Control & Relay Protection Philosophy for 400KV HALVAD Sub Station

advertisement
GETCO / E / 4S-065/ PP - 017 – 1A / R0 Dt.09.06.2011
Control & Relay Protection Philosophy for 400KV HALVAD Sub Station
A) Bus Bar Configuration
400kV System : Three Bus (Two Main and Transfer)
220kV System : Three Bus (Two Main and Transfer)
66kV System : One Bus (One Main Bus)
Isolator system
400kV System : Four isolator configuration (Three Bus isolators and a Line isolator)
220kV System : Four isolator configuration (Three Bus isolators and a Line isolator)
66kV System : Two isolator configuration (One Bus isolators and a Line isolator)
B) Control Voltage
220V DC
C) Control & Relay panels
Control & protection Panels to be mounted in Yard Kiosk
D) PLCC panels
PLCC Panels to be mounted in Control Room
PLCC BCU panel to be mounted in Control Room for interface between Control &
protection Panels and PLCC Panels, through GOOSE commands
E) Nos. of Bays & Bus Bar Protection
400 KV System
Feeder Bay – 8 Nos.
ICT Bay – 2,
Bus coupler Bay - 1,
Transfer Bus Coupler Bay - 1
Bus Reactor Bay - 1,
Bays to be connected to Bus Bar Protection in first phase - 13
Future bays - 5
Total bays in the Sub Station will be - 18
Bus Bar Protection
o Control Unit - 24 Bays
o Bay Units - 13 Nos. + 1 No. Spare
220 KV System
Feeder Bay – 6 Nos.
Transformer Bay – 3,
Bus coupler Bay - 1,
Transfer Bus Coupler Bay - 1
Bays to be connected to Bus Bar Protection in first phase - 11
Future bays - 9
Total bays in the Sub Station will be - 20
Bus Bar Protection
o Control Unit - 24 Bays
o Bay Units - 11 Nos. + 1 No. Spare
Page 1 of 4
GETCO / E / 4S-065/ PP - 017 – 1A / R0 Dt.09.06.2011
66 KV System
Feeder Bay – 6 Nos.
Transformer Bays – 1 No.
Bays to be connected in first phase - 7
Future bays - 3
Total bays in the Sub Station will be - 10
Control Philosophy – HALVAD Sub Station
System
Controlling Device to be Adopted
Type of Controlling Device
400 KV Bay
Bay Control Unit
BCU with IEC 61850 Protocol
220 KV Bay
Bay Control Unit
BCU with IEC 61850 Protocol
66 KV Bay
Bay Control & Protection Unit
BCPU with IEC 61850 Protocol
PROTECTION PHILOSOPHY – HALVAD Sub Station
A) Transmission Lines Protection
Line
400 KV Lines
Protection Adopted
Type of Relay
1 Two Distance Protection
Numerical Relays
[shall be of two different make (i.e. 61850 Protocol
from different manufacturers) or of
same make with two different
platforms with same specifications]
-Main-I Protection &
-Main II Protection
with
IEC
2 Two Stage Over Voltage Protection
- Stage I
- Static Relay
- Stage II
- Integrated in Main I &
Main II Protection
3 Local Breaker Backup (LBB) Protn. Integrated in Main I Protection
and Bus Bar protection
220 KV Lines
66 KV Lines
1 Two Distance Protection
[shall be of two different make (i.e.
from different manufacturers) or of
same make with two different
platforms with same specifications]
-Main-I Protection &
-Main II Protection
2 Two Stage Over Voltage Protection
- Stage I
- Stage II
3 Local Breaker Backup (LBB)
Protection.
1 Directional O/C & E/F Protection
Numerical Relays
61850 Protocol
with
IEC
Integrated in Main I & Main II
Protection.
Integrated in Main I Protection
and Bus Bar protection
Integrated in Bay Control &
Protection Unit (BCPU) with IEC
61850 Protocol
Page 2 of 4
GETCO / E / 4S-065/ PP - 017 – 1A / R0 Dt.09.06.2011
2 Local Breaker Backup (LBB)
Protection.
