Room Controller - Conference Room

advertisement
Room Controller - Conference Room
w/Daylight Dimming, Receptacle Control and Emergency Control
RC3DE
Summary
Proper lighting that emphasizes daylighting with natural light provides a more focused meeting environment. This application illustrates how conference rooms can use
daylight dimming in conjunction with natural light entering the space, while providing Scene Control/Automatic Off and receptacle control to achieve energy savings up
to 65% and achieve higher quality lighting. Providing optional control of individual lighting zones and HVAC output will allow for even greater energy savings.
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings.
Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work
immediately as defined on this application guide.
Room Controller Sample room layout (10ʹx15ʹ)
Half Lights
Full Lights
Raise
Lower
All Off
Half Lights
Full Lights
Room Controller QuicKit
Raise
Lower
Half
Lights
All Off
Full Lights
Half Lights
Raise
Full Lights
Lower
Raise
All Off
Lower
All Off
RCQK-OS3E-CR2-ZAD-W1-D1-P-W
RC3DE
RC3DE
Half Lights
Full Lights
RC3DE
(3 Relay + 3 Dimmer +
Normal Power 1 Emergency)
General
Zone 1 UP
Meeting
Zone 1 DN
Whiteboard
Zone 2 UP
Presentation
Zone 2 DN
All Off
Zone 3 UP
Zone 3 DN
Connection
Lower
RC3DE
RC3DE
All Off
General
Meeting
Half Lights
Whiteboard
Full Lights
Presentation
Raise
All Off
Lower
Half Lights
All OffLights
FullHalf
Lights
Full Lights
Raise
Qty1: RC-5TsB-CR2-W
General, Meeting, whiteboard, presentation, all off
Raise
Lower
OAWC-DT-120W
(Wall Corner Occupancy Sensor)
RC3DE
Lower
All Off
All Off
RC3DE
Zone 1 UP
Zone 1 DN
Zone 2 UP
Zone 2 DN
RC-6TSB-CR2-*
(Pre-engraved Wallstation)
Emergency Power
Connection
Qty1: RC3DE
3 On/off relays + 3 dimmers + 1 Emergency Relay
Raise
OCC-RJ45
(Connection to any Greengate sensor)
RC-6TSB-ZAD-*
(Pre-engraved Wallstation)
Product Legend
Half Lights
Zone 3 UP
Zone 3Full
DN
Lights
Raise
Lower
RC3DE
All Off
RC3DE
RC3DE
Entry
Lighting
Qty:1 RC-6tsb-zad-W
Zone 1 UP, Zone 1 DN, Zone 2 UP, Zone 2 DN, Zone 3 UP,
Zone 3 DN
Qty1: DSRC-FMOIR
Daylight Sensor
All Off
RC3DE
Qty1: OAWC-DT-120W
Wall Corner mount vacancy sensor
Qty1: OCC-RJ45
Occupancy sensor RJ45 connector
Load 3
Dimmer 3
Load 1
Dimmer 1
RC3D
Qty1: SPRC-R-20-120
Receptacle Control
Qty1: GGRJ45-03-G
Quickconnect cable 3’
Entry
Lighting
All Off
DSRC-FMOIR
(Multi-zone Daylight Sensor)
Load 2
Dimmer 2
Qty2: GGRJ45-10-G
Quickconnect cable 10’
General
Exam
Reading
All Off
Load 2
Dimmer 2
SPRC-R-20-120
(20A Receptacle Control)
Qty3: GGRJ45-25-G
Quickconnect cable 25’
Entry
Lighting
RC3D
TV
CHANNEL
VOLUME
All Off
cc
1
2
4
3
5
7
6
8
9
0
PREV
SLEEP
MUTE
OPTION
2
1
3
ALL
ON/OFF
Entry
Lighting
Entry
Lighting
All Off
Line Voltage
to J-Box
Single box packaging with wiring detail
and installation
All Off
Downlight and Suspended Fixtures
General
Exam
Reading
All Off
Entry
Lighting
AllGeneral
Off
Whiteboard
Quiet Time •
A/V Mode
Raise
For guaranteed compatibility refer to preferred
Cooper lighting fixture information below.
