SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 16101 GENERAL 101.01 THIS SECTION INCLUDES SPECIFICATIONS FOR TYPES OF MATERIAL. A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. 101.02 Material (16102) Area Classification (16103) Raceways - Material (16110) Raceways - Methods (16111) Conductors - Material (16120) Conductors - Methods (16121) Boxes - Material (16130) Boxes - Methods (16131) Telephone Cabinets (16132) Switches and Receptacles - Materials (16140) Receptacles - Special Duty - Materials (16141) Switches and Receptacles - Methods (16142) Motors (16150) Heating Equipment (16155) Backboards (16160) Equipment and Circuit Identification (16170) INCORPORATED DOCUMENTS Articles of the following sections shall apply: A. B. C. D. E. 101.03 16001 - General Conditions 16002 - Codes and Standards 16003 - Drawings 16010 - General Provisions Specific Documents Listed in Individual Sections ENVIRONMENTAL CONDITIONS - OUTDOOR: A. Equipment listed for outdoor installation, under this Section 16100, shall be capable of meeting the following: 1. 2. 3. 4. 5. 6. 16100-rev0 Elevation Above Sea Level Outdoor Ambient Temperature Outdoor Relative Humidity Maximum Outdoor Daily Temperature Range Outdoor Air Conditions Maximum Wind Velocity 16100 - 1 0-500 ft. 50 Deg. to 100 Deg. F 30% to 100% 20 Deg. to 120 Deg. F No Salt 80 MPH December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 16102 16103 MATERIALS 102.01 Electrical material and equipment shall be new and shall bear the inspection label of Underwriter's Laboratories, Inc., or shall show evidence of approval by an acceptable independent testing laboratory, and shall conform to the applicable specifications and standards of the Institute of Electrical and Electronics Engineers (IEEE), American National Standards Institute (ANSI), Joint Industry Committee (JIC), Insulated Power Cable Engineers Association (IPCEA), National Electrical Manufacturer's Association (NEMA), and National Fire Protection Association (NFPA). 102.02 Materials and workmanship are subject to approval by the Engineer. Any portion of the work, which, in the judgment of the Engineer, is defective shall be replaced by the Contractor as part of this contract, at no additional cost to the Owner. AREA CLASSIFICATION 103.01 Electrical equipment shall be applicable for the areas in which they are installed. Special areas will be shown on the drawings. 103.02 The following NEMA-type devices shall be installed as described below: A. Indoor-Dry; NEMA 1 or 12; see drawings for detailed information. B. Indoor-Wet or Nonhazardous Dust; NEMA 4 or 4X. C. Outdoor; NEMA 3R, 4 or 4X; as indicated on the drawings. D. Hazardous gas or vapor producing areas - indoor; NEMA 7 (Class I, Division I); groups as called for on the drawings, suitable for wet locations. F. Hazardous dust areas - indoor; NEMA 9, (Class II, Division I); group as called for on the drawings. G. Hazardous dust areas - outdoor; NEMA 9, (Class II, Division I); group as called for on the drawings, suitable for wet locations. H. 103.03 16110 Air plenums and areas below raised floors require materials to be noncombustible. Cables shall be rated teflon or teflon jacketed. Liquid tight conduit shall be rated for the use. RACEWAYS - MATERIAL 110.01 16100-rev0 Equipment utilizing a water spray, oil, a non corrosive coolant, or emitting a nonhazardous dust shall be equipped with NEMA 13 devices. GENERAL 16100 - 2 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS Conduit and associated fittings shall meet the requirements of ANSI C80 Series. 110.02 110.03 110.04 16100-rev0 RIGID GALVANIZED STEEL CONDUIT: A. Conduit shall be Western or approved equal in standard 10'-0" lengths with threads on both ends. B. Conduit shall be formed with continuous welded seams and shall have an interior/exterior coating of protective metallic zinc at least .0008 inch thick applied evenly over the surface. C. Conduit shall be UL listed. Use, installation , and construction shall comply with Article 344 of the National Electrical Code. D. Wall thickness shall be uniform throughout. E. Fittings shall be threaded steel and engaged a minimum of five threads of conduit. F. Elbows, nipples, couplings, and termination fittings shall be compatible with the conduit. RIGID STEEL INTERMEDIATE CONDUIT: A. Conduit shall be Western or equal. Use, installation , and construction shall comply with Article 344 of the National Electrical Code. B. Conduit shall be UL listed. and conform to Article 345 of the National Electrical Code. C. Conduit shall have same characteristics of rigid steel conduit, except for thinner wall. D. Elbows, nipples, couplings, and termination fittings shall be compatible with the conduit. ELECTRICAL METALLIC TUBING (EMT): A. Tubing shall be Western or approved equal in standard 10'-0" lengths of continuous welded seams with .0008 inch zinc coating inside and out. B. Tubing shall be UL listed and conform to Article 348 of the National Electrical Code. C. Wall thickness shall be uniform throughout. D. Joints or terminations shall be made with weather-tight compression fittings, no other type fittings shall be used. Fittings shall meet the 16100 - 3 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS same requirements for finish and materials as EMT. The Fittings shall be steel, compression ring-type, approved by the Underwriters' Laboratories and listed as raintight. Fittings shall comply with ANSI Specification C80.3, and Federal Specification WW-T-806. Set screw fittings are not acceptable. 