Exam
Reading
Reading
All Off
Raise
1
2
3
1
2
3
1
2
3
1
2
Lower
4
5
6
4
5
6
4
5
6
4
5
7
8
9
7
8
9
7
8
9
7
8
9
PREV
0
MUTE
PREV
0
MUTE
PREV
0
MUTE
PREV
0
MUTE
OPTION
SLEEP
OPTION
SLEEP
OPTION
SLEEP
TV
TV
POWER
CHANNEL
All Off
SLEEP
TV
POWER
VOLUME
CHANNEL
TV
POWER
VOLUME
CHANNEL
POWER
VOLUME
CHANNEL
VOLUME
RC-4TsB-hc1
RC-6TSB-hc2
LIGHTS
3
1
LIGHTS
3
1
LIGHTS
2
3
1
3
ALL
ON/OFF
ALL
ON/OFF
ALL
ON/OFF
Gen4
Gen4
Gen4
Gen4
gpcs-2z-DIM
gpcs-3z
gpcs-3z-dim
gpcs-2z
Button Text
Control
Type
1
General
Toggle
Load 1 (yellow) ON and OFF
2
Exam
Toggle
Load 2 (red) ON and OFF
3
Reading
Toggle
Load 3 (purple) ON and OFF
6
Raise
Raise
Raise All Dimmers†
7
Lower
Lower
Lower All Dimmers†
16
All On
Preset
Load 1 (yellow) ON, Load 2 (red) ON,
Load 3 (purple) ON
Preset
Load 1 (yellow) OFF, Load 2 (red) OFF,
Load 3 (purple) OFF
*For site specific engraving, please see the Room Controller
Wallstation custom engraving form on the Cooper Controls
website
Pillow Speaker Functionality
Function
(Unless a target level is indicated, the dimmer
output will default to daylight sensor control)
Program
No.
All Off
LIGHTS
ALL
ON/OFF
Healthcare Application Button Functionality
8
6
OPTION
2
1
3
Input
Button Icon
1
(General)
Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks
will always track with Load 1 (yellow lead).
Toggle
Load 1 (yellow) ON and OFF, Sets Raise/Lower
control action to control Dimmer 1
2
2
2
2
Toggle
Load 2 (red) ON and OFF, Sets Raise/Lower control
action to control Dimmer 2
3
(Reading)
3
3
3
3
Toggle
Load 3 (purple) ON and OFF, Sets Raise/Lower
control action to control Dimmer 3
Toggle
Load 1 (yellow), Load 2 (red), Load 3 (purple) ON
and OFF, Sets Raise/Lower control action to control
dimmers 1, 2 and 3
Raise
Raise the selected dimmer zone.† Zone controlled
is based on last GPCS button that was pressed. To
control all zones together, ensure that the ALL button
is pressed prior to raising the zones.
Lower
Lower the selected dimmer zone. Zone controlled
is based on last GPCS button that was pressed. To
control all zones together, ensure that the ALL button
is pressed prior to raising the zones.
†
Additional Information:
Emergency relay will always work under normal conditions with Load 1 (yellow lead).
Function
(Unless a target level is indicated, the dimmer
output will default to daylight sensor control)
2
(Exam)
6
(All)
Final dimmer output level is determined by the following combination:
• High end trim level
• Daylighting contribution
If enough natural light is entering the space and either of these features has been
implemented, raise commands from pushbuttons or the Greengate Patient Control
Station will not override or raise the lighting above the target threshold implemented
by these advanced energy savings methods.
1
1
1
1
Control
Type
Raise
ALL
1
ALL
ON/OFF
ALL
ON/OFF
ON/OFF
ALL
ON/OFF
2
3
ALL
ON/OFF
Lower
Final dimmer output level is determined by the following combination:
• High end trim level
• Daylighting contribution
If enough natural light is entering the space and either of these features has been
implemented, raise commands from pushbuttons or the Greengate Patient Control
Station will not override or raise the lighting above the target threshold
implemented by these advanced energy savings methods.
†
Additional Information:
Emergency relay will always work under normal conditions with Load 1 (yellow lead).
Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks
will always track with Load 1 (yellow lead).
Catalog #
†
Project
These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
Comments
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
Prepared by
www.coopercontrol.com
4
ACC130084