Lower
EntryTV
cc
Lighting
RC3D
CHANNEL
1
VOLUME
2
4
3
5
7
6
8
9
All Off0
PREV
MUTE
SLEEP
OPTION
2
Entry
1
3
Lighting
Entry
Lighting
ALL
ON/OFF
All Off
All Off
Control sequence
RC3D
RC3D
• Scene Control/Automatic Off
Entry
Lighting
1. All On, Dimmers set to: 100%,
80%, 100%
All Off
• Individual Zone Raise/Lower control
1. Press and hold raise lighting 5%
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
• Occupancy based HVAC or Egress control
General
2. All On, DimmersRC3D
set to:
80%, 20%, 100%
Zone 1 UP
General
Whiteboard
• Automatic Demand Response 10%-40% reduction based on input
Presentation
Reading
Zone 1 DN
All Off
Zone 2 UP
RC3D
3. All On, Dimmers
set to:
RC3D
RC3D
50%, 100%, 25%
General
Zone 2 DN
Exam
General
Reading
Exam
All
Off
All Off
Zone 3 UP
All Off
TV
CHANNEL
VOLUME
cc
4. All On, Dimmers set to:
30%, 0%, 25%
1
2
5
6
8
9
0
SLEEP
• UL 924 emergency relay control
6. Press and hold lowers lighting 5%
RC3D
TV
CHANNEL
5. All Off
VOLUME
cc
1
2 3
TV
4 General
5 6
cc
CHANNEL
VOLUME
7 Exam
8 9
1
2 3
0
4 Reading
5 6
PREV
MUTE
SLEEP
OPTION
7 All
28Off 9
1
3
0
PREV
MUTE
ALL
ON/OFF
SLEEP
RC-5TSB-CR2-W
Conference Room Wallstation
5. Press and hold raise lighting 5%
MUTE
3
ALL
ON/OFF
UL924
4. Press and hold lowers lighting 5%
OPTION
2
1
Zone 3 DN
3
4
7
PREV
• After-hours warn Offs and timers to ensure maximum efficiency and
savings
3. Press and hold raise lighting 5%
Reading
• Receptacle Control for additional energy savings
UL924
• High-end
trim/tuning to define target light levels
UL924
2. Press and hold lowers lighting 5%
Exam
Meeting
• Automatic multi-zone daylight dimming out-of-the-box
OPTION
2
1
RC-6TSB-ZAD-W
Individual Dimming Wallstation
3
ALL
ON/OFF
General
Exam
Reading
All Off
General
ExamGeneral
Exam
Reading
All OffReading
All Off
CHANNEL
TV
VOLUME
General
cc
1Whiteboard
2 3
4Quiet
5 Time
6 •
7
8
9
A/V Mode
0
PREV
Raise
SLEEP
MUTE
OPTION
2
1 Lower 3
Integrated capabilities
Cooper Lighting Guaranteed Compatible Fixtures
ALL
ON/OFF
CHANNEL
TV
VOLUME
cc
General
1
2 3
General
Whiteboard
4
5 6
Exam
7
8
General
Quiet
Time9 •
Reading
PREV
CHANNEL
TV
0
MUTE
VOLUME
Whiteboard
A/V
Mode
All Off
cc TV
2
Quiet Time •
Raise
1
33
1
2 cc
SLEEP
OPTION
CHANNEL
VOLUME
ALL
ON/OFF
Lower
4A/V Mode
1
5 62
Room Controller Conference Room Lighting Layouts
Corelite LFL
Room Controller Conference Room Lighting Layouts
7
0
Lower
SLEEP
2
PREV
1
3
Corelite LED
7Raise8
4
PREV
SLEEP
ALL
ON/OFF
1
95
6
8
9
MUTE
0
3
2
OPTION
MUTE
OPTION
3
ALL
ON/OFF
UL924
UL924
UL924
TV
CHANNEL
VOLUME
cc
1
2
3
General
4
Neoray LED
Room Controller Conference Room Lighting Layouts
Neoray LFL
Room Controller Conference Room Lighting Layouts
5
6
Whiteboard
7
8
9
Quiet Time
•
0
PREV
MUTE
SLEEP
A/V Mode
2
1
Raise
OPTION
3
ALL
ON/OFF
Lower
General
Whiteboard
Quiet Time •
A/V Mode
Raise
General
Occupancy/Vacancy
Sensing
Daylighting
Control
Manual
Control
Receptacle
Control
Emergency
Integration
Demand
Response
General
Lower
Whiteboard
QuietWhiteboard
Time •
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance
value information.
