Document no. Z-8000-BB-4076
2005 BP Exploration UK
Z1 20/01/2005 Revised RL RL
C6 2/12/2004 Addition of 4 th WI pump RL RL
C5 19/12/2003 4 th WI pump study RL RL
C4 14/12/2001 Risk assessed
C3 9/3/2001
C2 28/12/00
Revised onshore
Revised Offshore
CD RL
C1
B1
A1
Rev
7/7/98
20/5/98
2/7/97
Date
Validated for Use
Issued for Review
Issued for Comment
Description
DH RL
DH RL
AS DH
CD RL
PS RL
CD RL
By Check By Check By Check
REVISION Originated Validated Risk Assessed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 1 of 158
1. 4 INTRODUCTION
1.1 Purpose of Equipment/System
1.2 List of Reference Documents
4
5
2.
3.
DESCRIPTION
2.1
2.2
Summary of Equipment
Water Injection Deaeration Package Z-44101
2.3 Water Injection Pumps P-45001A/B/C
2.3.1 Water Injection Pumps P-45001A/B/C Drive Motors 11
7
7
8
10
2.3.2 Water Injection Pumps P-45001A/B/C Lube Oil System 11
2.4 4 th Water Injection Pump Package 11
2.4.1 4 th Water Injection Pump Gas Turbine 13
2.4.2 GT Combustion Air Intake System
2.4.3 GT Combustion Exhaust System
2.4.4 Gearbox
2.4.5 Water Injection Pump P-45001D
15
18
18
19
2.4.6 Lubricating Oil System
2.4.7 Gas Turbine Enclosure
2.4.8 Gas Turbine Local Control Room & LER
2.4.9 Gas Turbine Enclosure Fire Protection System
2.4.10 Wash Cart
2.5 Water Overboard Discharges, Monitoring & Reporting
2.6 Chemical Injection
22
26
28
30
34
36
38
39
39
40
2.7 Turret Water Injection, Swivel and Turret Valves
2.8 Water Injection Flexible Risers
2.9 Subsea Water Injection System
2.10 WI Wellheads (Tree, Choke, Master & Subsurface Valves) 47
2.11 Well Injectivity Decline
2.12 Water Injection Subsea Flowlines
2.13 Water Injection Wells
WATER INJECTION SYSTEM CONTROL PHILOSOPHY
3.1 Deaerator Tower V-44101Control
3.2 Stripping Gas Regeneration Control
3.3 Water Injection Pumps P-45001A/B/C Control
3.4 Gas Turbine Control System
3.5 Water Injection Pump P-45001D Control
3.6 Subsea Water Injection Valve Control
50
50
51
53
53
54
55
56
59
60
4. WATER INJECTION SYSTEM & GAS TURBINE OPERATION
4.1 Pre-Start Checks
4.2 De-Aerator Package Purge Procedure
4.3 De-Aerator Package Start-up
61
61
62
63
4.4 Water Injection Pumps P-45001A/B/C Start-up 64
4.5 Solar Gas Turbine & Water Injection Pump P-45001D Start-up 67
4.6 Exhaust Gas Purging
4.7 4 th Water Injection Pump & Turbine Start-up from CCR
73
73
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 2 of 158
4.8 Gas Turbine Compressor Cleaning using Wash Cart
4.9 Routine Operations of the 4 th Water Injection Pump and GT
4.10 Subsea/Well Operating Limits
4.11 Water Injection Pump P-45001D Speed Control
4.12 Water Injection Pump P-45001D Standby Mode
4.13 De-Aerator & Pumps P-45001A/B/C Shutdown
4.13.1 Normal Shutdown
4.13.2 Emergency Shutdown
4.14 Water Injection Pump P-45001D & Turbine Shutdowns
89
4.14.1 Normal Shutdown or Trip Turbine to Idle Speed
4.14.2 Manual Emergency Stop
4.14.3 Control System Stops
4.14.4 Back-up Active Shutdown
4.14.5 GT Enclosure Fire Detection
4.14.6 Turbine Back-up Overspeed
4.15 Isolation for Maintenance
4.16 Winterisation
4.17 Video Display Computer Operation
5. CONTROL & MONITORING
5.1 Subsea Control & Monitoring
5.1.1 Interlocks
5.2 Control & Monitoring of Water Injection System
5.3 Monitoring of Pump P-45001D & Gas Turbine
6. ALARMS & SHUTDOWNS
6.1 De-Aerator HIPS
6.2 Pumps P-45001A/B/C Alarms and Actions
6.2.1 Pump P-45001A Alarms & Actions
6.2.2 Pump P-45001B Alarms & Actions
6.2.3 Pump P-45001C Alarms & Actions
6.3 Pump P-45001D & Turbine Local & Remote Alarms
6.4 Pump P-45001D
– Alarms, Actions, Shutdowns & Resets
121
6.5 Pumps P-45001A/B/C Shutdowns
6.6 ESD Actions & Valve Closure Sequences
6.6.1 Yellow ESD Shutdown
6.7 Design Parameters
6.6.2 Water Injection Pump Trip PSD
7. FAULT FINDING
7.1 Water Injection Pumps Malfunctions
7.2 Gas Turbine Malfunctions
7.3 Control System Malfunctions
7.4 Gas Turbine Acoustic & Filtration Package Malfunctions
APPENDIX A - VALVE POSITION TABLES
4 TH WI PUMP GAS TURBINE EXHAUST DISPERSION STUDY
75
77
83
85
86
86
86
90
91
91
92
94
95
95
95
95
96
97
97
98
99
100
109
109
112
112
115
118
126
129
130
131
131
132
133
133
134
134
134
137
144
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 3 of 158
1.1 Purpose of Equipment/System
As Schiehallion oil is produced, the space once occupied (reservoir voidage) is filled up by natural aquifers attached to the reservoirs, but not at a sufficient rate to maintain the required reservoir pressure/voidage replacement.
Produced water and seawater is therefore injected from the FPSO through subsea equipment to the wells to assist the natural drive. The aquifers provide edge drive from the west on Schiehallion and the North and West for
Loyal. Water injection minimises loss of productivity and increases Gas Oil
Ratio (GOR). All produced water is normally re-injected into the reservoirs.
However, de-aerated seawater is used as make-up feed to the water injection system to maintain production.
Three 13.8kV motor-driven water injection pumps each of capacity 630m 3 /hr pump water at high pressure (over 200 bar) to the subsea water injection wells. They are fed with a combination of produced water and de-aerated sea water, depending on well fluids BS&W, reservoir performance, process separation and operational requirements. To cater for the requirements of the future North West production centre water injection wells, a new Solar
Taurus 70 gas turbine-driven water injection pump has been installed of capacity 930 m 3 /hr. The turbine burns fuel gas from production.
The water injection system receives filtered seawater from the seawater distribution system and removes oxygen from this water to prevent contamination of the reservoir. The water injection pumps serve to drive the treated seawater and/or produced water into selected water injection wells.
Well fluids from the reservoirs contain entrained water that must be separated out, treated and disposed of prior to the oil being stored in the cargo tanks. If this produced water was not removed, the cargo would be adulterated with water, cause possible corrosion in the FPSO storage tanks, and be of unmarketable quality for export. Currently excess water is drained off at
Sullom Voe Terminal. Produced water production is expected to rise and plateau at 217,000 bbl/day (1438m 3 /hr) in year 15 of production.
The produced water system can process 225,000bbl/day (1490m
3
/hr) of produced water from the separation trains, with the facility to upgrade to
270,000bbl/day (1790m
3
/hr). Produced water is processed using hydrocyclones to 25 ppmv oil-in-water and is then injected into the reservoir with de-aerated seawater. Some may be discharged overboard if clean enough do so and if it cannot be re-injected.
The water injection system total capacity has now been increased to
2820 m
3
/hr following the addition of the 4 th Water Injection Pump.
The volume of water required for water injection is greater than the volume of produced water obtained from the production profile. A water injection rate of
1.1 times total fluid production rate is required, so de-aerated sea water is always used to supplement the produced water (the pumps are not designed to pump produced water only).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 4 of 158
All water injection valving within the turret system is manually operated with no associated automatic control.
Treated produced water is utilised for water injection into the reservoirs under normal operations. Two hydrocyclone trains reduce the free oil content of the main flow of produced water; a separate hydrocyclone being utilised for water from the test separator. Both streams of treated water are then comingled, de-gassed, and fed to the water injection pumps.
When any produced water is discharged overboard, it is cleaner than current legislation requires thus minimising pollution and maximising recovery of oil back to the process system.
The following drawings and documents have been referred to in the preparation of this System Operating Procedure.
L-8000-GF-0004.00
L-8000-GF-0104.00
UFD - Water Injection System
PFD - Deaeration Plant
L-1000-GP-0041.01
L-1000-GP-0041.02
L-1000-GP-0043.00
L-8000-GP-0044.00
L-8000-GP-0046.01
L-8000-GP-0046.02
L-8000-GP-0004.01
L-8000-GP-0076.03
M-5031-MA -8007.00
M-5021-GP-8004.00
S-9000-NP-9203.02
S-9000-NP-9220.01
S-9000-NP-9221.01
S-9000-NP-9213
S-9000-NP-9215
S-9000-NP-9216
S-9000-NP-9224
S-9000-NP-9225
S-9000-NP-9226
L-8000-JC-0002.024
L-8000-JC-0002.037
S-9000-GC-9200
Produced Water Degasser
Produced Water Booster Pumps
P&ID - Water Injection Deaeration Tower V-44101
P&ID - Compression & De-Oxidiser Vessels
Water Injection Pumps P-45001 A/B/C
P&ID - Water Injection Pumps Interfaces
SBM/B&R/ and B&R/H&W Interface P&ID
Seawater Distribution
12” Water Injection Swivel (Turret)
Water Injection P&ID (Turret)
Water Injection Tree (Type 1) sheets 1&2
Water Injection Tree (Type 2) sheets 1&2
Water Injection Tree (Type 3) sheets 1&2
P&ID - Schiehallion Central Manifold
P&ID - Schiehallion FPSO West Manifold
P&ID - Schiehallion FPSO Loyal/North Manifold
P&ID - Schiehallion Loyal Manifold
P&ID - Schiehallion West Manifold
P&ID - Schiehallion North Manifold
Process CPS Cause and Effect WI System
Process CPS Cause & Effect Chemical Injection
Subsea/Wells Cause and Effect
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 5 of 158
Solar Turbine
Operator’s Guide, Volumes 1&2
Solar Turbine Data, Volumes IIIA, B & C
Solar Turbine Illustrated Parts List, Volume IV
Veritec Engineering, O&M manual for the LER
Sulzer Pumps O&M manuals, Volume 1, 2 & 3
WG Process Design Report, Volumes 1&2
Renk operation and maintenance instructions
Gas Turbine Filtration and Acoustic Package –
Installation and Maintenance manual, Altair Filter
Technology
GT Driven 4 th WI Pump Project Wood Group
37W022F0146/P/OP/000
7/000
Z-8000-BB-4001
Z-8000-BB-4007
Z-8000-BB-4051
Z-8000-BB-4052
Z-8000-BB-4054
Z-8000-BB-4057
Z-8000-BB-4035
Z-8000-BB-4023
Z-8000-BB-4077
Z-8000-BB-4029
Z-8000-BB-4012
Plant & Instrument Air Systems
Chemical Injection Systems
Methanol System
Nitrogen Generation & Distribution
Produced Water System
Seawater Circulation Systems
Fuel Gas System
Non-Haz Open Drains Collection System
Fresh Water System
Flare Systems
Cooling Medium System
Training and Competency in understanding this system is covered by documents Z-8000-BQ-4176/4276 which include questions and answers on the system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 6 of 158
The following table provides data on equipment in the water injection system:
Equipment
Water Injection
Deaerator Tower
V-44101
Water Injection Stripping
Gas Blowers P-
44201A/B
Stripping Gas
Exchanger
X-44201
Stripping Gas
De-oxidiser Vessel
V-44201
Start-up Heater
EEH-44201
13.8kV 5200kW Motordriven Water Injection
Pumps P-45001A/B/C
Gas Turbine-driven
Water Injection Pump
P-45001 D
Gear Box
Solar Taurus 70 gas turbine (burns fuel gas)
Wash Cart
Rating Location
Seawater Flow - 2250 m 3 /hr
Operating Pressure - 5 barg
Height - 15m
Diameter - 3.1m increasing to 4.2m
5 barg inlet - 6.4 barg outlet
Motor rating 55 kW
356 mm OD x 5180 mm
Shell side - 5.7 barg
Tube side - 6.4 barg
1200 mm OD x 3000 mm
187 mm x 1780 mm
Power - 20 kW
Max capacity 750 m 3 /hr (each)
Differential Pressure - 202 bar
(dependent on start-up DP or normal running DP)
Capacity 3 x 33%
Normal Case (100% Speed) 930 m 3 /hr
Package Z-44101
Fire Zone 201
(Port Aft)
Package Z-44101
Fire Zone 201
(Port Aft)
Package Z-44101
Fire Zone 201
(Port Aft)
Package Z-44101
Fire Zone 201
(Port Aft)
Package Z-44101
Fire Zone 201
(Port Aft)
Packages
Z-45001A/B/C
Fire Zone 251
(Starboard Aft)
Overspeed Case (105% Speed) 1150 m 3 / hr.
Installed forward of the aft Crane pedestal at frame 40
(Palette 7)
Fire Zone 258 Differential pressure: 202 Bar
(Dependant on the start-up DP or
Normal Running DP)
Rated for 6910 KW
Input Speed 11051 RPM
Output Speed 3650 RPM
Can be run continuously 5% above the rated speed.
6700-7800kW, depending on ambient temperature
Palette 7
Palette 7
Tank Capacity: 100 litres
Operating Pressure: 6.9 barg
Operating Temperature: Ambient
Design Temperature: 93.3 C
Design Pressure: 9 barg
Size (DxL): 0.406m x 0.483m
Palette 7
Table 1 Water Injection System Equipment Data
Note:
Information given in this document does not include details of the new
North-West drill centre.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 7 of 158
Refer to P&ID L-8000-GP-0043.00
.
Z-44101 de-aerates seawater to an oxygen content of below 20 ppb prior to the seawater being injected into the reservoir. The de-aeration package is based on ‘Minox’ technology and uses nitrogen stripping gas to remove oxygen from the seawater. Oxygen is subsequently removed from the stripping gas using a catalytic de-oxidising process. This system was selected in preference to the more normal vacuum deaeration systems as the ‘Minox’ column operates with a single stage of packing which leads to a lower column height. The height of the column was a concern due to its location adjacent to the helideck. Alternative designs all had columns which were above helideck elevation.
The system uses conventional counter-current flow (stripping gas against seawater) within a compact deaerator tower which contains structured packing to promote contact between the nitrogen and seawater. The oxygen-contaminated stripping gas leaves the tower and passes through blowers and a heat exchanger before being purified (i.e. its oxygen removed) through a catalytic reaction with methanol vapour. The purified stripping gas is then recycled to the deaerator tower. The de-aerator package comprises:
water injection de-aeration tower V-44101
water injection stripping gas blowers P-44201A/B
stripping gas exchanger X-44201
stripping gas de-oxidiser vessel V-44201
start-up heater EEH-44201.
Seawater is supplied to V-44101 from downstream of the cooling medium coolers X-81501A/B/C. The seawater is normally supplied between 22
C and
27
C with a minimum supply temperature of 5
C and a maximum supply temperature of 33
C (design temperatures. -10/+50
C). The oxygen content of the seawater entering de-aeration is approximately 10 ppm.
Seawater enters V44101 via an 18” line at the top of the tower after passing through the inlet flow control valve. Seawater leaving V-44101 is normally routed to the water injection pumps P-45001A/B/C/D. In the event that the seawater demand of P-45001A/B/C/D is low, seawater from V-44101 is routed overboard via the overboard dump valve.
Seawater entering V-44101 falls under gravity through a distributor and a bed of structured packing, and exits at the bottom of the tower before being routed the water injection pumps. Over-pressure protection of V-44101 is provided by PSV-441005 or PSV-441006 (set at 10 barg) which relieve to a safe location.
The deaerator is protected by a HIPS system which shuts the seawater inlet valves XXV-441040 and XXV-441002 on high vessel level, initiated by
LAHH-441013 and LAHH-441014.
Note: A HIPS system is required on the deaerator as the vessel relief valves are not designed for full seawater flow relief.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 8 of 158
The water passes down through the tower and mixes with a counter-current flow of stripping gas (nitrogen) fed into the tower at a mid-vessel point, below the packing column. The stripping gas absorbs oxygen contained in the seawater and then passes through a demister in the top of V-44101 before leaving the tower via a 6” line. Nitrogen is supplied to the deaerator tower at a flow of approximately 4,900 kg/hr. As the nitrogen passes through the tower packing, some of it is dissolved in the seawater and, therefore, there is a requirement to add nitrogen to the system to maintain the required stripping gas flowrate. In addition, to achieve the required oxygen concentration in the stripping gas, so as to maintain reactor efficiency, more oxygen must be added. The required nitrogen and oxygen make-up is achieved by using a combination of instrument air and nitrogen top-up lines.
Refer to P&ID L-8000-GP-0044.00.
Stripping gas is drawn off from V-44101 by the water injection stripping gas blowers P-44201A/B, which are rotary lobe, positive displacement type blowers. P-44201A/B are each fitted with their own single dedicated safety relief valve (PSV-442003 and PSV-442006 respectively) which have a setpoint of 10 barg and relieve to a safe location. P-44201A/B operate in duty/standby mode with auto-start of the standby blower initiated by the low flow alarm FAL-442008. P-44201A/B cannot be started until a normal operating level (i.e. flow and level healthy) is established in V-44101.
On leaving the blowers, the stripping gas passes through the tube side of the stripping gas exchanger X-44201 where it is pre-heated against stripping gas returning from the stripping gas de-oxidiser vessel V-44201.
Stripping gas from X-44201 enters the de-oxidiser vessel V-44201. The temperature of the gas entering V-44201 is controlled by TIC-442014. The gas flows downwards into a de-oxidiser catalyst bed in which is embedded the electric start-up heater EEH-44201. The catalyst is palladium pellets on an aluminium oxide core supported on a perforated plate.
To create the catalytic effect in V-44201 which is required to purify the nitrogen, methanol is added, as a fuel, to the stripping gas. This is injected as a side stream into the main stripping gas flow at an entry point upstream of the reactor V-44201. The catalyst within V-44201 needs to achieve a threshold temperature before the required catalytic reaction can take place.
The catalyst bed is pre-heated by EEH-44201 to this threshold temperature of
150
C. Once this temperature is achieved then the power supply to the start-up heater is shut-off as the resulting reaction within V-44201 is an exothermic reaction during which temperatures of 240
C to 260
C may be produced. Stripping gas leaving V-44201 is virtually oxygen-free (i.e. oxygen content below 20 ppb).
Stripping gas from the bottom outlet of V-44201 passes through the shell side of X-44201 and returns (via the restriction orifice RO-442022) to the deaerator tower, forming a closed loop for the circulation of stripping gas.
The gas path through the shell side is protected by a single relief valve
PSV-442011 (set at 10 barg) which relieves to a safe location.
Some of the stripping gas in the tower is dissolved in the seawater.
Additionally, the stripping gas oxygen concentration may fall below that required to maintain reactor efficiency. Nitrogen make up is supplied via
XV441024 on the 2” feed line from the nitrogen distribution system.
PIC-441021 on the deaerator outlet line controls nitrogen top-up via
PCV-441023 or vents to safe location via PCV-441021.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 9 of 158
Seawater as Deaerator Oxygen Scavenger Carrier
When oxygen scavenger injection is needed to reduce the oxygen content of the injection water, produced water taken from downstream of the booster pumps is used as the normal oxygen scavenger carrier. There are situations, however, when it may be necessary to inject oxygen scavenger into the deaerator and if there is either no, or insufficient, produced water available.
This will occur during early production before the produced water cut increases, on de-aeration system start-up and also during seawater injection, when the separation trains are down. A facility has therefore been included to substitute deaerated seawater as the carrier by routing seawater into the degasser from the outlet of the deaerator.
The manually-operated crossover line 2”-WI-450010-A10B is designed to transfer water from the discharge of the deaerator to the inlet line of the degasser. The rate is controlled by the manual globe valve downstream of
XV-540010, which will pass about 30 m 3 /hr when fully open. The scavenger carrier, (pumped in this mode by a single produced water booster pump), and taken from upstream of LCV430010B via 2”-PW-441006-A01B, has a rate set at 15 m 3 /hr, controlled by RO-441029. The globe valve should be set such that deaerated seawater accumulates in the degasser.
Refer to P&ID L-8000-GP-0046.02
.
3 x 33% Water Injection Pumps P-45001A/B/C are fed with a combination of de-aerated seawater and produced water.
The Sulzer 13.8kV 5200kW electric motor-driven water injection pumps take suction from deaerator V44101; or from produced water booster pumps P-
43001A/B/C and filters F-43001A/B via a 24” common inlet. The injection pumps then discharge via the oxygen analyser AT450020 into a common 16” line which reduces to a 12” prior to entering the turret and turret swivel N-
45080. Downstream of the turret, the water flows to a 12” water injection manifold and then down
10” flexible water injection risers. Subsea distribution routes the water to the water injection wells. The number of WI pumps in service is governed by the number of injection wells being fed.