110.05 110.06 110.07 16100-rev0 RIGID ALUMINUM CONDUIT: A. Conduit shall be New Jersey Aluminum Company or approved equal. B. Conduit shall be UL listed and conform to Article 344 of the National Electrical Code. C. Fittings shall be threaded aluminum and shall engage a minimum of five threads on conduit. D. Conduit shall be threaded on both ends and have a uniform wall thickness throughout. E. Elbows, nipples, couplings and termination fittings shall be compatible with the conduit. PLASTIC COATED RIGID STEEL CONDUIT: A. Coated conduit and fittings shall be the product of Ocal or approved equal, with the coating applied under controlled factory conditions. Coated material shall be installed and patched according to the manufacturer's recommendations. B. Conduit, prior to coating, shall conform to American National Standards Institute Specification C80.1. C. Stainless steel screws shall be furnished and used to attach the cover to the conduit body. FLEXIBLE METAL CONDUIT- FMC (STEEL OF ALUMINUM): A. Conduit shall be as manufactured by All-Flex Corporation or approved equal. B. Conduit shall be UL listed and conform to Article 348 of the National Electrical Code. C. Fittings shall be die-cast. D. Conduit shall have uniform diameter throughout. 16100 - 4 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 110.08 110.09 110.10 110.11 LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC): A. Conduit shall be Sealtight or equal. B. Conduit shall be listed by UL and shall conform to Article 350 of the National Electrical Code. C. Fittings shall be liquidtight at terminations. D. When used under raised floor areas or in air plenum spaces, shall be of a type suitable for the use and high temperature rated, 105 Degrees C minimum. NONMETALLIC CONDUIT (SCHEDULE 40 OR SCHEDULE 80) A. Conduit shall be Carlon PV Duit, 90 Degrees C UL rated or approved equal. B. Conduit shall be composed of polyvinyl chloride. C. Conduit shall be UL listed. Use, installation , and construction shall comply with Article 362 of the National Electrical Code. D. Materials must have a tensile strength of 7,000 psi at 73.4 Degrees F, flexural strength of 11,000 psi, and compressive strength of 8,600 psi or greater. E. Joints shall be solvent welded, as recommended by manufacturer. NONMETALLIC DUCT (TYPE EB): A. Duct shall be Carlon PVC Type EB for concrete encasement or approved equal. B. Duct shall be listed by UL and shall conform to NEMA Standard TC 6. C. Duct shall be manufactured from PVC compound consisting of at least 75% virgin PVC Monopolymer, not more than 20% inert additives and not more then 3% processing additives. D. Materials must have a tensile strength of 6,000 psi, modules of elasticity in tension of 500,000 and flexural strength of 11,000 psi. E. Joints shall be solvent welded, as recommended by manufacturer. WIREWAY A. 16100-rev0 Wireways shall be of lay in-type construction without knockouts in the sides or bottom. 16100 - 5 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 110.12 B. Wireways shall be listed by UL and shall conform to Article 362 of the National Electrical Code. C. Wireways shall be of NEMA-type and size as indicated on the drawings. D. Wireways shall be installed using manufacturer's recommended hardware, unless otherwise shown on the drawings. CABLE TRAY: A. Continuous rigid cable support system for power cables shall be Husky-Burndy, ladder-type construction. Substitutions shall have written approval from the Owner. B. Continuous rigid cable support system for telephone signal and control cable shall be Husky-Burndy, trough-type construction. Substitutions shall have written approval from the Owner. C. Ladders and troughs shall be galvanized steel, manufactured and tested in compliance with currently published NEMA Cable Tray Standard VE-1. D. Trough section bottoms shall be of one-piece construction with integral cross rungs on approximately 1" centers and shall have dividers. E. Ladder sections shall consist of 2 longitudinal side members connected by individual rungs spaced on 18 inch centers. F. Straight sections shall be capable of supporting a minimum uniform load of 35 lbs. per lineal foot in a 12'-0" simple span between supports, where connectors are located within ¼ point of the span of the tray. Load safety factor shall not be less than 1.5. G. The fittings shall be capable of supporting the same design load as straight sections when fittings are supported to minimum standards outlined in NEMA Standard VE-1 on ventilated cable tray, but with no span between supports exceeding that used for adjacent straight sections. Short time total loads on straight sections or fittings shall not exceed design load by more than one-third. 16100-rev0 H. The Cable Tray shall have an inside width as indicated on Drawings, with 3" clear inside depth. I. Fittings, both vertical and horizontal, shall have 8" minimum radius for troughs and 12" for ladders. 16100 - 6 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS J. 110.13 110.14 16100-rev0 Supports shall be in conformance with NEMA Standards and recommendations. Supports shall be capable of carrying required cable loads plus tray weight and any additional short time total loads not to exceed the design loads by more than one-third. On vertical tray runs, cable shall be held against thrust by supports external to tray. SURFACE RACEWAY: A. Surface metal raceways, junction boxes, elbows, extension boxes, and fittings for use in office areas subject to abuse by carts, forklifts, or vehicle traffic, rigid aluminum conduit shall be used. B. Floor mounted surface metal raceways, junction boxes, and fittings shall be Wiremold Series 1500 "Pancake." Duplex 15A, 125-Volt outlets for this series shall consist of Wiremold No. 1546B boxes, with Hubbell #5262 receptacles in office area applications. Power poles or conduit drops to benches should be used unless the drops or poles would interfere with the operation of the room. C. Multi-outlet raceway assemblies shall be Wiremold 3000, arranged as shown on the drawings. UNDERFLOOR RACEWAY: A. Underfloor raceway shall be "Walkerduct". Substitutions receive shall have written approval from the