B) Power Transformer Protection
Integrated in BCPU
Equipment
400/220 KV Transformer
Protection Adopted
1 Differential Protection
Type of Relay
Numerical Relay
61850 Protocol
2 Restricted Earth Fault Protection
3 Directional O/C & E/F Protection
(on HV & LV side)
4 Over Fluxing Protection
- 400KV side
with
IEC
Numerical Relays
61850 Protocol
with
IEC
Numerical Relays
61850 Protocol
with
IEC
-Integrated
Protection
in
Differential
- Separate static relay
- 220KV side
5 Local Breaker Backup (LBB) Protn.
- 400 KV side
-Integrated
in
Differential
Protection
and
Bus
Bar
protection
- 220 KV side
400 KV Bus reactor
6
7
8
9
10
1
-Integrated in Dir. O/C & E/F
Protection & Busbar protection
Buchholz Relay
Integrated in Transformer,
Pressure Relief Device
Integrated in Transformer
Oil & Wdg Temp. Alarm & Tripping Integrated in Transformer
OLTC Oil Surge Relay
Integrated in Transformer
Oil Level Low Alarm
Integrated in Transformer
Reactor Differential Protection
Numerical Relay with IEC
61850 Protocol
2 Restricted Earth Fault Protection
3
220/66KV Transformer
4
5
6
7
1
2
3
4
5
Numerical Relays with IEC
61850 Protocol
Backup impedance protection
Numerical Relays with IEC
61850 Protocol
Buchholz Relay
Integrated in Reactor
Pressure Relief Device
Integrated in Reactor
Oil & Wdg Temp. Alarm & Tripping Integrated in Reactor
Oil Level Low Alarm
Integrated in Reactor
Differential Protection
Numerical Relay with IEC
61850 Protocol
Restricted Earth Fault Protection
Numerical Relays with IEC
(on HV & LV side)
61850 Protocol
Directional O/C & E/F Protection
Numerical Relays with IEC
(HV side)
61850 Protocol
Directional O/C & E/F Protection (LV Integrated in Bay Control &
side)
Protection Unit (BCPU) with IEC
61850 Protocol
Over Fluxing Protection
Integrated
in
Differential
Protection
Page 3 of 4
GETCO / E / 4S-065/ PP - 017 – 1A / R0 Dt.09.06.2011
6 Local Breaker Backup (LBB) Protn.
- 220 KV side
-Integrated
Protection
protection
in
and
Differential
Bus
Bar
- 66 KV side
- Integrated in BCPU
Buchholz Relay
Integrated in Transformer
Pressure Relief Device
Integrated in Transformer
Oil & Wdg Temp. Alarm & Tripping Integrated in Transformer
OLTC Oil Surge Relay
Integrated in Transformer
Oil Level Low Alarm
Integrated in Transformer
7
8
9
10
11
C) Bus Coupler Protection
400 KV
1 Non Directional O/C & E/F
Numerical Relay with IEC
Bus coupler
Protection
61850 Protocol
2 Local Breaker Backup (LBB) Protn. Integrated in Non Dir. O/C &
E/F Protection and Bus Bar
protection.
220 KV
1 Non Directional O/C & E/F
Numerical Relay with IEC
Bus coupler
Protection
61850 Protocol
2 Local Breaker Backup (LBB) Protn. Integrated in Non Dir. O/C &
E/F Protection and Bus Bar
protection.
D) Bus Bar Protection
400 KV Bus bar
1 Bus Differential Protection
Numerical Relay with IEC
(Single scheme)
61850 Protocol
13 Bays, Extendable upto 24 Bays
(i. e. Control Unit - 24 Bays)
220 KV Bus bar
1 Bus Differential Protection
Numerical Relay with IEC
(Single scheme)
61850 Protocol
11 Bays, Extendable upto 24 Bays
(i. e. Control Unit - 24 Bays)
E) Disturbance Recorder & Event Loggers
Integrated feature of protective relays is used to provide the information about the Disturbance and
to log the events.
F) GPS based Time Synchronizing Equipment
The Sub station is to be provided with Global Positioning System based Time Synchronizing
Equipment to synchronize all the protections.