If any of the injection pumps supply more water than can be injected subsea, the excess will be discharged overboard via minimum flow dump valves
FCV450145/245/345 (fitted to each pump A, B, C) through a common 10” overboard discharge with vent. There is no flow monitoring or sampling on this common line.
Each pump’s discharge pressure will depend upon the pumped fluid density, and this in turn varies both with the different proportions of seawater and produced water and with temperature. The expected pump performance may be calculated as follows:
P in bar = Head (m) x water density (kg/m 3 ) x 9.81/1 x 10 5
During seawater-only injection at a normal temperature of 22
C, the pumps could generate 246 barg at 750 m 3 /hr. Currently, the nominal output from each pump is 630m 3 /hr. The pump performance curves and associated documentation show two duty points. The higher head duty point is indicative of an early field life case when there are only a few injection wells and the water injection requirement has not peaked.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 10 of 158
However, even for low injection water demand at the wells, a significant flow is required through the pump to reduce the system pressure and minimise the peak pressure which may be obtained due to pressure surge/locked-in pressure due to inadvertent wing valve closure. This is accomplished via a high set point for the minimum flow FCVs. At full capacity, the system is set up with four pumps operating. It is advantageous to inject as much water as possible into the reservoir and therefore no standby or auto-start operating mode is provided. The system can, however, be configured with any number of pumps (1, 2 ,3 or 4) as running duty pumps.
2.3.1 Water Injection Pumps P-45001A/B/C Drive Motors
Each water injection pump A/B/C is driven by a 13.8 kV electric motor
PM-45001A/B/C rated at 5200 kW and fed from the main switchboard
ESW-83401. Each motor winding is cooled by air circulation to vent using a
GEC Purgepak system. A heat exchanger cools the circulated air and is fed by water from the cooling medium system. High winding temperature is indicated locally. A casing high-level alarm and an anti-condensation heater are also fitted.
2.3.2 Water Injection Pumps P-45001A/B/C Lubricating Oil System
The water injection pump support and thrust bearings, together with the drive motor bearings, are lubricated by a self-contained lubricating oil system, integral with each unit. Oil is supplied by a main shaft-driven pump, backed up by a motor-driven auxiliary lubricating oil pump P-450100/200/300.
Lubricating oil is stored in a lubricating oil tank fitted with heater and level and temperature indicators. The auxiliary lubricating oil pumps are sited within the tank and supply oil to the bearings on starting. These pumps are automatically stopped when the shaft-driven pumps P-450101/201/301 supply sufficient lube oil pressure. Excess pressure flows back to the sump via
PCV-450137/237/337.
Oil flows through oil cooler X-450100/200/300 to lube oil filters A & B and
PCV-450138/238/338 and then to the bearings. Low oil pressure, high oil temperature, oil filter high differential, and high pump bearing alarms are indicated at the local control panel in the Aft Equipment Room. Sight glasses show oil flow back to the lube oil tank.
th
Currently, three 13.8kV motor-driven water injection pumps each of capacity
630m 3 /hr pump high pressure water (over 200 bar) to the subsea water injection wells. They are fed with a combination of produced water and deaerated sea water, depending on well fluids BS&W, reservoir performance, process separation and operational requirements.
To cater for the requirements of the North West production centre water injection wells, a new Solar Taurus 70 gas turbine-driven water injection pump has been installed forward of the aft Crane pedestal at frame 40 in Fire
Zone 258, fuelled by fuel gas. This is fitted with a 900mm exhaust discharging at an elevation of 55m and pointing forward at an angle of 10
above horizontal, thus creating minimal impact on Helideck operations. The output of the new engine is 6700-7800kW, depending on ambient temperature. The forward-pointing exhaust directs gases away from the
Helideck and the elevation eliminates any problems with hot gases on the
Crane boom.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 11 of 158
Figure 1 4 th Water Injection Pump Package – Plan View
The blast wall (capacity 0.5 bar) is not affected by the installation of the gas turbine-driven water injection pump. The fuel gas supply to the skid is high on the starboard outboard side, allowing any potential leaks to be dispersed away from the FPSO. High integrity joints have been used to connect the minimal number of pipe sections.
Further details of the 4 th Water Injection Pump exhaust dispersion arrangements can be found in the 4 th Water Injection Pump Gas Turbine
Exhaust Dispersion Study (enclosed at rear of this document).
Water injection pump P-45001D is a gas turbine-driven pump using a Solar
Taurus 70 as the driver and operates in parallel to the existing three electric driven water injection pumps P-45001A/B/C. The pump suction line is connected from the existing water injection suction manifold and the discharge line is connected to the existing water injection discharge line to the turret. Injection water supplied to the 4 th water injection pump suction is a mixture of seawater and produced water.
The three electric-driven water injection pumps P-45001A/B/C were designed for a capacity of 2025 m 3 /h and the new water injection pump P-45001D is designed for a capacity of 930 m 3 /h normal operating case and 1150m 3 /hr overspeed case. The total designed maximum water injection capacity is now
2955m3/h (444,500 bbl/day).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 12 of 158
The 4 th water injection package & system comprises:
1. 4 th water injection pump gas turbine
2. combustion air intake system
3. combustion exhaust system
4. gearbox
5. water injection pump
6. lubricating oil system
7. gas turbine enclosure
8. 4 th water injection pump gas turbine LCR & LER
9. CO
2
deluge system
10. wash cart.
2.4.1 4 th Water Injection Pump Gas Turbine
The 4th water injection pump driver is a Taurus 70S gas turbine which contains the following main components:
Accessory Drive Gear box
Air inlet plenum
Axial flow compressor
Annular Combustor with Fuel Injectors
Two Stage Gas Produce Turbine / Two Stage Power Turbine
Exhaust Collector
Output Drive Shaft to Gearbox and 4 th Water Injection Pump.
The gas turbine is mounted on a steel base frame. The accessory drive is attached to the air inlet assembly and is driven by the gas turbine’s axial compressor. This then supports and drives the lube oil pump and other accessories, which are initially driven by the start system. The turbine speed is directly related to the engine power level due to its two-shaft engine configuration and is electronically adjusted. Air enters the air inlet and is compressed by the 12-stage axial flow compressor. Pressurised air in the annular combustion chamber is injected with fuel and the mixture is ignited during the start cycle.
Figure 2 4 th Water Injection Pump Package – Looking to FPSO Port Side
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 13 of 158
If there is a sufficient flow of pressurised air the burning of fuel is maintained.
Hot pressurised gas from the combustion chamber expands and drives the turbine. As it exits the chamber its pressure and temperature drop.
Approximately a quarter of the total air compressed is required to completely combust the fuel. Excess air is used to cool the combustion chamber and mixes with the combustion products to reduce the gas temperature downstream at the inlet to the first stage turbine. The gas turbine is supported by the following auxiliary equipment:
Start System
Fuel System
Electrical Control System
Lube Oil System
Engine drain system
Acoustic and Filtration Package
Gas Turbine Start System
The start system consists of an AC direct start system, which includes a starter motor with variable frequency drive. It provides the torque to initiate rotation and enables the engine to reach a self-sustaining speed, after which the starter shuts down, the starter clutch overruns and the engine is able to accelerate under its own power to loading speed.
The starter motor (B330) is a squirrel-caged induction 15-minute inverter duty, polyphase-type motor which can accelerate the engine from standstill to starter dropout speed. The motor power is provided by the variable frequency drive (VFD430). This motor speed controller operates on 380-460V AC 3phase power at line frequencies of 48-62 Hz. It is rated at 231 amps
(maximum) and incorporates a keypad/display, which can be used to program configuration adjustments through software. When the start cycle is initiated a timed pre-lube sequence is activated. On expiry of this the control system directs power to the variable frequency drive, which provides power to the starter motor.
A low frequency and voltage is generated which begins rotation. The frequency and voltage are then ramped up to accelerate the engine to purging speed which is maintained by a programmed fixed current. Once purged, the engine coasts down to light-off speed. When light-off speed is detected the VFD430 is re-energized and it increases the motor velocity to starter drop-out speed. VFD430 is then deactivated by the control system, cuts power and the motor clutch is disengaged.
Gas Turbine Fuel System
The fuel system controls the fuel pressure and automatically regulates the fuel flow according to operating requirements in conjunction with the control system whilst the air system automatically schedules fuel for flow during the engine acceleration and load operation. Over-temperature and overspeed topping control of fuel flow and automatic shutdown is also provided by the fuel system, which comprises:
Gas fuel metering and control
Instrument air for the operation of the pilot-operated shutoff valves
SoLoNOx low-emissions system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 14 of 158
Before the engine cranks a valve check sequence is performed to confirm that the shut-off valves are operational. If the shut-off valve malfunctions, the control system initiates a valve failure and aborts the start cycle.
Once the valve check is complete the purge crank cycle is initiated; this removes all combustibles from the engine exhaust system. The start system cranks the engine and creates air movement through the exhaust system.
The purge crank cycle timer is programmed to correspond to the package exhaust system volume.
Following this, gas flows through the torch and is ignited in the presence of combustion air. The torch flares in to the airflow in the engine combustion liner. Equally-spaced fuel injectors mix fuel in the air stream and in the combustor liner. The torch then ignites the fuel/air mixture and the engine temperature increases rapidly. The control system increases fuel flow and consequently increases the engine temperature and the engine speed. When the engine speed reaches approximately 60-65%, the start system is deenergized. The engine continues to accelerate and the inlet variable vanes move toward the fully-open position. The compressor bleed valve also closes, which increases the engine temperature further. The control system then increases the fuel supply until the engine speed reaches 90% at which point the engine is ready for load.
Once the system is at 50% load and the engine speed is above 88% the fuel system transfers to the SoLoNOx mode. The inlet variable vane position, fuel flow and compressor bleed valve position are adjusted by the control system to maintain the engine temperature.
If the engine temperature exceeds the preset limit, a 20 second time delay is imposed. If the engine temperature remains above this limit, a high temperature alarm is initiated which shuts down the engine. A time delay is incorporated to allow for momentary over-temperature. If the temperature shutdown timer fails and the turbine temperature increases further, a backup high temperature circuit initiates engine shutdown.
2.4.2 GT Combustion Air Intake System
Air enters the engine through the air inlet plenum. Air through the annular opening is redirected from the radial flow path to an axial flow path. A heavy mesh screen minimises the entry of the large solid foreign material in to the engine compressor air inlet.
A Variable Inlet Guide Vane (IGVs) system is provided to avoid compressor surge and to maintain maximum engine performance over the full gas producer range. The variable vane control positions the angle of IGVs and the variable stator vanes (VSVs) of the first five compressor stages as a function of corrected gas producer speed (NgPcorr). This is done to aerodynamically match the effect of the air density changes over the -40 o C to 60 o C range of the compressor inlet temperatures.
The variable vane system uses a slave cylinder positioned by a hydraulic positioner connected to the engine ’s actuator arm. The positioner’s electronic control signal has a range of 4mA fully closed to 20mA fully open. If the electrical signal is lost, the IGVs and the VSVs move to a closed position
(minimum variable vane angle).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 15 of 158
Acoustic and Air Filtration Package
To ensure clean air is supplied to the turbine (and to reduce noise surrounding the gas turbine) an acoustic and filtration package is employed.
The acoustic and filtration package (designed and manufactured by Altair
Filter Technology Ltd) is a modular system and is made up of the following major system components:
Combustion Intake System -Mini Module
Gas Turbine Enclosure
Gas Turbine Enclosure Ventilation System
Combustion Exhaust System -Mini Module
Electrical / Instrumentation / Fire Protection System
Structural Steelwork and Access Facilities
Lube Oil Pipe work assemblies
The system is designed to withstand the following conditions:
High wind speed
Wind strength changes & gusting
Chloride attack by the atmosphere
Turbine process conditions
Thermal growth
Static & installation loading
The filtration system provided is an Altair System High Efficiency Filtration package and comprises 4 stages:
1st stage - Marine Vane Separator and Snow Hood
2nd stage - PBR pre filter (12)
3rd stage - HVX bag filter (12)
4th stage - Vane Separator
A manometric drain system is provided for the 4th stage vane separator and the housing drains.
1st stage - Marine Vane Separator and Snow Hood
The function of the Marine Vane Separator is to reduce the quantity of driving rain or heavy spray which may otherwise enter the intake under adverse weather conditions. A snow hood is fitted prior to the 1st stage separator to provide protection against driving snow.
The vane stage comprises stainless steel vanes held apart by spacers. The high inertia of the water droplets causes them to be thrown out of the air stream onto the vanes. The droplets collected on the vanes are then drained down into the drain trough situated at the base of the vanes. Drain slots are provided in the bottom of the separator for self-draining
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 16 of 158
2nd Stage – Pre-filter Bag Type PBR
The Altair PBR Cleanable Prefilter bag is a synthetic bag filter designed to retain large particles of dust and hydrocarbons which may enter the intake.
The PBR prefilter bags make up the first stage of filtration and fit into a 316grade stainless steel holding frame. The PBR pre-filter has 4 polyester pockets which fit inside the HVX high efficiency filter located immediately behind.
3rd Stage - High Efficiency Filter Bag Type HVX
The Altair HVX bag is made up of two layers of filter media, is disposable and should not be washed. The initial layer is an open-density polypropylene filter mat which stores the majority of the dust collected. The final filter is a highdensity polypropylene filter material which captures the smallest particles.
The HVX bag also acts as a coalescer and collects fine salt particles in the airstream. The aerosol salt which enters the bag is coalesced into larger droplets which either drain away or are re-entrained into the air stream and removed by the vane separator downstream of the filter bags. The two layers are made up into individual pockets and fitted into a stainless steel frame, which fits into the holding frame.
4th Stage - Vane Separator
The purpose of the Vane Separator is to intercept droplets re-entraining from the upstream stages under conditions of high humidity. The water droplets collected on the stainless steel vanes are drained down through pockets into a drain trough situated at the base of the vanes and then flow into the drain system
Drain System
The drain system removes any water caught within the air intake from:
The filter access housing
The interspace between the 3rd stage filter and 4th stage
The 4th stage - vane separator
No drainage is required between the 2nd and 3rd stage filter. Drains are fed into a drain trap, which allows drainage but prevents air being sucked into the drain system by the provision of a water seal.
Intake Silencer and Transition
The intake silencer and transition provide acoustic attenuation for the combustion intake to the gas turbine. The silencer comprises a series of vertical splitters and a lined duct which reduces external noise levels. The intake silencer can only be inspected internally during engine shut down and via the personnel access panel in the gas turbine collector duct.
Intake Elbow & Flexible Intake Silencer
The intake elbow is lined for acoustic attenuation and turns the combustion intake air through 90 degrees into the silencer. The system ensures an even distribution of air at the inlet to the flexible intake silencer which directs clean air into the turbine inlet. A weather seal and acoustic bolster is fitted around the interface within the acoustic enclosure.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 17 of 158
2.4.3 GT Combustion Exhaust System
The combustion exhaust system consists of a diffuser duct connected to the enclosure exhaust flange and has a support mechanism to allow for thermal growth of the duct section. A high temperature flexible compensator is fitted between diffuser duct and exhaust silencer. The compensator is designed to accommodate lateral, radial and axial movements set up by the hot gases discharging through the exhaust volute into the exhaust system.
The ducting system above the silencer is routed to suit the adjacent equipment and crane location and a 90º elbow diverts the exhaust gases to a safe location.
The exhaust collector receives the axial flow of exhaust gases from the exhaust diffuser and turns them in a radial direction. The exhaust collector and most other external areas that have high temperature surfaces are covered with an insulating stainless steel blanket to minimize heat rejection and to cover exposed surfaces.
2.4.4 Gearbox
A Renk gearbox is located between the turbine and the WI pump:
Rated Power: 6910 KW
Rated Speed:
Input: 11051 rpm
Output: 3650 rpm
Maximum Continuous Speed:
Input: 11604 rpm
Output: 3832 rpm
The gearbox can be run continuously 5% above the rated speed (overspeed design case for the pump) and has a mechanical efficiency of 98.7%.
Measuring and control instruments include:
Insufficient oil pressure at the gear unit inlet
Excessive oil temperature at gear unit oil inlet
Failure of the oil pump
Excessive bearing temperatures
Excessive shaft vibration
Oil enters the system on the suction side of the oil pump via a filler neck. The oil system must be operating before the gearbox is started and once it is stopped the oil pump must remain running until the unit has come to a complete standstill. A separate auxiliary pump is available during start-up and shutdown to ensure enough oil is supplied. This pump remains operating until the gearbox has reached nominal speed or until it has come to a complete standstill during shutdown.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 18 of 158
2.4.5 Water Injection Pump P-45001D
Refer to P&ID L-8000-GP-0046.03. This section is to be read in conjunction with the earlier text describing WI pumps P-45001A/B/C. P-45001D is fed with a combination of de-aerated seawater and produced water from a common suction line feeding the motor-driven water injection pumps, P-
45001 A/B/C. The pump then discharges into a common 16” line, which receives water from pumps P-45001A/B/C. The flow control valve FCV-
450445 protects the pump if the flow drops below a set value. The valve discharges any excess water overboard through a com mon 10” overboard discharge.
Pump Discharge Characteristics
The GT-driven pump discharge pressure depends not only upon the pumped fluid density, but also on the speed of the gas turbine. The expected pump performance may be calculated as follows:
P in bar = Head (m) x water density (kg/m 3 ) x 9.81/1 x 10 5
During seawater-only injection mode and at a normal temperature of 22
C, the GT-driven pump P-45001D can generate 222 barg at 745 m 3 /h, when two out of three electrically-driven pumps P45001A/B/C are in operation. The total injection capacity in this mode will be 1890 m 3 /h.
During combined Seawater and Produced water injection mode and at a normal temperature of 22
C, P-45001D can generate 207 barg at 930m 3 /h.
The total injection capacity in this mode will be 2955 m 3 /h.
P-45001D can also operate in an overspeed mode, when it can generate 207 barg at 1150 m 3 /hr.
Note:
The GT-driven pump can be run either with combined seawater and produced water or with seawater only. It is not designed to run with produced water alone.
Graph 1 overleaf shows pump discharge pressure as a function of pump speed and flow rate, based on a suction pressure of 5.5 bara.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 19 of 158
PUMP DELIVERY PRESSURE
300
250
200
150
100
50
0
200 400
3833 RPM
3200 RPM
2250 RPM
Pump Speed Characteristics
600 800
FLOWRATE M3/H
3650 RPM
3000 RPM
TRIP-PRESSURE
1000 1200
3400 RPM
2750 RPM
The expected flow, head and power as a function of speed can be calculated as follows:
Q
NEW
= New Flow Rate, Q
OLD
= Old Flow Rate
Head
NEW
= New Head, Head
OLD
= Old Head
Power
NEW
= New Power, POWER
OLD
= Old Power
N
NEW
= New Speed of pump, N
NEW
= Old Speed of pump
The relationship for flow rate:
Q
NEW
= Q
OLD
*
N
NEW
N
OLD
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 20 of 158
The relationship for pump head:
HEAD
NEW
= HEAD
OLD
*
N
N
NEW
OLD
2
The relationship for power:
POWER
NEW
= POWER
OLD
*
N
NEW
N
OLD
3
The minimum flow rate for the pump is 330m3/h. When the pump discharge pressure exceeds 260barg, the pump will trip on high pressure.
Graph 2 below shows required power from the gas turbine as a function of speed and flow rate. The turbine has a power limit of 6755 kW at 23 o C.
Note: If low ambient temperatures are experienced the power limit increases,
Sulzer have specified a maximum overspeed power limit as 8075 kW.
9000
8000
7000
6000
5000
4000
3000
2000
1000
0
200
3833 RPM
3400 RPM
3000 RPM
2250 RPM
400 600 800 1000 1200
FLOWRATE M3/H
3650 RPM
3200 RPM
2750 RPM
POWER LIMIT @ 20 Deg C
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 21 of 158
Graph 3 below shows turbine power as function of air temperature. As the air temperature drops, more water can be injected in the wintertime. The turbine is designed for a maximum air temperature of 23 o C.
The pump design speed is 3650 rpm
Pump overspeed is 3833 rpm
Pump idle speed is 2555 rpm (70% turbine speed)
TURBINE POWER
9000
7500
7000
6500
8500
8000
6000
-6 0 5 10
AIR TEMPERATURE o
C
15 23
2.4.6 Lubricating Oil System
The lube oil system supplies filtered lubricating oil to the turbine engine bearings, the speed reducing gearbox, the pump bearings and various package components within specified operating temperature and pressure limits. In addition, the system supplies oil at engine inlet pressure to related hydraulic subsystems. The lube oil system consists of the lube oil reservoir, oil cooling system, pumps, filters, pressure control devices and temperature control valves and is monitored by the package control system.
Lube oil is pumped from the reservoir by the main lube oil pump to the lube oil manifold. The main lube oil pressure control valve regulates oil pressure in the manifold. If the oil temperature becomes low the temperature control valve diverts flow from the water/oil cooler. As the temperature rises the control valve gradually diverts the flow of oil back in to the water/oil cooler.
From the cooler oil flows through the main lube oil filters to the oil supply manifold and through various supply lines to points of lubrication.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 22 of 158
Lube Oil Pump Checks
When the start cycle begins the control system tests the Backup Post Lube
Pump/ Motor Assembly. If the pressure at the assembly reaches 4 psi, the control system de-energises the Pump/ Motor assembly and energises the
Pre/Post Lube Oil Pump. When the oil pressure reaches 6 psi the control system allows the Engine Pre-lube Cycle to begin.