Owner. B. Underfloor ducts shall be steel, dual system-type raceway, providing minimum capacities of 3 sq. in. (19cm(2)) and 8.5 sq. in. (55cm(2)) for convenience outlets and telephone service, respectively. Duct spacing should not exceed 6' (1.8m) on centers. Duct systems shall be interconnected with a system of trench headers, terminating in electrical or telephone closets. Header entries into telephone closets or terminal cabinets shall provide at least 1 sq. in. of raceway per 100 sq. ft. (9.3m(2)) of net productive area. C. Ducts may be as described above or may be an electrified cellular system. Header ducts or trenches as described above shall be included. D. Splices and taps shall be made in approved junction boxes. E. Loop wiring (continuous unbroken) conductor connecting individual receptacles shall not be permitted. F. The circuit conductors supplying the outlet shall be removed from the raceway when an outlet is removed. 16100 - 7 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 16111 RACEWAYS - METHODS 111.01 GENERAL: A. The Contractor shall install items in their proper locations as shown on the Contract Drawings, rigid and secure, plumb and level, and in true alignment with related and adjoining work. B. Seismic Design Requirements 1. Items covered in this section shall be seismically braced as specified in Section 16001.1.12. C. The Contractor shall provide templates, layout drawings, and supervision at the job site to ensure correct placing of anchorage items in concrete. Check embedded items for correctness of location and detail before concrete is placed. Anchoring of equipment and associated support(s) shall be capable of withstanding a seismic disturbance of 0.5 g. in any direction without damage to equipment. D. The Contractor shall control the installation so as not to impair the strength, safety, serviceability, or appearance of any work, determine exact location of conduit and route all conduit parallel to building lines. E. The trade size, type, and general routing and location of conduit raceways and boxes shall be installed as shown on the Contract Drawings. F. The Contractor shall install individual conductors, conduits in raceways, ducts, and trenches as shown on the Contract Drawings. G. The Contractor shall install switches, receptacles, special purpose outlets, and cover plates in a neat manner, as shown on drawings. 16100-rev0 H. Provide an insulated ground wire in all raceways. I. Hazardous Areas 1. Conduit, flexible conduit, fittings, junction and/or terminal boxes, connectors, and flexible cords shall be listed for the area described on the drawings. 2. Such arcing devices as pushbuttons, pilot lights, limit switches, and other equipment, shall be either factory sealed or the conduit shall be sealed per the requirements of the National Electrical Code. 3. Conduit entering or leaving the hazardous area shall be sealed on either side of the boundary walls per the requirements of the National Electrical Code. 16100 - 8 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 4. 111.02 Seals shall not be poured until wiring is pulled and conductors have been tested for proper function. RACEWAY CONDUIT - GENERAL: Wiring for circuits over 24 Volts shall be run in conduit. Conduit sizes shall conform to the drawings and to applicable electrical codes. Conduits shall be installed concealed, wherever possible, and shall be parallel to building lines. There shall be no cutting across or diagonal runs. Condulets Conduit fittings or pull boxes shall be installed when structural obstructions are encountered. All conduit and fittings for power, control instrumentation and lighting circuits, and in exposed installations shall be hot-dipped galvanized rigid steel with threaded fittings except for underground/ liquid tight flexible conduit installations or as noted. In corrosive area installations, hot-dipped galvanized steel conduits with PVC coating shall be used. A. Rigid Galvanized Steel Conduit: Shall be used in outdoor areas exposed to weather or vehicle traffic, concrete slabs or walls, vertical drops over 10', under raised floors, in hazardous classified areas, for penetration through concrete floors or foundations, unless otherwise noted on the drawings. Rigid steel elbows shall be used where underground feeders enter panel boards, junction or device boxes. Expansion joints shall be used where required. Conduit in contact with the earth shall be protected by Scotchwrap 10 mil tape applied in double thickness using ½ lap turns. Conduits shall not be installed at a radius smaller than recommended by NEC the National Electrical Code. Conduits carrying conductors above 600 volts shall be painted yellow, with an identifying marker at 10' intervals indicating the voltage level and feeder designation. B. Rigid Steel Intermediate Conduit: May be used in lieu of rigid steel conduit in all above ground area installations where steel conduit in permitted, except for wire conductors over 600 volts, but only if specified. C. Electrical Metallic Tubing (EMT): Electric metallic tube (EMT) shall be used for 2" or smaller in indoors locations in the administration building, laboratory building, and the office areas of the shops and warehouse building only, 3/4" minimum size for home runs. Couplings shall be of the steel compression type. D. Rigid Aluminum Conduit: May be used in lieu of rigid steel in interior dry locations. It shall not be used under the ground floor slab in concrete or in earth. E. 16100-rev0 Plastic-Coated Rigid Steel Conduit 16100 - 9 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS F. 1. Plastic-coated, rigid steel conduit and fittings shall be installed in highly corrosive areas indoors or outdoors, as shown on the drawings. 