Room Controller - Classroom w/Daylight Dimming, Receptacle Control and Suspended Fixtures Summary A well designed control system requires the consideration of energy codes, the building occupants’ use patterns and the type of lighting that is used in each room. Careful design and the use of strategies such as daylighting, ambient task lighting, and advanced technologies can achieve even greater energy efficiency and higher quality lighting. The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide. Half Lights Full Lights Raise Lower All Off Room Controller Sample room layout (30ʹ x 30ʹ) Room Controller QuicKit Half Lights Half Lights Lights Full Full Lights Half Lights Raise Raise Full Lights Lower Lower Raise All Off All Off Lower All Off RCQK-CR3E-ES1-TS1-W1-D1-P-W RC3DE RC3DE Half Lights Full Lights Load 3 General On Raise RC3DE RC3DE Lower All Off AV Mode Normal Power Connection Whiteboard Quiet Time Raise Lower RC-6TSB-TS2-* (Pre-engraved Wallstation) Full Lights FullLower Lights Entry Lighting Raise All Off AllFull Off Lights All Off Raise Lower RC3DE All Off Load 1 RC3DE (3 Relay + 3 Dimmer + 1 Emergency Relay) RC3DE Half Lights Full Lights Half Lights Raise Full Lights Lower Raise All Off Lower RC3DE RC3DE All Off RC3DE General On Off RC3DE RC3DE RC3D DSRC-FMOIR (Multi-zone Daylight Sensor) RC-2TLB-ES1-* (Pre-engraved Wallstation) Qty1: RC-2TLB-ES1-W (Entry, All Off) Qty1: RC-6TSB-TS1-W (General, Whiteboard, Quiet Time, A/V Mode, Raise, LoweR) Qty1: DSRC-FMOIR Daylight Sensor Qty1: OAWC-DT-120W Wall Corner Mount vacancy sensor Qty1: OCC-RJ45 Occupancy sensor RJ45 connector Qty1: SPRC-R-20-120 Receptacle Control General Exam Reading Daylighting Zone 3 Daylighting Zone 2 All Off Daylighting Zone 1 Qty1: RC3DE 3 relay + 3 dimmer + 1 emergency relay Half Lights Half Lights Raise Half Lights Lower EM Load Product Legend TV CHANNEL VOLUME cc 1 2 3 4 5 6 7 8 9 0 PREV SLEEP MUTE OPTION 2 Entry 1 Lighting Qty1: GGRJ45-10-G Quickconnect cable 10’ 3 ALL ON/OFF All Off Qty3: GGRJ45-25-G Quickconnect cable 25’ Qty1: GGRJ45-50-G Quickconnect cable 50’ Entry Lighting All Off OCC-RJ45 (Connection to any Greengate Sensor) General Whiteboard Quiet Time • A/V Mode Raise Lower RC3D Single box packaging with wiring detail and installation Entry Lighting Entry Lighting All Off All Off OAWC-DT-120W (Wall Corner Dual Tech) SPRC-R-20-120 (20A Receptacle Control) suspended Fixture Line Voltage to J-Box General Exam Entry Lighting Reading All Off All Off RC3D For guaranteed compatibility refer to preferred Cooper lighting fixture information below. Entry Lighting Entry Lighting All Off TV CHANNEL VOLUME cc 1 2 3 All Off 4Entry 5 6 7 8 9 Lighting 0 PREV SLEEP MUTE OPTION 2 1 3 All Off ALL ON/OFF Control sequence RC3D RC3D Entry Lighting • Manual On/Automatic Off or Automatic On (50%)/Automatic Off • High-end trim/tuning to define target light levels 1. Toggle Load 2 Entry Lighting All Off All Off 2. Toggle Load 3 General General Whiteboard Exam Quiet Time • Reading A/V Mode General • Automatic multi-zone daylight dimming out-of-the-box Raise All Off RC3D Lower 3. Disable Occ Sensor for 1 hr Whiteboard Quiet Time • • Receptacle control based on occupancy A/V Mode RC3D RC3D 4. Set Dimmers to 20% RC3D 2. Load 1, 2, 3 Off All Off Exam TV CHANNEL VOLUME cc All Off Exam Raise 1. Toggle Load 1 General Reading General • Emergency UL 924 control (tracks with relay 1) UL924 • Automatic UL924 Demand Response 10%-40% reduction based on input Entry 1 Reading All Off 2 4 3 5 7 6 8 9 5. Raise Dimmers 5% 0 PREV SLEEP 1 MUTE OPTION 2 3 ALL ON/OFF Lower 6. Lower Dimmers 5% RC3D RC3D UL924 TV