Pre-lube Cycle
Following the lube oil pump checks the pre-lube timeout timer (60 seconds) is started, this is the allowable time for the Pre/Post Lube Pump to complete the
Pre-lube cycle. When the lube oil pressure exceeds the pre-lube lowpressure limit of 6 psi the pre-lube timer (30 seconds) is started. The engine must be pre-lubed at 6 psi continuously for the full 30 seconds and it must occur within the pre-lube timeout period (60 seconds). If it is not completed within the 60 seconds the start is aborted and a pre-lube Fast Stop nonlockout alarm is enunciated.
Lube Oil Supply when Engine Running
On completion of the Pre-lube Cycle the Pre/ Post Lube Pump de-energises when the engine is above the starter dropout speed and when the lube oil pressure is above 35 psi. At this point the Engine-Driven Pump begins supplying Lube Oil Pressure and continues to steady state condition. Once this pump reaches steady state the Lube Oil Schedule become active.
During steady state condition the Pre/Post Lube Oil Pump energises if:
The engine is below the starter dropout speed and the lube oil pressure is at or below 25 psi.
Engine speed of greater than 5% engine speed (Ngp) is detected.
The Pre/Post Lube Pump will not be annunciated as failed during steady state engine running condition when the Lube oil pressure is less than the Post
Lube Low Pressure Shutdown Limit because the Engine Driven Pump may be at fault.
Run protection for the engine is provided during steady state engine running.
This achieved by energising the pump/motor assembly at any time the lube oil is below the lube oil low-pressure alarm limit. The pump runs for 30 seconds and is then de-energised. The following scenarios are possible:
If the lube oil pressure continues to fall below the allowable limit to the shutdown limit, a Fast Stop Lockout engine shutdown is initiated and the pump/motor BP 903 helps to protect the engine bearings during shut down.
If the lube oil pressure continues to drop below the allowable low limit but stabilises between this limit and the shutdown limit continuously for 5 seconds again this initiates a Fast stop Non-lockout engine shutdown and the pump aids bearing protection during shutdown.
If the lube oil pressure increases above the low pressure limit after 30 seconds or when pump/motor BP 903 is de-energised and the pressure once again decreases, the pump/motor is energised again.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 23 of 158
Lube Oil Reservoir Separator/Filter
Lube Oil Reservoir Separator/Filter (FSA901), located in the lube vent stack, is a coalescing-type separator/filter which collects oil mist droplets and drains oil back to the lube oil reservoir. The oil mist eliminator is a freestanding vessel with the oil reservoir vent ducted to it. The vented air stream enters the bottom of the case and passes through a glass-fibre element where the oil particles are captured. The clean air exits from the top of the vessel and oil collected drains to a liquid seal and back to the lube oil reservoir.
Figure 3 Main Lube Filter Assembly
1 Equalising Hand valve VH903 8 Stud (8 off)
2 Lube Oil Filter Transfer Valve VT901 9 Filter Case Cover
3&4 Filter 10 Filter Case Spiral Gasket
5&6 Filter Bleed Valve VH902-1 & VH902-2 11 Filter Element
7 Nut (16 off)
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 24 of 158
The main lube oil filter assembly FS901, located downstream from
Temperature Control Valve (TCV901/TCV01409D), is a non-bypass, pedestal-type oil filter assembly containing replaceable filter elements. Lube oil flow, as manually selected by positioning Lube Oil Filter Transfer Valve
(VT901), may be directed through either, or both, filters in the assembly. To facilitate filter element replacement, each filter case cover includes a Bleed
Valve (VH902-1, VH902-2). A Drain Valve (VH902-3, VH902-4) is installed at the bottom of each filter case. The two filters are interconnected by a line with a Cross Feed Valve (VH903) which enables equalizing the pressure within the cases during filter changeover and element replacement. The filter case should be completely drained before replacing filter elements.
Bellows-type Differential Pressure Gauge PDI902/ PDG01418D is connected in parallel with Main Lube Oil Filter Assembly Alarm Differential Pressure
Switch (S397-1/PDSHO1417D). The gauge indicates the differential pressure across the inlet and outlet of Main Lube Oil Filter Assembly (FS901).
Instrument Isolation Hand Valve (VI901 –1) is used to isolate the differential pressure gage from the system for calibration, testing, or replacement. After the first 1000 hours of engine operation and as appropriate thereafter, the following should be performed in addition to routine inspection items (shutting down engine prior to performing checks):
Replace lube oil and, if applicable, servo oil filter elements. Lube oil and servo oil filter elements should be replaced when visible contamination is present, when the differential pressure "pop-up" indicators are popped, or when differential pressure limits are exceeded. If none of these conditions occur, the filters should be replaced at least annually.
Check sample of lubrication oil for contamination and, if required, drain and refill oil reservoir with oil as specified on Mechanical
Installation Drawing 149708.
Check the oil cooler for accumulation of foreign material that could obstruct cooling airflow. Clean per manufacturer’s instructions.
Inspect all oil lines and oil system components for security and condition.
Top off oil reservoir as required.
Since the Main Lube Oil Filter Assembly is designed to operate using one filter of Main Lube Oil Filter Assembly (FS901) at a time, filter service may be performed during engine operation or during shutdown. It is preferred to shut the unit down and have the post lube cycle completed prior to servicing. This arrangement also permits the unit to be started while filter element replacement is in progress.
Filter elements should be changed when the filter dp indicates a need for service, whenever the oil is changed, or as annual maintenance. Increasing dp will activate an alarm.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 25 of 158
REMOVAL OF FILTER ELEMENT
1.
2.
Open Equalising Hand Valve VH903
Position Transfer Valve VT901 to isolate the desired filter
3. Close hand valve VH903
4. Attach drain hose or place suitable container beneath drain outlet.
Remove cap from drain line and open Filter Drain Hand Valve VH902-
3 or VH902-4 for filter being serviced
5.
6.
7.
8.
Lube oil may be hot and squirt out as pressure is relieved.
Open Filter Bleed Valve VH902-1 or VH902-2 for filter being serviced.
Drain oil from filter.
Remove nuts and studs from filter case cover.
Swing filter case cover up and to one side from filter body
9. Remove spiral gasket and filter element
10. Clean filter case cover and filter case sides.
INSTALLATION OF NEW FILTER ELEMENT
1.
2.
3.
Install new filter element
Install new spiral gasket and swing filter case cover closed
Install case cover retaining studs and nuts. Torque nuts to 100 ft-lb
(135.6 N·m) torque
4.
5.
Replace cap on drain line & close hand valve VH902-3 or VH902-4
Leak check filter by opening hand valve VH903 slightly to allow transfer of oil into filter.
6.
7.
8.
When oil is seen draining from hand valve VH902-1 or VH902-2, close hand valve VH902-1 or VH902-2 and then close valve VH903.
Do not transfer oil filter to operating lube oil system until all air has escaped from filter body.
Move transfer valve VT901 to desired position.
If required, repeat procedure for second filter.
2.4.7 Gas Turbine Enclosure
The gas turbine enclosure is designed and constructed primarily to provide acoustic attenuation of the noise emissions from the gas generator and the gas turbine, and to meet hazardous area limitations. The enclosure is constructed in a panel form to provide maximum access for maintenance. All side panels can be removed. One plain end panel is nominated for electrical/instrumentation equipment and hook-up. The end panels around the drive coupling are split for access/installation to the drive coupling if required.
The roof panel is fixed and has a number of penetrations for each pipework and ducting.
Personnel access doors are provided in each side of the gas turbine enclosure for periodic maintenance and inspection. An access hatch is also provided for easy access to the intake collector duct.
Each door is fitted with a lock and an internal panic release, which is able to override the door lock if the door is inadvertently closed and locked.
An internal lighting system is fitted and operated by two-way switches located between each pair of doors. Mains and emergency lighting is installed for maintenance. The enclosure is fitted with a ventilation system to reduce the temperature within the enclosure.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 26 of 158
Gas Turbine Enclosure Ventilation System
The GT enclosure ventilation system maintains a negative pressure of (-)700
Pa inside the enclosure; a maxim um air outlet temperature of 39ºC and a maximum inlet temperature of 25ºC. The intake system and silencer allows clean air to be drawn in through the filters and into the enclosure. All construction is in grade 316L stainless steel. The ventilation exhaust system includes 2 x 100% AC axial flow fans, an exhaust silencer, gravity exhaust louvre interconnecting ducting and a flexible connection to the GT Enclosure.
Shut-off dampers are provided at the inlet and outlet to the enclosure. The damper is automatically closed by the LER fire protection control panel, preventing system airflow if a fire occurs.
Gas Turbine Enclosure Ventilation Intake System
Two axial flow fans located within the ventilation exhaust ductwork provide cooling air for the gas turbine enclosure. One fan only is used in normal operation; the second fan provides a stand-by facility in the event of a fan failure. The air is drawn from atmosphere into the intake filter system. The system comprises of two stages. The first stage – storm-proof weather louvre and the second stage - GT2 bag filter.
Water drainage 'U' traps are provided in the base of the weather louvre. The filter house has a side access panel for filter withdrawal for maintenance: access to the panel is achieved by use of the platform adjacent to the filter house. A vent intake system silencer reduces the noise emissions from the gas turbine enclosure. The silencer is specifically designed to meet the system flow rates and noise levels generated by the gas turbine. The airflow from the silencer passes through an elbow and into the gas turbine enclosures. A flexible connection is installed at this interface to the enclosure for isolation and alignment of the equipment. An intake shut-off damper is provided on the inside of the Enclosure.
Gas Turbine Enclosure Ventilation Exhaust System
An exhaust shut-off damper is fitted inside the enclosure, at the air outlet connection on the gas turbine enclosure. When the CO
2 system is activated the shut-off damper will close sealing the enclosure ventilation apertures. An exhaust flexible is fitted for isolation and alignment of the equipment. The main and standby fan assemblies are mounted onto the end of the elbow duct. The vent fans are supported between the elbow and silencer transition.
The lower elbow has adjustable support brackets for use during fan removal.
The fans take the exhaust air into the exhaust silencer. The fans are fitted with a flow or no-flow status device. Each fan has a local emergency stop button. System Instrumentation monitors:
Combustion Intake Filter Condition
• Filter differential pressure gauge - local indication/monitor
• Filter diff pressure (high) transmitter - alarm/trip with LCD display
GT Ventilation System, Filter Condition and Air Flow Status
• Filter differential pressure gauge - local indication/monitor
• Filter diff pressure transmitter - local indication/monitor & LCD display
• Flow failure switch - alarm/control
GT Enclosure Pressure & Temperature
• Operating pressure transmitter - MCC & local indication / monitor
• Operating temperature - resistance temperature detector - alarm
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 27 of 158
2.4.8 Gas Turbine Local Control Room & LER
The electrical control system operates on 24V dc power and provides automatic starting, acceleration to operating speed, engine and driven equipment monitoring during operation and normal and emergency
(malfunction) shutdown. The system also controls safe operating parameters such as temperatures, pressures, flow, speed and vibration. Start-up and shutdown also require controlled sequenced processes.
The control system is operated from the local control room, which has a turbine control panel, with all the necessary switches, pushbuttons and indicators for engine operational status on the front; plus a programmable logic controller (PLC) and a computer adapted for control tasks which controls the turbine engine package systems. The PLC reads inputs such as control panel pushbuttons, makes decisions and sets the outputs such as indicators, positioners, or heating coils. Pressure and temperature sensors, speed, vibrations, pick-ups and other sensors, transfer measured data to the
PLC which evaluates the inputs and sends commands to control devices.
Communication modules accommodate data transmission between control system devices using dissimilar data formats.
The local control room is located above the 4 th water injection pump and performs various operations of the turbine package. It contains:
Batteries & Charger
Turbine Control Panel
Motor Control Centre
Variable Frequency Driver
Fire and Gas Panel
HVAC System
The Local Equipment Room (LER) provides a stand-alone self-contained room to house the equipment for the various operations of the turbine package. The LER structure is built on a carbon steel base raised at one end to allow the LER to be positioned clear of pipe work. The main walls are stainless steel outer, thermally insulated with Rockwool and finished internally with ‘Capeboard’. The main elements of the LER are as follows:
External weather cowls to inlet and exhaust
1 no. multivane coalescer / water separator
1 no. air filter
2 no pneumatically operated fire dampers and 2 fans /motors.
1 no 3 kW duct heater with T3 rating
EE xd pressurisation/F&G control panels with alarm outputs
Fireman’s panel: includes vent valve & air supply regulator assembly
2 no. Eexi fan speed sensors
2 no. Eexd local fan motor isolators
External high gas purge button
The turbine is remotely controlled and monitored from the CCR.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 28 of 158
LER Ventilation / Pressurisation
Two EE xd pressurisation fans (duty and standby) are located internally within the floor void. A connecting duct on the intake side joins the fans. Air is drawn through an external cowl located at the base of the LER. Air then flows through a coalescer, fore damper and filter before entering the intake plenum that connects both fans. Air passes through the duty fan and is expelled in to the supply duct, through a non-return back draught damper and finally through the 3 kW heater before entering the floor void. From the floor void air passes through two ventilation panels.
The pressurisation system maintains a positive pressure within the LER during normal operation. The fans deliver airflow of 0.1 cubic meters per second, which allows 12 air changes per hour within the LER. The pressurisation and ventilation system is primarily controlled from a pressurisation/F&G system comprising two EE xd rated panels. The control panel also interfaces with F&G devices within the turbine enclosure.
Either fan may be selected as the duty fan. It is possible to change the duty fan even when the system is running in normal mode. Engaging the start button on the panel starts the system. The fire dampers open and allow airflow and pressure to establish and the system energises the control power at the two MCCB (Motor Controller Centre Breaker) panels, ready for manual activation by the operator. If the duty fan fails the system will automatically changeover to the standby fan. A HVAC common fault output signal will also be activated so that the correct procedure can be followed to repair the failed fan. If there is a loss of LER air pressure or airflow, the system alarms for a period of 30 seconds (adjustable at the PLC controller in the control panel).
After this time the fire dampers are closed and the duty fan is stopped.
Gas Purge of LER
The LER must be purged occasionally to remove any residue gases. There is a keyswitch fitted in the local control panel and also remotely on the exterior of the LER for this function. Engaging either switch will open the fire dampers and run the selected duty fan for an indefinite period. When the gas has been purged the keyswitch is returned to the normal position and the normal start-up sequence initiated. During gas purge, gas levels are monitored at the control panel.
LER Gas & Smoke Detection
If 20% LEL gas is detected in the LER the system alarms. If 60% is detected the system will alarm, close the fire dampers, and stop the duty fan. If smoke is detected in the LER the system will alarm, close the fire dampers and also stop the duty fan (refer to Solar Installation & Maintenance Manual
104.471.253 Volume 3 for details regarding HVAC system).
The selector switch on the control panel must be set to Fan 1 or Fan 2.
Either fan can be selected as the duty fan while the other becomes the standby fan. To run a fan for duty the start button must be pushed to commence the purge period, then the selected fan will energise. The LER exhaust inlet and exhaust dampers then open and the damper status will be displayed on the screen. The fan will run when the fan speed has increased through the RPM monitor set point.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 29 of 158
2.4.9 Gas Turbine Enclosure Fire Protection System
A CO
2
deluge system is provided for emergency use should a fire be detected within the turbine enclosure and comprises this equipment:
An extinguishant skid complete with bottles, weight monitoring, valves and actuation/monitoring electrical equipment
Piping with isolation valve and position switches
Discharge nozzles (positioned within the acoustic enclosure)
Extinguishing agent
Type of system
Actuation method at the skid
System operating pressure
Extinguishant quantity
Engine requirements
Fire Zone
Carbon dioxide
Total flooding a) Electrical solenoid actuator/Pilot nitrogen b) Manual lever actuator c) Refer also to electrical operating instructions covering field devices and the control system (Altair operating manual 90398/L1327)
51 barg at 20 o C
45 kg capacity per cylinder
2 initial cylinders + 2 reserve cylinders
(each with a nitrogen Pilot cylinder)
258
GT Enclosure CO
2
Fire Protection System
A How Fire CO
2
Fire Protection System is provided for the 7.3m long x 3.0m high x 2.7 m wide turbine enclosure which complies with NFPA 12 or BS 5306
Part 4. The system comprises:
CO
2
Fire Protection System and CO
2 bottles (by How)
Field Run Pipe work (by WG / others)
Turbine Enclosure CO
2
Distribution System with nozzles.
The enclosure is fitted with seven personnel access doors. Visual indication is provided locally, one on each side of enclosure. A CO
2 lockout switch is provided each side of the enclosure should access to the enclosure be necessary whilst the engine is running. The status of lockout is visually indicated locally and in the CCR. Indications include:
System on Automatic Control (green)
System on Manual Control (amber)
System Operated - 1st shot (red)
System operated -2nd shot (red)
System Locked Out - (amber)
CO
2
fire protection system audible and visual alarms are installed on each side of enclosure. The CO
2
cabinet is fitted with extinguishant bottle rack and associated process hardware, and is located adjacent to the Gas Turbine
Enclosure. All equipment is suitable for open deck duty in a marine, offshore environment. The fire & gas panel in the LER controls the operation of the
CO
2
system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 30 of 158
Each cylinder is connected to an overhead manifold using flexible discharge loops; each manifold port is fitted with an adapter and a check valve. The adaptor is fitted prior to the check valve to provide a 3/16” flexible pilot loop connection to the relevant discharge pressure switch (initial/reserve). The check valve allows for cylinder removal whilst maintaining operation.
The manifold incorporates further check valves (100% redundancy) to allow for positive differentiation between initial and reserve discharge signals. The control/monitoring system is programmed to initiate reserve cylinder discharge if confirmation of gas in the pipe is not received within 5 seconds from instruction to release the initial system. The collector manifold is piped to both sides of the skid, offering options for field pipe work connection, with the unused port remaining plugged. The manifold is connected to a network of discharge pipe work and nozzles.
Connections are provided off the CO
2
pipework to operate dampers. An isolation ball valve is installed within the discharge pipe work outside the protected area at an accessible level. This device allows the CO
2
supply to be manually isolated. The ball valve is supplied with limit switches to provide electrical confirmation of operation (open and closed) back to the turbine control/monitoring system.
Note: The CO
2
bottles are clamped to allow for movement of the ship. The bottles are weighed periodically during calm conditions; the bottles are unclamped to allow counterweights to confirm the bottle ’s weight (details relating to the weight monitoring system can be found in the Altair operating manual 90398/L1327).
GT Enclosure Fire & Gas Detection System
The primary means of fire detection within engine compartments is electromechanical rate-compensated heat detectors located in the engine compartment between ventilation air inlet and outlet ducting, and in the vent exhaust duct.
To accommodate abnormal operating conditions (which could render the detectors in the ventilation outlet ducting ineffective) additional detectors are located in the engine compartment. 2 out of 3 voting is used.
Secondary fire detection is by optical beam smoke/oil mist detection
(Wormald model 6003/7). This is primarily for the detection of a release of lube oil or diesel, or the early stages of combustion, and comprises a single detector in the engine enclosure viewing across the ventilation air outlets.
The turbine enclosure is also protected with a gas detection system. Three
Infrared point-type detectors are installed at each of the following locations:
Combustion Air Intake
Ventilation Air Inlet
Ventilation Exhaust
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 31 of 158
Figure 4 4 th Water Injection Pump Package Fire & Gas Detection System Cause & Effect Chart
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 32 of 158
Z-8000-BB-4076 Rev Z1 20 January 2005
Figure 5 4 th Water Injection Pump Enclosure showing Fire & Gas Detectors
Page 33 of 158
2.4.10 Wash Cart
Contaminants such as dust, oil and salt can pass through the air filters and adhere to the compressor blades thus decreasing engine performance. The wash cart is used to supply demineralised water to the turbine for ingestive cleaning to help eliminate performance problems:
Failure to accelerate to full speed/general lack of acceleration
Compressor surge/ loss of compressor discharge pressure
Inability to develop full output power
Increase in turbine temperature.
To determine if cleaning is required, engine performance is evaluated using the following parameters:
Gas producer speed (Ngp)
Compressor inlet temperature
Barometric pressure
Turbine gas temperature
Compressor discharge pressure
Output power
Inlet and exhaust duct pressure drop
Water injection rate
Fuel gas flow/usage.
When to clean is best determined by measuring performance loss. A rule of thumb is to clean before a 10% reduction in power occurs or the power turbine temperature increase by 5% or there is a 8-10% reduction in output power. Baseline conditions (output power and air inlet temperature) should be used for comparison. Deposits should not be allowed to accumulate, otherwise water-washing will become ineffective over time.
Water is used to remove water-soluble contaminants. Cleaning can be carried out while the engine is cranking ( on-crank cleaning ) or while the engine is operating in the simple cycle ( on-line cleaning ). On-crank cleaning is when the engine operates at the maximum speed obtainable by the starter alone with the fuel and ignition de-activated (providing turbine gas temperatures are below 66 o C and/or gas producer speed is below 60%).
This type of cleaning is more effective than on-line cleaning. On-line cleaning is when the engine operates at any power level ranging from idle to full rated power with the temperature stabilized at operating speed.
