CODE GTU102 SPECIFICATIONS ELECTRICAL POWER ENGINEERING TRAINING LABORATORY The Electrical Power Engineering Training System must be composed of one work bench , one set of experimental modules and one set of measuring and testing instruments. The system must allow performance of at least the following experiments: Power transmission and distribution Three phase transformer Determination of the vector group of the three-phase transformer Voltage transformation ratio of the transformer Current transformation ratio Equivalent circuit quantities on active and reactive power consumed Measurement of the effect of the load type Efficiency of the transformer Analysis of the load capacity of the secondary side Determination of the influence of a delta stabilizing winding of a transformer Autotransformer Overhead line model Voltages in no-load operation on a overhead line model Operating capacitance concept Line model with increased operating capacitance Current and voltage relationship of an overhead line in matched-load operation. Current and voltage ratios of a transmission line during a three-phase short-circuit Current and voltage ratios of a transmission line with mixed R-L and R-C loads Earth-fault current and the voltage rise of the faulty phases Techniques to determine the zero-phase sequence impedance of the overhead line model Series and parallel connection Voltage distribution in the series and parallel connection of two lines Voltage distribution in the parallel connection of two lines Busbar systems Switching station with two busbars Busbar transfer with and without interruption Switching sequence for power circuit breakers QTY DL 1013T1 DL 7901TT DL 1080TT DL 1017R Set of experimental modules Metal casing Bench-top and/or vertical panel type Isolated panels for insertion in work frames Modules must allow connection of an electrical component, electrical circuit or a test instrument Modules must clearly display on front side standard diagrams using standard units and symbols. All electrical connections must be available through safety banana connectors of 2mm for control signals and 4mm for power lines. The minimum set of power engineering modules should include the following: THREE-PHASE POWER SUPPLY - Didactic equipment: three-phase variable power supply, power supply unit for variable 3-phase voltage suitable for supplying ac machines. It must provide an AC output 3-phase from 0 to 380 V, 8 A minimum. It must be provided with a 16 A, 30 mA differential magneto-thermal main switch, a key operated emergency push-button, start and stop pushbuttons, a motor protection circuit breaker: 6.3 to 10 A, a digital ammeter and a digital switchable voltmeter. 4 mm safety terminals for electrical connections included. The output voltage must be set by a rotary knob with 0-100% scale. Supply voltage: three-phase from mains. OVERHEAD LINE MODEL - Didactic equipment: module with insulated panel, three-phase line model of an overhead power transmission line of 360 km long, voltage 380 kV and current 1000 A, scale factor: 1:1000. Line resistance: 13 Q, line inductance: 290 mH, mutual capacitance: 1 uF, earth capacitance: 2 (iF, earth resistance: 11 Q, earth inductance: 250 mH. 4 mm. safety terminal included on the front panel. THREE-PHASE TRANSORMER - Didactic equipment: three-phase transformer for feeding a transmission line model, 380 kV with scale factor 1:1000. Primary: 3 x 380 V with tap at 220 V, star or delta connection. Secondary: 3 x 220 V windings with taps at +5%, -5%, -10%, -15%,star connection for 3 x 380 V, various star connections possible. Nominal power: 800 VA minimum. Tertiary: 3 x 220 V windings, delta connection for stabilizing the third harmonic voltage components, rated power: 266VA. 4 mm. safety terminal included on the front panel for the electrical connection. RESISTIVE LOAD - didactic equipment It must consist in a single or three-phase resistive step-variable load. Housed in a metallic box. MECHANICAL FEATURES The load shall be composed of a rugged metal structure and of a front metal panel. On the front panel all the controls, the protection, the output terminals and a clear synoptic diagram, shall be collected. ELECTRIC FEATURES The load shall be composed of resistances, with possibility of star, delta and parallel connection, controlled by three switches. This item must be provided also with fuses protection. As a function of the switch positions, there shall be the following phase values: Position Resistance Max power per phase 1 1050 Ohm 46 W 1 2 1 1 DL 1017L DL 1017C 2 750 Ohm 65 W 3 435 Ohm 110 W 4 300 Ohm 160 W 5 213 Ohm 230 W 6 150 Ohm 330 W 7 123 Ohm 400 W Maximum power in single or three phase connection must be 1200 W. Rated voltage in star connection must be 380 V, in D connection must be 220V, in single-phase must be 220V. 4 mm. safety terminal included on the front panel for the electrical connection. INDUCTIVE LOAD - didactic equipment It must consist of a single or three-phase inductive step-variable load. Housed in a metallic box. MECHANICAL FEATURES The load shall be composed of a rugged metal