CHANNEL VOLUME cc 1 CHANNEL 4 7 1 PREV 4 RC-6TSB-TS1 2 TV 5 cc 8 3 VOLUME 6 General 9 2 3 Exam 0 5 28 MUTE 6 Reading SLEEP 7 1 OPTION 9 3 All Off 0 ALL ON/OFF PREV SLEEP RC-2TLB-EC1 MUTE OPTION 2 1 3 ALL ON/OFF General Exam Reading General All Off Exam General Reading Whiteboard All Off Quiet Time • General A/V Mode Exam Integrated capabilities Raise Reading All Lower Off TV CHANNEL VOLUME cc 1 2 4 3 5 7 6 8 0 PREV SLEEP 9 Cooper Lighting Guaranteed Compatible Fixtures MUTE OPTION 2 1 3 ALL ON/OFF CHANNEL TV General VOLUME cc Exam General 1 2 3 General TV Reading Whiteboard CHANNEL 4 5 6 VOLUME cc Exam 7Off 8 9 All Quiet Time • General 1 PREV 2 3 Reading 0 MUTE Whiteboard A/V Mode 4 SLEEP 5 6 ALL ON/OFF SLEEP UL924 OPTION 3 6 ALL ON/OFF Lower 7 8 0 PREV SLEEP 1 2 9 MUTE OPTION 3 ALL ON/OFF TV VOLUME cc 1 4 7 PREV SLEEP 1 2 CHANNEL 5 81 TV 3 92 3 MUTE OPTION 2 A/V 1 Mode 3 ALL ON/OFF Lower Receptacle Control Emergency Integration Demand Response General Whiteboard Quiet Time • General A/V Mode Whiteboard Raise Quiet Time • Lower A/V Mode General Raise Whiteboard Lower Quiet Time • A/V Mode Raise Lower General www.coopercontrol.com Whiteboard General Quiet Time • Whiteboard A/V Mode Quiet Time • Raise A/V Mode Lower Raise Lower 1 Room Controller Classroom Lighting Layouts 6 OPTION PREV Raise Manual Control Room Controller Classroom Lighting Layouts Neoray LFL 3 5 MUTE 7 8 9 Whiteboard 2 Quiet 0 Time • SLEEP Daylighting Control Neoray LED VOLUME cc 6 General 04 ALL ON/OFF Occupancy/Vacancy Sensing Room Controller Classroom Lighting Layouts VOLUME MUTE 2 21 1Raise 3 4 5 CHANNEL Room Controller Classroom Lighting Layouts Corelite LFL OPTION CHANNEL 0 cc Lower A/V Mode UL924 Corelite LED All Off 2 7Quiet Raise 9 1 8Time TV 3• PREV UL924 Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information. Room Controller - Classroom w/Daylight Dimming, Receptacle Control and Suspended Fixtures Room Controller and Smart Devices use Click & Go technology The RC3DE will automatically recognize any smart device connected with the quick connect cable (provided) and start working immediately upon power up with no programming required. The RC3DE defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Entry wallstations will provide On/Off control of the Yellow load. Teacher stations provide On/Off control of the Red and Purple loads as well as manual Raise/Lower of all dimmers. The daylight sensor will automatically provide multi-zone daylight dimming in the space. (Remote adjustments can be made later.) *Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Solatube Control, Egress Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations. EMERGENCY NEUTRAL YELLOW Emergency Power OUT WHT/ORG or WHT/BLK Neutral BLACK - Hot (120/277 VAC) Emergency Lighting Load (Tracks with normal lighting YELLOW load) YELLOW Lighting Load (1) RED Lighting Load (2) PURPLE Lighting Load (3) BLUE - Relay In (120/277 VAC) BLUE - Emergency Power In (120/277 VAC) Requires 0-10V dimming ballasts Violet - Dimmer 1 Gray - Dimmer 1 Violet - Dimmer 2 Gray - Dimmer 2 Emergency Note: Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%. Violet - Dimmer 3 Gray - Dimmer 3 0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones. In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds. The RC3DE is UL 924 listed. Receptacle Control: 20Amp 120 VAC receptacle control immediately works upon power up and connection to the Room Controller. Receptacle turns On by button press or occupancy and Off when space is vacant. QuickConnect coupler (GGRC-COUPLER) Adjustable daylight sensor dome Daylight sensor (DSRC-FMOIR) *Immediately provides multi-zone daylight dimming upon powerup Allows connection to any Greengate Occupancy/Vacancy Sensor (OCC-RJ45) 120V receptacle circuit SPRC-R-20-120 20A Receptacle Control Button 1: Toggle Load (1) Button 2: Load (1),(2),(3) Off Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts Entry Lighting General Whiteboard Quiet Time All Off A/V Mode Connect up to four wallstations per Room Controller RC-2TLB-EC1-* Entry Station Raise Lower RC-6TSB-TS1-* Teacher Station Dual Technology Wall Corner Occupancy/Vacancy Sensor (OAWC-DT-120W) *Defaults to vacancy sensor mode Manual On/Automatic Off (all loads) for maximum energy savings Button 1: Toggle Load (2) Button 2: Toggle Load (3) Button 3: Disable Occupancy Sensor for 1hr. Button 4: Toggle dimmers between 20% and daylight level Button 5: Press and hold increase lighting 5% Button 6: Press and hold decrease lighting 5% Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: controls@cooperindustries.com Website: www.coopercontrol.com Room Controller - RC3DE Three Relay + Three Dimmers Wiring Diagram + One Emergency Relay Drawing Name: Drawing Date: RC3DE-ClassroomReceptacleWC.dwg 1/10/2013 www.coopercontrol.com 2 Room Controller - Classroom w/Daylight Dimming, Receptacle Control and Suspended Fixtures Mounting The Room Controller The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller include breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller. Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller. Sample Placement Diagram Daylight Sensor Ceiling Location (for example purposes only) 1. Mount the daylight sensor one to two times the window height from the window wall. 2. Position the sensor so its arrow is pointed toward the nearest window. 3. Ensure the daylight sensor is not obstructed or looking directly at electric light. 4. For narrow spaces mount the daylight sensor near the window facing into the space. Sample Placement Diagram (for example purposes only) Room Controller (above entry door) Wall/Corner Mount Occupancy Sensor Additional Wallstation General On AV Mode Whiteboard Quiet Time Raise Lower Entry Wallstation General On Off Window Daylight Sensor 60° Area viewed by daylight sensor Occupancy sensor Coverage Diagram (OAWC-DT-120W) Wiring Diagram 24’ (7.3 mm) Room Controller Normal Power (20A Receptacle Control) (Above Entry Door) (Line In & Load Out) Line Voltage to J-Box Line Voltage to receptacles (low voltage, class 2) RC3DE 20’ (6 mm) SPRC-R-20-120 12’ (3.7 mm) (Line In & Load Out) 0-10V Dimmer Wiring (Dimming Models Only) Major Motion, IR Minor Motion, Ultrasonic 12’ (3.7 mm) DSRC-FMOIR RC3DE model only Minor Motion, IR 8’ (2.4 mm) 0 8’ (2.4 mm) OCC-RJ45 Emergency Power Major Motion, Ultrasonic (Multi-zone daylight sensor) Maximum coverage area may vary somewhat according to room shape and the presence of obstacles. (Any Greengate Occupancy Sensor) Wallstation Wallstation (Entry) The NEMA WD 7 Guide and robotic method were utilized to verify coverage patterns. 24’ (7.3 mm) 10 ft (3 mm) (Additional) Half Lights Half Lights Full Lights Full Lights Raise Raise Lower Lower All Off All Off 20’ (6 mm) 24 ft 6 ft 15 ft (1.7 mm) (4.6 mm) (7.3 mm) 50 ft (15.3 mm) Connections Room Controller and Smart Devices use Click & Go Connections Room Controller 0-10V Dimming Connections Dimmer 1: Near the Window Dimmer 2: Middle of Room Dimmer 3: Far from Window - Dimmer 3 + - Dimmer 2 + - Dimmer 1 + The daylight sensor will automatically provide multi-zone dimming based on this wiring configuration 0-10V Dimming 1 0-10V Gray (-) 0-10V Violet (+) www.coopercontrol.com 3 2 5 34 6 1. 