Wash Cart Components
The wash cart is a horizontal stainless steel pressure injection vessel, which is plumbed in to the on/crank / water wash and online manifolds. The tank is constructed to the Pressure Vessel Code ASME VIII specifications and PER
/PED for a normal working pressure of 6.9 barg and up to 95 o C. In addition to this the cart has the following components:
ASME UV stamped pressure relief valve set at 8.95 bar
Tank capacity of 26 gal (100L)
On-crank air and on-line air, water and chemical inlet ball valves with check valves
Air, water and chemical Y inlet strainers with 100 micron insert
Wash fluid outlet connection with ball valve
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 34 of 158
Wash fluid outlet filter Y strainer with 100-micron filter insert
Drain and vent with ball valves
Magnetic level gauge with dial face
Heavy-duty chemical-resistant hose with female quick disconnects between injection tank and engine on-crank manifold ring and water/chemical supply
Heavy-duty hose with female quick disconnect at each end for air supply to tank
Hand-held spraying wand
Pressure Safety Valve (PSV)
Male quick-disconnect couplers for air, water and chemicals.
Figure 6 4 th Water Injection Pump Turbine Wash Cart (without PSV)
There are two separate skid edge connections; one for on-line cleaning and the other for on-crank cleaning. Each connection is plumbed to the respective manifold with the following components:
Inlet strainer
Shutoff solenoid
Triple cartridge filter
Three-way hand valve (on-crank only).
The on-crank three-way hand valve is downstream of the shutoff solenoid with a quick disconnect for the hand wand. The control system logic prevents the on-crank solenoid from opening when the turbine gas temperatures are above 66
°
C and/or the corrected gas producer speed is above 60%.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 35 of 158
2.5 Water Overboard Discharges, Monitoring & Reporting
Not all overboard discharges from the Schiehallion FPSO process systems are monitored for oil-in-water content, but this does not mean that oily water is disposed of indiscriminately. There are several discharges to sea that could contain oil:
Produced Water Degasser outlet (20”) discharge overboard
Deaerator Tower outlet (10”) overboard discharge & 3” drain
Water Injection Pumps (10 ”/14”) overboard discharge
For each discharge the information required for reporting is as follows. o Average monthly oil-in-water quality in ppm (wt) - by sampling o Average discharge rate in m 3 /day and number of days on stream o Total volume of water discharged in m
3 o Weight of oil discharged in tonnes.
The Degasser 20” overboard discharge oil-in-water content is determined by sampling on the Degasser outlet. An oil-in-water analyser provides continuous monitoring and initiates a high oil-in-water alarm if 30 ppmv oil-inwater is exceeded.
The De-aerator Tower V-44101 10” overboard discharge FCV-441019 controls the water flow overboard using a FIC which controls the flow through the tower by modulating the tower seawater inlet to match water injection demand. This opens the FCV which dumps water to sea to maintain a minimum flow through the tower. The 3” De-aerator drain is isolated by a manual valve and is only used for maintenance.
Each motor-driven water injection pump P-45001A/B/C 10” discharge has a
6” branch line FCV, which is modulated according to injection system demand. Supply overdemand will open each pump’s respective discharge
FCV and discharge water into a common 10” discharge line with vent and through the 14” discharge pipe overboard. There is no flow monitoring or sampling on this common line.
Minimum flow protection for the GT-driven pump is provided by an overboard dump valve FCV-450445 which opens at a predefined minimum flow of 330 m 3 /h to protect the pump from damage.
The quantity discharged overboard is determined by calculation in the CPS, being the difference between the total flow through the water injection pumps
(integrated over the same time period), less the amount discharged down the water injection risers:
{ Integration of (FI 450145 + FI 450245 + FI 450345) }
- (FQI 180800 + FQI 182800)
Quantity is displayed at FQI-450004.
All environmental discharges from Schiehallion Installation are published on the Schiehallion website.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 36 of 158
Z-8000-BB-4076 Rev Z1 20 January 2005
3 ” Overboard
10 ”
10 ” Overboard
Figure 7 Water Injection System Schematic
Page 37 of 158
2.6 Chemical Injection
Antifoam, biocide and calcium nitrate may be injected at the inlet to the deaerator. A scale inhibitor injection point is provided at the outlet. Refer to Z-
8000-BB-4007 for details of the chemical injection system.
The biocide and anti-foam injection point is a common line. Biocide dosing must only occur when the deaerator tower is off-line to prevent foaming in the column and to ensure that biocide is not routed to the reservoir where it could negate the benefit of calcium nitrate injection. To maintain the quality of the injection water, scale Inhibitor may be required to be injected at the outlet of the deaerator on a continuous basis to avoid the scaling subsea which would result from the mixing of the produced water and seawater. Any scales formed would be pumped into the reservoir. Antifoam can be injected if required at the deaerator inlet. The chemical dosing rates are:
Antifoam
Scale Inhibitor
2 ppm (normal)
5 ppm (normal)
Oxygen Scavenger 5 ppm (normal)
Calcium nitrate 60 ppm (this will vary as the produced water make increases)
The de-aeration system is designed to be capable of meeting the required oxygen specification without the use of oxygen scavenger injection. However, rough weather may cause poor distribution of seawater in the deaerator column causing the unit to go off specification. Under these circumstances, the column may be returned to specification by the injection of oxygen scavenger chemical, which is fed into the tower by mixing via a 2” line from the discharge of the produced water booster pumps P-43001A/B/C.
The chlorine analyser AT-441017 and the oxygen analyser AT-441018 monitor water quality at the outlet of the deaerator. A manual sample connection is also provided. Sodium hypochlorite is injected to the seawater lift pumps
P-85401A/B/C suction and should not exceed 2 ppm(wt) of free chlorine. The maximum oxygen level is 20 ppb.
The chlorine analyser AT-441017 is located in a purged cabinet. The purge gas pressure is maintained at a constant pressure by an integral flow controller within the purge system control unit, which is located in the field. In the event that the purge pressure exceeds or falls below the set operating pressure then an alarm will be generated PAH/L-441034 by a pressure switch located in the purge cabinet. Initiation of this alarm will cause the power to the instrumentation within the purged cabinet to be isolated by the purge system control unit.
To safeguard against any leaks in the purged cabinet, a liquid level instrument is located at the bottom of the drip tray. In the event of liquids leaking into the cabinet, an alarm LAH-441033 will be generated by the level switch LS-441033.
Initiation of the alarm will remove power from the instrumentation within the purged cabinet. This is controlled by the purge system control unit.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 38 of 158
2.7 Turret Water Injection, Swivel and Turret Valves
Refer to P&ID M-5021-GP-8004.00.
The 16” line containing produced water and de-aerated seawater from pumps P-45001A/B/C/D is discharged at approx. 22
°
C and up to 246 bar via a dedicated pressurised 12” turret water swivel N-45080 to three 10” risers. The injection water then flows to the subsea distribution system.
PG-450803 is located downstream of the turret.
The 12” water injection manifold in the turret has four connections. One is for future use and is currently blanked off. The re maining 12” line connects to three
10” nominal bore risers. Each 10” line has two sonic flowmeters (FE-180800A/B,
FE-181800A/B & FE-182800A/B), check valves (with 2” bypass to allow depressurisation of the downstream pipeline), local flow indicators, and 10” isolating valves. The three 10” risers then connect to two 9.5” ID flexible risers and one 11.5” ID flexible riser to form part of the subsea water injection distribution system.
2.8 Water Injection Flexible Risers
The two 9.5”ID risers connect at their bases with plastic-lined pipelines to
Schiehallion Central & North, and to Loyal and West via North. The third 11 .5”ID riser connects at its base with plastic-lined pipeline to Schiehallion North West.
Refer to P&ID M-5021-GP-8004.
Water from the turret’s 12” water injection manifold is passed down three
10” nominal bore flexible risers, each lined with a carcass to protect against vacuum conditions on injection pump shutdown. When the pumps are shut down, it is expected that the hydrostatic pressure in the risers will exceed water injection well(s) pressure. Closing the injection wells’ wing valves when the water injection pumps are shut down will minimise the likelihood of vacuum conditions occurring in the risers.
The unbounded flexible pipe structure is built with the specific arrangement of coaxial layers of different material. Each layer has its own function that helps the flexible system to fulfil its main functional requirements. The basic design used for the Schiehallion water injection lines is a smooth bore structure, because no gas is involved in the transport fluid and it remains full all the time. The structure comprises of the following layers:
Layer 1: Inner plastic tube for pipe leak resistance.
Layer 2: Spiralled steel layer to sustain the radial load generated by the internal pressure.
Layer 3: An anti-collapse thermo-plastic sheath to submit the external pressure onto the underlying steel layer - most of the time this layer is not needed if the line remains full of the fluid.
Layer 4: Cross-wound armoured layers to withstand tensile and torque loads.
Layer 5: External thermo-plastic sheath to ensure the leak resistance to environmental fluid.
Layer 6: Anti-friction layers for dynamic application.
The flexible risers and the flowline jumpers have essentially identical construction, with an inner carcass of Grade 316L austenitic stainless steel, which supports a pressure sheath of polyamide, or, for the WI risers, PE. The inner layers are mechanically protected by a hydrogen sulphide-resistant external wire armour layer, with polymer coating layers.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 39 of 158
Riser Group Drill Centre
Schiehallion
Central
Schiehallion
West &
Gas Disposal
Loyal &
Schiehallion
North
Schiehallion
Central
Schiehallion
West
Gas Disposal
Loyal
Schiehallion
North
North West North West
Drill Centre Duty
Production wells
Water injection wells
Production wells
Water injection wells
Gas disposal well
Production wells
Water injection wells
Water injection wells only
Production wells
Water injection wells
Riser/Flowline
Service
Production line A
Production line B
Production line C
Production/Test
Gas Lift [1]
Water Injection
Umbilical
Production
Production/Test
Gas Lift [1]
Water Injection [2]
Umbilical [4]
Gas Disposal
Umbilical [4]
Spare Riser Base
Gas Lift
Production
Production/Test
Gas Lift
Water Injection [2]
Umbilical [3]
Water injection
Umbilical
Production
Gas Lift [5]
Water injection
Umbilical [6]
Riser
NB
(in)
9.5
9.5
9.5
7.5
-
9.5 n/a
9.5
7.5
-
-
-
7.5
-
5
9
9.5
7.5
7.5
-
-
9.5 n/a
9.5
-
11.5
-
Table 2 Water Injection Flowlines & Umbilicals Dimensions
Notes: [1] Gas lift lines branched off Loyal Line
[2] Loyal and Schiehallion West Water Injection Line Branches off Schiehallion North
[3] Loyal Umbilical Branches off Schiehallion North
[4] Schiehallion West & Gas Disposal Umbilical Branches off Schiehallion Central
[5] North West gas lift is from West drill centre (HOLD)
[6] North West umbilical is from West drill centre (HOLD)
10
8
6
10 n/a
10 n/a
10
8
10
-
Flowline
NB
(in) length
(km)
10
10
10
8
8
12 n/a
10
8
6
10 n/a
8 n/a
2.65
2.65
2.65
2.65
2.90
2.65
2.630
4.30
4.30
4.75
4.80
2.989
9.30
5.009
5.90
5.90
5.90
4.90
4.920
2.40
2.313
6
2
2
2
2.9 Subsea Water Injection System
Refer to P&IDs S-9000-NP-9203/13/14/15/16/20/21/24/25/26
Subsea Water Injection System Equipment
The subsea water injection system consists of three sets of equipment: the first to deliver injection water to Schiehallion Central, the second to deliver injection water to Schiehallion West, North and Loyal, and the third (HOLD) to deliver water to the new North-West Drill Centre. Water delivered to these drill centres should have been filtered and the oxygen removed to the following specification:
Dissolved Gases
Maximum particle size
Negligible, i.e. < 20 ppb O
2
80 microns.
Each drill centre is supplied by a dedicated flowline, except for Schiehallion North and Loyal centres which share a flowline between the riser base and the North
Injection site. Distribution to individual wells is via a water injection manifold at each drill centre.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 40 of 158
Injection rates to individual wells is controlled at each injection wellhead by ROVoperated chokes with flow control provided by shutting in components of the system - either individual wells or one of the four injection pumps. For operation of the first two injection wells, the pump minimum flow FCVs also serve to control the pump flow. The design is aimed at infrequent adjustments to the water injection rates; the rates being monitored using a venturi-type flowmeter which is mounted at each wellhead, upstream of the injection choke.
Note: If ROV control of the injection chokes provides insufficient operational flexibility, there is an option to provide actuated chokes on the later water injection trees with some impact to the control systems.
Schiehallion Central
Schiehallion Central is located some 2.9 km South East of the FPSO. The eight water injection trees are supplied ind ividually from the 12” plastic-lined flowline via two water injection manifolds M2 & M2A which are connected to the pipeline FTA using 10” flexible jumpers. Each water injection tree is connected to the manifold by a 6” flexible wellhead jumper.
Electro-hydraulic control functions and chemical supplies for the central manifold and the production and water injection trees are provided by a control umbilical from the FPSO. These services are distributed through the Controls Distribution
Trunking (CDT) which forms the upper section of the central manifold. The water injection tree controls are supplied by two separate umbilicals, connected to separate outlets on the CDT, each supplying an SCM on an injection tree, each of which in turn controls another injection wellhead by direct hydraulic control.
Schiehallion West
Schiehallion West is located 3.2 km to the South West of the FPSO and has five water injection wells. The wells are connected to the F PSO by 10” & 12” plasticlined rigid flowlines. These flowlines are terminated by FTAs at both ends. The water injection supply is provided from a 10” riser and a 12” riser via two FTAs, located beneath the FPSO, which supplies Schiehallion North and Loyal. The five water injection trees are supplied individually from the 10” & 12” plastic-lined flowlines via two connected water injection manifolds M22 & M22A; these are connected to pipeline FTAs with 10” and 12” flexible jumpers. The water injection tree controls are supplied by an umbilical jumper from the UTA to an SCM on one of the trees. This provides direct hydraulic control functions for all water injection trees.
Schiehallion North
Schiehallion North is located some 2.7 km to the North East of the FPSO and has three water injection wells. The wells are supplied with injection water through a
10”, plastic-lined flowline from the FPSO through a three-porch water injection manifold via 6” bore flexible wellhead jumpers. The flowline also extends via a
10” flexible jumper from one end of the manifold to the FTA on the end of a 10” plastic-lined pipeline which is routed to the Loyal wellsite. Control functions to the trees are provided from a UTA to an SCM on one of the trees. This controls the other tree using direct hydraulics, and has a spare connection for the third tree.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 41 of 158
Loyal
Loyal is located 6.1 km North of the FPSO and has four water injection wells.
The water injection supply is provided from the FPSO by a 10” flowline which is routed via the Schiehallion North manifold. The four water injection trees are supplied individually from the 10” plastic-lined flowline via a separate four-porch water injection manifold which is connected to the pipeline FTA with a 10” flexible jumper. The water injection tree controls are supplied by an umbilical jumper from the UTA to the SCM on one of the trees. This provides direct hydraulic control to the other three water injection trees.
From Water 16
”
Injection
Pumps P-45001A/B/C/D
12
” Water Injection
Swivel N-45080
12
” Water Injection Manifold
FTA
9
½” ID
Flexible
Riser
FTA
Central Manifold
Schiehallion
Central WI Wells
FTA
9
½” ID
Flexible
Riser
Future Riser
Connection (blanked off)
FTA
11
½” ID
Flexible
Riser
Injection water to North-West Drill
Centre (HOLD)
FTA FTA
North Manifold
Schiehallion
North WI Wells
West Manifold
Schiehallion
West WI Wells
FTA
FTA
KEY
Riser
Jumper
Flowline
Loyal
WI Wells
Figure 8 Subsea Equipment Schematic (prior to NW drill centre development)
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 42 of 158
Components Location
Common Water Injection manifold Turret
One spare connector (for future use) Turret
Schiehallion Central – Water Distribution System
Schiehallion Central Riser (slot EC )
Schiehallion FPSO FTA
Flowline (FPSO FTA to Central FTA)
Schiehallion Central FTA (WI)
Flexible Jumper to Central Manifold
Central Water Injection Manifold
Flexible Jumper to Tree on Slot CW12
Water Injection Tree on Slot CW12 (Type 1)
Flexible Jumper to Tree on Slot CW10
Water Injection Tree on Slot CW10 (Type 2)
Flexible Jumper to Tree on Slot CW11
Water Injection Tree on Slot CW11 (Type 2)
Flexible Jumper to Tree on Slot CW13
Water Injection Tree on Slot CW13 (Type 1)
Flexible Jumper to Tree on Slot CW16
Water Injection Tree on Slot CW16 (Type 1)
Flexible Jumper, Central Manifold M2 to Manifold M2A
Flexible Jumper to Tree on Slot CW17
Water Injection Tree on Slot CW17 (DTHT)
Flexible Jumper to Tree on Slot CW15
Water Injection Tree on Slot CW15 (Type 3)
Flexible Jumper to Tree on Slot CW18
Water Injection Tree on Slot CW18 (DTHT)
Central
Central
Central
Central
Central
Central
Flexible Jumper to Tree on Slot CW19
Water Injection Tree on Slot CW19 (DTHT)
Central
Central
Schiehallion West, North & Loyal – Distribution System
Under FPSO seabed
Seabed
Central
Central
Central
Central
Central
Central
Central
Central
Central
Central
Central
Central
Central
Central
West, North & Loyal Riser (Slot NF)
FTA FPSO
Flexible Jumper to FTA-185-92
FTA FPSO to West WI
Flowline to West FTA
FTA West WI
Under FPSO
Seabed
Seabed
Seabed
West
West
ID No
12”-WI-450803
-
10-R-180
FTA-180-92
12 ”-L-180
FTA-180-93
10-J-180
MAN-180-92
06-W-105-922
XTI-105-92P
06-W-105-923
XTI-105-92Q
06-W-105-921
XTI-105-92N
06-W-105-924
XTI-105-92R
06-W-105-923
XTI-105-92T
10-J-180-921
06-W-105-927
XTI-105-92U
06-W-105-925
XTI-105-92S
06-W-105-928
XTI-105-92V
06-W-105-929
XTI-105-92W
Flexible Jumper to West Manifold M22
West WI Manifold
Flexible Jumper to Tree XTI-125-92Q
Well WW05 Water Injection Tree (Type1)
Flexible Jumper to Tree XTI-125-92P
Well WW04 Water Injection Tree (Type1)
Flexible Jumper to Tree XTI-125-92N
Well WW06 Water Injection Tree (Type 3)
Flexible Jumper to West Manifold M22A
Flexible Jumper to Tree XTI-125-92R
Well WW08 Water Injection Tree
Flexible Jumper to Tree XTI-125-92S
Well WW09 Water Injection Tree
Flexible Jumper from West FTA-185-96 F29
West
West
West
West
West
West
West
West
West
West
West
West
West
West
10-R-182
FTA-182-92
10-J-185-921
FTA-185-92
10-L-185
FTA -185-93
FTA 26
10-J-185-93
MAN-185-92 M22
06-W-125-923
XTI-125-92Q
06-W-125-922
XTI-125-92P
06-W-125-921
XTI-125-92 N
10-J-185-923
06-W-125-924
XTI-125-92R
06-W-125-925
XTI-125-92S
12-J-185-926
Table 3 Subsea Components and Sizes (prior to NW development)
Size
12"
12 ”
6”
N/A
6”
N/A
6”
N/A
6”
N/A
9.5”
10”
10”
10”
10”
10”
10”
10”
6”
N/A
6”
N/A
6”
N/A
10”
6”
N/A
6”
N/A
12 ”
9.5
”
10 ”/12”
12 ”
12”/10”
10”
10”
6”
N/A
6”
N/A
6”
N/A
6”
N/A
6”
N/A
10”
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 43 of 158
Schiehallion North & Loyal - Distribution System
Flowline to North FTA
FTA North WI
Flexible Jumper to North Manifold
North Water Injection Manifold
Flexible Jumper to Tree XTI-135-92P
Water Injection Tree NW02 (Type 1)
Flexible Jumper to Tree XTI-135-92N
Water Injection Tree NW01 (Type 3)
Flexible Jumper to Tree XTI-135-92Q
Water Injection Tree NW03 (Type 3)
Flexible Jumper from North Manifold to
FTA-186-92
Flexible Jumper from FTA-186-92 to
Loyal FTA-186-93
Flexible Jumper from FTA-186-93 to
Loyal FTA-186-92
Loyal Water Injection Manifold
Flexible Jumper to Tree XTI-145-92Q
Water Injection Tree LW06 (Type 1)
Flexible Jumper to Tree XTI-145-92P
Water Injection Tree LW05 (Type 1)
Flexible Jumper to Tree XTI-145-92N
Water Injection Tree LW04 (Type 3)
Flexible Jumper to Tree XTI-145-92R
Water Injection Tree LW04
North
North
North
North
North
North
North
North
North
North
North to Loyal
North to Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
Loyal
10-L-182
FTA-182-93
10-J-182
MAN-182-92
06-W-135-922
XTI-135-92P
06-W-135-921
XTI-135-92N
06-W-135-923
XTI-135-92Q
10-J-186-921
10-L-186
10-J-186-922
MAN-185-92
06-W-145-923
XTI-145-92Q
06-W-145-922
XTI-145-92P
06-W-145-921
XTI-145-92N
06-W-145-924
XTI-145-92R
Table 3 Subsea Components and Sizes (prior to NW development)
(continued)
10”
10”
10”
10”
6”
N/A
6”
N/A
6”
N/A
10 ”
10 ”
10 ”
10”
6”
N/A
6”
6”
6”
N/A
6”
N/A
Normal Operation (Overview)
Once the chokes have been set by the ROV, the only operations will concern start up and shutdown of either the entire system or of individual wells. Fine tuning and optimisation of the water injection header can be controlled to an extent by the adjustment of surface-controlled choke valves on CW17, 18 and 19.