2. The Contractor shall patch any damaged coating according to the manufacturer's instructions and to the satisfaction of the Engineer. Flexible Metal Conduit, Steel or Aluminum: 1. Shall be used in dry locations for recessed lighting fixtures only, unless otherwise noted on the drawings. 2. The Contractor shall provide a green insulated ground wire in all flexible metal conduit. G. Liquid Tight Flexible Metal Conduit: H. 1. Shall be used for conduit connections for motors, transformers or in areas of movement which are subject to moisture or oil. 2. Provide a green insulated ground wire in all liquidtight flexible metal conduit. Nonmetallic Conduit (Schedule 40): Shall be used for all power, signal feeders and branch circuits below the ground floor slab or in earth, unless otherwise noted on the drawings. Conduits below grade must be converted to rigid steel wrapped with 10 mil tape, applied in double thickness using ½ lap turns. Conduits shall contain a continuous grounding conductor as designated in the National Electrical Code. Conduits shall be buried in earth a minimum of 24". 111.03 16100-rev0 CONDUIT INSTALLATION: A. Conduits shall be concealed in the walls or ceilings, unless otherwise noted on the drawings. Conduits in basement areas and conduits to surface mounted equipment in unfinished areas shall be exposed. Conduits shall be parallel to the building lines. B. Changes in direction of exposed conduits shall be made with conduit fittings or long radius bends. Conduit shall be supported by pipe hangers, U-bolts, or "Unistrut" framing channel and straps. As a minimum, conduit shall be supported per the requirements of the National Electrical Code. C. Jetline, Cat. No. 232, polyolefin pull line shall be installed in any empty conduits; readily accessible for future use. 16100 - 10 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS D. Roof penetrations shall be sealed and finished by a licensed roofing contractor. E. Provide redwood sleepers for conduit runs exposed on any roof. F. Threads on conduits and fittings shall be lubricated with a conducting and sealing compound approved by the field representative. G. Conduit shall be kept a minimum of 6 inches away from any hot water pipe, air duct, or any surface above 125 Degrees F. H. Conduits may be banked together, using Unistrut (or Equal) to obtain the beam effect for intermediate support or long spans. I. Conduit joints shall be made up tight and conduit unions shall be used wherever necessary. No running threads shall be permitted. J. Liquidtight, flexible conduit shall be used when flexible connections are required. (Metallic, flexible conduit shall be used in dry locations for recessed lighting fixtures). K. Installed conduits shall be temporarily plugged or otherwise protected, during construction, from the entrance of moisture and debris. Any conduit damaged, through neglect, shall be replaced by the Contractor without additional expense to the Owner. No kinked, clogged or deformed raceways will be permitted. L. Open knockouts or holes in boxes shall be plugged with suitable blanking devices. Boxes shall be cleared of debris before either the installation of any wiring devices, or before the installation of cover plates. M. The locations of boxes and fittings shall be in accordance with good installation practice, making them readily accessible for maintenance. Fittings with gasketed covers shall be installed with covers on the side or bottom. N. Rigid conduit, terminating in a cabinet or a pressed steel box, shall have locknuts and an insulating type bushing. O. Horizontal conduit runs outdoors with an elevation change greater than five (5) feet shall have a drain. P. Vents and drains shall be thoroughly cleaned to ensure proper operation. Q. The entire conduit system shall be fished, snaked, and cleaned before pulling in wires or cables. 16100-rev0 16100 - 11 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS R. 111.04 Electrical conduit shall not be installed on top, within or directly beneath roof decks. Special hangers shall be installed to suspend conduit below the roof deck so mechanical fasteners do not penetrate the conduit. PULL BOXES: Pull boxes shall be used to facilitate the pulling of wire and cable to ensure manufacturer's recommended pulling tensions and bending radii are not exceeded. Pull boxes shall be sized according to the National Electrical Code requirements, furnished with screw covers and accessible when the work is completed. The installation of a pull box in a public space, open to view, shall have prior approval by the Owner. 111.05 CONDUIT SUPPORT SYSTEMS: A. Conduits shall be rigidly supported so as to prevent excessive vibration or deflection. B. Conduit and conduit fittings shall not be welded to any structure. C. Conduits shall be spaced so that conduit fittings are accessible for pulling or splicing. D. Conduit supports shall be used to support conduits only. Conduit supports shall use Framing Channel clamped to building steel where feasible. No roof or roof pan penetrations are permitted for conduit supports. Refer to Appendices "H" and "J" for details. E. Supports of approved design shall be used in vertical runs of conduit as required by the National Electrical Code. F. Necessary supports for proper installation of all electrical equipment, raceways and cables shall be fabricated and installed in a neat and workman-like manner, and care shall be taken that at no time shall any portion of the building be overloaded. Building steel shall not be drilled or cut. Should the building structure or installation by any other contractor sustain damage through failure of this Contractor to properly support and install the electrical equipment, this Contractor shall bear all costs involved in repairing or replacing such installation. No welding will be permitted to any structure, piping, machinery, or equipment for mounting or support of electrical items unless specifically indicated on the drawings. G. Steel structures exposed to the weather shall be galvanized after all cutting, drilling and/or welding is done. Shop connections shall be bolted on outdoor structures. Where field cutting or drilling of galvanized steel is necessary, the Contractor shall apply one coat of priming paint and one finish coat of aluminum or oil paint. 