ASHRAE Annual Meeting June 29, 2010 Albuquerque, NM Energy Saving Analysis for ASHRAE Standard 90.1-2010 Bing Liu, P.E., C.E.M. LEED AP Senior Research Engineer Pacific Northwest National Laboratory PNNL’s Energy Modeling Support to 90.1 Progress Indicator Measure progress toward the 30% improvement goal in Standard 90.1-2010 Update Progress Indicator (PI) and report to ASHRAE 90.1 committee at each quarterly meeting Energy Saving Analyses Support subcommittees’ new proposals Develop the building load profile spreadsheet tools for mechanical subcommittee DOE’s Determination Estimate the energy savings of 90.1-2007 and 90.1-2010 as part of DOE’s Quantitative Analysis. 2 90.1 Progress Indicator Structure Develop prototype building models Apply to climate zones Generate minimally code-compliant models for 90.1-2004, 90.1-2007, and 90.1-2010 Develop new construction weighting factors Calculate the national weighted energy use intensity and energy cost index 3 90.1 Prototype Buildings - Approach Convene the 90.1 Simulation Working Group Representing the 90.1 subcommittees Establish the ground rules for modeling Review the key building modeling inputs and assumptions Review the energy saving analysis results Follow the 80-20 Rule to determine the prototype buildings Generate the models for the whole building energy Receptacle loads (office equipment, cooking appliance, refrigeration etc) Elevator Exterior lighting, including façade, walk way, entry, and parking lot 4 90.1 Prototype Buildings - Source DOE’s Commercial Reference Building Models formerly DOE’s benchmark buildings http://www1.eere.energy.gov/buildings/commercial_initiative/new_construction.html Advanced Energy Design Guides http://www.ashrae.org/technology/page/938 PNNL’s new construction drawings database Previous research and studies Experts reviews and inputs from 90.1 SWG and committee members 5 90.1 Prototype Buildings Principal Building Activity Office Mercantile Education Health Care Lodging Number of Floors Small office 5,500 Medium office Heating Cooling 1 Heat Pump Unitary DX 53,600 3 Gas furnace Unitary DX Large office 498,600 12 Boiler Standalone retail Strip mall Primary school 24,695 22,500 74,000 1 1 1 Gas furnace Gas furnace Gas furnace Secondary school 210,900 2 Boiler Outpatient health care 40,950 3 Boiler Hospital 241,410 5 Boiler Small hotel/motel 43,200 4 Electricity Large hotel 122,132 6 Boiler 49,500 1 2,500 1 5,500 Non-refrigerated warehouse Fast food restaurant Food Service Sit-down restaurant Mid-rise apartment Apartment High-rise apartment Warehouse 6 Floor area (ft²) Building Prototype Chiller, cooling tower Unitary DX Unitary DX Unitary DX Air cooled chiller Unitary DX Chiller, cooling tower DX Air cooled chiller Primary System CAV VAV w/ elect. reheat Secondary System No No VAV w/reheat No CAV CAV CAV No No No VAV w/reheat CAV VAV w/reheat No VAV w/reheat Central CAV PTAC No Fan-coil units VAV w/reheat Unitary DX Unit heater CAV Gas furnace Unitary DX CAV No 1 Gas furnace Unitary DX CAV No 33,700 4 Gas Split DX CAV No 84,360 10 Boiler Fluid Cooler Water-source No heat pump Gas furnace 3 Office Prototypes Large Office Small Office Floor area (ft²) Number of Floors Aspect Ratio 5,500 