Actuator exchange in case of compressors Background Scopes of supply (see figures 1–3) In compressor operation, requirements as to the reliability of actuators increase. The actuators trigger the Inlet Guide Vanes (IGV), thus adjusting media flow rates. Control unit In the past various types of failures occurred with actuators: leakages at diverse connections corrosion damages increased vibrations at electronic components pressure switch explosion protection (upon request) two control circuits for controlling two operating cylinders (dependent upon actuator size) automatic control using SIPART PS2 controller terminal strip self ventilation of control unit transducer failures Improvements In order to increase the IGV’s availability a new actuator was designed, eliminating the disadvantages of the existing type. It has been modified as follows: Pneumatic and electronic drive and control components are separated from each other to avoid vibration damages of the electronics. Leakages with seals and pipe fittings are avoided by use of modified types. An innovative, contactless position measuring system with magnetostrictive position sensors avoids contact damages. Magnetic position sensors allow for an uncorrected linearity tolerance of +/- 0.02 % and a measurement repeat accuracy of 0.001 %. This is possible with no other position measuring system. The rugged design is particularly suitable for continuous operation. Answers for energy. Operating cylinder explosion protection (upon request) reinforced hose 2 x 3 m, 2 x 1.5 m (from DS 160 3 x 3 m and 3 x 1.5 m, respectively) joint head fork head control unit support (with sealing plate) The package additionally includes reinforced hoses with 3/8-NPT external threads. Furthermore, control units are supplied with aluminum brackets that may be mounted on a base either by doweling or by welding. machine reinforced hose length 3.00 m control unit reinforced hose length 1.50 m customer‘s pipe third reinforced hose from DN 160 reinforced hose connections 3/8-NPT-outside thread Figure 1: schematic connection diagram Seal Gas Booster control cabinet pneumatic control positioner SIPART PS2 filter governor Figure 2: circuit diagram of actuators with SIPART PS2-controller Installation period Published by and copyright © 2008: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens Power Generation, Inc. 4400 Alafaya Trail Orlando, FL 32826-2399, USA The actuator is delivered as an assembled unit including panel and can be installed during a short shutdown period within one or two working days. Customer benefits For more information, contact our Customer Support Center. Phone:+49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) e-mail: support.energy@siemens.com www.siemens.com/energy-support low maintenance Order No. A96001-G90-B174-X-4A00 Printed in Germany 1386 J DA 0308 1. fast assembly of components due to simple interchangeability All rights reserved. Subject to change without prior notice. Printed on paper treated with chlorinefree bleach. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. high operational safety high reliability non-contact position measuring system Figure 3: control unit with SIPART PS2-controller