However, due to the design limitations of the water injection system, there will be a defined maximum operating flow rate for any component. This is to prevent over-pressurisation which can occur as a result of a hydraulic surge during an unplanned shutdown.
The relatively high pump discharge pressure of approximately 200 barg (3000 psig) at the design water injection rate has been aimed at overcoming uncertainties in the reservoir injectivity. Depending on the well injectivity and required injection rate, the pressure drop across the water injection chokes during normal operation could be high (i.e. up to 133 barg (2000 psig)). The system operating temperatures will also be relatively high (28 - 60
C). This is due to the injection of produced water, the use of the injection water as a cooling medium
(i.e. used in the topsides cooling medium coolers) and the polyethylene liner in the pipeline which provides a high level of insulation.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 44 of 158
2 -3 /8 ” B y-P a ss T u b in g
N ip p le
P e rf. p u p a n d b u ll p lu g
T u b in g H a n g e r 7 ” x 2 ”, c/w 6 .1 8 7 ” p ro file
7 ” T R -S C S S S V
1 1 ¾ ” 6 0 lb /ft C a sin g
1 1 ¾ ” x 9 -5 /8 ” C ro sso ve r
9 -5 /8 ” 4 7 lb /ft L -8 0 C a sin g
7 ” 2 9 lb /ft o r 5 -1 /2 ” 2 0 lb /ft N S C C
T u b in g , L -8 0 , G R P L in e d
9 -5 /8 ” P e rm a n e n t P a cke r
(H y d ro s ta tic P re s s u re S e t)
5 1 /2 ” T a ilp ip e
S h e a ra b le T a ilp ip e C e n tra ils e r
L in e r T o p Is o la tio n V a lv e (L T IV )
5 ½ ” x 7 ” x 9 -5 /8 ” L in e r H a n g e r, P a cke r.
9 -5 /8 ” S h o e
5 1 /2 ” S a n d C o n tro l S cre e n s
(cro sse d o ve r to 7 ” T b g & H g r)
Figure 9 Typical Water Injection Well Completion Schematic
System Start up (Overview)
Start-up of the water injection system is based around ensuring the main water injection pumps are not started against a vacuum condition in the injection riser.
To achieve these aims, the produced water booster pumps or seawater lift pumps are employed to overcome any vacuum condition prior to starting the main pumps, but with the main pump discharge open to allow flow. If the well annulus pressure exceeds 275 barg, the wing valve will need to be closed before opening the cross-over valve otherwise it will not be possible to relieve sufficient pressure from the annulus.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 45 of 158
System Shutdown (Overview)
On shut-down of the WI system there are four key considerations:
The potential for a vacuum condition in the water injection system due to reservoir under-pressure.
Hydraulic surge due to closure of the wing valves, with the potential for the shut-in pressure to exceed the system design pressure under certain circumstances and for the transient pressures during the shut-in process to exceed the maximum over-pressure allowances on some components.
Closure of the wing valves is required to ensure that cross-flow between injectors via the respective Xmas trees is prevented. Thus, reducing the potential for damage to the lower completion due to sand ingress. (Note that this is protected against to some extent by the use of sand screens within the water injection wells).
Excessive wear of WI wing valve if it is closed against the main pump.
Due to the above points, the shut-in of the wells is a compromise between the requirement to shut-in quickly to prevent a vacuum in the riser and cross-flow between wells and the requirement to shut-off slowly to prevent hydraulic surge in the system. To this end, any water injection trip will also close all subsea water injection wing valves with wing valve closure staggered over a period of 60 seconds to reduce the surge problem. This allows the run down of the pump and the closure of the pump discharge valve to occur before the closure of the last wing valve (once the water injection system is fully operational). The set point for opening the overboard dump valve on each pump ensures that the system pressure prior to shut down is relatively low – thus reducing the risk of over-pressure due to surge.
Protection of the wing valves against erosion is not possible and therefore closure against full operating pressure will occur under some circumstances. However, on a planned shut down of the water injection system, it is beneficial to close the wing valves and shut in pumps in a sequence that minimises the wear on the valves. To ensure that surge considerations are taken into account, safe operating limits for each well must be adhered to.
Corrosion Management
Refer to the Corrosion Management Strategy Z-8000-ZS-4027 .
The subsea components of the water injection system are constructed from corrosion resistant alloys. The flexible risers and flowline jumpers have a duplex carcass, the flexible well jumpers have a stainless steel 316 carcass, the carbon steel flowlines are provided with polyethylene lining and all other major components are alloy 625 clad carbon steel. Injection water is de-oxygenated to a level of <20 ppbv and OS-2 scavenger is employed, if required, to ensure that the sweet service design of the subsea system is satisfactory. During operation, corrosion management of the water injection system is limited to monitoring of the oxygen content of the injected water. There is no capability to intelligent pig the water injection system.
The well tubing is fibre glass-lined. However this lining can be damaged during well workovers giving the potential of the L80 carbon steel tubing to corrode. The maintenance of the water injection oxygen specification is primarily to protect against this corrosion potential.
No subsea chemical injection is required in the water injection system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 46 of 158
Injection of Oxygen Scavenger
These guidelines are used to determine when oxygen scavenger is required:
Oxygen Level (ppb O
2
) Duration Condition
< 20 ppb
> 20 ppb
50-500 ppb
> 500 ppb
-
> 2 hours
> 3 hours
> 1 hour
Normal Operations
Inject Oxygen Scavenger to bring down level
Shutdown Injection
Shutdown Injection
Table 4 Oxygen Scavenger Injection Decision Table
Scale Deposition
The potential for scale deposition is relatively low. However, to mitigate against the risk of deposition, the subsea system will be protected from scale deposition by the continuous injection of scale inhibitor on the FPSO.
2.10 Water Injection Wellheads (Tree, Choke, Master & Subsurface Valves)
Water Injection Tree Assembly (refer to P&IDs S-9000-NP-9203, S-9000-NP-
9220 & S-9000-NP-9221).
Three different types of water injection tree are installed subsea. The X-mas tree valving arrangement is the same for each tree, what does differ is whether a tree has a Subsea Control Module (SCM) and how many trees are controlled from that
SCM.
Type 1 has no SCM and control is via a Type 2 tree configuration
Type 2 has an SCM and controls one other Type 1 trees
Type 3 has an SCM and controls two other Type 1 trees.
Components
Slot Number
Tree Tag No.
SCSSV
UIMV
IWV
AMV
XOVT
Injection pressure & temp.
Annulus Pressure
WI Flowmeter
MP Hydraulic Supply
Pressure Sensor
HP Hydraulic Supply
Pressure Sensor
Schiehallion Central
CW12 CW13
XTI-10592P
105931P
105933P
105934P
105935P
105937P
PTT-105922P
XTI-10592R
105931R
105933R
105934R
105935R
105937R
PTT-105922R
PT-105923P
FT-105929P
PT-105991N
PT-105992N
PT-105923R
FT-105929R
PT-105991Q
PT-105992Q
Schiehallion Central
CW16
XTI-10592T
105931T
105933T
105934T
105935T
105937T
PTT-105922T
PT-105923T
FT-105929T
PT-105991T
PT-105992T
Table 5 Type 1 Water Injection Wells
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 47 of 158
Components
Slot Number
Tree Tag No.
SCSSV
UIMV
IWV
AMV
XOVT
Injection pressure & temp.
Annulus Pressure
WI Flowmeter
MP Hydraulic Supply
Pressure Sensor
HP Hydraulic Supply
Pressure Sensor
PT-125992N
Components
Slot Number
Tree Tag Number
SCSSV
UIMV
IWV
AMV
XOVT
Injection Pressure & Temp.
Annulus Press. Sensor
WI Flowmeter
MP Hydraulic Supply Pressure
Sensor
HP Hydraulic Supply Pressure
Sensor
Schiehallion West
WW04
XTI-12592P
125931P
125933P
125934P
125935P
125937P
PTT-125922P
PT-125923P
FT-125929P
PT-125991N
LW05
PT-125992N
XTI-14592P
145931P
145933P
145934P
145935P
145937P
PTT-145922P
PT-145923P
PT-145929P
PT-145991N
PT-145992N
WW05
XTI-12592Q
125931Q
125933Q
125934Q
125935Q
125937Q
PTT-125922Q
PT-125923Q
FT-125929Q
PT-125991N
Loyal
LW06
XTI-14592Q
145931Q
145933Q
145934Q
145935Q
145937Q
PTT-145922Q
PT-145923Q
PT-145929Q
PT-145991N
Schiehallion North
NW02
XTI-13592P
135931P
135933P
135934P
135935P
135937P
PTT-135922P
PT-135923P
FT-135929P
PT-135991N
PT-135992N
PT-145992N
NW03
XTI-13592Q
13591Q
135933Q
135934Q
135935Q
135937Q
PTT-135922Q
PT-135923Q
FT-135929Q
PT-135991N
PT-135992N
Table 5 Type 1 Water Injection Wells (continued)
Component Schiehallion Central
Slot Number
Tree Tag Number
SCSSV
UIMV
IWV
AMV
XOVT
Injection Pressure & Temp.
Annulus Pressure Sensor
Water Injection Flowmeter
MP Hydraulic Supply Pressure
HP Hydraulic Supply Pressure
CW11
XTI-10592N
105931N
105933N
105934N
105935N
105937N
PTT-105922N
PT-105923N
PT-105929N
PT-105991N
PT-105992N
Table 6 Type 2 Water Injection Wells
CW10
XTI-10592Q
105931Q
105933Q
105934Q
105935Q
105937Q
PTT-105922Q
PT-105923Q
PT-105929Q
PT-105991Q
PT-105992Q
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 48 of 158
Components West Loyal
Slot Number
Tree Tag Number
SCSSV
UIMV
IWV
AMV
XOVT
Injection Pressure and Temperature
Sensor
Annulus Pressure Sensor
Water Injection Flowmeter
MP Hydraulic Supply Pressure
Sensor
HP Hydraulic Supply Pressure
Sensor
Components
WW06
XTI-12592N
125931N
125933N
125934N
125935N
125937N
PTT-125922N
PT-125923N
FT-125929N
PT-125991N
PT-125992N
LW04
XTI-14592N
145931N
145933N
145934N
145935N
145937N
PTT-145922N
PT-145923N
PT-145929N
PT-145991N
PT-145992N
North Central
Slot Number
Tree Tag Number
SCSSV
UIMV
IWV
AMV
XOVT
Injection Pressure and Temperature
Sensor
Annulus Pressure Sensor
Water Injection Flowmeter
MP Hydraulic Supply Pressure
Sensor
HP Hydraulic Supply Pressure
Sensor
NW01
XTI-13592N
135931N
135933N
135934N
135935N
135937N
PTT-135922N
PT-135923N
PT-135929N
PT-135991N
PT-135992N
CW15
XTI-10592S
105931N
105933N
105934N
105935N
105937N
PTT-105922N
PT-105923N
PT-105929N
PT-105991N
PT-105992N
Table 7 Type 3 Water Injection Wells
Components
Slot Number
Schiehallion Central
CW17 CW18
Schiehallion Central
CW19
Tree Tag No.
SCSSV
UIMV
IWV
XTI-10592U
105931U
105933U
105934U
XTI-10592V
105931V
105933V
105934V
XTI-10592W
105931W
105933W
105934W
AMV
XOVT
105935U
105937U
105935V
105937V
105935W
105937W
CHI 105926U 105926V 105936W
Injection pressure & Temp. Sensor PTT-105922U PTT-105922V PTT-105922W
Annulus Pressure Sensor PT-105923U PT-105923V PT-105923W
Injection Pressure Sensor
WI Flowmeter
Injection Choke Position Indicator
MP Hydraulic Supply Press. Sensor
HP Hydraulic Supply Press. Sensor
PT-105924U
FT-105929U
ZI-105926U
PT-105991U
PT-105992U
PT-105924V PT-105924W
FT-105929V FT-105929W
ZI-105926V ZI-105926W
PT-105991V PT-105991W
PT-105992V PT-105992W
Table 8 Type DTHT Water Injection Wells
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 49 of 158
Water Injection Tree Configuration
Refer to P&ID S-9000-NP-9203.
Each water injection tree has similar valves and instruments. The table below identifies valves which can be operated from the CCR and those valves which are
ROV operated. Remotely actuated valves are fitted with an override device which allows these valves to be operated by ROV if required. Injection Swab Valve and
Annulus Swab Valve are remotely operated from a workover vessel.
Component
WI Differential Pressure Flow Sensor
Injection Choke Valve
Injection Wing Valve (IWV)
Inlet Pressure & Temperature Sensor
Injection Swab Valve (SVI)
Annulus Swab Valve (ASV)
Crossover Valve (XOVT)
Annulus Pressure Sensor
Upper Injection Master Valve (UIMV)
Annulus Master Valve (AMV)
Lower Injection Master Valve (LIMV)
Hydraulic Supply Valve to SCSSV
Surface Controlled Subsea Safety Valve
Remotely
Operated
N/A
CW17, 18, 19 only
Yes
N/A
Yes
Yes
Yes
N/A
Yes
Yes
No
No
Yes
ROV Operated
Table 9 Water Injection Tree – Valve Operation
N/A
Yes
No
N/A
No
No
No
N/A
NO
No
Yes
Yes
No
Note: Type 1 wells at the West, Loyal and North drill centres share the same control function on the subsurface safety valves. Hence, opening of the valve on one tree will also open the valve on the tree sharing this function, i.e. the following valves are operating by the same command:
SCSSV125931P and SCSSV125931Q
SCSSV135931P and SCSSV135931Q
This implies that the interlock sequences for these two wells are dependent on the position of valves on both Xmas trees.
2.11 Well Injectivity Decline
Injection of produced water can lead to a loss of injectivity of up to 40% relative to sea water injection. Generally, the “dirtier” the water injected, the greater the decline in injectivity. Thus, changing from produced water to sea water injection may restore original well injectivity. If a decline in well injectivity is experienced, it may be beneficial to revert to sea water injection for a period until injectivity rates are back to normal. During this time, all produced water would have to be discharged overboard. Further information on expected reservoir performance can be obtained from the Schiehallion Well Operating Handbook.
2.12 Water Injection Subsea Flowlines
The water injection seabed flowlines are rigid pipe of 10” diameter. A 1mm internal corrosion allowance has been included. No insulation is provided; however the pipelines are provided with a barrier coating for external corrosion protection. A system of sacrificial anodes supports the coating system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 50 of 158
2.13 Water Injection Wells
Water injection wells are not horizontal, but high angle. Flow calculations indicated that the majority of wells required 5 1/2” tubing, and some required 7" tubing, made of GRP-lined, carbon steel. Flow-wetted parts of crucial completion equipment such as the tubing-retrievable safety valve are made of 25% Cr for maximum reliability.
Other completion equipment is made of ceramic-coated carbon steel. Due to low reservoir temps (56°C), an expansion device is not required above the packer. If the wellhead is lost, downhole shut-in is achieved by a tubing-retrievable subsurface safety valve. In water injection wells completed below the oil-water contact (in a position where the well could not flow hydrocarbons if the wellhead was lost) the SSSV may be omitted from the completion. Nipples and profiles are included for testing the tubing, setting the packer and plugging the well for Xmas tree removal.
As in production wells the tailpipe below the packer is landed in a receptacle below the liner hanger. A permanent downhole gauge is not in the water injector as reservoir pressures can readily be calculated from wellhead pressures (which will always be higher than zero). For this purpose, a high-resolution injection xmas tree quartz gauge is specified.
Sand strengths are such that sand control is required in injectors to prevent sand fill due to possible cross flow during shut-in. sand control is achieved by using screens. On loyal, where sand strengths are slightly higher, cased and perforated injectors are installed instead, if necessary, for flow control.
Well Valve Status Date
IWV IMV SCSSV Date Time
CW10 Closed Closed Closed 03/05/2004 16:30
CW11 Closed Open Open 03/05/2004 16:30
CW12
CW13
CW15
CW16
CW17
CW18
CW19
WW04
WWO5
WWO6
WWO8
WW09
NW01
Closed
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Isol
Open
Open
Open
Open
Open
Isol
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Isol
Open
Open
03/05/2004
03/05/2004
03/05/2004
03/05/2004
03/05/2004
03/05/2004
03/05/2004
16:30
16:30
16:30
03/05/2004 16:30
03/05/2004 16:30
03/05/2004
03/05/2004
03/05/2004
03/05/2004
16:30
16:30
16:30
16:30
16:30
16:30
16:30
16:30
NW02
NW03
LW04
LW05
LW06
Isol
Isol
Isol
Isol
Open
Open
Isol
Open
Open
Open
Isol
Open
03/05/2004 16:30
03/05/2004 16:30
03/05/2004 16:30
03/05/2004 16:30
Pressure after 1 hour
SIWHP (bar)
68.8
49.7
80.5
19.8
41.7
54.5
70.1
43.2
109.3
37
38.2
68.4
68.5
Isol Open Open 03/05/2004 16:30 99.2
Table 10 Pressure Fall-off Final Pressure Record – May 2004
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 51 of 158
Cluster
North
Central
West
Loyal
North West *
* Proposed
Slot name DTI Name
CW10
CW11
CW12
CW13
CW15
CW16
CW17
CW18
CW 19
WW04
WW05
WW06
WW07
WW08
WW09
NW01
NW02
NW03
LW04
LW04A
LW05
LW06
LW10
LW11
FP03
FP04
FW01
FW02
FW03
C08
C02
C04
C09
C14
C16
C19
WS29
C21
W06
W07
W03
W05
W08
W09
N03
N02z
N01z
L02
L02A
L05
L06
TBC
TBC
TBC
TBC
TBC
TBC
TBC
Table 11 Water Injection Wells Summary
Zone
T31a/T31b
T31a
T31a/T34/T35
T31a
T31 a
T31 a
T31 a
T31 a
T31a
T34a/T34b/T31a
T31qa
T31a/T31b
T31a
T31a
T31 a
T34
T31 a
T31a
T35b
T35b
T35
T35
Duty
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Water Injector
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 52 of 158
The supply of seawater to and from the deaerator tower V-44101 is controlled by:
FIC-441001 (seawater inlet)
FIC-441019 (seawater outlet)
LIC-441010 (V-44101 seawater level).
During normal operation, the outlet flow from V-44101 (i.e. the demand of the water injection pumps P-45001A/B/C) is measured by FT-441019 and transmitted to FIC-441019.
FIC-441019 supplies a remote setpoint to FIC-441001 which modulates
FCV-441001, as required, to match inlet flow to outlet flow. LIC-441010 also has an input to FIC-441001 which affects the positioning of FCV-441001. In the event that the level in V-44101 falls below the setpoint of LIC-441010, this controller transmits a signal to FIC-441001 which tends to open FCV-441001 and increase the level in V-44101. Alternatively, when the level in V-44101 rises above the setpoint of LIC-441010 then a signal is transmitted which tends to close FCV-441001.
However, the operation of LIC441010 is ‘slow acting’ such that a small change in level does not immediately result in a signal being sent to FIC-441001.
FIC-441001 and FIC441019 are ‘fast acting’ controllers which are capable of responding quickly to changes in seawater demand and provide the main means of control of flow through V-44101. LIC441010 provides a ‘fine tuning’ control input which ‘smoothes’ the action of FIC-441001.
V-44101 has a 50% turndown capacity. When the demand of the water injection pumps P-45001A/B/C falls to less than 50% of the maximum throughput of
V-44101, the overboard dump valve FCV-441019 is opened, in response to a signal from FIC-441019.
Note: The control scheme described above ensures that the de-aeration system can cope with large changes in demand for seawater by the injection system.
FIC-441001 also provides output to the stroke control of the methanol injection pumps P-82601A/B to ensure that the amount of methanol injected for regeneration of the stripping gas (see below) is in proportion to seawater flow through V-44101. The calibration of the methanol pumps should be periodically checked to ensure that injection rates are correctly matched with seawater flow.
Refer to Z-8000-BB-4051 for details of the Methanol System.
Seawater outlet from V-44101 is continuously monitored for chlorine and oxygen content by AT-441017 and AT-441018 respectively.
Note: All actuated valves relay positional information to the CPS using limit switches, with the exception of control valves.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 53 of 158
The water injection stripping gas blowers P-44201A/B operate in duty/standby mode to draw stripping gas from V-44101. P-44201A/B suction pressure is controlled by the split level controller PIC-441021 which acts on PCV-441021
(vent valve) and PCV-441023 (nitrogen supply valve). Too high a suction pressure will cause PCV-441021 to open and relieve pressure via a local vent.
Too low a suction pressure will cause PCV-441023 to open and admit nitrogen into the suction line. The stripping gas supply to P-44201A/B is monitored by hydrocarbon analyser AI-441026 which will initiate and alarm if the hydrocarbon content of the gas exceeds a preset limit.
Instrument air must also be added to the stripping gas to ensure that the requirements of the de-oxidiser vessel reaction are met (i.e. sufficient oxygen is contained in the stripping gas to support the catalytic reaction in the de-oxidiser vessel). The addition of instrument air is controlled by FIC-441027 (locally compensated by TE-441029) acting on FCV-441027, in the instrument air supply line to provide a fixed flow of approximately 97.8 kg/hr.
