New Experience in the Transformer Diagnosis Michael Krüger, OMICRON Austria Electrical Measurement Methods I Measurement Method Application Contact problems, broken or loose Winding resistance (static) connections, broken conductors Contact problems at the Winding resistance (dynamic) diverter switch, broken transition resistors Leakage reactance (stray Winding deformation reactance) Indicated by Kind of on-/offTest* line High internal temperatures, e.g. indicated by DGA results or Buchholz Relay FRT off DGA, Buchholz Relay FRT off High through-fault currents FRT off Frequency Response of the Stray Losses (FRSL) Shorted parallel strands of CTC's High internal temperatures, e.g. indicated by DGA results FT off No-load impedance Core problems, shorted turns High internal temperatures, e.g. indicated by DGA results FT off No-load current Core problems, shorted turns High internal temperatures, e.g. indicated by DGA results FT off *F=Fingerprint, R=Routine, T=Troubleshooting, S=Special Annual Convention 2012 – Eilat, Israel PAGE 2 Electrical Measurement Methods II Measurement Method Turns ratio Frequency Response Analysis (FRA) Application After Buchholz Relay tripping Winding deformation, winding displacement, core faults, faulty screen or core connections Indicated by Kind of on-/offTest* line Buchholz Relay has tripped T off High through-fault currents, transportation F(R)T off FRT off Breakdowns, Buchholz Relay tripping Insulation resistance Insulation problems Capacitance and Dielectric Dissipation Factor Main insulation: ageing, moisture - Bushings: DGA ageing, partial breakdowns FRT on/off Dielectric Response Measurement (FDS and PDC) Main insulation: ageing, high water content in oil / moisture - Bushings: high dielectric losses ageing, partial breakdowns FRT off Partial Discharge Insulation problems T on/off DGA *F=Fingerprint, R=Routine, T=Troubleshooting, S=Special Annual Convention 2012 – Eilat, Israel PAGE 3 Content • Winding Resistance Measurement • Fault Finding on Transformer Windings with FRA • Moisture Measurement on Transformers • Partial Discharge Measurement on Transformers Annual Convention 2012 – Eilat, Israel PAGE 4 Winding Resistance Measurement Annual Convention 2012 – Eilat, Israel PAGE 5 Diverter Switch Contact of Phase V Annual Convention 2012 – Eilat, Israel PAGE 6 Winding Resistance after Repair Annual Convention 2012 – Eilat, Israel PAGE 7 Content • Winding Resistance Measurement • Fault Finding on Transformer Windings with FRA • Moisture Measurement on Transformers • Partial Discharge Measurement on Transformers Annual Convention 2012 – Eilat, Israel PAGE 8 Fault on a 115kV / 34.5kV Transformer • There was a breakdown in phase B of the 34.5 kV busbar in the substation • The differential protection relay of the faulty transformer tripped Annual Convention 2012 – Eilat, Israel PAGE 9 DGA Phase 1: Trip out of Service, Differential Phase 2: DGA second DGA showed 19ppm C2H2 Annual Convention 2012 – Eilat, Israel PAGE 10 Transformer Model for FRA Annual Convention 2012 – Eilat, Israel PAGE 11 Swept Frequency Response