Document 10443967

advertisement
R48-1000
DC Power
for Business-Critical Continuity™
Technical Specifications, R48-1000
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power, Derated for Input Voltage
Output Current
Efficiency
Psophometric Noise (System)
Temperature Derating
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
R48-1000 Output Power vs. Temperature at
264V ≥ Vin ≥ 176 Vac
% of output power
200 to 250 V AC
85 to 300 V AC
45 to 65 Hz
6.8 A
0.99
≤5% for 50%-100% load
120
100
80
60
40
20
0
-40 -20
0
For R48-1000
-42 to -58 V DC
1000W@Vout >48VDC
See Diagram
20.83 A @ -48 VDC
>92%
≤1mV; ≤32dBrnc
See Diagram
Environmental
Temperature Range, Operating
-40 to +75°C, -40 to +167°F
Temperature Range, Storage
-40 to +75°C, -40 to +167°F
Relative Humidity
Altitude
EMC
Safety
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B
IEC 60950, EN 60950, UL 60950
Mechanics
Dimensions (H×W×D)
Weight
40.8×86.5×241mm (1.6×3.4×9.5 inches)
1.25 kg (2.76 lbs)
Other parts
Controller Units
See separate ACU+ and SCU+ datasheets
Ordering information
Product Name
Rectifier R48-1000
www.emersonnetworkpower.com
www.emersonnetworkpower.com/energysystems
www.DCpowerefficiency.com
40
60
80
100
Temperature (°C)
Output Power vs. Input voltage and Vo > 48V at Temp ≥45°C
Alarm and status reported via CAN bus to system controller
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™
20
Output Power vs. Input Voltage at Tamb<45°C
% of output power
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
120
100
80
60
40
20
0
0
50
100 150 200 250 300
For R48-1000
350
Input voltage (VAC)
AC Power
Embedded Power
Precision Cooling
Connectivity
Monitoring
Racks & Integrated Cabinets
DC Power
Outside Plant
Services
Embedded Computing
Power Switching & Controls
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
©2009 Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service.
2009.12
Download