SYMMETRICAL COMPONENETS

OF POWER SYSTEM

1

OUTLINE OF THE PRESENTATION

 INTRODUCTION

 NEED FOR THE SYMMETRICAL

COMPONENET METHOD

 TECHINQUES USED TO ANALYSIS

SYMMETRICAL

 SYMMETRICAL METHODS USED TO STUDY

POWER SYSTEM FAULTS

 CONCLUSION

 REFERENCES

2

INTRODUCTION

 The normal operating conditions of an electric power system are occasionally disrupted because of faults.

Analysis of power systems usually implies the computation of network voltages and currents under a given set of conditions.

Under many circumstances we tend to ignore the unbalanced operation in the system and unbalanced operation is always present.

3

An organization of power system analysis problem

Source (Reference #1)

4

Effects of faults on power system

Flow of excessive current

Abnormal voltages

Voltage elevation of system neutral

Induce over voltages on neighbouring equipments .

Hazards to human, equipment and animals.

5

Need for fault analysis

Design of protection system requires the knowledge of fault current.

The information obtained from the fault studies are used: to select the sizes of circuit breaker, fuse and characteristic, setting of relay.

6

Normal types of fault are:

Fault due to lightning

Tree limbs falling on the line

Wind damage

Insulation deterioration

Vandalism

7

Types of fault

Symmetrical fault :

Usually three phase to ground fault

Unsymmetrical fault

The fault is unbalanced in nature

8

Sources of Asymmetrical fault are:

(Reference#2)

9

Sources of Asymmetrical fault are (cont.)

One phase open circuit

Unbalanced in load mainly the arc loads

10

Sources of Asymmetrical fault are (cont.)

One phase open circuit

11

Sources of Asymmetrical fault are (cont.)

SLG fault

12

Need for the symmetrical component analysis

Negative sequence relay in generator has helped in protecting the generator from over heating in the event of unbalanced loads.

The positive sequence segregating network is used to supply the sensing voltage to generator voltage regulators

Certain connections of CT and PT develop zero sequence components that are used in protective ground relaying scheme.

13

Method of adopted for symmetrical component analysis (cont)

Mathematically:

V a

= V a1+

V a2+

V a3+----------

V an

V b

= V b1+

V b2+

V b3+----------

V bn

;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;

V n

= V n1+

V n2+

V n3+----------

V nn

Where:

V a,

V b…….

V n are unbalanced set of phosors

V a1,

V b1……

V n1 first set of n balanced phasors with an angle 2pi/n between components a,b,…..n

14

Method of adopted for symmetrical component analysis (cont)

Mathematically:

 V a2,

V b2……

V n2 second set of n balanced phasors with an angle

4pi/n between components a, b………,…..n

……………………………………………………….

 V a(n-1),

V b(n-1)……

V n(n-1)are (n-1)th set of n balanced phasors with an angle 2pi(n-1)/n between components a, b………,…..n

15

Phasor a or a-operator

The phasor notation of a-operator

16

Phasor a or a-operator

17

Phasor a or a-operator

18

Equation in matrix form

19

Symmetrical components for three Phase system

The n-phase system presented above is of academic interest only and only the practical three phase system will be emphasised.

Power is generated, transmitted and consumed mostly in three phase only.

20

Symmetrical components for three Phase system

(cont)

The phasor representation of three phase system (source reference#2)

21

Symmetrical components for three Phase system

(cont)

The positive sequence set consisting of three components of equal magnitude, displaced by 120 & 240 o respectively and having the phase sequence of abca.

The negative sequence set consisting of three components of equal magnitude displaced by 240 & 120 o respectively, having phase sequence of acba.

The zero sequence set of the component of which being equal both in magnitude and and phase.

22

Symmetrical components for three Phase system

(cont)

Relations of voltage components in matrix form

23

Symmetrical components of generator

24

Symmetrical components of generator

25

Symmetrical components of transformer (zero)

26

Fault analysis using symmetrical components

The most common type of fault is the single line to ground fault:

27

Fault analysis using symmetrical components

(cont)

The sequence component connection for the single line to ground fault:

28

Fault analysis using symmetrical components

(cont)

The sequence component connection for the single line to ground fault:

The sequence components are connected in series.

The three currents in the case of SLG fault are equal.

29

Fault analysis using symmetrical components

(cont)

LL fault:

30

Fault analysis using symmetrical components

(cont)

LL fault:

There is no zero sequence component due to absence of ground return path.

The positive and negative sequence components are connected in parallel.

31

Fault analysis using symmetrical components

(cont)

LLG fault:

32

Fault analysis using symmetrical components

(cont)

LLG fault:

For the zero sequence component it requires to add an external impedance of Z f

+3Z g

The networks are connected in parallel.

33

Software available for carrying fault analysis

The most commonly used soft ware are:

MATLAB

EDSA

ETAP

CYME

34

Conclusion

Power system analysis using symmetrical component is very helpful in improving the reliability of the power system.

The principle adopted for the analysis of unbalanced fault system is symmetrical component method.

By knowing the principle, the results obtained from the computer can be analysed.

35