Building Consistency Meeting

advertisement
Building Consistency Meeting
Residential
Date: 6/6/12 Recorder and minutes prepared by: Danny Wooten/Jeff Griffin/Lon
McSwain
Staff present: On file.
Public present: Greg Sloan (Ryland Homes); Ryan Meevwsen/Charles Sofinowski
(MI Homes); Mike Winn/Jonathan Hess (Ryan Homes); Chris Carroll (Meeting
Street); Brian Hall (Classic Homes); James Nelson (Shea Homes); Steven Brusko
(Landis Reed Homes); Daniel McBride (Cunnane Group); Jeff Gerdes (Livewell);
Dave Reynolds (Bldrs 1st Source); Jerry Andersen (Ryan); Kelly Strickland (The
Colville Group); Keur Adkins (Regent Homes); John Tammao (Alan Simonini
Homes); Matthew Klapheke (L&M Homes); Marcel Papineau; Darren Pride;
Jackson (Classic Homes);
Topics/Subject
Decisions/Conclusions/Actions
Old
Business
None
New
Business
Average of
Fenestration
Glazing
Windows In a
New Addition
Section N1102.3.2, see attached explanation.
Wall Bracing
When a second story addition is made to a residence the first floor wall
bracing must be brought up to code with engineering documentation. If
an addition is made to a residence care should be taken that the existing
is not compromised and that the wall bracing is still within code
compliance.
New load tables are being established for southern yellow pine. The
load table for 2X4 lumber has been adopted by SPIB which will affect
the truss manufactures but will not be a code requirement until 2015.
When the floor framing is perpendicular to the rated wall heavy timber
construction may be used at the band to meet the 1 hr. fire rating.
Wood Products
Exterior Rated
Wall
Construction
Distance to
Property Line.
Windows in an addition must meet the current code. Old windows from
the existing house cannot be used unless they can meet the 15%
exception allowed by Section N1102.3.3
This is measured from the property line to the face of the finished wall,
(includes siding or cladding material such as vinyl siding, hardboard,
fiber-cement and brick veneer, etc…).
Townhouse
You cannot use 2 independent 1 hr rated walls to meet the exception for
Separation
sprinklers. You must use common 2 hour rated walls between
Section 302.2.5 townhouses. There is a code change proposal in the works and will
monitor for BCC approval.
Wall Bracing
It is acceptable to use gypsum wall board as wall bracing for interior
walls.
Fenestration calculation example
Approved By ___Lon McSwain_________ Date _____07/09/2012__