eSure Rectifier ™ eSure™ Rectifier

advertisement
eSure™ Rectifier
DC Power
for Business-Critical Continuity™
R48-4000e
eSure™ Rectifier
-48 V DC, 4000 W
Features and Benefits
Optimized depth-reduced footprint
allows installation in short-depth racks
and cabinets
DSP (Digital Signaling Processor)means fewer components, optimized
operation and active load sharing for
increased reliability
Description
The eSure™ R48-4000e rectifier converts standard AC supply voltages into stable
nominal-48V DC voltage adjustable to the needs of the application. The R484000e is a constant power rectifier designed with the latest patented switchmode
technology using DSP (Digital Signaling Processor) functionality for
efficient operation.
For a higher load capacity, rectifiers can be connected in parallel and intelligent
control can be added with the help of a separate controller.
High efficiency, 95.3%-reduces power
consumption for lower operating costs
Hot pluggable-facilitates future
extensions
Wide input voltage range-operates in
the most demanding environments
where input voltage changes
Wide temperature operating range
(-40°C / -40 °F to +75°C / 167°F) -meets
the harshest climatic environment
requirements
R48-4000e
eSure™ Rectifier
R48-4000e
Technical Specifications, R48-4000e
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power, Derated for Input Voltage
Output Current
Output Current limit set Point
Psophometric noise (system)
Temperature Derating
Output power vs. Temperature at
264V ≥Vin ≥184 Vac
% of output power
184 to 250 V AC
85 to 300 V AC
45 to 65 Hz
22A
0.99
<5% from 50 to 100% of rated load
-42 to -58 V DC
4000W@Vout >48VDC
See Diagram
83.3A
6.9 to 83.3A
95.3% peak
<2 mV at 70% max load
See diagram
120
100
80
60
40
20
0
-40
Temperature Range, Storage
-40 to +75°C, -40 to +167°F
Relative Humidity
Altitude
EMC
Safety
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class A
IEC 60950, EN 60950
Mechanics
Dimensions (H×W×D)
Weight
132×85.3×293mm / 5.2×3.36×11.5 inches
3.5kg / 7.7Ibs
Other parts
Controller Units
Ordering information
Description
80
100
60
40
20
50
100
150
200
250
Input voltage (Vac)
300
400
60
50
40
30
20
10
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Output current(A)
Efficiency Curve
98
96
94
92
90
88
86
84
Product Code
1R484000eXXX
www.emersonnetworkpower.com
www.emersonnetworkpower.com/energysystems
60
80
0
See separate ACU+ and SCU+ datasheets
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
40
Output voltage v.s. Output current at max.
Power 4000W
Output Voltaqe(V)
-40 to +75°C, -40 to +167°F
20
100
0
Alarm and status reported via CAN bus to system Controller
Green LED: Normal Operation
Yellow LED: Alarm
Red LED: Failure
Flashing Red LED: Fan Failure
Environmental
Temperature Range, Operating
0
Temperature (°C)
120
Control and Monitoring
Visual Indications
-20
Output power vs. Input voltage and Vo
>48V at Temp≤50°C
% of output power
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
0
1
20
30
40
50
60
70
80
90
100
Load (% of rated load)
AC Power
Embedded Power
Precision Cooling
Connectivity
Infrastructure Management & Monitoring
Racks & Integrated Cabinets
DC Power
Outside Plant
Services
Embedded Computing
Power Switching & Controls
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
©2014 Emerson Electric Co.
2014.11
Download