1 1.5 WWR Floor area (ft²) 15% 498,600 Number of Floors Aspect Ratio 12 (plus basement) 1.5 WWR 40% 1 Warehouse Prototype Medium Office Non-refrigerated warehouse Floor area (ft²) 53,600 7 Number of Floors Aspect Ratio 3 1.5 WWR Floor area (ft²) 33% 49,500 Number of Floors Aspect Ratio 1 2.2 WWR Office area: 12% Storage Area: 0% Overall: 0.71% 2 Mercantile Prototypes 2 Education Prototypes Stand-alone Retail Floor area (ft²) 24,695 Primary School Number of Floors Aspect Ratio 1 1.28 WWR Floor area (ft²) 7% 74,000 Strip Mall Floor area (ft²) 22,500 8 Number of Floors Aspect Ratio 1 NA WWR 35% Secondary School Number of Floors Aspect Ratio 1 4 WWR Floor area (ft²) 11% 210,900 Number of Floors Aspect Ratio 2 NA WWR 33% 2 Health Care Prototypes 2 Lodging Prototypes Outpatient Health Care Floor area (ft²) 40,950 Small Hotel Number of Floors Aspect Ratio 3 NA WWR Floor area (ft²) 20% 43,200 Hospital Floor area (ft²) 241,410 4 3 WWR 11% Large Hotel Number of Floors Aspect Ratio 5 (plus basement) 1.33 WWR Floor area (ft²) Number of Floors Aspect Ratio 16% 122,132 9 Number of Floors Aspect Ratio 6 (plus basement) Ground & basement floor: 3.8 All other floors: 5.1 WWR 27% 2 Food Service Prototypes 2 Apartment Prototypes Mid-rise Apartment Full-Service Restaurant Floor area (ft²) 5,500 Number of Floors Aspect Ratio 1 1 WWR Floor area (ft²) 18% 33,700 2,500 10 Number of Floors Aspect Ratio 1 4 2.74 High-rise Apartment Quick-Service Restaurant Floor area (ft²) Number of Floors Aspect Ratio 1 WWR Floor area (ft²) No. of Floors Aspect Ratio WWR 14% 84,360 10 2.75 15% WWR 15% Climate Zones Climate Zone 11 Climate Zone Type Representative City 1A Very Hot - Humid Miami FL 1B Very Hot - Dry Riyadh, Saudi Arabia 2A Hot - Humid Houston, TX 2B Hot - Dry Phoenix AZ 3A Warm - Humid Memphis, TN 3B Warm - Dry El Paso, TX 3C Warm - Marine San Francisco, CA 4A Mixed - Humid Baltimore, MD 4B Mixed - Dry Albuquerque NM 4C Mixed - Marine Salem OR 5A Cool - Humid Chicago IL 5B Cool - Dry Boise ID 5C Cool - Marine Vancouver, BC 6A Cool - Humid Burlington VT 6B Cool - Dry Helena MT 7 Very Cold Duluth, MN 8 Subarctic Fairbanks, AK New Construction Weighting Factors McGraw-Hill New Construction Data by Building Type Serial No 12 ASHRAE Prototype Total Floor Area (x1000 ft²) Construction Weights 1 Large Office 220,134 2.66% 2 Medium Office 400,091 4.84% 3 Small Office 371,009 4.49% 4 Stand-alone Retail 1,009,246 12.21% 5 Strip Mall 375,093 4.54% 6 Primary School 330,418 4.00% 7 Secondary School 685,508 8.29% 8 Hospital 228,131 2.76% 9 Outpatient Health Care 289,171 3.50% 10 Full-service Restaurant 43,650 0.53% 11 Quick -service Restaurant 38,809 0.47% 12 Large Hotel 327,562 3.96% 13 Small hotel/motel 113,837 1.38% 14 Non-refrigerated warehouse 1,105,951 13.38% 15 High-rise apartment 593,241 7.18% 16 Mid-rise apartment 484,343 5.86% Covered by Prototypes 6,616,193 80.0% 17 No Prototype 1,649,785 20.0% 18 Total 8,265,977 100.0% Download PNNL report on construction weights: http://www.pnl.gov/main/publications/external/techni cal_reports/PNNL-19116.pdf CBECS Type Total Floor Area (x1000 ft²) Weights 17A Pubic Assembly 414,953 5.02% 17B Food Sales 96,990 1.17% 17C Other 769,423 9.31% 17D Public Order and Safety 