16100-rev0 16100 - 12 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 111.06 16120 RACEWAYS - WIREWAY: A. Wireway shall be suspended above the floor, or from the ceiling, at elevations as indicated on the drawings. B. Wireway shall be securely supported at intervals not exceeding 5 feet, unless approved for greater lengths, but in no case shall these intervals exceed 10 feet. C. Installation of wireways shall conform to the National Electrical Code D. Installation of conductors in wireway shall be as shown on the drawings, but under no circumstances shall exceed the limits of the National Electrical Code, Article 362, Paragraphs 4, 5, 6 and 7. CONDUCTORS - MATERIAL 120.01 MEDIUM VOLTAGE CABLE - 5KV AND 15KV: A. General 1. Scope: a. This specification covers the requirements for single conductor, medium voltage cables used for 5KV and 15KV solidly grounded neutral systems. Cable shall be manufactured by Kerite, Okonite, or approved equal, and shall have copper conductors and EPR insulation. b. This specification shall be used to supplement all local, state, and national codes, laws, and regulations dealing with such materials and occupational safety and health. The more stringent requirement shall govern in cases of regulatory conflict. B. Cable Design 1. General Requirements: a. The cable shall comply with all applicable requirements of the latest Insulated Power Cable Engineers' Association (IPCEA) standards and the applicable sections of the latest issues of the Association of Edison Illuminating Companies (AEIC) publications, except as modified by this specification. b. The cable shall be suitable for use in wet and dry locations and in nonmetallic or metallic conduits. Insulation level shall be 133%. 16100-rev0 16100 - 13 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS c. The cable shall be able to operate continuously at 105 Degrees C conductor temperature; it shall have an emergency rating of 140 Degrees C and a short circuit rating of 250 Degrees C. d. Materials covered by this specification shall be subject to inspection by HGST. HGST's representative shall have access to the area where the cable is being manufactured and stored. e. An extruded semiconducting insulation screen shall be vulcanized to the insulation. Minimum average thickness shall not be less than 30 mils. The insulation screen shall be surface-printed: "Semi-conducting Remove when splicing and terminating." f. Metallic Shielding System: A 5 mil bare or tinned copper tape with a minimum overlap of 12.5% shall be applied over the insulation screen. In addition, #20 AWG bare solid copper wires per ASTM B3, each applied spirally with a layer of 8 times the core diameter, shall be applied over the copper shield. Provide a lapped nonmetallic tape over the shielding wires. Minimum jacket thickness required is shown below. Cable Size 4/0 AWG 250 kcmil 350 kcmil 500 kcmil 750 kcmil 1000 kcmil Jacket Thickness mils 14 16 17 18 20 22 g. Jacket: A protective extruded polyvinyl chloride jacket (black) shall be applied over the shielding system. The following average thickness shall be provided: Cable Size Up to 500 750 to 1000 Jacket Thickness (mils) 80 110 Minimum thickness shall not be less than 80% of the average thickness. The voltage class, type of insulation, conductor size, and date of manufacturing shall be printed on the jacket. 16100-rev0 16100 - 14 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS C. Factory Tests 1. General Requirements: a. HGST's representative shall be notified of any final factory test dates one week prior to tests. All final factory tests will be witnessed by an HGST representative unless otherwise directed. All cable shall be subject to factory tests made in accordance with IPCEA standard procedures as specified in IPCEA publication Nos. S-68-516 latest edition, except for the corona level test apparatus and procedures which shall be in accordance with AEIC publication 6-75, unless specifically waived in the contract document. b. Six (6) certified sets of factory test results shall be submitted to HGST representative prior to shipment of cable. 2. Specific Tests: The following factory tests shall be performed. The results shall meet or exceed the values listed here or shown in the reference IPCEA and AEIC tables. a. Conductor Resistance - The conductor resistance, corrected to 25 Degrees C, shall be less than the maximum value shown in S-68-516. b. AC High Voltage Test (entire reel) - The cable shall withstand the following voltages for a minimum of five minutes: 5KV cable 15KV cable ---- 16,000 Volts, AC ---- 33,000 Volts, AC c. DC High Voltage Test (entire reel) - The cable shall withstand the following voltages for a minimum of fifteen minutes: 5KV cable 15KV cable ---- 45,000 Volts, DC ---- 80,000 Volts, DC d. Corona Level Test (entire reel) - The corona discharge level for EP insulated cables shall comply with AEIC requirements. e. Insulation Resistance shall be measured and recorded in megohms per 1,000 feet and when corrected to 60 Degrees F, per IPCEA 68-516, paragraph 6.28, the Specific Insulation Resistance (SIR) shall not be less than 50,000 ohms. 16100-rev0 16100 - 15 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS f. Physical and Electrical Testing of Material Samples 1) Physical Dissection: A short sample shall be taken from each end of each shipping length (one sample will suffice at cutting points in a master reel) and shall be checked for (a) dimensional compliance, and (b) quality of cable components. 