Analysis (SFRA) 5.0 5.0 Transformer U0*(1-K(f1)) 3.0 3.0 1.0 1 N -1.0 0 0.2 0.4 0.6 0.8 1 1 U 1 V 1.0 1 W 1/f1 -1.0 0 1.2 -3.0 0.2 0.4 0.6 -3.0 complex RLCM-Network -5.0 0.8 1 1.2 (f1) -5.0 sine generator (variable frequency) (f1) K(f1) Phase Magnitude transfer function (magnitude) 2.5 2.0 2.0 K(f) transfer function (phase) 3.0 1.0 1.5 (f) 1.0 0.0 -1.0 0.5 -2.0 0.0 -3.0 0.0 0.2 0.4 0.6 0.8 Frequenz f frequency f 1.0 1.2 MHz 1.4 0.0 0.2 0.4 0.6 0.8 Frequenz f 1.0 MHz 1.2 1.4 frequency f Annual Convention 2012 – Eilat, Israel PAGE 12 FRA LV Winding – Comparison of the 3 Phases B Phase Annual Convention 2012 – Eilat, Israel PAGE 13 Radial Forces Higher order or forced Buckling Buckling with inner supports The conductors can bend between the supports all along the circumference Free mode or free Buckling Buckling without inner supports Source: Brochure CIGRE WG 12.19 : The Short Circuit Performance of Power Transformers Annual Convention 2012 – Eilat, Israel PAGE 14 Radial Failure (Buckling) Annual Convention 2012 – Eilat, Israel PAGE 15 Failure Modes due to Radial Forces B phase with buckling C phase without buckling Source: Cigre Brochure 342 “ MECHANICAL-CONDITION ASSESSMENT OF TRANSFORMER WINDINGS USING FREQUENCY RESPONSE ANALYSIS (FRA)” Annual Convention 2012 – Eilat, Israel PAGE 16 Comparison FRA LV Winding with Cigre Case Study of Buckling Systematic shift of several resonances www.e-cigre.org B Phase Annual Convention 2012 – Eilat, Israel PAGE 17 B Phase Take a closer look Annual Convention 2012 – Eilat, Israel PAGE 18 B Phase Annual Convention 2012 – Eilat, Israel PAGE 19 Content • Winding Resistance Measurement • Fault Finding on Transformer Windings with FRA • Moisture Measurement on Transformers • Partial Discharge Measurement on Transformers Annual Convention 2012 – Eilat, Israel PAGE 20 Water in the Transformer Most of the water is contained in the paper! Mass of the oil: 100,000 kg = 220,000 Lbs Mass of the solid insulation: 13,000 kg = 20,000 Lbs Water content at 60 °C: 40 ppm Water content at 60 °C: 4% Mass of the water, dissolved in the oil: Mass of the water contained in the paper: 4 kg = 8.8 Lbs 520 kg = 1200 Lbs Annual Convention 2012 – Eilat, Israel PAGE 21 Determination of the Water Content in Paper [Karl Fischer Titration and Equilibrium Curves] • Curves are only valid for new oil and new paper, for aged oil/paper different curves are necessary 11 20 °C [%] 30 °C 40 °C Water Content in the Paper 9 50 °C 8 7 low 6 60 °C 5 Temperature 4 80 °C high 3 2 100°C 1 0 0 10 20 30 40 50 60 Water Content in the Oil 70 [ppm] 90 • Oil sampling is critical (round robin tests) • Balance between water content in the paper and in oil needs constant temperatures over a long period • Only average measurement Annual Convention 2012 – Eilat, Israel PAGE 22 History of Dielectric Diagnostic Methods • 1960+ U U(t) Ur,max • Dissipation factor at power frequency • Polarization index • At that time: No reliable method for onsite moisture diagnostics • 1991 RVM for water determination • Soon questioned by users (Kachler 1996) tc 1999+ Polarization Depolarization Currents • Technical University Zurich Switzerland • 1999+ Frequency Domain Spectroscopy • KTH Stockholm with ABB • 2007 Combination of PDC and FDS Annual Convention 2012 – Eilat, Israel ipol (t) TC Uc (t) idep (t) Dissipation factor • U, I t t d t peak Frequency PAGE 23 t Dielektric Response in the Time Domain Polarisation Depolarisation Current (PDC) Current = f(t) Annual Convention 2012 – Eilat, Israel PAGE 24 Dielektric Response in the Frequency Domain Frequency Domain Spectroscopy (FDS) or Dielectric Frequency Response (DFR) Annual Convention 2012 – Eilat, Israel PAGE 25 Dielectric Response Measurement with Frequency Domain Spectroscopy (FDS) and Polarisation & Depolarisation Current (PDC) 1 1 Time [s] 1000 0.001 0.1 FDS 1000 Frequency [Hz] Transformation Power factor 1 1000 12 100 10 10 8 1 6 0,1 4 0,01 2 0,001 0,0001 0 FDS Combination of PDC und FDS reduces measurement time 0.001 0.001 14 Frequency [Hz] PDC DIRANA 1000 Annual Convention 2012 – Eilat, Israel PAGE 26 Frequency range / Hz 1 Power factor Current [nA] PDC Duration / h 100 Interpretation and Analysis Dissipation factor Pressboard: Water, lmw Acids Transition from Capacitive to Resistive Voltage Distribution Oil: Carbon, Sludge, hmw Acids 10 1 Pressboard Overall Response 0.1 1%, 1pS/m, X30, Y15 0.01 0.001 0.0001 0.0001 0.001 0.01 0.1 1.0 10 Annual Convention 2012 – Eilat, Israel 100 1000 f/Hz PAGE 27 Analysis of the Water Content by Comparison to Model Results Measurement Laboratory Results Temperature Oil Y XY-Model Oil Spacers Barriers X Comparison Fitting Tangent Delta 10 Water Content Oil Conductivity Source: Weidmann 0,1 0,01 0,0001 0,01 Frequency [Hz] 100 Annual Convention 2012 – Eilat, Israel PAGE 28 FDS / PDC Measurement on a 130 MVA Transformer – Situation 2006 • 130 MVA • 230 / 115 / 48 kV • Year of manf. 1967 • Rubber membrane in the expansion vessel Annual Convention 2012 – Eilat, Israel PAGE 29 FDS / PDC Measurement on a 130 MVA Transformer – Water Content Distribution Moisture in paper [%] 5 4 3 Tertiary not in use 2 Average 1 0 FDS HV-LV FDS LV- Tertiary FDS/PDC FDS TertiaryTank Oilsample Oilsample RH % Karl Fischer mg/kg (Oommen equilibrium) 1mHz-1kHz Annual Convention 2012 – Eilat, Israel PAGE 30 130 MVA Transformer On-Line Drying Annual Convention 2012 – Eilat, Israel PAGE 31 History 2006 – 2008 - 2010 Annual Convention 2012 – Eilat, Israel PAGE 32 Content • Winding Resistance Measurement • Fault Finding on Transformer Windings with FRA • Moisture Measurement on Transformers • Partial Discharge Measurement on Transformers Annual Convention 2012 – Eilat, Israel PAGE 33 Diagnostic Measurement on a Cast Resin Type Transformer Annual Convention 2012 – Eilat, Israel PAGE 34 Cracks in the Epoxy Annual Convention 2012 – Eilat, Israel PAGE 35 PD Measurement Circuit Annual Convention 2012 – Eilat, Israel PAGE 36 Test Arangement CPC100 CP CU1 Compensating Capacitors Annual Convention 2012 – Eilat, Israel PAGE 37 Test Arangement Coupling Capacitor and MPD600 Annual Convention 2012 – Eilat, Israel PAGE 38 Separation of PD Sources in 3CFRD 