The stripping gas blowers P-44201A/B can only be operated one at a time. Startup of the blowers is interlocked with level instrumentation in the deaerator tower to ensure that the blowers cannot be started until normal deaerator tower level has been established. The blowers are started via the CPS with no local start facility, however, local emergency stops are provided. The methanol supply to the
Minox reactor is interlocked with the stripping gas blowers running signal.
Addition of methanol without an established nitrogen flow through the deoxidiser could lead to excessive temperatures being generated in the vessel.
Discharge flow from P-44201A/B is monitored by flow transmitters FT-442008 and FT-442009 respectively. A minimum flowrate of 4410 kg/hr is required to ensure a sufficient volume of stripping gas is supplied to the deaerator tower. If the discharge falls below this minimum flowrate, FAL-442008 will initiate the automatic start-up of the standby blower. The electric start-up heater EEH-44201 is controlled by a gap action controller TIC-442015 which has a set point of
150
C. The heater is protected from overheating by TS-442017 and TS-442028 which initiate power isolation of the heater, via the MCC, if the heater temperature exceeds preset limits.
A high temperature in the deoxidiser indicates that there is an excess of oxygen or methanol in the vessel. If this temperature reaches 350C, the methanol feed will be shut off and the stripping gas blowers left running to quench the reaction to avoid potential damage to the vessel, which has a design temperature of 400C.
Pre-heating of the stripping gas, prior to it entering V-44201, is controlled by
TIC-442014 acting on TCV-442014 which is located in the heat exchanger bypass line. If the temperature exceeds the setpoint, TCV-442014 tends to open to increase the flow of gas through X-44201 bypass. If the temperature falls below the setpoint, the opposite applies.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 54 of 158
Water injection pumps suction pressure is determined by the operating pressure of the deaerator tower, and is approximately 5 barg. The booster pumps always discharge water into the suction line at the expense of de-aerated seawater drawn from the tower. The pump overboard dump valves will open to maintain a minimum flow of 600 m3/hr through each pump: the pumps are also equipped with low-low flow trips via transmitters FIT-450146/450246/450346 set at 200 m3/hr. The pump discharge valves XV-450146/246/346 are manually opened following pump start. These valves will close automatically on a pump trip, but will not close automatically on a normal pump stop. On a pump stop, the respective minimum flow overboard dump valve FCV-450145/245/345 will at first move to the open position, driven by the minimum flow controller. Following a time delay of 60 seconds the dump valve will then be driven closed by the CPS logic. Closing the dump valve after pump stop prevents water flowing through the non-running pump casing, and the delay ensures the FCV will close only after the discharge valve is fully closed to minimise transient/locked-in pressures.
On receipt of pump start signal, CPS will confirm that the main discharge valve is closed, (by reference to the limit switch), open the respective overboard dump valve, and send a signal to the pump ECP to initiate a pump start sequence.
Start-up Overrides
Field inputs which cause a trip and require plant to be running before the field measurement goes healthy, require a start-up override applied and then to be reset in the PSD system. This is achieved at the operator workstations:
1. On “Main System” graphic select “PSD”, this will display “PSD
Shutdown/Reset Page”.
2. On this page all the process systems status will be displayed, i.e. input trip, output trip etc. On this page at the bottom there is a button for “Start-up
Overrides Page 1”, “Start-up Overrides Page 2”, etc. Select the page required, the override can be applied on a process group basis or individually.
3. Return to “PSD Shutdown/Reset Page”. On this page against each process system there is a reset pushbutton. Operation of this pushbutton should clear all healthy field inputs which were active and the ones which require a start-up override. Input trips should change from red to green.
Relative Speed of Control Loops
Whilst running, it is important that the water injection pumps are always supplied with suction pressure whatever the injection demand. This pressure is primarily ensured by flow from the de-aeration system and specifically the de-aeration tower. The residence time in the base of the deaerator, at the design rate of
1890 m 3 /hr, between NLL and low alarm, is 15 seconds; between NLL and lowlow trip, around 25 seconds. The response of controllers FIC-441019 and FIC-
441001 must be fast enough to prevent system shutdown on step changes in demand, such as start-up (and shutdown) of pumps. LIC-441010, which acts to adjust for any miss-match between the flow measurement out and flow measurement in, should be slow relative to the flow loops, to minimise overcorrection. The speed of LIC-430010, which is responsible for injecting the produced water into the suction of the water injection pumps, should be relatively slow to avoid introducing large changes in the deaerator flow loops.
The split range operation of the degasser level control will cause excess produced water to be safely dumped overboard should the degasser be subjected to a rapid influx from the separation trains.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 55 of 158
The gas turbine control system functions are:
Sequence
Local Control
Protect
Local Display
Display pre selected parameters via serial link in the CCR.
Remote control pre selected parameters via hardwire from the CCR.
The turbine control panel is electrical switch-based and allows command input and indicates status. In addition to this when included a video display device exhibits control parameters.
Instrumentation is included in the turbine package to report operating conditions to control the system and control devices to receive control outputs from primary and backup control systems.
Pre selected parameters can be monitored via serial link in the CCR and pre selected parameters can be controlled via hard wire in the CCR.
Figure 10 shows the control system block diagram for the gas turbine and link with the CCR.
Sequence functions monitor and sense events and perform computations to operate components in the system. Sequence elements include:
Start
Load
Stop
Post lube
Start includes the following manual actions:
Arm the system: - turning on the electrical supply and resetting any alarm or shutdown malfunctions.
Reset malfunctions. Prior to start, all shutdown malfunctions must be cleared. Uncorrected shutdown malfunction prevent the package from being started. Only cool down and fast lockout malfunctions require clearing from the LER.
Select operating mode: Achieved by putting the OFF/LOCAL/ REMOTE key switch in a local or remote position. This package should always be remote operation and can only be started from the CCR.
The turbine should only be started from the CCR and the Solar Turbine
Control Panel has had the key removed to the central control room. The key can be issued from there under the permit to work system when required for maintenance access or following a “Cooldown Lockout” or
“Fast Stop Lockout”.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 56 of 158
Initiate start: In summary, once a start has been initiated the control system performs a lube and driven equipment system check, starts package fans, performs a fuel shutoff valve test and pre-crank status check.
In detail, when a Start is initiated the following occurs:
The fuel valve and lube pressures are checked, the purge is cranked, light off
(includes; torch ignition, combustion and acceleration to self sustaining speed), starter dropout and lube monitoring.
The pre-crank check comprises of lube system and seal checks, confirmation of lube oil pressure and fuel valve checks. On completion of this the engine is cranked.
Once the start is set the post-lube back up and pre/post-lube oil pumps start on a test cycle and the pre-lube timer starts, if a hot re-start is being performed the pre-lube pump test is not carried out. Following this the control system performs a pressure check on the gas fuel valves, to ensure that they open and close correctly and fuel pressure switch/transmitter signals are verified.
Purge crank rotates the engine with the starter to circulate air and to purge gas accumulated in the engine, air inlet and the exhaust duct. This reduces rotor bow caused by an extended inactive period; on hot starts it cools the gas turbine hot section. Once the purge crank is initiated the engine accelerates to a preset speed typically 10-18% and the crank timer begins. If the engine fails to reach
10-15% within this time the start sequence is aborted and the fail to crank alarm is initiated.
When the preset speed is reached the purge cycle and timer begin. Once the liquid purge timer times out the liquid purge valve closes. The engine accelerates, purging the engine, inlet and exhaust ducts. The crank duration is determined by the exhaust duct volume and after time out of the purge time the start cycle begins.
After light off, the fuel control valves gradually ramp open during the combustion of the fuel gas. The inlet guide vanes ramp open and the bleed valve gradually ramps closed based on the corrected engine speed. The bleed valve and the guide vanes control the airflow through the engine to prevent surge.
If the correct engine temperature is not reached before the ignition times out an ignition failure malfunction is enunciated and the start sequence aborted. Speed and load is sensed by the controlling fuel valve and is regulated to accelerate the engine and to increase the engine temperature.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 57 of 158
Operator control
REMOTE
CONTROL
CENTRAL CONTROL
ROOM
REMOTE
DATA
Figure 10 Gas Turbine Control Schematic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 58 of 158
Pump P-45001D is installed in parallel to the three existing electric-driven pumps and its control philosophy is similar to that of the current pumps with the additional facility to control the pump speed which can be adjusted to match the required water injection flow rate. New and modified graphics have been installed. The pump is started, controlled and stopped from the CCR. There is no requirement to operate the pump from the LER, except for emergency stop of the turbine.
Valve control functions on the Valve Access Platform are performed via the CPS system in the CCR. The Turbine Control Panel TCP) in the LER provides a dedicated control/monitoring facility for the gas turbine driven pump package, with common fault and trip reporting back to the CPS.
The water injection pumps suction pressure is determined by the operating pressure of the deaerator tower and is approximately 5 barg. The produced water booster pumps always discharge water into the suction line at the expense of de-aerated seawater drawn from the tower.
Minimum flow protection for the pump is provided by an overboard dump valve
FCV-450445, which will open at a predefined minimum flow of 330 m 3 /h to protect the pump from damage. The pump is also equipped with a low-low flow trip, FT-
450445 LL set at 280 m 3 /h.
The pump has a discharge double block & bleed valve isolation facility. The discharge valve, XV-450446, start up equalisation line valve, XV-450501 and overboard dump valve, FCV-450445 are actuated based on the pump start-up or shutdown sequence. To prevent high flow rate in the start up equalisation line, an orifice plate has been fitted. On receipt of a pump start signal, the CPS confirms that the main discharge valve is closed (by reference to the limit switch), open the respective overboard dump valve, and then send a signal to the Pump’s Electric
Control Panel (ECP) to initiate the pump start sequence. The differential pressure across the actuated discharge valve will be monitored to provide a permissive to open the valve.
The existing pumps operate against backpressure from the wells and provide a water injection rate and discharge pressure as required by the system. When the
DP between the outlet PT-450443 and the inlet PT-450441 to the pump is less than 2.0 bar, the minimum flow control valve FCV-450445 is shut and the minimum flow controller FIC-450445 is inhibited. When the DP is larger than 2.0 bar, the minimum flow controller is activated and FCV-450445 is allowed to operate under automatic control. The minimum flow 330 m 3 /hr is achieved in a pre-determined time to prevent pump damage. This arrangement indicates when the pump has started ‘pumping’.
4 th Water Injection Pump Start-up Overrides
The 4 th water injection pump package is independently controlled by an associated TCP. The CPS provides routine control functions, which are carried out from the CCR. Start-up overrides are:
TA 850005 LL (fuel gas system)
TA 850006 LL (fuel gas system)
PA 850005 LL (fuel gas system)
PA 450444 LL (pump suction side)
FA 450446 LL (pump discharge side)
These are automatically set and removed by the control system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 59 of 158
Figure 11 CCR Start-up Override Graphic
The subsea valves operated from the FPSO are:
Wing Valves
Upper Master Valve
SSSV
Annulus Master Valve
Crossover valve
These valves have a ROV override. Subsea valves operated by ROV are:
Choke Valves
Lower Master Valve
Vent valves (downstream of swab valves)
All WI manifold valves.
The choke is adjusted by ROV from the intervention vessel when the associated well is on-line. The swab valves (annulus and tubing) are remotely operated but only from an intervention vessel and not from the FPSO. These valves provide flow paths into the water injection well for the intervention rig and are only required to be operated when such work is ongoing. They must remain under control from the intervention vessel and therefore cannot be operated from the
FPSO. The swab valves remain closed when the well is under control from the
FPSO and they have no part to play in any operational scenario. It should be noted that once the workover riser is connected through the tree cap then all actuated tree valves operable from the FPSO are operable from the Intervention
Vessel.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 60 of 158
5
6
7
8
9
Step
1
2
3
4
10
11
12
13
14
15
16
17
Procedure
Confirm that water injection system is mechanically complete and that all associated Work Permits have been closed out.
Purge deaerator tower if required.
Note: Purging must be carried out following intrusive maintenance.
Purging is not required if the system is to be started after a short-term shutdown (i.e. with a normal operating seawater level in the deaerator).
Confirm that turret and subsea system are prepared for water injection.
Confirm that the manual valves are positioned as detailed in the ‘Startup’ column of the Valve Position Tables.
Confirm that instrument air supply is available.
Confirm that the seawater distribution system is operational.
Confirm that a methanol supply is available to the de-aeration package.
Confirm that a nitrogen supply is available to the de-aeration package.
Confirm that power is available to the water injection pumps from the HV switchroom (switchboard SWBDB(P)) as below:
P-45001A - cubicle A
P-45001B - cubicle W
P-45001C - cubicle X.
Confirm that power is available to the auxiliary lube oil pumps (water injection pumping packages) from the LV aft switchroom (440V switchboard SWBDA(P)) as listed below:
P-45002A - cubicle BF3
P-45002B - cubicle AHR5
P-45002C - cubicle BF11.
Confirm that power is available to the water injection pumps’ lube oil heaters EEH-45001A/B/C from EDB-83801 in the LV aft switchroom.
Confirm that power is available to the stripping gas blowers from the LV aft switchroom (440V switchboard SWBDA(P)) :
P-44201A - cubicle DF8
P-44201B - cubicle AGR8.
Confirm that power is available to the de-oxidiser vessel start-up heater
EEH-44201 from the LV aft switchroom (440V switchboard SWBDA(P) - cubicle LR5).
Confirm that the de-aeration package trace heating system is operational.
Confirm that FIC-441001 is set to manual and that FCV-441001 and
FCV-441019 are closed.
Confirm that power is available for 4 th Water Injection pump and gas turbine auxiliaries, control systems and the fuel gas heater.
Confirm that the following shutdown valves are closed.
XV-441024 - nitrogen supply
XV-442026 - methanol supply
XV-441028 - air supply.
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 61 of 158
4.2 De-aerator Package Purge Procedure
Step
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Procedure
Confirm that water injection system is mechanically complete and that all associated Work Permits have been closed-out.
Ensure that the following shutdown valves are closed as listed below:
XV-441024 - nitrogen supply
XV-442026 - methanol supply
XV-441028 - air supply
XXV-441040 - V-44101 seawater inlet.
Ensure shutdown valve XXV-441002 (V-44101 seawater inlet) is open.
Ensure the manual valves on the package chemical injection lines are closed as listed below:
HV-441002 - biocide (V-44101 seawater inlet)
HV-441003 - antifoam (V-44101 seawater inlet)
HV-441088 - scale inhibitor (V-44101 water outlet)
HV-441019 - O
2
scavenger (V-44101 produced water inlet).
Ensure V-44101 manual vent line valves HV-441024 and HV-441025 are closed.
Ensure stripping gas de-oxidiser vessel manual vent valves HV-442029 and HV-442030 are closed.
Ensure HV-441016 (V-44101 water outlet) is open.
Ensure that HV-441017 (V-44101 produced water inlet) is closed.
Ensure that HV-441014 (V-44101 overboard dump line) is closed.
Set PIC441021 to ‘manual’ and ensure that PCV-441021 (nitrogen/air supply line vent valve) is closed.
Ensure stripping gas exchanger X-44201 bypass valves HV-442040 and
HV-442041 are open.
Set TIC442014 to ‘manual’ and ensure TCV-442014 is open.
Ensure de-oxidiser vessel outlet valve HV-442035 is open.
Ensure nitrogen supply manual block valves HV-441063 and HV-441065 are open.
Ensure stripping gas blowers’ P-44201A/B isolation valves are open:
HV-442001 and HV-442006 (P-44201A)
HV-442007 and HV-442012 (P-44201B).
Connect a temporary nitrogen hose to HV-442026 on the stripping gas exchanger X-44201 and open the utility station nitrogen valve to charge the hose.
Note: The system is now lined-up and prepared for purging.
CAUTION: Ensure that the start-up heater EEH-44201 is not energised throughout the purging procedure as this could result in excessive nitrogen temperatures which would damage the deaerator tower packing .
Open HV-442026 to begin nitrogen purge. Monitor pressure using PG-
441022 (V-44101 stripping gas outlet line) until the pressure reaches approximately 1.5 barg and then close HV-442026.
Note: Although system purging causes a reverse flow across the catalyst bed in V-44201, this should not cause any damage to the bed.
Open HV-441024 and HV-441025 in V-44101 manual vent line to depressurise the system and then close these valves.
Repeat steps 17 and 18 twice.
On completion of purging confirm that HV-441024, HV-441025 and HV-
442026 are closed.
Remove nitrogen hose and re-fit blank flange to HV-442026.
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 62 of 158
4.3 De-aerator Package Start-up
Step
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Procedure
Carry Pre-start Checks.
Confirm XXV-441002 (deaerator inlet) is open, then open XXV-441040.
Slowly open FCV-441001 to allow flow to V-44101 and set FIC-441001 to ‘auto’ when the control valve is open. FCV-441001 must be opened slowly to avoid water hammer.
Set FIC-441001 setpoint to approximately 945 m 3 /h so that all flow through V-44101 can pass through the overboard dump line. This is set by adjusting FIC-441019. The flow should be greater than the water injection pump(s) minimum flow.
Set controllers LIC-441010, FIC-441001 and FIC441019 to ‘auto’.
Note: LIC-441010 will send a diminishing signal to FIC-441001 as V-
44101 reached its normal operating level. This will cause
FCV-441001 to close. FCV-441019 in the overboard dump line will tend to open to maintain V-44101 level and establish flow though V-44101. FCV-441001 is a fail-closed control valve while FCV-441019 fails open.
CAUTION: Seawater circulation must be established before starting nitrogen circulation as heat generated by P-
44201A/B could cause localised overheating of V-44101 packing.
Confirm that TIC-442014 (de-oxidiser vessel V-44201 temperature controller) is set to ‘auto’.
Confirm that PIC-441021 (stripping gas blowers supply pressure controller) is set to ‘auto’ and controlling at a pressure of approx. 6 barg.
Open XV-441024 in the nitrogen supply line.
Confirm that FIC441027 is in ‘auto’ and then open XV-441028 in the air supply line.
Confirm that FIC-441001 is maintaining a seawater flow through V-
44101 of approximately 945 m3/h.
Confirm that FALL-442009 (stripping gas blowers discharge flow) is inhibited using the start-up over-ride and the PSD reset.
Start duty blower and monitor FI-442008 to confirm flow through X-
44201 and V-44201. Each of the blowers should not be started more than four times in any one hour period.
Note: The minimum nitrogen flow required prior to energising the startup heater EEH-44201 is 50% of the design flowrate 2450 kg/h.
Energise the start-up heater EEH-44201.
Note: EEH-44201 is controlled by the gap action controller TIC-442015 when temperature in V-44201 exceeds 150
C. It is anticipated that preheating should continue for 1-2 hours to ensure uniform heating of the catalyst bed is achieved.
Circulate stripping gas with the heater on for 1 hour to ensure the temperature is uniform throughout the bed and no longer rising. It will probably settle out at 45 50°C from a cold start.
15 Confirm that HV-442021 is open and then open XV-442026 to establish methanol flow to upstream of X-44201. Ramp up te methanol flow to 50 l/h over 30 minutes.
Note: Flow from the ‘Minox’ methanol pumps is controlled by FIC-
441001 which varies pump stroke length dependent on the flow through the deaerator tower.
Note: During start-up, the methanol injection rate should be manually controlled to provide a gradual increase in methanol flow until the setpoint is reached. The resulting exothermic reaction in V-42201 will initially only occur local to the start-up heater until the flow of stripping gas produces a uniform temperature across the catalyst bed.
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 63 of 158
4.3 De-aerator Package Start-up (continued)
Step
16
17
18
19
Procedure
Monitor the temperature in V-44201 and when the exit temperature reaches 250
C, set the methanol flow to maintain this temperature.
Dosing rates are controlled by FIC-441001.
Note: To ensure complete catalytic reaction, a 10% excess of methanol is injected.
Remove standby stripping gas blower inhibit when stripping gas flow is established.
Establish chemical injection, if required, by opening injection point valves as listed below:
HV-441121 - calcium nitrate(V-44101 seawater inlet)
HV-441003 - antifoam (V-44101 seawater inlet)
HV-441088 - scale inhibitor (V-44101 water outlet)
HV-441019 - O
2
scavenger (V-44101 produced water inlet).
Note: O
2
scavenger injection is required if the de-aeration package fails to reduce the oxygen content of the seawater to below
20 ppb (vol). The use of oxygen scavenger impacts on the type and amount of other chemicals used.
Monitor the oxygen content of the treated seawater using AI-441018.
Note: When the oxygen content has been reduced to below 20 ppb
(vol), the water injection pumps can be started.
Signature
Prior to starting the pumps, the deaerator package must in operation, the oxygen content of the seawater be below 20 ppb (vol) and treated water be routed overboard via FCV-441019. Start-up of the water injection system is based around the following requirements:
Ensuring the main water injection pumps are not started against a vacuum condition in the injection riser.
Ensuring that the water injection wing valves are open against a low differential pressure.
To achieve these aims, the produced water booster pumps or seawater lift pumps are used to overcome any vacuum condition prior to starting the main pumps, but with the main pump discharge open to allow flow. To prevent wear on the water injection wing valves, these are opened after the system has been pressurised with the produced water booster pumps or seawater lift pumps, but prior to the start-up of the main pumps.