2) Insulation - Physical/Electrical Requirements: Die cut specimens shall be taken from the cable insulation. Insulation material shall meet requirements of attached Table "A" this section. 3) Semiconductive Screen: Resistivity The resistance of the semi-conductive screen material shall be measured as specified in AEIC Publication No. 675 the volume resistivity shall be less than 50,000 ohmcm at 90 Degrees C. Material shall be taken from the above samples. Adhesion On the same samples, the pounds of adhesion between the outer semi-conductive screen and the insulation shall be determined. A one-half inch wide strip of insulation/semiconductor shall be tested. Adhesion shall be between 4 and 18 pounds, when tested per AEIC No. 6-75. Physical Property The compound shall have a minimum elongation after an air oven test at 121 Degrees F for 168 hours of 100% and a brittleness temperature not warmer than minus 30 Degrees C. 4) 16100-rev0 Jacket - Physical/Electrical Requirements: Specimens shall be taken from the cable jacket. Jacket material shall meet requirements of Table "B" this section. 16100 - 16 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS D. Final Preparation 1. Pulling Eyes: Individual pulling eyes shall be installed on single or triplex conductor lengths of cable, after completion of the factory tests. Pulling eyes shall be suitable for maximum allowable pulling tension on the conductors, and shall be sealed against entrance of water. 2. Protection: Cable shall be adequately protected to prevent: (1) physical damage, and (2) entry of water and other foreign matter during shipment and outdoor storage. Cable ends shall be effectively moisture sealed with heat shrinkable plastic end seals. E. Guarantee-Warranty 1. Guarantee: The manufacturer shall guarantee that: (a) the material used, and (b) the construction of the cable is in accordance with this specification. Refer to Tables A and B for detail. TABLE A The insulation samples shall meet the following values: Unaged Physical Properties Tensile Strength, Minimum PSI at Room Temp. Elongation, Minimum % at Room Temp. 200% Modulus, Minimum PSI at Room Temp. 100% Modulus, Minimum PSI at 130 Degrees C Aged Physical Properties After Air Oven Tests for 168 Hours at 150 Degrees C Tensile Strength Minimum % of Unaged Elongation, Minimum % of Unaged Electrical Properties At Room Temperature (15.6 Degrees C), Dielectric Constant Specific Inductive Capacity (SIC): Maximum at 80V/mil Power Factory, PF % at 80V/mil, Maximum Insulation Resistance Constant (K) Minimum Electrical Properties at 90 Degrees C After 24 Hours Water Immersion, at 90 Degrees C: Dielectric Constant, SIC at 80V/mil, Maximum Power Factor, PF % at 80V/mil, Maximum Stability Factor, (PF at 80-40V/mil), Maximum After 26 Weeks Water Immersion at 90 Degrees C Dielectric Constant, SIC, at 80V/mil, Maximum 16100-rev0 16100 - 17 Ethylene Propylene 90 250 600 200 75 60 3.0 2.0 50,000 3.0 1.5 0.2 3.1 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS TABLE A The insulation samples shall meet the following values: Power Factor, PF % at 80V/mil, Maximum Stability Factor, (PF at 80-40V/mil, Maximum Moisture Resistance Mechanical Moisture Absorption After 7 Days in 70 Degrees C: Water Maximum mg/sq. in Cold Blend No Cracks at Temp. Degrees C (Insulation, Not Jacket) Hot Modules Deformation Resistance: After Air Oven Temp. Degrees C At Elongation % Conditioning Period Minimum Minimum psi Heat Distortion Maximum % (Buffed Samples of Insulation Taken in Close Proximity to Conductor Screen TABLE B The jacket samples shall meet the following requirements: Unaged Physical Properties Tensile Strength, Minimum PSI Elongation, Minimum % Aged Physical Properties After Air Oven Test: Temperature Degrees C Days Elongation - Minimum % of Unaged After Oil Immersion at 70% for 4 Hours: Tensile Strength, Minimum % of Unaged Elongation, Minimum % of Unaged Heat Distortion at 121 Degrees C Maximum % Heat Shock After 1 Hour at 121 Degrees C Cold Bend After 20 Hours at - 35 Degrees C 120.02 16100-rev0 1.5 0.2 5 Polyvinyl Chloride -40 130 100 15 200 5 Polyvinyl Chloride 1500 100 100 6 75 80 60 50 No Cracks No Cracks WIRE (600V INSULATION) A. Wire shall be UL listed and conform to the National Electrical Code Section 310. B. Wire from Size #10 and smaller shall be stranded copper, with THWN insulation, except as otherwise noted. C. Wire from Size #8 and larger shall be stranded copper, with THW insulation, except as otherwise noted. D. Wire for motor control circuits shall be #14 stranded, with MTW insulation for interconnections inside enclosures. Where control wiring is run in conduit, use THWN insulation. 16100 - 18 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 120.03 120.04 E. Wire in high temperature areas and in lighting fixtures shall be solid copper with THWN insulation. F. Manufacturer's name, insulation type, and voltage rating shall be permanently marked at regular intervals on all wire. WIRE - LOW VOLTAGE: A. Low voltage wire shall be Belden. B. Size and type shall be as indicated on the drawings WIRE CONNECTORS/TERMINATIONS A. Connections for #8 and smaller wire shall be with spring steel connectors, UL listed, as manufactured by 3M. B. Connections for #6 and larger wire shall be compression-type, UL listed, as manufactured by T&B, Burndy, or AMP. C. Uninsulated joints shall be insulated with Scotchfill and double wrap of Scotch 33+ tape, as manufactured by 3M Company. D. Terminal lugs shall be UL listed. Crimp lugs shall be applied with the manufacturer's recommended tools only. Mechanical lugs shall be torqued to the recommended torque. Lugs shall be used for one conductor only unless UL listed and identified otherwise. Lugs shall only be stacked if designed and listed for the application. 