3CFRD 500kHz 500 kHz 2 MHz 8 MHz 2MHz 8 MHz 2 MHz 500 kHz 8MHz timeframe 1 µs 3CFRD = 3 Center Frequency Relation Diagram Annual Convention 2012 – Eilat, Israel PAGE 39 PD Measurement without 3CFRD Filtering Annual Convention 2012 – Eilat, Israel PAGE 40 3CFRD Filtering Annual Convention 2012 – Eilat, Israel PAGE 41 PD Measurement with 3CFRD Filtering Annual Convention 2012 – Eilat, Israel PAGE 42 PD Measurement without 3CFRD Filtering Annual Convention 2012 – Eilat, Israel PAGE 43 On-Line PD Measurement on a Transformer Annual Convention 2012 – Eilat, Israel PAGE 44 On-Line PD Measurement on a Transformer GIS - Cable Connection (GIS Side) 3 2 1 Annual Convention 2012 – Eilat, Israel PAGE 45 Online PD Measurement at the GIS Side red phase GIS yellow phase GIS blue phase GIS Annual Convention 2012 – Eilat, Israel PAGE 46 Sensors 1, 2 and 3 at the GIS Side and Sensor 4 at the Transformer Side 4 100m Annual Convention 2012 – Eilat, Israel PAGE 47 PD Measurement at the GIS and the Transformer Side blue phase GIS blue phase Tr Annual Convention 2012 – Eilat, Israel PAGE 48 PD Measurement at GIS and TR Side Trigger = TR Side - Delay on GIS Side trigger = blue phase Tr delayed signal blue phase GIS Annual Convention 2012 – Eilat, Israel PAGE 49 Jumper between Oil/Oil Bushing and Cable Termination Annual Convention 2012 – Eilat, Israel PAGE 50 Jumper between Oil/Oil Bushing and Cable Termination Annual Convention 2012 – Eilat, Israel PAGE 51 michael.krueger@omicron.at Questions and Remarks? A last Example: Fault Investigation on a 220kV Transformer Annual Convention 2012 – Eilat, Israel PAGE 53 DGA Parameter H2 CH4 C2H6 C2H4 C2H2 CO CO2 TDCG DGA 7 Nov 2011 Main Tank OLTC 1008.8 1183 67 65 54.8 55 668 710 1130 1214 95 107 720 740 3024 3337 Condition 1 ≤ 100 ≤ 120 ≤ 65 ≤ 50 ≤ 1 ≤ 350 ≤ 2500 ≤ 720 IEEE C57.104-2008 Condition 2 Condition 3 Condition 4 101 - 700 701 - 1800 > 1800 121 - 400 401 - 1000 > 1000 66 - 100 101 - 150 > 150 51 - 100 101 - 200 > 200 29 10 35 > 35 351 - 570 571 - 1400 > 1400 2501 - 4000 4001 - 10000 > 10000 721 - 1920 1921 - 4630 > 4630 Annual Convention 2012 – Eilat, Israel PAGE 54 Ratio Measurement HV to LV Annual Convention 2012 – Eilat, Israel PAGE 55 Ratio HV to LV Phase A=R A: Tap A 001 A 002 A 003 A 004 A 005 A 006 A 007 A 008 A 009 A 010 A 011 A 012 A 013 A 014 A 015 A 016 A 017 A 018 V prim. Nom. Vsec.Nom. Ratio nom. V prim. 165750.0/√3V 163500.0/√3V 161250.0/√3V 159000.0/√3V 156750.0/√3V 154500.0/√3V 152250.0/√3V 150000.0/√3V 147750.0/√3V 145500.0/√3V 143250.0/√3V 141000.0/√3V 138750.0/√3V 136500.0/√3V 134250.0/√3V 132000.0/√3V 129750.0/√3V 127500.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 8.2875:1 8.175:1 8.0625:1 7.95:1 7.8375:1 7.725:1 7.6125:1 7.5:1 7.3875:1 7.275:1 7.1625:1 7.05:1 6.9375:1 6.825:1 6.7125:1 6.6:1 6.4875:1 6.375:1 1999.5V 1999.57V 1999.39V 1999.35V 1999.5V 1999.42V 1999.58V 1999.74V 1999.5V 1999.42V 1999.4V 1999.43V 1999.54V 1999.49V 1999.49V 1999.5V 1999.43V 1999.56V Vsec. 0.022947V 0.023128V 0.022972V 0.024964V 0.024298V 0.023854V 0.024173V 0.024195V 0.02426V 0.022962V 0.022158V 0.024335V 