structure and of a front panel. On the front panel all the controls, the protections, the output terminals and a clear synoptic diagram, shall be collected. ELECTRICAL FEATURES The load shall be composed of inductances, with possibility of star, delta and parallel connection, controlled by three switches. This item must be provided also with fuses protection. As a function of the switch position there shall be the following phase values. Position Inductance Max. Power per phase 1 4.46 H 34 VAr 2 3.19 H 48 VAr 3 1.84 H 83 VAr 4 1.27 H 121 VAr 5 0.90 H 171 VAr 6 0.64 H 242 VAr 7 0.52 H 297 VAr Max reactive power 890 VAr in three-phase or single-phase connection. Rated voltage in star connection must be 380V, in D connection must be 220V, in single-phase must be 220V. 4 mm. safety terminal included on the front panel for the electrical connection. CAPACITIVE LOAD - didactic equipment It must consist of a single or three-phase capacitive step-variable load. Housed in a metallic box. MECHANICAL FEATURES The load shall be composed of a rugged metal structure and on the front panel all the controls, the protections, the output terminals and a clear synoptic diagram shall be collected. This item must be provided also with fuses protection. ELECTRICAL FEATURES The load shall be composed of capacitors, with possibility of star, delta and parallel connection, controlled by three switches. As a function of the switch position, there shall be the following phase values (at 50Hz): Position Capacitance Max power per phase 1 2 uF 30 VAR 2 3 uF 45 VAR 3 5 uF 76 VAR 1 1 DL 2108TAL -SW DL 2108T02 4 8 uF 121 VAR 5 10 uF 152 VAR 6 13 uF 197 VAR 7 18 uF 275 VAR Max reactive power in single-phase or three-phase connection 825 VAr. Rated voltage in star connection must be 380V, in D connection must be 220V, in single-phase must be 220V. 4 mm. safety terminal included on the front panel for the electrical connection. THREE-PHASE SUPPLY UNIT - Didactic equipment: Power supply unit for three-phase connection with 4-pole cam mains switch. 25 A current operated earth leakage circuit breaker, sensitivity 30 mA. Triple-pole motor protection switch: 6.3 to 10 A. Three-phase indicator lamps. Output through 5 safety terminals: L1, L2, L3, N and PE. Switch for simulation of wind or photovoltaic energy power source 4 mm. safety terminal included on the front panel for the electrical connection. POWER CIRCUIT BREAKER - Didactic equipment: Three-phase power circuit breaker with normally closed auxiliary contact. Features: Contact load capability: 400 Vac, 3 A Supply voltage: single-phase from mains Power circuit: Insulation voltage: 750V Thermal current : 20A Auxiliary contact: Insulation voltage: 750V. Rated current: 3A Auxiliary power: Single-phase voltage 220V, 50-60Hz It must be possible to control manually the power breaker switch using the push-buttons “on”and “off” or externally via the switching contact PLC or RELAY. This power contacts state shall be indicated by leds: Green led = open contacts. Red led = closed contacts. While at SIGNAL OUTPUT terminals will be available a TTL level: Low level ( 0V )= open contacts. High level ( 5V )= closed contacts. The RS flip-flop state shall be indicated by a led: Yellow led = set flip-flop. 4 mm. safety terminal and 2 mm. terminals included on the front panel for the electrical connection. It must be supplied with manual in English language 1 4 DL 2108T02/2 DL 2108T02/4 DL 2108T03 DL 2108T04 DOUBLE BUSBAR WITH TWO DISCONNECTORS - Didactic equipment: module with insulated panel Suitable for extending the double busbar system. The module must have insulated front panel and four light push buttons (two red and two green). Each busbar must have a supply branch that will be connected or disconnected by using a disconnector. It must be possible to control manually the power breaker switch using two couples of push-buttons “on”and “off” or externally via the switching contact PLC or RELAY. This power contacts state shall be indicated by leds: Green led = open contacts. Red led = closed contacts. While at SIGNAL OUTPUT terminals will be available a TTL level: Low level ( 0V )= open contacts. High level ( 5V )= closed contacts. The RS flip-flop state shall be indicated by a led: Yellow led = set flip-flop. 4 mm. safety terminal and 2 mm. terminals included on the front panel for the electrical connection. It must be supplied with manual in English language DOUBLE BUSBAR WITH FOUR DISCONNECTORS Didactic equipment: module with insulated panel Suitable for extending the double busbar system. The module must have insulated front panel and eight light push buttons (four red and four green). Each busbar must have a supply branch that will be connected or disconnected by using a disconnector. It must be possible to control manually the power breaker switch using four couples of push-buttons “on”and “off” or externally via the switching contact PLC or RELAY. This power contacts state shall be indicated by leds: Green led = open contacts. Red led = closed contacts. While at SIGNAL OUTPUT terminals will be available a TTL level: Low level ( 0V )= open contacts. High level ( 5V )= closed contacts. The RS flip-flop state shall be indicated by a led: Yellow led = set flip-flop. 4 mm. safety terminal and 2 mm. terminals included on the front panel for the electrical connection. It must be supplied with manual in English language LINE CAPACITOR - Didactic equipment: module with insulated panel, three-phase transmission line capacitor with exactly half of the operating capacitance of the 380 kV transmission line model with a length of 360 km, Capacitance:3 x 2.5 uF, 450 Vac. 4 mm. safety terminal included on the front panel for the electrical connection. PETERSEN COIL - Didactic equipment: module with insulated panel, Petersen coil, inductance with 20 taps for earth fault compensation in transmission lines: 2000mH-1800mH-1600mH-1400mH-1250mH-1100mH-980mH-860mH-750mH-620mH-500mH-400mH-300mH-220mH-160mH-120mH-80mH- 1 1 2 1 DL 2109T1A DL 2109T2A5 DL 2109T1PV DL 2109T3PV DL 2109T26 40mH-20mH-5mH-0. • Inductance: 0.005 ... 2 H • Rated voltage: 220 V • Rated current: 0.5 A 4 mm. safety terminal included on the front panel for the electrical connection. MOVING COIL AMMETER MODULE - didactic equipment The module must consist of a magneto-electric meter for ac and dc measurements. Scale: 50 divisions - the scale shall made open and reasonably uniform down to about 20 percent of the full-scale reading. Range: 100, 500 and 1000 mA, ac/dc Accuracy class: 1.5 This module must have insulated front panel , 4 mm safety terminals, one selector and one analog meter. The module must be supplied with manual in English language. MOVING COIL AMMETER MODULE - didactic equipment This module must be suitable for ac and dc current measurements. Technical features: •Scale: 50 divisions - the scale shall made open and reasonably uniform down to about 20 percent of the full-scale reading. •Range: 2.5 A - 1.25 A •Accuracy class: 1.5 •AC/DC measurements This module must have insulated front panel, 4 mm. safety terminals, one selector and one analog meter. The module must be supplied with manual in English language. MOVING IRON VOLTMETER MODULE - didactic equipment This module must be suitable for ac and dc voltage measurements. Technical features: Scale: 30 divisions - the scale shall be made open and reasonably uniform down to about 20% of the full-scale reading. Range: 600 V Accuracy class: 1.5 This module must have insulated front panel with the electrical scheme, 4 mm safety terminals, fuse protection and one analog meter. The module must be supplied with manual in English language. MOVING IRON VOLTMETER MODULE - didactic equipment This module must be suitable for ac and dc voltage measurements. Technical features: •Scale: 50 divisions - the scale shall be made open and reasonably uniform down to about 20% of the full-scale reading. •Range: 125-250-500 V •Range changeover switch •Accuracy class: 1.5 This module must have insulated front panel with the electrical scheme, 4 mm safety terminals, fuse protection and one analog meter. One selector shall be included in this panel. The module must be supplied with manual in English language. POWER METER - Didactic equipment : This module must consist in a demonstration single-phase meter for active power and capacitive/inductive reactive power. 1 3 2 3 2 DL 2109T27 DL 2100T2 DL 2100TA DL 1155GTU Technical features: Measurement ranges: Voltage: 3/10/30/100/300/1000 V Current: 0.1/0.3/1/3/10/30 A Frequency range: Active power: 0 ... 20 kHz Reactive power: 50 Hz LED indicators: capacitive reactive power, inductive reactive power, overload voltage (with acoustic sound), overload current (with acoustic sound). Auxiliary supply: single-phase from mains This module must have insulated type front panel with the electrical scheme and also 4 mm safety terminals. Two selectors, one switch and one push-button shall be included in this panel. POWER FACTOR METER - Didactic equipment: The module must consist of one single-phase power factor meter with measurement of the power factor and phase-angle with ranges: power factor: 0 cap to 1 to 0 ind, phase-angle: -90°cap to 0 ... +90°ind. Measurement ranges: voltage 3 / 10 / 30 / 100 / 300 / 1000V Current 0.1 / 0.3 / 1 / 3 / 10 / 30A Frequency range: active power 0…20 kHz reactive power 50Hz Led indicators: capacitive reactive power inductive reactive power overload voltage, with acoustic sound overload current, with acoustic sound Auxiliary supply: 220V, 50-60Hz 4 mm safety terminals for electrical connections included. It must be supplied with manual in English language. TWO LEVEL FRAME WITH TABLE Metal frame for fitting the modules of the laboratory. Mounted on a bilaminated wooden top of a table. Metal square legs with compensating feet which can be adjusted to offset the uneveness of the floor. STORAGE CABINET Fire varnished steel-plate, provided with shelves for module storage and key-locked doors. Supplied with 4 rubber casters, the cabinet should be fitted under the experimental table A set of cables with at least 80 connecting leads with security plugs of different colours, length and sections. 1 1 1 1