Quiet Time •
A/V Mode
RaiseA/V Mode
Raise
Lower
Lower
General
Whiteboard
Quiet Time •
A/V Mode
Raise
www.coopercontrol.com
1
Lower
Room Controller - Conference Room
w/Daylight Dimming, Receptacle Control and Emergency Control
Room Controller and Smart Devices use Click & Go technology
The RC3DE will automtically recognize any smart device connected with the QuickConnect cable (provided) and start working immediately upon power up with no
programming required. The RC3DE defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Entry wallstations will provide On/Off
control of the Yellow load. Teacher stations provide On/Off control of the Red and Purple loads as well as manual Raise/Lower of all dimmers.
The daylight sensor will automatically, on power up, provide multi-zone daylight dimming in the space. (Remote adjustments can be made later.)
*Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress
Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations.
EMERGENCY NEUTRAL
Emergency Lighting Load
YELLOW
Emergency Power OUT (Tracks with normal
lighting YELLOW load)
WHT/ORG or WHT/BLK
Neutral
BLACK - Hot
(120/277 VAC)
YELLOW
Lighting Load (1)
RED
Lighting Load (2)
PURPLE
Lighting Load (3)
BLUE - Relay In
(120/277 VAC)
BLUE - Emergency Power In
(120/277 VAC)
Requires 0-10V
dimming ballasts
Violet - Dimmer 1
Gray - Dimmer 1
Violet - Dimmer 2
Gray - Dimmer 2
Emergency Note:
Emergency load tracks with normal lighting
YELLOW load for On/OFF. If dimming it will be
adjusted with the dimming zone it is connected to.
Upon loss of normal power to the RC3DE, the
emergency load will be forced On and full bright to
100%.
Violet - Dimmer 3
Gray - Dimmer 3
0-10V Dimming Zone Note:
The 0-10V dimming zones within the
Room Controller can be wired and
controlled independent of the connected
loads. This allows a each load to have a
dedicated 0-10V dimming zone or a single
load to have up to three 0-10V dimming zones.
In room ladderless testing is done by pressing the
"All Off" button four times, within 3 seconds.
The RC3DE is UL 924 listed.
Receptacle Control:
20Amp 120 VAC receptacle control immediately works
upon power up and connection to the Room Controller.
Receptacle turns On by button press or occupancy and
Off when space is vacant.
QuickConnect coupler
(GGRC-COUPLER)
Adjustable daylight
sensor dome
120V receptacle
circuit
Quick connect cables
are pre-terminated and
included in the Room
Controller QuicKit and
measured to fit
typical room layouts
*Immediately provides multi-zone
daylight dimming upon powerup
Allows connection to
any Greengate
Occupancy/Vacancy
Sensor
(OCC-RJ45)
Dual Technology
Wall Corner
Occupancy/Vacancy Sensor
(OAWC-DT-120W)
*Defaults to vacancy sensor mode
Manual On/Automatic Off (all loads)
for maximum energy savings
SPRC-R-20-120
20A Receptacle Control
quick connect
mming required.
