Room Controller - Conference Room w/Daylight Dimming, Receptacle Control and Emergency Control RC3DE Summary Proper lighting that emphasizes daylighting with natural light provides a more focused meeting environment. This application illustrates how conference rooms can use daylight dimming in conjunction with natural light entering the space, while providing Scene Control/Automatic Off and receptacle control to achieve energy savings up to 65% and achieve higher quality lighting. Providing optional control of individual lighting zones and HVAC output will allow for even greater energy savings. The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide. Room Controller Sample room layout (10ʹx15ʹ) Half Lights Full Lights Raise Lower All Off Half Lights Full Lights Room Controller QuicKit Raise Lower Half Lights All Off Full Lights Half Lights Raise Full Lights Lower Raise All Off Lower All Off RCQK-OS3E-CR2-ZAD-W1-D1-P-W RC3DE RC3DE Half Lights Full Lights RC3DE (3 Relay + 3 Dimmer + Normal Power 1 Emergency) General Zone 1 UP Meeting Zone 1 DN Whiteboard Zone 2 UP Presentation Zone 2 DN All Off Zone 3 UP Zone 3 DN Connection Lower RC3DE RC3DE All Off General Meeting Half Lights Whiteboard Full Lights Presentation Raise All Off Lower Half Lights All OffLights FullHalf Lights Full Lights Raise Qty1: RC-5TsB-CR2-W General, Meeting, whiteboard, presentation, all off Raise Lower OAWC-DT-120W (Wall Corner Occupancy Sensor) RC3DE Lower All Off All Off RC3DE Zone 1 UP Zone 1 DN Zone 2 UP Zone 2 DN RC-6TSB-CR2-* (Pre-engraved Wallstation) Emergency Power Connection Qty1: RC3DE 3 On/off relays + 3 dimmers + 1 Emergency Relay Raise OCC-RJ45 (Connection to any Greengate sensor) RC-6TSB-ZAD-* (Pre-engraved Wallstation) Product Legend Half Lights Zone 3 UP Zone 3Full DN Lights Raise Lower RC3DE All Off RC3DE RC3DE Entry Lighting Qty:1 RC-6tsb-zad-W Zone 1 UP, Zone 1 DN, Zone 2 UP, Zone 2 DN, Zone 3 UP, Zone 3 DN Qty1: DSRC-FMOIR Daylight Sensor All Off RC3DE Qty1: OAWC-DT-120W Wall Corner mount vacancy sensor Qty1: OCC-RJ45 Occupancy sensor RJ45 connector Load 3 Dimmer 3 Load 1 Dimmer 1 RC3D Qty1: SPRC-R-20-120 Receptacle Control Qty1: GGRJ45-03-G Quickconnect cable 3’ Entry Lighting All Off DSRC-FMOIR (Multi-zone Daylight Sensor) Load 2 Dimmer 2 Qty2: GGRJ45-10-G Quickconnect cable 10’ General Exam Reading All Off Load 2 Dimmer 2 SPRC-R-20-120 (20A Receptacle Control) Qty3: GGRJ45-25-G Quickconnect cable 25’ Entry Lighting RC3D TV CHANNEL VOLUME All Off cc 1 2 4 3 5 7 6 8 9 0 PREV SLEEP MUTE OPTION 2 1 3 ALL ON/OFF Entry Lighting Entry Lighting All Off Line Voltage to J-Box Single box packaging with wiring detail and installation All Off Downlight and Suspended Fixtures General Exam Reading All Off Entry Lighting AllGeneral Off Whiteboard Quiet Time • A/V Mode Raise For guaranteed compatibility refer to preferred Cooper lighting fixture information below. Lower EntryTV cc Lighting RC3D CHANNEL 1 VOLUME 2 4 3 5 7 6 8 9 All Off0 PREV MUTE SLEEP OPTION 2 Entry 1 3 Lighting Entry Lighting ALL ON/OFF All Off All Off Control sequence RC3D RC3D • Scene Control/Automatic Off Entry Lighting 1. All On, Dimmers set to: 100%, 80%, 100% All Off • Individual Zone Raise/Lower control 1. Press and hold raise lighting 5% General Whiteboard Quiet Time • A/V Mode Raise Lower • Occupancy based HVAC or Egress control General 2. All On, DimmersRC3D set to: 80%, 20%, 100% Zone 1 UP General Whiteboard • Automatic Demand Response 10%-40% reduction based on input Presentation Reading Zone 1 DN All Off Zone 2 UP RC3D 3. All On, Dimmers set to: RC3D RC3D 50%, 100%, 25% General Zone 2 DN Exam General Reading Exam All Off All Off Zone 3 UP All Off TV CHANNEL VOLUME cc 4. All On, Dimmers set to: 30%, 0%, 25% 1 2 5 6 8 9 0 SLEEP • UL 924 emergency relay control 6. Press and hold lowers lighting 5% RC3D TV CHANNEL 5. All Off VOLUME cc 1 2 3 TV 4 General 5 6 cc CHANNEL