120.05 E. All lugs shall be ring tongue. F. Belleville-type compression washers shall be used when the ambient temperature exceeds 30 Degrees C. They shall be T&B catalog Series 60800, or equal. COLOR CODING: A. Color coding of branch circuit conductors shall be in accordance with the Nation Electrical Code requirements and shall be coded as follows: 208Y/120-Volt Circuits White or Natural Gray Neutral Black Phase A Red Phase B Blue Phase C Green Equipment Ground 16100-rev0 16100 - 19 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 480Y/277-Volt Circuits White or Natural Gray Neutral Brown Phase A Yellow Phase B Purple Phase C Green Equipment Ground Control Wires #1 Red for AC controls #3 Blue for DC controls 16100-rev0 B. Wire in Sizes not available in colors shall have colored tape of the appropriate color wrapped around them at areas where accessible. C. Color codes shall be maintained from wire origin to final destination for a given phase, including where wires pass through wiring devices. D. Color coding of branch circuit conductors for 240/120-Volt delta circuits shall be as follows (non approved or plant site, included for reference only): 240/120-Volt Circuits White or Natural Gray Neutral Black Phase A Red Phase B Orange Phase C Green Equipment Ground 16100 - 20 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 120.06 TAGGING AND IDENTIFICATION: A. All feeders, mains, and special circuits shall be tagged in pull box or panels in which they connect by means of non conductive, permanent tags. B. All conductors in panels, starters, pushbuttons, motors, junction boxes, lighting, branch circuits shall be identified by tagging with Brady Labels or equal. . 16121 CONDUCTORS - INSTALLATIONS and METHODS 121.01 INSTALLATION - MEDIUM VOLTAGE CABLE, 5KV AND 15KV: A. The Contractor shall make use of field engineering services furnished by the cable manufacturer. B. Cable shall be installed with a minimum number of splices. Proposed splice locations shall be submitted to HGST's representative for approval. C. The Contractor shall determine the cutting lengths, reel arrangements, and total lengths of cable required and shall furnish this data to the cable manufacturer prior to the required shipment date of cable. D Manufacturer’s recommended pulling tension and bending radius requirements shall not be exceeded. E. Cable pulling lubricant shall be approved by the cable manufacturer. The entire conduit system shall be fished, snaked, and cleaned with donut type brush before pulling in wires or cables. F. Special attention shall be given to prevent moisture from entering the cable during pulling; after cutting in manholes and during storage of cut cables on reels. Cable shall be sealed immediately after cutting by means of heat shrinkable plastic end seals. G. The cables shall be positively identified prior to splicing and terminating. 16100-rev0 H. Splicing and terminating work shall be performed by electricians having at least three years experience in this type of work. The name of these splicers and their experience shall be submitted to the Engineer for approval. I. The work area shall be kept warm, dry and ventilated, during splicing and terminating of cables. 16100 - 21 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS J. Material and/or splicing and terminating kits shall be as recommended by the cable manufacturer, supplying the cable. A submittal of materials shall be provided to HGST and approved prior to the actual work. K. Cables shall be spliced and terminated in accordance with the cable manufacturer's drawings or the kit supplier's drawings. L. Compression sleeves which excessively deform or otherwise damage the conductor shall not be used. Sleeves recommended by the cable manufacturer shall be used. M. Terminal connections shall be insulated as follows: N. 1. Completely fill in voids and cover terminal lugs to eliminate sharp edges with Scotchfill electrical insulation putty. 2. Apply a minimum of 7 layers of Scotch Tape #23, with a minimum overlap of 50%. 3. Finish with a minimum of 3 layers of Scotch Tape #33, each with an overlap of 50% Cables shall be phased prior to terminating and identified as follows: 1. Black plastic nameplates, with white engraved letters, shall be installed on each pull, splice, and terminating point. These nameplates shall show the phase, feeder designation and the date when the splice or termination was made. The feeder designation shall be as indicated on the drawings. Nameplates shall be tied on each cable with nylon cord. O. Exposed sections of new medium voltage cable installed on racks in manholes and switchgear vaults shall be fireproofed by wrapping with one half-lapped layer of Minnesota Mining and Manufacturing Co., or equal, #770 Irvington Brand arc-proofing tape and random wrapped with #27 glass cloth having pressure-sensitive adhesive. 16100-rev0 16100 - 22 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS 121.02 FIELD TESTING - MEDIUM VOLTAGE CABLE, 5KV & 15KV: A. B. General Requirements 1. New cables shall be tested prior to connections to equipment after terminations and splices have been made. 2. A DC high potential test has specified herein shall be made on each new cable using test voltages equal to 80% of the final factory DC test. Potential testing shall be performed in the presence of HGST's representative. The field potential test shall not be applied to potential transformers, switchgear, transformers, lightning arresters, or other equipment connected to the cable system. The entire cable, when splicing is completed, shall be tested at a test voltage to be determined by HGST's representative. Disconnect cables to be tested at the first point of termination, prior to any testing. 3. Any defective cable furnished and installed by the Contractor shall be replaced by the Contractor at no cost to HGST. Preparatory Step: 1. 