Start Permissives
The motor-driven water injection pumps can be started in one of three ways dependant upon mode selection at the electrical control panel (ECP):
Manual The main drive motor & auxiliary lube oil pumps are manually started/stopped via their start/stop pushbutton on the front of the
ECP. Manual control is for maintenance/testing purposes only.
ECP Auto On operation of the injection pump start pushbutton on the ECP, the auxiliary lube oil pump is automatically started. Once lube oil pressure is established, the main drive motor automatically starts.
CPS Auto The main drive and all auxiliaries are automatically started on receipt of a start command from CPS.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 64 of 158
LOCAL/CPS START
Assuming all on-skid trips and PSD/ESD trips are healthy and all necessary drives available, the pumps can be started. Irrespective of start mode, the “CPS start permissive” is required. The “CPS start permissive” is dependent on:
suction pressure above 3 barg (measured by loop PI-450141)
discharge valve closed XV-450146)
activation of operator pushbutton.
This “CPS start permissive” is only valid for 20 minutes, if the pump has not started by then it times out and the operator must reactivate the CPS pushbutton
(assuming the valve position and pressure have not changed).
Local Start : for either Manual or ECP Auto only the “CPS start permissive” is required, all other status/indication can be monitored at the ECP.
CPS Start : on the water injection start sequence pop-up, the following indications aid start:
“Water injection pump available” - indication from ECP that all onskid trips have been reset and start permissives are healthy
“Injection pump CPS start available” - indication from ECP that
“CPS Auto” has been selected
Operati on off the “CPS start permissive” and then “Start” on the pop-up start the pump
“Start sequence initiated” - indicates pump is in a start sequence
“Water injection pump online” - this indicates the pump start sequence is complete.
Upon receipt of the pump running signal, CPS drives the overboard dump valve
FCV-450145 fully open for 20 seconds. Thereafter the FIC is placed in auto FCV to control the FCV. The water goes overboard until the discharge valve XV-
450146 is manually opened via CPS and forward flow to the turret is established.
Start Sequence Summary
1. Pump Stopped.
2. Pump Permitted to Start AND (ECP Mode AND Start P/B) OR (CPS Mode
AND Remote Start).
3. Start Aux Lube Oil Pump, Reset Low Lube Oil Press Alarm, Injection Pump
Sequence Initiated Sent to CPS.
4. Lube Oil established and Aux. Pump Running, Start Timer running (10 secs).
5. Main Injection Pump Main Drive Started. Confirmed Running.
6. Command Discharge Valve to Open, enable minimum Flow Valve Control.
Repeat Pump Running to CPS. Remove Lube Oil Override.
7. Discharge Pressure Established.
8. Start Timer Initiated ( 10 Sec,)
9. Stop Auxiliary Lube Oil Pump. Start Sequence Complete.
The required water injection rate is set by the position of the ROV-operated subsea choke valves on each water injection wellhead.
All stops are operable regardless of mode selected. The mode selector is keyoperated, the key being removable when in “CPS Auto”.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 65 of 158
Water Injection Pumps P-45001A/B/C Startup Checklist Summary
Step
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Procedure
Confirm that the water injection pumps P-45001A/B/C are prepared for operation. This procedure covers start-up of water injection using a single injection pump A, B or C. Additional pumps can be started as required when injection flow is established.
Ensure that water injection riser(s) are correctly lined up, eg:
Schiehallion Central riser selected:
HV-180855 open - riser 10” block valve
HV-180853 closed - NRV bypass 2” globe valve
Schiehallion West, North and Loyal riser selected:
HV-182855 open - riser 10” block valve
HV-182853 closed - NRV bypass 2 “ globe valve
HV-181503 open - riser 12” block valve
Check pressure downstream of the injection pumps using PI-450001.
Note: If the pressure exceeds 5 bar, the water injection pump can be started and steps 4, 6, 7 and 8 below can be ignored.
Confirm that injection pumps are fully primed. Vent valves on pump’s suction and discharge lines can be used to purge air from the pump.
Confirm associated lube oil pumps are running.
Open pump equalisation line valves to charge the water injection system to 5 bar (i.e. de-aerator pressure). (HV-450133/4 or HV-450233/4 or HV-
450333/4).
Monitor de-aerator tower level as water injection system is charged.
After charging to 5 bar, close the pump equalisation line valves. (HV-
450133/4 or HV-450233/4 or HV-450333/4).
Start injection pump using correct start mode and sequence.
Note: Pump discharge valve should be closed and pump discharge water routed overboard via the minimum flow recycle valve.
Commence injection of Scale Inhibitor by opening HV-441088 (V-44101 water outlet).
Open pump discharge valve equalising line (HV-450133/4 or HV-450233/4 or HV-450333/4) to charge the subsea system to 250 barg on PI-450001.
When subsea system is charged, close the equalising line and open the pump discharge valve (XV-450146 or XV-450246 or XV-450346).
For selected injection well, confirm well’s upper master valve is open.
Notes: Software interlocks prevent the upper master valve being opened unless the wing valve is closed.
Subsea valves and indications are provided at the subsea
Master Control Station (MCS).
For the selected injection well, open annulus master valve.
For the selected injection well, open the wing valve.
Note: Software interlocks prevent the wing valve being opened unless the upper master valve is also opened.
Monitor FI-xxx929N to confirm flow into the injection well
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 66 of 158
Step
17
18
19
20
21
22
23
24
25
Procedure
For the selected injection well, confirm that the surface controlled subsea safety valve (SCSSV) is open.
Note: Software interlocks prevent the SCSSV being opened unless the wing valve and the upper master valve are open.
Monitor annulus pressure using PI-xxx923N until the injection water temperature (TI-xxx922N) stabilises. The allowable annulus pressure range is 0 to 310 barg.
If annulus pressure outside acceptable range, close injection wing valve.
Open crossover valve to equalise pressure.
Once pressure has equalised, close crossover valve and open wing valve to continue injection.
Record pressure downstream of the choke (PI-xxx922N) and the injection flowrate (FI-xxx929N)
Plot pressure and flow readings on graph provided with the Well
Operating Limits, associated with the selected injection well, to determine whether operating conditions are within the allowable range.
If conditions are outside allowable ranges, stop injection and report findings.
If required, open additional injection wells.
Start additional pump(s) as required while monitoring injection pressures and flow rates and confirming that conditions at each well are with acceptable operating limits.
Signature
WARNING: Before starting the pump drive engine, contact maintenance personnel or verify from written records that all maintenance items have been completed. A physical inspection should be performed by walking around the package to verify that there are no maintenance tags attached to any equipment, that indicate equipment should not be energised or started. Injury to personnel or damage to equipment may result if this Warning is not observed.
The following pre-start checks should be performed prior to each engine start.
The combination of pre-start checks, start procedure and post start procedure should reveal any abnormal conditions that may affect package performance:
Turbine package and gearbox
Water Injection Pump D
Local Control Room LER - (the pressurisation and ventilation system is
primarily controlled from a pressurisation / F&G system that comprises two EE xd-rated panels. The control panel also interfaces with F&G devices within the turbine enclosure)
Control System
There is a permissive to start in the fuel gas system: if the fuel gas temperature is above 10 o C upstream of XV-850005, permissive to open
XV-850005 will be given even at the maximum delta P across the PCV-
850012, i.e. 55barg –1 barg = 54 bar. If the fuel gas temperature is below
10 o C and the pressure above 17 barg downstream of PCV-850012 or the delta P is less than 38 bar across the PCV-850012, then a permissive to open XV-850005 will be given.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 67 of 158
Gas Turbine Pre-Start Checks
Step
1
2
3
4
5
Procedure
Confirm that the gas turbine and auxiliary system are mechanically complete and that all associated work permits have been closed-out.
Verify that the water seals from the oil cooler drip pan are filled with water and valves are open.
Verify that the water seal from the oil filter drain is filled with water and the valve is open.
Verify that water seals from the combustion air coalescer and turbine enclosure HVAC intake coalescers are water filled.
Verify that the valves from the lube oil system are closed. HV-864513,
HV-864514, HV-864515. Reference drg: 37W022F0146-A-8000-GP-
0090.02-2C.
Confirm that instrument air supply is available. 6
7
8
Confirm that the Fuel gas supply is available.
Confirm that the cooling medium is available
9 Confirm that the flare system is available.
10 Confirm that the open drain is available.
11 Confirm that power is available from the switch room.
12 Check inside the turbine enclosure for any signs of leakage.
13 Close Enclosure doors.
14 Confirm that the enclosure F&G system is operational,
15 Confirm that CO2 deluge cylinders are charged and armed.
16 Start selected enclosure ventilation fan and confirm flow rate is acceptable by checking that the correct pressure is being maintained using the operating pressure transmitter
Gear Box Pre-Start Checks
Step
1
Procedure
Confirm that the gearbox is mechanically complete and that all associated work permits have been closed-out.
Local Control Room
Step
1
2
Procedure
Confirm that all associated work Permits are closed out.
Confirm HVAC air fan is running and that the fan and air pressure is being sustained and is remaining above the LER set point. (Indication lights should be green.)
Control System
Step Procedure
1 Confirm that all associated work permits have been closed-out.
Valve Access Platform
Step
1
Procedure
Verify that the fence area on the main walk way below the valve access platform is intact and present to prevent water up to 60 o C dripping on to personnel during start up.
Pump D Pre-Start Checks include:
Step
1
2
3
4
5
Procedure
Confirm that the water injection system is mechanically complete and that all associated Work Permits have been closed out.
Confirm that the manual valves for the pump are positioned for normal operation as detailed in this document.
Confirm that valves XV-450501, XV-450446 & FCV-450445 are shut.
Confirm that the pump is fully primed. If necessary use the vent valves on the pump’s suction and discharge lines to purge air from the pump.
Confirm pump casing drain valve HV-450443 is closed.
Confirm that all instrument impulse line valves are open.
Signature
Signature
Signature
Signature
Signature
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 68 of 158
Pump D start-up logic is dependant on the turbine start-up sequence, which is divided in to five main sections as shown by the start graphic in Figure 10 .
1 Request Permissive to Start the Turbine is firstly initiated from the start-up graphic by pressing the push button (XHS-450450). A signal is sent to set up the following valve positions:
Pump Discharge Valve, XV-450446 SHUT
Pump Discharge Equalisation valve, XV-450501 SHUT
Turbine Fuel Gas Supply Valve, XV-850005 OPEN
Set Start-up overrides
If the fuel gas temperature in the supply system is above 10 o C upstream of XV-
850005, permissive to open XV-850005 will be given even at the maximum delta
P across the PCV-850012, i.e. 55barg –1 barg = 54 bar.
If the fuel gas supply temperature is below 10 o C and the pressure above 17 barg downstream of PCV-850012 or the delta P is less than 38 bar across the PCV-
850012, then a permissive to open XV-850005 will be given.
Once the Request Permissive to Start the Turbine is initiated there may be a requirement for the water injection PSD Reset button to be pressed depending on the status of the 4 th water injection system trips; e.g. if trips exist, overrides will be required to be set before enabling reactivation of valves XV-450446, XV-450501 and XV-850005.
2 Permissive to Start the Turbine is given once the status of the valve positions is checked by the PLC:
Pump discharge valve XV-450446 confirmed closed
Pump discharge equalisation valve XV-450501 confirmed closed
Turbine fuel gas supply valve XV-850005 confirmed open.
In addition, the PLC will check whether the permissive to start the turbine is given by the Solar Turbine Control Panel or not. This permissive is indicated by XI-
450407. All required permissives are indicated on the start-up graphic when they are fulfilled. The request to start turbine to idle will only be given once the
Request to Start Turbine to Idle push button XHS-450451 has been pressed.
Once all the permissives are healthy XI450450 illuminates, which is ‘permissive to start’. This will be valid for 20 minutes; if this is exceeded and the request to start the turbine is not given the following will occur;
XV-850005 closes
Start up overrides, which were set will be removed.
3 Request to Start Turbine to Idle from the start graphic may be requested by using XHS-450451 pushbutton (when the start permissive is active). On detection of this, the TCP will proceed through the start sequence to bring the turbine to
70% of the design speed. A start request indication will be displayed through XI-
450408. Simultaneously, a request is sent to switch on the Fuel Gas Heater
ETP-85002. When the speed has reached idle status, the Solar Turbine Control
Panel will send a signal back to the CPS to indicate that the turbine is “ready to load
” through XI-450430. This forms the feed forward permissive.
When the differential pressure across the pump is larger than 2.0 bar, the minimum flow controller FIC-450445 will be activated and the FCV-450445 will be allowed to operate under automatic control. The minimum flow of 330 m 3 /hr will be achieved in a pre-determined time to prevent pump damage.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 69 of 158
4 Request to Feed Forward Flow : When the turbine is ready to load the operator operates the Feed Forward pushbutton (XHS-450452) from the start-up screen.
When this has been initiated, the startup graphics indicate “Request to Feed” status through XI-450452. Feed Forward is based on the differential pressure across the discharge valve XV-450446 (Differential Pressure Indicator PDI-
450446). There are two routes:
If the differential pressure is positive (the discharge pressure is greater than the downstream pressure) the discharge equalisation valve XV-
450501 opens. The downstream pressure will slowly increase. When the differential pressure is less than two bar the discharge valve XV-450446 opens; once fully open the equalisation valve XV-450501 is closed.
If the differential pressure is negative (the discharge pressure is lower than the downstream pressure) the turbine set point will be increased using the SIC-450453 until the differential pressure is less than 2 bar. At this point, the CPS logic will open the discharge valve XV-450446.
Once the normal Feed Forward is established, the pump speed will be manually entered from the Control and Safety System (C&SS). The CPS logic will switch
SIC-450453 from auto to manual control mode and XI-450453 will indicate the set point speed of the turbine.
5 Request to Trip Turbine to Idle : To trip the turbine to idle pushbutton XHS-
450454 must be operated. This will generate an on screen indication that a Trip
Turbine to Idle has been requested. On detection of XHS-450454 the CPS will close XV-450446 and XV-450501 after a 30 second time delay. The CPS output
XHS-450454 sends a signal to the TCP which will proceed through the slow to idle sequence and bring the pump to idle speed. As XV-450446 closes, FIC-
450445 and FCV-450445 will open under PID (Proportional, Integral and
Derivative) control to protect the pump against low flow rates.
A cool down signal, indicated by XI-450410, will be generated to indicate a trip to idle/ Normal stop has occurred. The TCP will remain at idle for 3 hours before performing a full stop sequence, unless the feed forward button is pressed within the 180 mins. Restart to Feed Forward can only occur under these conditions:
XV-450446 CLOSED
XV-450501 CLOSED
Turbine tripped to idle.
Once feed forward is re-activated, the CPS will automatically bring the turbine up to idle speed and ‘ready to load’ before ‘re-feeding forward’.
Start faults may include:
Permissive not given to open the inlet fuel gas valve XV-850005
Fault: The gas from the fuel gas heaters is less than 10 o C and 17 barg, and too cold to enter the engine burner management system
Correction:
P&ID drawing: 37W022f0146-A-8000-GP-0090.00-2C
Open valve HV-850538 and HV-850539 until permission is given.
Permissive not given start the turbine
Fault: Fast stop or Cooldown lock-outs have occurred
Correction: Reset LER acknowledge & reset switches.
Table 12 Water Injection Pump P-45001 Gas Turbine Start Faults
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 70 of 158
Figure 12 shows the turbine start-up graphic displayed in the CCR and can be found in the screen f or pump “C” and “D”, Figure 13.
Figure 12 CCR Turbine Start-up Graphic
Figure 13 CCR Graphic Display Screen for Water Injection Pumps C & D
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 71 of 158
Refer to P&ID L-8000-GP-0046.03, A-8000-GP-0090.02.
Pump P-45001D valve positions for start-up and normal operation are listed below:
Valve Tag No.
HV-450527
HV-450501
HV-450502
HV- 450505
HV-450506
HV-450411
HV-450412
HV-450513
HV-450514
HV-450515
HV-450522
HV-450521
HV-450525
HV-450526
Description
P-45001D suction vent valve
P-45001D suction block valve
P-45001D suction drain valve
P-45001D air vent block valve
P-45001D discharge vent valve
P-45001D discharge drain valve
P-45001D suction automatic air vent valve
XV- 450446 (P45001D) drain valve
XV-450446 (P45001D) block valve
XV-450501 (P45001D) drain valve
FCV-450445 (P45001D) block valve
XV-450501 (P45001D) block valve
P-45001D vent system
P-45001D Bypass vent
Start-up
Position
Closed
Open
Closed
Open
Closed
Closed and blanked off
Open
Closed and blanked off
Open
Closed
(Locked)
Open
Open
Closed
Closed
Pump P-45001D turbine valve positions for start-up and normal operation are:
Normal
Operation
Closed
Open
Closed
Closed
Closed
Closed and blanked off
Closed
Closed and blanked off
Open
Closed
(Locked)
Open
Open
Closed
Closed
Valve Tag
Number
HV-804807
HV-520503
HV-520510
HV-520511
HV-815502
HV-815503
HV-815515
Description
G-45001 instrument air block valve
G-45001 LP flare block valve
G-45001 LP flare drain line
G-45001 LP flare drain line
G-45001 cooling medium supply valve
X-45003 cooling medium drain valve
G-45001 cooling medium return block valve
Start-up
Position
Open
Open
Closed
Closed
Open
Closed and blanked off
Open
Normal
Operation
Open
Open
Closed
Closed
Open
Closed and blanked off
Open
HV-815514 G-45001 cooling medium return drain valve
HV-864510
HV-864516
G-45001 oil origin drain valve
G-45001 oil train drain valve
Closed and blanked off
Closed
Closed
Closed and blanked off
Closed
Closed
HV-864511
HV-864512
HV-864518
HV-864513
HV-864514
HV-864515
G-45001 lube oil filter drain valve
G-45001 combustion drain valve
G-45001 sampling Valve
G-45001 lube oil tank drain valve
G-45001 lube oil tank drain valve
G-45001 lube oil tank drain valve
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 72 of 158
If unburnt fuel or other combustibles are present in the exhaust system they may ignite and cause damage. Fuel may accumulate in the exhaust system before a start or after an engine flameout or ignition failure. Hence, the exhaust system must be purged by following the procedure below.
The internal free volume of the exhaust path to be purged is 1236 cu ft.
A purge of a minimum 3 air changes in the exhaust is required.
Ensure that the normal gas producer speed (NGP) is reached during the purge crank. Minimum speed is 15% and recommended speed is 20-25%.
Purging must not occur at speeds greater than 25%.
Purge Air Flow:
Crank Speed (NGP)
15%
20%
25%
Air Flow, SCFM
2250
3000
3750
Purge Crank time required is calculated to be: 98 seconds (based on a crank speed of 15%)
The advised minimum purge time is 240 seconds.
In addition, the following should be checked on a continuous basis:
Properly maintain and adjust all gas turbine, controls and exhaust system as recommended by the manufacturer.
If the engine is to be started after an engine flameout it must be ensured that all corrective measures have been taken to correct any root causes for the failure before any attempt is made to restart.
Ensure that any exhaust gas valves are installed correctly and are working properly; particularly the free passage of exhaust gas to the atmosphere must be maintained during the engine start-up and operation.
Ensure that the exhaust collector and the exhaust system liquid drains are operating properly.
Maintain fuel quality. Any deviation from the required specification could lead to a malfunction of the fuel control system.
th
Step
1
2
3
4
5
6
The table below describes the start-up sequence on the turbine control panel in the LER, before the gas turbine can be started from the CCR.
Procedure
Ensure all relevant personnel are aware that the 4 th water injection pump is about to be started. Make a tannoy announcement.
Get the key to the turbine control panel from the CCR, under Permit to
Work
Rotate OFF/LOCAL/REMOTE Key switch (S101) to LOCAL position.
Verify LOCAL Light (DS101) is illuminated.
Select Operation Summary display screen.
Press LAMP TEST switch (S113). Verify all indicator lights illuminate.
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 73 of 158
7
8
9
10
11
12
13
14
Press and release the ACKNOWLEDGE Switch (S117) and then press and release RESET Switch (S114) to acknowledge and clear any alarm or shutdown indications.
Select alarm summary display screen and check for alarm and shutdown indications. Correct any alarm and shutdown indications that remains
Verify that AUTO/MANUAL switch is in AUTO
Verify READY light (DS177) illuminates and [Ready] is highlighted on
Operation Summary Display screen
Rotate OFF/LOCAL/REMOTE keyswitch (S101) to REMOTE position.
Verify that “Ready to start” light turns green on the start up screen for the turbine in the CCR.
Check fuel gas pressure on the LER control panel.
Return the key to the turbine control panel back to the CCR under Permit to Work.
Note: If any malfunctions remain the READY light will not illuminate. If this occurs the malfunction must be corrected and the ACKNOWLEDGE
Switch and RESET Switch (S114) must be pressed again to reset the malfunction circuit.
WARNING: The turbine package is now ready for operation from the CCR.
When the turbine is “ready to start”, “running” and “stopping”, DO NOT
ROTATE the OFF/LOCAL/REMOTE keyswitch (S101) to the LOCAL position.
If the switch is rotated to the LOCAL position all remote operation functions cease and all control is lost between turbine package and CCR.
When the turbine has totally stopped the OFF/LOCAL/REMOTE keyswitch
(S101) can be rotated to the LOCAL position.
On the turbine control panel there is a START Switch (S110) that has been disabled. The reason for this is that if the turbine is started from the LER, the water injection pump may be damaged.