VOLUME 7 Exam 8 9 1 2 3 0 4 Reading 5 6 PREV MUTE SLEEP OPTION 7 All 28Off 9 1 3 0 PREV MUTE ALL ON/OFF SLEEP RC-5TSB-CR2-W Conference Room Wallstation 5. Press and hold raise lighting 5% MUTE 3 ALL ON/OFF UL924 4. Press and hold lowers lighting 5% OPTION 2 1 Zone 3 DN 3 4 7 PREV • After-hours warn Offs and timers to ensure maximum efficiency and savings 3. Press and hold raise lighting 5% Reading • Receptacle Control for additional energy savings UL924 • High-end trim/tuning to define target light levels UL924 2. Press and hold lowers lighting 5% Exam Meeting • Automatic multi-zone daylight dimming out-of-the-box OPTION 2 1 RC-6TSB-ZAD-W Individual Dimming Wallstation 3 ALL ON/OFF General Exam Reading All Off General ExamGeneral Exam Reading All OffReading All Off CHANNEL TV VOLUME General cc 1Whiteboard 2 3 4Quiet 5 Time 6 • 7 8 9 A/V Mode 0 PREV Raise SLEEP MUTE OPTION 2 1 Lower 3 Integrated capabilities Cooper Lighting Guaranteed Compatible Fixtures ALL ON/OFF CHANNEL TV VOLUME cc General 1 2 3 General Whiteboard 4 5 6 Exam 7 8 General Quiet Time9 • Reading PREV CHANNEL TV 0 MUTE VOLUME Whiteboard A/V Mode All Off cc TV 2 Quiet Time • Raise 1 33 1 2 cc SLEEP OPTION CHANNEL VOLUME ALL ON/OFF Lower 4A/V Mode 1 5 62 Room Controller Conference Room Lighting Layouts Corelite LFL Room Controller Conference Room Lighting Layouts 7 0 Lower SLEEP 2 PREV 1 3 Corelite LED 7Raise8 4 PREV SLEEP ALL ON/OFF 1 95 6 8 9 MUTE 0 3 2 OPTION MUTE OPTION 3 ALL ON/OFF UL924 UL924 UL924 TV CHANNEL VOLUME cc 1 2 3 General 4 Neoray LED Room Controller Conference Room Lighting Layouts Neoray LFL Room Controller Conference Room Lighting Layouts 5 6 Whiteboard 7 8 9 Quiet Time • 0 PREV MUTE SLEEP A/V Mode 2 1 Raise OPTION 3 ALL ON/OFF Lower General Whiteboard Quiet Time • A/V Mode Raise General Occupancy/Vacancy Sensing Daylighting Control Manual Control Receptacle Control Emergency Integration Demand Response General Lower Whiteboard QuietWhiteboard Time • Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information. Quiet Time • A/V Mode RaiseA/V Mode Raise Lower Lower General Whiteboard Quiet Time • A/V Mode Raise www.coopercontrol.com 1 Lower Room Controller - Conference Room w/Daylight Dimming, Receptacle Control and Emergency Control Room Controller and Smart Devices use Click & Go technology The RC3DE will automtically recognize any smart device connected with the QuickConnect cable (provided) and start working immediately upon power up with no programming required. The RC3DE defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Entry wallstations will provide On/Off control of the Yellow load. Teacher stations provide On/Off control of the Red and Purple loads as well as manual Raise/Lower of all dimmers. The daylight sensor will automatically, on power up, provide multi-zone daylight dimming in the space. (Remote adjustments can be made later.) *Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations. EMERGENCY NEUTRAL Emergency Lighting Load YELLOW Emergency Power OUT (Tracks with normal lighting YELLOW load) WHT/ORG or WHT/BLK Neutral BLACK - Hot (120/277 VAC) YELLOW Lighting Load (1) RED Lighting Load (2) PURPLE Lighting Load (3) BLUE - Relay In (120/277 VAC) BLUE - Emergency Power In (120/277 VAC) Requires 0-10V dimming ballasts Violet - Dimmer 1 Gray - Dimmer 1 Violet - Dimmer 2 Gray - Dimmer 2 Emergency Note: Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%. Violet - Dimmer 3 Gray - Dimmer 3 0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones. In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds. The RC3DE is UL 924 listed. Receptacle Control: 20Amp 120 VAC receptacle control immediately works upon power up and connection to the Room Controller. Receptacle turns On by button press or occupancy and Off when space is vacant. QuickConnect coupler (GGRC-COUPLER) Adjustable daylight sensor dome 120V receptacle