121,907 1.47% 17E Religious Worship 184,143 2.23% 17F Service 62,369 0.75% New Construction Weights (cont’d) 1 2A 2B 3A 3B 3C 4A 4B 4C 5A 5B 6A 6B 7 8 weights by bldg type Large office 0.102 0.326 0.061 0.445 0.285 0.117 1.132 0.000 0.154 0.442 0.121 0.133 0.000 0.011 0.000 3.33 Medium office 0.129 0.813 0.292 0.766 0.715 0.136 1.190 0.036 0.196 1.060 0.342 0.298 0.035 0.033 0.007 6.05 Small office 0.084 1.064 0.289 0.963 0.475 0.078 0.936 0.047 0.123 0.920 0.322 0.241 0.030 0.032 0.005 5.61 Standalone retail 0.224 2.220 0.507 2.386 1.250 0.191 2.545 0.119 0.428 3.429 0.792 0.948 0.091 0.109 0.014 15.25 Strip mall retail 0.137 0.991 0.254 1.021 0.626 0.103 1.008 0.023 0.107 1.023 0.201 0.153 0.016 0.007 0.001 5.67 Primary school 0.064 0.933 0.164 0.944 0.446 0.048 0.895 0.030 0.094 0.920 0.224 0.168 0.037 0.023 0.003 4.99 Secondary school 0.160 1.523 0.230 1.893 0.819 0.109 2.013 0.063 0.243 2.282 0.438 0.415 0.086 0.075 0.012 10.36 Hospital 0.040 0.479 0.096 0.468 0.273 0.039 0.615 0.022 0.106 0.812 0.218 0.221 0.024 0.034 0.001 3.45 Outpatient health care 0.037 0.567 0.134 0.581 0.275 0.061 0.818 0.023 0.181 1.058 0.218 0.342 0.033 0.039 0.002 4.37 Full-service restaurant 0.009 0.106 0.025 0.111 0.047 0.006 0.127 0.006 0.010 0.143 0.031 0.031 0.004 0.004 0.000 0.66 Quick-service restaurant 0.008 0.092 0.020 0.102 0.063 0.007 0.089 0.005 0.014 0.128 0.026 0.025 0.003 0.004 0.000 0.59 Large hotel 0.109 0.621 0.125 0.635 0.793 0.106 0.958 0.037 0.123 0.919 0.200 0.227 0.058 0.038 0.004 4.95 Small hotel 0.010 0.288 0.030 0.268 0.114 0.022 0.315 0.020 0.039 0.365 0.089 0.107 0.031 0.020 0.004 1.72 Warehouse 0.349 2.590 0.580 2.966 2.298 0.154 2.446 0.068 0.435 3.580 0.688 0.466 0.049 0.043 0.002 16.72 High-rise apartment 1.521 1.512 0.076 0.652 0.741 0.173 2.506 0.000 0.358 1.163 0.115 0.125 0.016 0.008 0.000 8.97 Mid-rise apartment 0.257 1.094 0.093 0.825 0.862 0.260 1.694 0.022 0.371 1.122 0.318 0.313 0.056 0.032 0.000 7.32 13 weights by zone 3.24 15.22 2.98 15.03 10.08 1.61 19.29 0.52 2.98 19.37 4.34 4.21 0.57 0.51 0.06 100.00 Progress Indicator – Addenda Update 90.1-2004 = baseline 90.1-2007 = 90.1-2004 + 44 addenda June 2010 Progress Indicator Total 108 addenda considered 44 addenda to 90.1-2004 60 addenda to 90.1-2007 (through May 2010) 4 addenda pending for approval (BB, BY, CB, CY) 90 addenda in Section 5 through 10 53 addenda have energy saving impacts 41 addenda captured in PI 12 addenda can’t be captured in PI 14 Progress Indicator Structure Multiple ventilation standards • 90.1-2004 refers to 62-1999 • 90.1-2007 refers to 62.1-2004 • 90.1-2010 refers to 62.1-2007 Massive simulation runs • Each set of PI requires 1632 model runs • 1632 runs = 16 prototypes x 17 locations x 3 Standards x 2 Ventilation Standards PNNL’s simulation framework • Design day to size HVAC equipment • Annual run to calculate the energy use • Automatic process to generate inputs and extract results from EnergyPlus models 15 June 2010 PI Summary (Same Ventilation Std) Prototype EUI vs. National Weighted Average EUI same OA standards 600 BaseSite Energy [kBtu/sf] 6.4% Prototypes EUI National Weighted Average EUI Energy Use Intensity [kBtu/sf] 500 TargetSite Energy [kBtu/sf] 400 9.5% 300 