0.024313V 0.023602V 0.024304V 0.02426V 0.024024V 0.023816V Ratio 164.81° 163.61° 164.95° 166.1° 163.59° 162.68° 165.95° 166.09° 163.8° 164.95° 163.12° 164.51° 163.74° 165.97° 165.52° 164.07° 166.21° 166.46° 87143.1684:1 86449.2002:1 87043.535:1 80086.1206:1 82283.9506:1 83815.5523:1 82712.7198:1 82650.9609:1 82419.6208:1 87082.7526:1 90225.6318:1 82162.7286:1 82234.8345:1 84724.1525:1 82266.6118:1 82419.6208:1 83222.8928:1 83962.2087:1 I prim. 1051401.28% 1057382.57% 1079509.74% 1007272.59% 1049774.97% 1084890.97% 1086438.19% 1101912.81% 1115563.23% 1196913.78% 1259594.68% 1165328.77% 1185266.98% 1241279.52% 1225473.36% 1248682.13% 1282719.16% 1316954.25% 0.002665A 0.002657A 0.002673A 0.002634A 0.002631A 0.002637A 0.002651A 0.002648A 0.002632A 0.00267A 0.00267A 0.002629A 0.002629A 0.002663A 0.002641A 0.002625A 0.002654A 0.002636A 77.53° 77.67° 77.14° 77.17° 77.06° 77.55° 76.95° 76.92° 77.03° 77.19° 76.95° 77.23° 77.03° 77.14° 76.95° 77.3° 76.97° 76.95° 2kV on HV -> 23mV on LV on all taps ! Annual Convention 2012 – Eilat, Israel PAGE 56 Ratio HV to LV Phase B=S B: Tap B 001 B 002 B 003 B 004 B 005 B 006 B 007 B 008 B 009 B 010 B 011 B 012 B 013 B 014 B 015 B 016 B 018 V prim. Nom. Vsec.Nom. 165750.0/√3V 163500.0/√3V 161250.0/√3V 159000.0/√3V 156750.0/√3V 154500.0/√3V 152250.0/√3V 150000.0/√3V 147750.0/√3V 145500.0/√3V 143250.0/√3V 141000.0/√3V 138750.0/√3V 136500.0/√3V 134250.0/√3V 132000.0/√3V 127500.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V Ratio nom. V prim. 8.2875:1 8.175:1 8.0625:1 7.95:1 7.8375:1 7.725:1 7.6125:1 7.5:1 7.3875:1 7.275:1 7.1625:1 7.05:1 6.9375:1 6.825:1 6.7125:1 6.6:1 6.375:1 999.76V 999.76V 999.81V 999.79V 999.71V 999.83V 999.88V 999.62V 999.78V 999.81V 999.72V 999.87V 999.82V 999.82V 999.84V 999.74V 999.74V Vsec. 139.451279V 139.450928V 139.457031V 139.454666V 139.442612V 139.460587V 139.466415V 139.43132V 139.453995V 139.453735V 139.43515V 139.456238V 139.448944V 139.449051V 139.452438V 139.436752V 139.438568V Ratio -0.04° -0.03° -0.03° -0.03° -0.03° -0.03° -0.02° -0.02° -0.03° -0.03° -0.03° -0.03° -0.03° -0.04° -0.04° -0.02° -0.03° 7.1692:1 7.1693:1 7.1693:1 7.1693:1 7.1693:1 7.1693:1 7.1693:1 7.1693:1 7.1692:1 7.1695:1 7.1698:1 7.1698:1 7.1698:1 7.1698:1 7.1698:1 7.1698:1 7.1698:1 I prim. -13.49% -12.3% -11.08% -9.82% -8.53% -7.19% -5.82% -4.41% -2.95% -1.45% 0.1% 1.7% 3.35% 5.05% 6.81% 8.63% 12.47% 0.013008A 0.013062A 0.013101A 0.013075A 0.013093A 0.013151A 0.013023A 0.013017A 0.01313A 0.013136A 0.013087A 0.013013A 0.013118A 0.013131A 0.013061A 0.013088A 0.013088A -54.74° -54.89° -54.94° -54.92° -54.7° -54.94° -54.64° -54.79° -54.97° -54.96° -54.67° -54.65° -54.87° -54.94° -54.9° -54.71° -54.73° All taps have the same ratio 7.2:1 of position 11 ! Annual Convention 2012 – Eilat, Israel PAGE 57 Ratio HV to LV Phase C=T C: Tap C 001 C 002 C 003 C 004 C 005 C 006 C 007 C 008 C 009 C 010 C 011 C 012 C 013 C 014 C 015 C 016 C 017 V prim. Nom. Vsec.Nom. Ratio nom. V prim. 165750.0/√3V 163500.0/√3V 161250.0/√3V 159000.0/√3V 156750.0/√3V 154500.0/√3V 152250.0/√3V 150000.0/√3V 147750.0/√3V 145500.0/√3V 143250.0/√3V 141000.0/√3V 138750.0/√3V 136500.0/√3V 134250.0/√3V 132000.0/√3V 129750.