circuit Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts *Immediately provides multi-zone daylight dimming upon powerup Allows connection to any Greengate Occupancy/Vacancy Sensor (OCC-RJ45) Dual Technology Wall Corner Occupancy/Vacancy Sensor (OAWC-DT-120W) *Defaults to vacancy sensor mode Manual On/Automatic Off (all loads) for maximum energy savings SPRC-R-20-120 20A Receptacle Control quick connect mming required. aximum energy cher stations Lower of all Button 1: Load (1),(2),(3) ON, Dimmer 1: 100%, Zone 1 UP General Dimmer 2: 80%, Dimmer 3: 100% Button 1: Press and hold increase Zone 1 lighting 5% Meeting Zone 1 DN Button 2: Press and hold decrease Zone 1 lighting 5% Button 2: Load (1),(2),(3) ON, Dimmer 1: 80%, Whiteboard Zone 2 UP Dimmer 2: 20%, Dimmer 3: 100% Button 3: Press and hold increase Zone 2 lighting 5% Presentation Zone 2 DN Button 4: Press and hold decrease Zone 2 lighting 5% Button 3: Load (1),(2),(3) ON, Dimmer 1: 50%, Zone 3 UP All Off Button 5: Press and hold increase Zone 3 lighting 5% Dimmer 2: 100%, Dimmer 3: 25% Zone 3 DN Button 6: Press and hold decrease Zone 3 lighting 5% Button 4: Load (1),(2),(3) ON, Dimmer 1: 30%, Dimmer 2: 0%, Dimmer 3: 25% Button 5: Load (1),(2),(3) OFF RC-5TSB-CR2-*RC-6TSB-ZAD-* Office Station Office Station Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: controls@cooperindustries.com Website: www.coopercontrol.com Room Controller - RC3DE Three Relay + Three Dimmers Wiring Diagram + One Emergency Relay dimming in the Drawing Name: Drawing Date: RC3DE-ConferenceReceptacleWC.dwg1/10/2013 ogramming MS Output, Alert www.coopercontrol.com 2 Daylight sensor (DSRC-FMOIR) Room Controller - Conference Room w/Daylight Dimming, Receptacle Control and Emergency Control Mounting The Room Controller The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller. Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller. Sample Placement Diagram Daylight Sensor Ceiling Location (for example purposes only) 1. Mount the daylight sensor one to two times the window height from the window wall. 2. Position the sensor so its arrow is pointed toward the nearest window. 3. Ensure the daylight sensor is not obstructed or looking directly at electric light. 4. For narrow spaces mount the daylight sensor near the window facing into the space. Sample Placement Diagram (for example purposes only) Room Controller (above entry door) Wall/Corner Mount Occupancy Sensor Additional Wallstation General On AV Mode Whiteboard Quiet Time Raise Lower Entry Wallstation General On Off Window Daylight Sensor 60° Area viewed by daylight sensor Occupancy sensor Coverage Diagram (OAWC-DT-120W) 24’ (7.3 mm) Wiring Diagram 20’ (6 mm) SPRC-R-20-120 Room Controller Normal Power (20A Receptacle Control) (Above Entry Door) (Line In & Load Out) RC3DE 24’ (7.3 mm) Line Voltage to J-Box 20’ (6 mm) 12’ (3.7 mm) Line Voltage to receptacles (low voltage, class 2) OCC-RJ45 Emergency Power (Line In & Load Out) 0-10V Dimmer Wiring (Dimming Models Only) Major Motion, IR Minor Motion, Ultrasonic 12’ (3.7 mm) 12’ (3.7 mm) 8’ (2.4 mm) 0 8’ (2.4 mm) DSRC-FMOIR RC3DE model only Minor Motion, IR 8’ (2.4 mm) 0 8’ (2.4 mm) (Multi-zone daylight sensor) Major Motion, Ultrasonic Minor Motion, IR Major Motion, IR Maximum coverage area may Minor Ultrasonic varyMotion, somewhat according to room shapeMotion, and theUltrasonic presence of obstacles. Major 12’ (3.7 mm) (Any Greengate Occupancy Sensor) Wallstation Wallstation (Entry) The NEMA WD 7 Guide and robotic method coverage were utilized verify Maximum areatomay coverage patterns. vary somewhat according to room shape and the presence of obstacles. 24’ (7.3 mm) (Additional) Half Lights Half Lights Full Lights Full Lights Raise Raise Lower Lower All Off All Off 20’ (6 mm) 10 ft (3 mm) 10 ft (3 mm) 24’ (7.3 mm) 24 ft 6 ft 15 ft 20’ (6 mm) (1.7 mm) (4.6 mm) (7.3 mm) 24 ft 6 ft 15 ft (1.7 mm) (4.6 mm) (7.3 mm) 50 ft (15.3 mm) The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. 