2. Both ends of the cable shall be disconnected and free of all equipment. Adequate safety precautions shall be taken so that personnel cannot come into contact with either end during testing. Each cable shall be given a continuity test and identified with phase designation (A, B, C). 3. The cable ends opposite to the end on which the test set is going to be connected shall be completely sealed to prevent corona from forming at sharp ends of cable. (Wrap completely, tightly and without voids with "Scotch" Brand No. 23 Electrical Tape. 4. Shields shall be grounded to a common ground bus. 5. Connect high voltage lead of test set to the cable being tested and seal the connection to prevent corona from forming. 6. Cables not being tested shall be grounded to the same common ground as the shields. 7. Connect and set up the controls of the Hi-Pot tester as recommended by the test set manufacturer. 8. Make final safety check. a) Cable ends supported securely and hanging free of equipment. b) Ends are guarded and protected. 16100-rev0 16100 - 23 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS c) Grounds are secure. C. Test Voltage: Initial Acceptance Test Voltage (DC) a) 5KV cable initial test voltage shall be 36KV. b) 15KV cable initial test voltage shall be 64KV. c) If initial acceptance test is unsatisfactory, subsequent tests shall be performed at HGST's direction. D. Test Procedure: 1. A minimum of eight (8) steps should be considered to make a good graph. 2. Raise test voltage to first step slowly. a) There should be an initial charging which indicates that test set is properly connected. If there is a ground on the system, a high current will flow immediately and possibly the overload relay of the test set will open. b) Hold test voltage on initial step until current reading has dropped to the constant value. Record the time this takes on the test form. This decay time should be approximately the same for all test steps and should not exceed 30 seconds. 3. Raise test voltage slowly to start the second step. a) Repeat Step D2b above; leave test voltage on for same period of time as for previous step. b) Start plotting voltage versus leakage current on graph paper. NOTE: If curve indicates a definite knee in curve, discontinue any further testing. Find and correct fault and consult with HGST's representative on further testing. 4. Raise test voltage slowly to the next step; continue the increase in accordance with the predetermined steps until maximum test voltage is reached. Record the stable leakage current at each step ad at the maximum test voltage at tie zero. Record and interpolate readings. 5. Leave test voltage on for five minutes. a) Record and plot reading at end of 15 seconds. 16100-rev0 16100 - 24 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS b) Record and plot reading at end of 30 seconds. c) Record and plot reading at end of first minute, and every subsequent minute until the fifth minute is reached. If a questionable test is indicated, stop and correct fault. Consult with HGST's representative on further testing. 6. Reduce and remove test voltage from cable. a) DO NOT ground cable until voltage has reduced to less than 3,000 volts. b) Ground cable: The cable must be grounded for a sufficient time to ensure complete discharge. c) Remove high voltage test leads. NOTE: The total time for the direct current voltage test shall not exceed 15 minutes. 7. E. Repeat test steps for other cables. Test Report: Six (6) copies of complete test reports shall be forwarded to HGST's representative upon completion of the tests. Test reports shall show date of tests, circuit numbers, test voltages and leakage currents measured. 121.03 16100-rev0 INSTALLATION - 600-VOLT WIRE AND CABLE: A. Conduit and wireways shall be installed and thoroughly cleaned and dried prior to pulling wires. The maximum number of conductors in a conduit shall not exceed the values as allowed in the National Electrical Code. B. Wires and cables shall be pulled into their conduits by application of commercial pulling compounds. Pulling distance of wire and cable shall generally not exceed the equivalent of 200 feet of straight run or contain more than the equivalent of four 90 degree bends. Manufacturer's recommended pulling tensions and bending radii shall not be exceeded. Sufficient wire shall be left at outlets for connecting fixtures and wiring devices. When conduit bodies are equipped with lugs for possible future extensions, sufficient wire loop shall be left for this purpose. C. Conductors shall be continuous from outlet and no splices or joints will be permitted in either feeders or branches, except at outlets or accessible junction boxes, as indicated on the drawings. 16100 - 25 December 2004 SECTION 16100 ELECTRICAL - MATERIAL AND METHODS D. Conductors shall be colored coded as specified below. The color coding assigned to each phase wire shall be consistently followed throughout the entire job. E. Tagging and Identification F. 1. Feeders, mains and special circuits shall be identified in equipment in which they are terminated by means of nonconductive, permanent tags. 2. Conductors in panels, starters, pushbuttons, motors termination enclosures and junction boxes along with lighting and branch circuit conductors shall be identified by tagging with Brady Labels or equal. 3. Terminal blocks requiring numbers shall be identified by the Contractor with the designations shown on the wiring diagram in permanent type (not pencil or ink pen). 4. Contractor shall install tags clearly visible. Wire and Cable Splices Wire and cable splicing material manufacturer's instructions shall be followed. All splices and taps shall be made in accordance with the best craft practices and shall be mechanically and electrically equivalent to the wire or cable with which they are used. ***END OF SECTION 16121*** 16100-rev0 16100 - 26 December 2004