200 15.7% 26.6% 26.9% 100 17.7% 17.1% 22.9% 32.3% 23.5% 24.2% 30.0% 23.6% 0 Prototype Name 16 21.7% 10.3% 11.2% 8.2% June 2010 PI Summary (Same Ventilation Std) Building Prototype Energy Cost [$/sf] 90.1-2004 June2010 PI 90.1-2004 June2010 PI Site Energy Savings Small office 40.0 32.9 $1.04 $0.86 17.7% 17.4% Medium office 47.3 39.2 $1.23 $0.98 17.1% 19.9% Large office 45.9 35.4 $1.18 $0.92 22.9% 22.1% Standalone retail 71.2 48.2 $1.69 $1.18 32.3% 29.9% Strip mall 75.4 57.6 $1.77 $1.34 23.5% 24.5% Primary school 69.8 52.9 $1.59 $1.25 24.2% 21.5% Secondary school 70.4 49.2 $1.68 $1.24 30.0% 26.2% Outpatient healthcare 151.2 110.5 $3.56 $2.59 26.9% 27.1% Hospital 186.5 136.8 $4.31 $3.19 26.6% 26.1% Small hotel 69.2 62.1 $1.53 $1.36 10.3% 11.4% Large hotel 208.5 175.8 $4.44 $3.67 15.7% 17.4% 27.4 20.9 $0.56 $0.43 23.6% 22.1% Fast food restaurant 557.9 522.3 $10.18 $9.35 6.4% 8.2% Sit-down restaurant 388.7 351.8 $7.50 $6.46 9.5% 13.9% Mid-rise apartment 43.5 38.7 $1.04 $0.94 11.2% 9.7% High-rise apartment 44.0 40.4 $1.11 $1.03 8.2% 7.3% National-weighted average 74.6 58.4 $1.71 $1.35 21.7% 21.4% Warehouse 17 Site Energy [kBtu/sf] Energy Cost Savings Example: Standalone Retail Progress Indicator (Jun '10): Stand-alone Retail Energy End Use 160 Refrigeration Humidification 140 National Weighted-Average Energy Saving: 32.3% National Weighted-Average Energy Cost Saving: 29.9% SWH Heating Cooling 120 Heat Recovery Aux. Pumps Site EUI (kBtu/sf/year) Fans 100 Plug Loads Exterior Lights 35% Interior Lights 80 21% 24% 60 27% 34% 30% 31% 35% 24% 24% 21% 21% 40 20 0 Climate Location 18 35% 40% 20% 38% 34% Example: Fast Food Restaurant Progress Indicator (Jun '10): Fast-food Restaurant Energy End Use 1200 Refrigeration Humidification National Weighted-Average Energy Saving: 6.4% National Weighted-Average Energy Cost Saving: 8.2% SWH 1000 Heating Cooling Heat Recovery Aux. 8% Pumps 800 Fans Site EUI (kBtu/sf/year) Plug Loads Exterior Lights 8% Interior Lights 8% 600 7% 8% 4% 6% 7% 6% 6% 4% 7% 7% 3% 400 200 0 Climate Location 19 8% 8% 7% June 2010 PI Summary (Different Ventilation Std) Building Prototype Energy Cost [$/sf] 90.1-2004 June2010 PI 90.1-2004 June2010 PI Site Energy Savings Energy Cost Savings Small office 40.3 32.9 $1.05 $0.86 18.4% 17.9% Medium office 48.0 39.2 $1.24 $0.98 18.4% 20.5% Large office 46.3 35.4 $1.18 $0.92 23.6% 22.3% Standalone retail 76.0 48.2 $1.75 $1.18 36.5% 32.4% Strip mall 80.1 57.6 $1.84 $1.34 28.1% 27.2% Primary school 73.6 52.9 $1.65 $1.25 28.0% 24.2% Secondary school 78.3 49.2 $1.82 $1.24 37.1% 31.8% Outpatient healthcare 153.2 110.5 $3.59 $2.59 27.8% 27.8% Hospital 184.8 136.8 $4.28 $3.19 26.0% 25.5% Small hotel 72.7 62.1 $1.58 $1.36 14.6% 14.3% Large hotel 221.9 175.8 $4.65 $3.67 20.8% 21.1% 27.4 20.9 $0.56 $0.43 23.6% 22.1% Fast food restaurant 567.4 522.3 $10.23 $9.35 8.0% 8.6% Sit-down restaurant 403.5 351.8 $7.69 $6.46 12.8% 16.1% Mid-rise apartment 43.6 38.7 $1.04 $0.94 11.2% 9.8% High-rise apartment 44.0 40.4 $1.11 $1.03 8.3% 7.3% National-weighted average 77.6 58.4 $1.76 $1.35 24.8% 23.4% Warehouse 20 Site Energy [kBtu/sf] 2010 Progress Indicator Summary Building Type Office Retail Education Same Ventilation Standard Building Prototype January