2. 3. 4. 5. 6. Wallstations (up to four) Slider Station Connection (one) Occupancy Sensors (up to two) Daylight Sensor (one) Receptacle Control or BMS Output Switchpack (controlled with Load 1 for alternate voltage) Room Controller - Classroom w/Daylight Dimming, Receptacle Control and Suspended Fixtures Ordering RCQK - CR3E - ES1 Room Controller - TS1 - W1 - D1 - P - Daylight Office Stations (Choose up to 4) W Station Color D1 - Multi-zone Daylight Sensor ES1 - Entry, All Off (2 Large Buttons) Entry Station (Choose 1) DH - Multi-zone Daylight Sensor w/ TS1 - General, Whiteboard, Quiet Time, ES1 - Entry, All Off (2 Large Buttons) Handheld Remote A/V Mode, Raise, Lower † (6 Small Buttons) Options TS5 - Entry, General, Whiteboard, TS2 - General, Whiteboard, Quiet Time, Raise, P - Plug Load Types of Space All Off (4 Small Buttons) Lower, All Off † (6 Small Buttons) B - BMS/Egress and Control Occupancy Sensor TS3 - General, Whiteboard, Quiet Time, A/V Mode, All Off † CR - Classroom Switching (RC3) C1 - Ceiling DT 2000 sq. ft. (5 Small Buttons) CR2 - Classroom 2 Zone Dimming (RC3D2) C2 - Ceiling PIR 1500 sq. ft. TS4 - General, Whiteboard, A/V Mode, Raise, Lower, All Off † CR3 - Classroom 3 Zone Dimming (RC3D) C3 - Ceiling DT 1000 sq. ft. (6 Small Buttons) CR3E - Classroom 3 Zone Dimming and W1 - Wall Corner DT TS5 - Entry, General, Whiteboard, All Off (4 Small Buttons) and Emergency Relay (RC3DE) W2 - Wall Corner PIR TS6 - Entry, General, Whiteboard, Raise, Lower, All Off † W3 - Hallway PIR (6 Small Buttons) QuicKit W - White G - Gray V - Ivory B - Black TS7 - Row 1, Row 2, Row 3, Raise, Lower, All Off † (6 Small Buttons) TS8 - Uplights, Downlights, Accent, Raise, Lower, All Off † *Catalog number automatically includes low voltage (6 Small Buttons) connection cable, wallplates and connectors based on room SS1 - Slider Station †† type and configuration. Pre-defined Wallstation Model numbers Entry All Off General General General General Entry Entry Row 1 Uplights Whiteboard Whiteboard Whiteboard Whiteboard General General Row 2 Downlights Quiet Time • Quiet Time • Quiet Time A/V Mode Whiteboard Whiteboard Row 3 Accent A/V Mode Raise A/V Mode Raise All Off Raise Raise Raise Raise Lower All Off Lower Lower Lower Lower All Off All Off All Off All Off All Off Lower RC-2TLB-ES1 RC-6TSB-TS1 RC-6tsb-TS2 RC-5TSB-TS3 RC-6tsb-TS4 RC-4tsb-TS5 RC-6Tsb-TS6 RC-6tsb-TS7 RC-6tsb-TS8 *For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website Applications Classroom Application Button Functionality Function (Unless a target level is indicated, the dimmer output will default to daylight sensor control) Program No. Button Text Control Type 1 Entry Row 1 Uplights Toggle Load 1 (yellow) ON and OFF Solatube Open (RC3DE only) 2 General Row 2 Downlights Toggle Load 2 (red) ON and OFF 3 Whiteboard Row 3 Toggle Load 3 (purple) ON and OFF 4 A/V Mode Toggle Toggles between A/V Mode and Normal Mode relay will stay in their previous configuration. Dimmers will be reduced to maintain light levels at 20% 5 Quiet Time Toggle Disables occupancy sesnors and wallstation timers for 60 minutes. Toggle allows for re-enabling of Normal Mode prior to the timer expiring 6 Raise Raise Raise All Dimmers 7 Lower Lower Lower All Dimmers 8 All Off Slider † † Load 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF Solatube Closed (RC3DE only) Slider †† Raise and Lower All Dimmers Catalog # Type Project † These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE) †† Slider stations can not be used if a wallstation with Raise/Lower buttons are used Comments Prepared by www.coopercontrol.com 4 ACC130082 Date