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 20000.0/√3V 8.2875:1 8.175:1 8.0625:1 7.95:1 7.8375:1 7.725:1 7.6125:1 7.5:1 7.3875:1 7.275:1 7.1625:1 7.05:1 6.9375:1 6.825:1 6.7125:1 6.6:1 6.4875:1 999.87V 999.78V 999.92V 999.93V 999.74V 999.95V 999.91V 999.68V 999.85V 999.73V 999.69V 999.79V 999.77V 999.67V 999.78V 999.65V 999.85V Vsec. 139.558258V 139.544296V 139.565689V 139.567307V 139.539001V 139.569595V 139.553513V 139.52594V 139.555328V 139.538071V 139.533554V 139.544205V 139.530441V 139.531235V 139.54483V 139.529968V 139.555405V Ratio -0.04° -0.02° -0.03° -0.03° -0.01° -0.04° -0.04° -0.01° -0.01° -0.01° -0.01° -0.01° -0.03° -0.02° -0.01° -0.03° -0.02° 7.1645:1 7.1646:1 7.1645:1 7.1645:1 7.1646:1 7.1645:1 7.1651:1 7.1648:1 7.1645:1 7.1646:1 7.1645:1 7.1647:1 7.1652:1 7.1645:1 7.1646:1 7.1644:1 7.1645:1 I prim. -13.55% -12.36% -11.14% -9.88% -8.59% -7.26% -5.88% -4.47% -3.02% -1.52% 0.03% 1.63% 3.28% 4.97% 6.73% 8.55% 10.44% 0.010944A 0.011008A 0.010951A 0.010956A 0.010937A 0.010964A 0.01097A 0.011007A 0.010945A 0.010946A 0.010938A 0.010944A 0.010938A 0.011001A 0.010996A 0.010932A 0.010954A -47.77° -47.85° -47.68° -47.71° -47.67° -47.73° -47.83° -47.82° -47.65° -47.7° -47.66° -47.7° -47.58° -47.81° -47.79° -47.55° -47.68° All taps have the same ratio 7.2:1 of position 11 ! Annual Convention 2012 – Eilat, Israel PAGE 58 FRA HV Interruption in phase R, HV side Annual Convention 2012 – Eilat, Israel PAGE 59 FRA LV with HV open Short circuit in phase R, but on LV or HV side ??? Annual Convention 2012 – Eilat, Israel PAGE 60 FRA LV with HV Open and Shorted A LV with open loop HV (red line) B LV with open loop HV (blue solid line) B LV with shorted HV (blue dashed line) Annual Convention 2012 – Eilat, Israel PAGE 61 Winding Resistance of LV Phase R LV doesn’t look damaged Annual Convention 2012 – Eilat, Israel PAGE 62 Conclusions • Phase R=A is interrupted on HV side • The tap changer is broken – in position 11 • The limb R has a shorted winding • The short circuit in limb R is not on the LV side but on the HV side Annual Convention 2012 – Eilat, Israel PAGE 63 Opening of the OLTC Compartment Annual Convention 2012 – Eilat, Israel PAGE 64 Opened OLTC Compartment Interruption in phase R, HV side Annual Convention 2012 – Eilat, Israel PAGE 65 Interruption due to Open OLTC Contacts Annual Convention 2012 – Eilat, Israel PAGE 66 Removed OLTC – Cables to the Tap Winding Annual Convention 2012 – Eilat, Israel PAGE 67 FRA on the Single Tap Winding Segments Annual Convention 2012 – Eilat, Israel PAGE 68 FRA on the Single Tap Winding Segments Segments 11 - 13 9 - 11 8- 9 7- 8 6- 7 5- 6 4- 5 3- 4 2- 3 14 - 2 Annual Convention 2012 – Eilat, Israel PAGE 69 FRA on the Single Tap Winding Segments Annual Convention 2012 – Eilat, Israel PAGE 70 Winding Resistance of the Tap Winding Segments 4 14mΩ 25mΩ 5 14mΩ 6mΩ 7mΩ 25mΩ 6 The fault was between tap conductor 4 and 6 ! Annual Convention 2012 – Eilat, Israel PAGE 71 michael.krueger@omicron.at Questions and Remarks?