aximum energy
cher stations
Lower of all
Button 1: Load (1),(2),(3) ON, Dimmer 1: 100%,
Zone 1 UP
General
Dimmer 2: 80%, Dimmer 3: 100%
Button 1: Press and hold increase Zone 1 lighting 5%
Meeting
Zone 1 DN
Button 2: Press and hold decrease Zone 1 lighting 5%
Button 2: Load (1),(2),(3) ON, Dimmer 1: 80%,
Whiteboard
Zone 2 UP
Dimmer 2: 20%, Dimmer 3: 100%
Button 3: Press and hold increase Zone 2 lighting 5%
Presentation
Zone 2 DN
Button 4: Press and hold decrease Zone 2 lighting 5%
Button 3: Load (1),(2),(3) ON, Dimmer 1: 50%,
Zone 3 UP
All Off
Button 5: Press and hold increase Zone 3 lighting 5%
Dimmer 2: 100%, Dimmer 3: 25%
Zone 3 DN
Button 6: Press and hold decrease Zone 3 lighting 5%
Button 4: Load (1),(2),(3) ON, Dimmer 1: 30%,
Dimmer 2: 0%, Dimmer 3: 25%
Button 5: Load (1),(2),(3) OFF
RC-5TSB-CR2-*RC-6TSB-ZAD-*
Office Station Office Station
Cooper Controls
203 Cooper Circle
Peachtree City,
GA 30269. USA
Tel: +1-800-553-3879
Fax: +1-800-954-7016
Email: controls@cooperindustries.com
Website: www.coopercontrol.com
Room Controller - RC3DE
Three Relay + Three Dimmers Wiring Diagram + One Emergency Relay
dimming in the
Drawing Name:
Drawing Date:
RC3DE-ConferenceReceptacleWC.dwg1/10/2013
ogramming
MS Output, Alert
www.coopercontrol.com
2
Daylight sensor
(DSRC-FMOIR)
Room Controller - Conference Room
w/Daylight Dimming, Receptacle Control and Emergency Control
Mounting The Room Controller
The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller includes breakouts for
direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using
the holes at the bottom of the Room Controller.
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout
openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Sample Placement Diagram
Daylight Sensor Ceiling Location
(for example purposes only)
1. Mount the daylight sensor one to two times the window height from the window wall.
2. Position the sensor so its arrow is pointed toward
the nearest window.
3. Ensure the daylight sensor is not obstructed or
looking directly at electric light.
4. For narrow spaces mount the daylight sensor near
the window facing into the space.
Sample Placement Diagram
(for example purposes only)
Room Controller
(above entry door)
Wall/Corner Mount
Occupancy Sensor
Additional
Wallstation
General On
AV Mode
Whiteboard
Quiet Time
Raise
Lower
Entry
Wallstation
General On
Off
Window
Daylight
Sensor
60°
Area viewed by
daylight sensor
Occupancy sensor
Coverage Diagram (OAWC-DT-120W)
24’ (7.3 mm)
Wiring Diagram
20’ (6 mm)
SPRC-R-20-120
Room Controller
Normal Power
(20A Receptacle Control)
(Above Entry Door)
(Line In & Load Out)
RC3DE
24’ (7.3 mm)
Line Voltage
to J-Box
20’ (6 mm)
12’ (3.7 mm)
Line Voltage
to receptacles
(low voltage, class 2)
OCC-RJ45
Emergency Power
(Line In & Load Out)
0-10V Dimmer Wiring
(Dimming Models Only)
Major Motion, IR
Minor Motion, Ultrasonic
12’ (3.7 mm)
12’ (3.7 mm)
8’ (2.4 mm)
0
8’ (2.4 mm)
DSRC-FMOIR
RC3DE model only
Minor Motion, IR
8’ (2.4 mm)
0
8’ (2.4 mm)
(Multi-zone
daylight sensor)
Major Motion, Ultrasonic
Minor Motion, IR
Major Motion, IR
Maximum coverage area may
Minor
Ultrasonic
varyMotion,
somewhat
according to room
shapeMotion,
and theUltrasonic
presence of obstacles.
Major
12’ (3.7 mm)
(Any Greengate
Occupancy Sensor)
Wallstation Wallstation
(Entry)
The NEMA WD 7 Guide and robotic
method coverage
were utilized
verify
Maximum
areatomay
coverage
patterns.
vary somewhat
according
to room
shape and the presence of obstacles.