50 ft (15.3 mm) Connections Room Controller and Smart Devices use Click & Go Connections Room Controller 0-10V Dimming Connections Dimmer 1: Near the Window Dimmer 2: Middle of Room Dimmer 3: Far from Window - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + The daylight sensor will automatically provide multi-zone daylight dimming based on this wiring configuration 0-10V Dimming 1 0-10V Gray (-) 0-10V Violet (+) www.coopercontrol.com 3 2 5 34 6 1. Wallstations (up to four) 2. Slider Station Connection (one) 3. Occupancy Sensors (up to two) 4. Daylight Sensor (one) 5. Receptacle Control or BMS Output 6. Switchpack (controlled with Load 1 for alternate voltage) Room Controller - Conference Room w/Daylight Dimming, Receptacle Control and Emergency Control Ordering RCQK - OS3E - CR2 - ZAD - W1 - D1 - P - W Room Controller Daylight Station Color QuicKit D1 - Multi-zone Daylight Sensor DH - Multi-zone Daylight Sensor w/ Handheld Remote W - White G - Gray V - Ivory B - Black Office Stations (Choose up to 4) Types of Space and Control OS - Office Switching (RC3) OS2 - Office 2 Zone Dimming (RC3D2) OS3 - Office 3 Zone Dimming (RC3D) OS3E - Office 3 Zone Dimming and and Emergency Relay (RC3DE) OS1 - Half Lights, Full Lights, All Off (3 Large Buttons) OS2 - Half Lights, Full Lights, Raise, Lower, All Off † (5 Small Buttons) OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off † (6 Small Buttons) OS4 - All On, All Off (2 Large Buttons) CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower (6 Small Buttons - Scenes) CR2 - General, Meeting, Whiteboard, Presentation, All Off (5 Small Buttons - Scenes) SS1 - Slider Station †† ZAD - Zone 1 UP, Zone 2 DN, Zone 3 UP, Zone 3 DN (6 Small Buttons - Scenes) Occupancy Sensor C1 - Ceiling DT 2000 sq. ft. C2 - Ceiling PIR 1500 sq. ft. C3 - Ceiling DT 1000 sq. ft. W1 - Wall Corner DT W2 - Wall Corner PIR W3 - Hallway PIR Options P - Plug Load B - BMS/Egress *Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration. Pre-defined Wallstation Model numbers Half lights Half Lights Half Lights Full Lights Full Lights Raise Undercabinet Lower Raise All Off Lower All Off Lower All On Full lights All Off RC-3TLB-OS1 RC-5TSB-OS2 All Off RC-6tsb-OS3 RC-2tlb-OS4 General General Meeting Meeting Zone 1 DN Whiteboard Whiteboard Zone 2 UP Presentation Presentation Zone 2 DN Raise All Off Zone 3 UP Zone 1 UP Zone 3 DN RC-6tsb-cr1 RC-5tsb-cr2 RC-6tsb-ZAD *For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website Applications Conference Room Application Button Functionality Program No. Button Text Control Type Function (Unless a target level is indicated, the dimmer output will default to daylight sensor control) 12 General Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON Dimmer 1: 100%, Dimmer 2 80%, Dimmer 3 80% Solatube Open (RC3DE only) 13 Meeting Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON Dimmer 1: 80%, Dimmer 2 20%, Dimmer 3 100% Solatube Open (RC3DE only) 14 Whiteboard Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON Dimmer 1: 50%, Dimmer 2: 100%, Dimmer 3: 50% Solatube Closed (RC3DE only) 15 Presentation Preset Load 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON Dimmer 1: 30%, Dimmer 2: 0%, Dimmer 3: 25% Solatube Closed (RC3DE only) 6 Raise Raise Raise All Dimmers 7 Lower Lower Lower All Dimmers 16 All On Preset Load 1 (yellow) ON, Load 2 (red) ON Load 3 (purple) ON All Dimmers 100% 8 All Off Preset Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF Solatube closed (RC3DE only) Slider Raise and Lower All Dimmers Slider † † †† Catalog # Type Project † These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE) †† Slider stations can not be used if a wallstation with Raise/Lower buttons are used Comments Prepared by www.coopercontrol.com 4 ACC130079 Date