PI April PI June PI January PI April PI June PI Small office 11.3% 11.3% 17.7% 12.0% 12.1% 18.4% Medium office 13.0% 12.8% 17.1% 14.0% 13.8% 18.4% Large office 11.7% 11.8% 22.9% 12.8% 12.9% 23.6% Standalone retail 18.2% 27.8% 32.3% 23.6% 32.6% 36.5% Strip mall 17.2% 17.1% 23.5% 22.3% 22.2% 28.1% Primary school 13.0% 19.9% 24.2% 17.9% 24.7% 28.0% Secondary school 14.0% 26.4% 30.0% 23.6% 34.7% 37.1% Outpatient healthcare 11.8% 11.4% 26.9% 13.0% 12.9% 27.8% Hospital 5.8% 5.8% 26.6% 6.1% 6.0% 26.0% Small hotel 6.1% 6.4% 10.3% 10.6% 10.9% 14.6% Large hotel 6.7% 6.7% 15.7% 13.4% 13.4% 20.8% 14.0% 17.9% 23.6% 13.9% 17.9% 23.6% Fast food restaurant 4.3% 4.3% 6.4% 5.5% 5.8% 8.0% Sit-down restaurant 4.9% 5.3% 9.5% 8.9% 8.4% 12.8% Mid-rise apartment 8.7% 8.7% 11.2% 8.8% 8.8% 11.2% High-rise apartment 4.6% 6.2% 8.2% 4.6% 6.3% 8.3% 11.4% 14.7% 21.7% 15.1% 18.3% 24.8% Health Care Lodging Warehouse Warehouse Food Service Apartment National-weighted Average 21 Different Ventilation Standard Alternative June 2010 PI (exclude receptacle loads in the saving calculations) EnergySaving % Building Prototype ( EUIbase EUIreceptacle) Same Ventilation Standard EUI [kBtu/sf] Different Ventilation Standard EUI [kBtu/sf] 90.1-2004 June2010 PI Savings 90.1-2004 June2010 PI Savings Small office Medium office 30.9 32.4 23.8 24.5 22.9% 24.2% 31.2 33.1 23.8 24.5 23.7% 25.9% Large office Standalone retail Strip mall Primary school Secondary school 31.5 63.7 70.0 48.5 56.3 21.2 40.7 52.2 31.9 35.4 32.6% 36.1% 25.4% 34.2% 37.2% 31.9 68.5 74.7 52.3 64.2 21.2 40.7 52.2 31.9 35.4 33.4% 40.5% 30.1% 39.0% 44.9% Outpatient healthcare 118.8 78.2 34.2% 120.8 78.2 35.3% Hospital Small hotel 136.6 52.1 87.4 45.0 36.0% 13.6% 134.8 55.6 87.4 45.0 35.2% 19.1% Large hotel 173.1 140.7 18.7% 186.5 140.7 24.6% 24.9 288.5 235.9 32.6 32.7 18.4 252.9 198.9 27.8 29.2 26.0% 12.3% 15.7% 14.9% 10.6% 24.9 298.0 250.6 32.6 32.7 18.4 252.9 198.9 27.8 29.2 26.0% 15.1% 20.6% 15.0% 10.7% 58.8 42.7 27.4% 61.8 42.6 30.9% Warehouse 22 ( EUIbase EUIreceptacle) ( EUI Base EUIreceptacle) Fast food restaurant Sit-down restaurant Mid-rise apartment High-rise apartment National-weighted average Summary of June 2010 PI Results Same Ventilation Rate National-weighted Energy Saving 23 62.1-2004 Different Ventilation Rate 90.1-2004|62-1999 90.1-2010|62.1-2007 With Receptacle Loads Without Receptacle Loads With Receptacle Loads Without Receptacle Loads Site Energy 21.7% 27.4% 24.8% 30.9% Energy Cost 21.4% 26.5% 23.4% 28.9% This is not the final yet… Apply the remaining BOD-approved addenda to Final PI (90.1-2010) S (DX performance) CK (Ventilation reset) and more… Document PNNL’s Energy Saving Analysis for 90.1-2010 and publish as a technical report Complete all the load profiles for all 16 prototype buildings in 17 locations Support DOE’s 90.1-2010 Determination analysis 24 Time for Questions… PNNL’s Building Simulation Team Bing Liu, team lead Bing.Liu@pnl.gov Mike Rosenberg, Dr. Weimin Wang, Brian Thornton Dr. Yulong Xie, Dr. Heejin Cho, Dr. Jian Zhang Yunzhi Huang, Rahul Athalye, Vrushali Mendon With many thanks to 90.1 Simulation Working Group Ron Jarnagin, Drake Erbe, Dick Lord, Susanna Hanson, Merle McBride, John Hogan, and Martha VanGeem 25