24’ (7.3 mm)
(Additional)
Half Lights
Half Lights
Full Lights
Full Lights
Raise
Raise
Lower
Lower
All Off
All Off
20’ (6 mm)
10 ft
(3 mm)
10 ft
(3 mm)
24’ (7.3 mm)
24 ft
6 ft
15 ft
20’ (6 mm)
(1.7 mm) (4.6 mm) (7.3 mm)
24 ft
6 ft
15 ft
(1.7 mm) (4.6 mm) (7.3 mm)
50 ft
(15.3 mm)
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
50 ft
(15.3 mm)
Connections
Room Controller and Smart Devices
use Click & Go Connections
Room Controller 0-10V Dimming Connections
Dimmer 1: Near the Window
Dimmer 2: Middle of Room
Dimmer 3: Far from Window
-
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
+
The daylight sensor will automatically provide multi-zone
daylight dimming based on this wiring configuration
0-10V Dimming
1
0-10V Gray (-)
0-10V Violet (+)
www.coopercontrol.com
3
2
5
34
6
1. Wallstations (up to four)
2. Slider Station Connection (one)
3. Occupancy Sensors (up to two)
4. Daylight Sensor (one)
5. Receptacle Control or BMS Output
6. Switchpack (controlled with Load 1 for
alternate voltage)
Room Controller - Conference Room
w/Daylight Dimming, Receptacle Control and Emergency Control
Ordering
RCQK
-
OS3E
-
CR2 - ZAD
-
W1
-
D1
-
P
-
W
Room Controller
Daylight
Station Color
QuicKit
D1 - Multi-zone Daylight Sensor
DH - Multi-zone Daylight Sensor w/
Handheld Remote
W - White
G - Gray
V - Ivory
B - Black
Office Stations (Choose up to 4)
Types of Space
and Control
OS - Office Switching (RC3)
OS2 - Office 2 Zone Dimming (RC3D2)
OS3 - Office 3 Zone Dimming (RC3D)
OS3E - Office 3 Zone Dimming and
and Emergency Relay (RC3DE)
OS1 - Half Lights, Full Lights, All Off
(3 Large Buttons)
OS2 - Half Lights, Full Lights, Raise, Lower, All Off †
(5 Small Buttons)
OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off †
(6 Small Buttons)
OS4 - All On, All Off (2 Large Buttons)
CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower
(6 Small Buttons - Scenes)
CR2 - General, Meeting, Whiteboard, Presentation, All Off
(5 Small Buttons - Scenes)
SS1 - Slider Station ††
ZAD - Zone 1 UP, Zone 2 DN, Zone 3 UP, Zone 3 DN
(6 Small Buttons - Scenes)
Occupancy Sensor
C1 - Ceiling DT 2000 sq. ft.
C2 - Ceiling PIR 1500 sq. ft.
C3 - Ceiling DT 1000 sq. ft.
W1 - Wall Corner DT
W2 - Wall Corner PIR
W3 - Hallway PIR
Options
P - Plug Load
B - BMS/Egress
*Catalog number automatically includes low voltage
connection cable, wallplates and connectors based on room
type and configuration.
Pre-defined Wallstation Model numbers
Half lights
Half Lights
Half Lights
Full Lights
Full Lights
Raise
Undercabinet
Lower
Raise
All Off
Lower
All Off
Lower
All On
Full lights
All Off
RC-3TLB-OS1
RC-5TSB-OS2
All Off
RC-6tsb-OS3
RC-2tlb-OS4
General
General
Meeting
Meeting
Zone 1 DN
Whiteboard
Whiteboard
Zone 2 UP
Presentation
Presentation
Zone 2 DN
Raise
All Off
Zone 3 UP
Zone 1 UP
Zone 3 DN
RC-6tsb-cr1
RC-5tsb-cr2
RC-6tsb-ZAD
*For site specific engraving, please see the Room Controller
Wallstation custom engraving form on the Cooper Controls
website
Applications
Conference Room Application Button Functionality
Program
No.
Button Text
Control
Type
Function
(Unless a target level is indicated, the dimmer output
will default to daylight sensor control)
12
General
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 100%, Dimmer 2 80%, Dimmer 3 80%
Solatube Open (RC3DE only)
13
Meeting
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 80%, Dimmer 2 20%, Dimmer 3 100%
Solatube Open (RC3DE only)
14
Whiteboard
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 50%, Dimmer 2: 100%, Dimmer 3: 50%
Solatube Closed (RC3DE only)
15
Presentation
Preset
Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
Dimmer 1: 30%, Dimmer 2: 0%, Dimmer 3: 25%
Solatube Closed (RC3DE only)
6
Raise
Raise
Raise All Dimmers
7
Lower
Lower
Lower All Dimmers
16
All On
Preset
Load 1 (yellow) ON, Load 2 (red) ON Load 3 (purple) ON
All Dimmers 100%
8
All Off
Preset
Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF
Solatube closed (RC3DE only)
Slider
Raise and Lower All Dimmers
Slider
†
†
††
Catalog #
Type
Project
†
These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
Comments
Prepared by
www.coopercontrol.com