The Key to the turbine control panel is held in the CCR and can only be used under a Permit to Work. Under normal operation, Keyswitch S101 should be in the REMOTE position at all times.
Note: Finally perform the post start sequence and compare against norms. If significant deviations are present shut down the engine and determine the cause.
The control system monitors the temperatures, system pressures, engine speed, vibration levels and other indicators. It also provides throttling (fuel topping) to compensate if parameters are exceeded, indicators for malfunctions on the operator display, and displays alarms providing automatic control of the engine shutdown and the post lube unit.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 74 of 158
Reference drawing: 37W022F0146-A-8000-GP-0090.01-2C
As Schiehallion’s environment contains salt, cleaning needs special care. Online cleaning must be systematic not sporadic. If cleaning is sporadic, concentrated salt deposits will accumulate in the air compressor and then online cleaning will send a ‘slug’ of salt through the turbine. The slug acts as a catalyst for other contaminants provoking an erosive reaction. Frequent on-line washing will be required to prevent the build up of salt deposits.
2
3
4
It must be verified prior to cleaning that the Demineralised water plant is in operation, to ensure a Wash water supply.
The cleaning system must be flushed prior to use to ensure all debris is removed and to pressure check for leaks. Flush out as follows:
Step
1
2
3
4
5
6
7
8
9
10
11
12
13
Procedure
Check that the water inlet that connects the demineralised water source and the tank water inlet is opened.
Open the following valves: HV-803700, HV-803711, HV-803701, HV-
803702 and control the water rate by HV-803710.
The vent valve is also opened and the tank filled with water until it begins to flow out of the vent valve.
Open valve HV-530501, vent line on the skid
Close the water inlet.
Close the following valves: HV-803700, HV-803711, HV-803701, HV-
803702 and globe HV-803710
Close the vent valve HV-530501
Open the on-line air inlet valve to pressurize the tank to normal working air pressure 6.9 barg and then close the air inlet valve.
Open valve HV-804805 and HV-804808.
Leave the tank under pressure for 10 minutes. There should be no pressure drop or leakage to any of the fittings.
Slowly open the drain valve and allow the water to safely run to the drain until the tank pressure is zero.
Open valve HV-864517
Close the drain valve, remove and clean and replace filter inserts from the air water and chemical Y inlet strainers
Close valve HV-864517
Signature
14
Engine on-crank or on-line wash nozzle/manifold ring assembly pressure is checked thus:
Step
1
Procedure
Open the demineralised water inlet valve and the vent valve and half fill the tank.
Open the on-crank or online air inlet valve to pressurize the tank to 2.0 barg. Connect the corresponding hoses between the tank outlet and the on-line or on crank wash manifold inlet and slowly open the tank wash fluid outlet.
If any leaks occur tighten the fittings. Repeat this procedure increasing the pressure each time until the max working pressure of 6.9 barg is reached without leaks.
Pressure test the atomising nozzles to confirm correct spraying. If any of them appear blocked disconnect them and back flush the nozzle tip through the orifice with a commercial electrical instrument cleaner followed by high-pressure air or water.
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 75 of 158
On-Crank Engine Compressor Cleaning (maintenance only)
Cleaning
Method
Cleaning Solution
(Volume/Dosage)
Gallons
Solution
Rinse
16
25 2
Distilled
Water to solution
Ratio.
4:1
N/a
Flow GPM
Air
Pressure
Psig 1
4.4
4.4
85-100
85-100
Air Flow
SCFM
4.6
4.6
On-Line Engine Compressor Cleaning
The objective of on-line cleaning is to clean the engine compressor on a regular basis to reduce the build up of deposits in the compressor, i.e. maintaining a clean engine rather than allow it to become fouled. On-line cleaning extends the period between on-crank cleaning. However incorrect on-line cleaning can induce fouling and chemical cleaning frequency cannot be accurately estimated hence a trial run period should be used to determine this and before on-line cleaning commences the baseline fouling trend should be established.
Cleaning
Method
Solution
Rinse
Cleaning Solution
(Volume/Dosage)
Gallons
16
8
Distilled
Water to solution
Ratio.
4:1
N/a
Flow GPM
1.7
1.7
Air
Pressure
Psig 1
85-100
85-100
Air Flow
SCFM
1.8
1.8
Notes:
1) The optimum pressure at the injectors is between 90-100 Psig (6.1-6.9 barg) measured at the skid edge connection.
2) This is the recommended dosage. Compressor should be rinsed until a clean waste stream is noted in engine drains.
6
7
8
9
10
11
12
On-line Engine Compressor Cleaning Procedure
Step
1
2
3
4
5
Procedure
Confirm that engine is stabilised and at operating speed
Confirm that ambient temperatures are above 4 o C
Close all valves on the pressure injection tank
Open the wash cart vent valve and the wash cart water inlet valve
Fill the cart with the required amount of water and then close the tank water inlet valve and disconnect the water supply
Connect the hose to the chemical source and the chemical inlet
Open the cart chemical inlet valve and fill the tank as required
Close the chemical inlet valve and disconnect the chemical supply
Close the Cart vent valve
Pressurise the tank to normal working pressure by opening the cart air inlet valve and leave the valve open for the duration of the on-line wash to maintain a steady injection pressure and flow
By selecting the appropriate on-line wash key and by opening the fluid outlet valve start the on-line wash
Use all the cleaning solution in the tank
Signature
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 76 of 158
Post Cleaning Procedure
Step Procedure Signature
1
2
3
4
5
6
7
8
Purge the line for 2-3 minutes by leaving the air inlet valve open.
Close the air inlet valve and leave the outlet open to allow the cart pressure to drop between 1.4 and 2.1 barg.
Select the appropriate function key to switch off the on-line cleaning, close the fluid outlet valve and disconnect supply hose
Slowly open the vent valve and allow the pressure to discharge to 0 barg.
Within 20 minutes of the chemical wash a water rinse should be performed to ensure the Cart is free of the Chemical Solution/ Water mixture.
Open the water inlet valve and fill the cart with the required amount of demineralised water.
Close the water inlet valve, disconnect the hose and flush the system as above when the chemical wash was completed.
Compare performance figures with those before the wash and confirm the contamination factor has decreased below 5%.
th
A check out should be performed daily when the 4 th water injection pump package is running in order to confirm normal operation. A summary of the system condition is displayed on the operation summary screen. Normal operating data, instrument ranges, alarms, trip points for the water injection system, water injection pump, gear box, gas turbine, start motor, accessory gear box, lube oil and enclosure are listed below. If significant deviations occur the engine should be shut down and the cause of the deviation established.
Expected Operating Data for Water Injection System
Description
Suction to pump
Suction to pump
Discharge from Pump
Discharge from Pump
Water Injection Rate FIC-
450445
Instrument
PI-450441
PA-450442
PI-450443
PA-450444
FIC-450445
Discharge from Pump
Delta Pressure for
Valve XV-450501
FA-450446
PDI-450446
Minimum flow valve position ZI-450445
Value
Normal: 4.6 Barg
High Alarm: 7 Barg
Low Alarm 3 Barg
Trip high: 8 Barg
Trip Low: 2 Barg
Normal: 207-223 Barg
High Alarm: 250 Barg
Low Alarm 100 Barg
Trip high: 260 Barg
Trip Low: 95 Barg
Normal: 930 m3/h
Over speed case: 1150 m3/h
Low Alarm: 290 m3/h
Trip low: 280 m3/h
Normal: 0
Start up: 0 to 256 barg
Normal value: 0 to 100 % open
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 77 of 158
Expected Operating Data for Water Injection Pump P-4001D
Description
DE Vibration
DE Vibration
DE Seal Pressure
NDE Seal Pressure
DE Journal Bearing
Temperature
NDE Journal Bearing
Temperature
NDE Vibration
NDE Vibration
I/B Thrust Bearing
Temperature
O/B Thrust Bearing
Temperature
Balance Return Line
Temperature
Pump Speed
Pump HP
Instrument
YI-450400X
YI-450400Y
PI-450416
PI-450417
TI-450405
TI-450406
YI-450401X
YI-450401Y
TI-450407
TI-450408
TI-450409
SI-450404
XI-450425
Value m m m m m m m m
Range: 0 to 2.5 Barg Normal: 0
Barg
Alarm: 0.3 Barg
Trip: 0.5 Barg
Range: 0 to 2.5 Barg
Normal: 0 Barg
Alarm: 0.3 Barg
Trip: 0.5 Barg
Range 0 to 200 o C
Normal: 59 o C
Alarm: 90 o C
Trip: 100 o C
Range 0 to 200 o C C
Normal: 37.6 o C
Alarm: 90 o C
Trip: 100 o C m
Normal: 11 m m m m
Normal: 11 m m m
Range: 0 to 200 o C
Normal: 42 o C
Alarm: 110 o C
Trip: 120 o C
Range: 0 to 200 o C
Normal: 42 o C
Alarm: 110 o C
Trip: 120 o C
Range: 0 to 200 o C
Alarm: 90 o C
Trip: 95 o C
Range: 0 to 4000 RPM
Normal: 3650 RPM Design
Over speed: 3833 RPM
Range: 0-11 MW
Normal: 6.56 MW Design
Overspeed: 8.075 MW
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 78 of 158
Expected Operating Data for Turbine to Pump Gear Box
Description Instrument Value
Thrust Brg Outboard Temp
RDN
TI-450414B Range: 0 to 200 o C
Alarm: 70 o C
Trip: 75 o C
Thrust Overboard BRG Temp TI-450414A Range: 0 to 200 o C
LSS End Bearing Temp TI-450412
Alarm: 70 o C
Trip: 75 o C
Range: 0 to 200 o C
Axial ZI-450405
Alarm: 100 o C
Trip: 105 o C
Range: 1-0-1 mm
Accelerator
Bearing HSS Y axis
XI-450408
YI-450405Y
Alarm: 0.1 mm
Range: 0 to 25 mm/s rms
Alarm: 7.0 mm/s rms
Trip: 18.0 mm/s rms
Range: 0 to 150 µm
Bearing HSS X axis
Bearing LSS Y axis
YI-450405X
YI-450406Y
Alarm: 63 µm
Trip: 93 µm
Range: 0 to 150 µm
Alarm: 63 µm
Trip: 93 µm
Range: 0 to 150 µm
Bearing LSS X axis YI-450406X
Alarm: 97 µm
Trip: 142 µm
Range: 0 to 150 µm
LSS DE END Bearing Temp TI-450413
Alarm: 97 µm
Trip: 142 µm
Range: 0 to 200 o C
Alarm: 100 o C
Trip: 105 o C
Thrust inboard BRG Temp
RDN
Thrust inboard Bearing temp
HSS NDE end Bearing Temp
TI-450415B Range: 0 to 200 C o C
Alarm: 70 o C
Trip: 75 o C
TI-450415A Range: 0 to 200 o C
Alarm: 70 o C
Trip: 75 o C
TI-450411 Range: 0 to 200 o C
Alarm: 110 o C
Trip: 115 o C
Expected Operating Data for Water Injection Pump P-45001D Gas Turbine .
Description
Power Turbine Speed
Gas Turbine Air Inlet
Instrument
SI-450405
TI-450422
PDI-450401
Value
Maximum: 100% (Design
Speed)
Range: 0 to 120 %
Normal: -6 to 23 o C
Range: -40 to 70 o C
Range: 0 to 24.9 mbar Gas Turbine Air Inlet Filter Delta
Pressure:
Gas Turbine Inlet Filter Delta
Pressure:
Gas Turbine Compressor Discharge
Pressure:
PI-450432 Normal: 3 barg
Range: 0 to 20.7 barg
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 79 of 158
Expected Operating Data for WI P-45001D Gas Turbine (continued)
Gas Turbine T5 Average
Fuel Gas Rate
Gas Turbine T5 Max- T5 average
Fuel Gas Pressure
Fuel Gas Temperature:
At the turbine inlet, assuming that the superheater is online. (Trip low is to prevent dewpoint being reached and liquids reaching the turbine)
Power Turbine BRG 5-X-axis
Power Turbine BRG 5-Y-axis
Power Turbine Axial
Power Turbine Thrust Bearing
Power Turbine BRG 4-X-axis
Power Turbine BRG 4-Y-axis
Gas Producer NGP PV
Gas Producer BRG 3-X-Axis
Gas Producer BRG 3-Y-Axis
Gas Producer BRG 2-X-Axis
Gas Producer BRG 2-Y-Axis
Gas Producer BRG 1-X-Axis
Gas Producer BRG 1-Y-Axis
Gas Producer Axial
Gas Producer Thrust Bearing
TI-450433
FI-850005
TI-450434
PI-450433
TI-850099
YI-450415X
YI-450415Y
YI-450412
TI-450417
Y-450407X
Y-450407Y
SI-450406
YI-450408X
YI-450408Y
YI-450409X
YI-450409Y
YI-450410X
YI-450410Y
YI-450411
TI-450431
Range: 0 to 1000 o C
Set point: 290 o C
0 to 2177 kg/hr
Range: 0 to 1000 o C
Normal: 24 barg
Alarm low: 22 barg
Alarm high: 27.6 barg
Trip low: 19.7 barg
Trip High: 28.6 barg
Range: 0 to 41.4 barg
Normal: 35.2 o C
Alarm low: 31 o C
Alarm high: 45 o C
Trip low: 28 o C
Trip high: 55 o C
Range: 0 to 150 o C
Norm
Range: -1 to 1 mm
Range: 0 to 150 o C
Maximum: 100%
Range: 0 to 120 %
Normal: -0.08 mm
Range: -1 to 1 mm
Range: 0 to 150 o C
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 80 of 158
Expected Operating Data for Gas Turbine Start Motor
Description
Voltage
Current
Motor Speed
Instrument
XI-450424
XI-450423
Si-450407
Value
Range: 0 to 500 V
Range: 0 to 600A
Range: 0-5000 RPM
Expected Operating Data for Gas Turbine Accessory Gear Box
Description
Accessory Gearbox Velocity
Instrument
XI-450428
Value
Range: 0 to 20 mm/s
Expected Operating Data for Gas Turbine Lube Oil System
Description
Header Temperature RDN
Header Temperature
Header Pressure RDN
Header Pressure
Oil Filter Delta Pressure
Pre Post Pressure
Oil Tank Temperature
Oil Tank Pressure
Oil Tank Level
Accessory Gearbox bearing Drain
Temperature
Gas Producer Bearing Drain
Temperature
Gas Producer Bearing Drain
Temperature
Power Turbine Bearing Drain
Temperature
Scavenge Pump Pressure
Back-Up Lube Pressure Test
Instrument
TI-450424
TI-450425
PI-450434
PI-450435
PDI-450405
PI-450436
TI-450426
PI-450437
LI-450401
TI-450427
TI-450428
TI-450429
TI-450430
PI-450438
PI-450439
Value
Normal: 57.6 o C
Maximum: 68 o C
Range: 0 to 150 o C
Alarm: 71 o C
Trip: 82.2 o C
Normal: 60.2 o C
Maximum: 68 o C
Range: 0 to 150 o C
Alarm: 71 o C
Trip: 82.2 o C
Normal: 3.4 barg
Range: 0 to 6.89 barg
Alarm: 1.86 barg
Trip: 1.03 barg
Normal: 3.45 barg
Range: 0 to 6.89 barg
Alarm: 1.86 barg
Trip: 1.03 barg
Range: 0 to 6.89 barg
Alarm: 2.07 barg
Range: 0 to 6.89 barg
Range: 0 to 150 o C Normal:
63.7 o C
Range: 0 to 37.3 mbarg
Range: 0 to 711 mm
High alarm: 550 mm
Low alarm: 483 mm
Maximum: 121 o C
Range: 0 to 150 o C
Maximum: 121 o C
Range: 0 to 150 o C
Maximum: 121 o C
Range: 0 to 150 o C
Maximum: 121 o C
Range: 0 to 150 o C
Range: 0 to 6.89 barg
Range: 0 to 6.89 barg
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 81 of 158
Expected Operating Data for Gas Turbine Enclosure
Description
Primary Vent Fan
Enclosure Temperature
Backup Vent Fan
Enclosure Pressure (note)
Instrument
XI-450426
TI-450432
XI-450427
PI-450420
Value
On / Off
Range: 0 to 150 o C
High alarm: 75 o C
On / Off
Range: 0 to 24.9 mbar
Range: 0 to 24.9 mbar Enclosure Filter Delta Pressure
(note)
PDI-450404
Note: The enclosure pressure is negative.
WI Pump P-45001D Discharge Pressure for Different Operating Scenarios
Case Flow from
Deaeration
Tower
1 m3/h
1411
Flow
Produced
Water m3/h
1490
Electric pumps
Running
A, B, C
Turbine driven pump
Design
Speed
Pump Discharge
Pressure Barg
Total flow rate: m3/h
2
3
4
5
6
7
8
9
10
1890
1890
1890
1890
300
300
1150
1631
930
0
0
0
0
0
0
0
1490
0
Running
A, B, C
Running
A, B
Running
A, B
Running
A, B, C
Not running
Not running
Not running
Running
A, B, C
Not running
Design
Speed
Design
Speed
Over
Speed
Not
Running
Over
Speed
Design
Speed
Over
Speed
Over
Speed
Design
Speed
Pressure: 206.2
Flow rate: 2901
Pressure: 234.9
Flow rate: 1890
Pressure: 221.9
Flow rate: 1890
Pressure: 231.8
Flow rate: 1890
Pressure: 210.7
Flow rate: 1890
Pressure: 271.9
Flow rate: 300
Pressure: 246.3
Flow rate: 300
Pressure: 208.6
Flow rate: 1150
Pressure: 206.1
Flow rate: 3121
Pressure: 210
Flow rate: 930
Design speed for water injection pump P-45001D:
Over speed for water injection pump P-45001D:
3650 PRM
3833 RPM
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 82 of 158
For each well there is a safe operating limit as defined on a graph of wellhead injection pressure (from PI-sss922n) against well injection flowrate (FI-sss929n).
An example is shown below:
Well Operating Limits
300
250
200
150
100
50
0
0
BHIP Limit
Erosional Velocity Limit
Surge Limits
Operating Line
Op Pt
50 100 150 200 250 300
Flowrate (m3/hr) - FIsss929n
350 400
Figure 14 Well Operating Limits
The allowable operating envelope is bounded by the following key limits:
Bottom Hole Injection Pressure Limit (BHIP Limit) - This is the maximum injection pressure allowable at the top of the completed zone. Injection pressures in excess of this limit could lead to failure of the formation above the completed zone and therefore permanent damage to the well’s injection capability. This line has been converted into a wellhead injection pressure limit which is flowrate dependent.
Erosional Velocity Limit - This is the maximum allowable injection rate from an erosion viewpoint. It also represents the maximum measurable rate on the wellhead venturi.
Surge Limit - This represents the maximum allowable injection rate to ensure that hydraulic surge on shutdown does not lead to an over-pressuring of the subsea system.
The allowable operating envelope lies below the BHIP limit curve and to the left of both surge limit and erosional velocity limit lines.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 83 of 158
The additional limes on this plot show the expected operating point of the water injection based on the seawater injection choke position. This line covers the range of possible injection indices expected for this well (dotted line) and the most likely injection index range (solid line). This line is primarily for information.
Operation outside this line indicates incorrect choke position, an unexpected choke performance or an unexpected reservoir performance.
If operation of the well is outside this limit, the well must be shut in and advice obtained. It may be required that the ROV choke position will need to be modified before injection can recommence.
Note: The allowable operating envelope will change during field life and this plot will be updated on a regular basis.
In addition to the above operating limits there is also a maximum allowable injection rate to each drill centre (for Central it was 90mbd initially).
Well Annulus Operating Limits
The allowable range of operating pressures in the well annulus is 0 to 310 barg.
To ensure that annulus pressures are measurable using Pisss923n, the annulus master valve AMVsss935n, must be open.
If these values are exceeded during start-up or shutdown of the well, the well must be temporarily shut in at the wing valve and the tree cross-over valve must be opened to relieve pressure into the tubing. Note that due to the high injection temperatures at the tree, the pressure in the annulus may increase on shutdown or start-up.
Well Start-Up and Shutdown
The main consideration (operating the wing valves when the water injection pumps are running) applies equally to start-up and shutdown of individual wells.
Hence, prior to a wing valve on a water injection well being opened or closed, the main injection pumps will be shutdown and flow is maintained through these pumps using the produced water booster pumps and/or seawater lift pumps.
Once the wing valve operation has been completed, the main pumps can be restarted.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 84 of 158
The pump will float on the system pressure, at the prevailing flow rate when the system runs at constant speed.
The facility to adjust pump speed set point (SIC-450453) to match the flow rate to water injection requirements is provided. The CRT can manually adjust the speed of the turbine using “the Manual Speed Set Point Controller” SIC-450453.
Raising or lowering the speed would result in increase or decrease in flow rate.
Any adjustments to the speed set point will be carried out by sending a signal to
TCP SY-6000.
The rate of change of speed will be restricted within the TCP. The set point can only be in the range between 70-105% of the turbine speed.
The pump discharge PT-450443 will be used as a process variable input to the speed controller SIC-450443. If PT-450443 high discharge pressure alarm is activated the speed set point will be reduced to 95% of the pump design speed by the CPS, which will be done only once. This will reduce the pump shut in pressure in the event the discharge is closed.
It is possible to increase the pump speed to 5 percent above the pump design speed to allow the pump to flow at its maximum flow rate. This facility will only be required when one, or more of the three motor driven water injection pumps are not available and will only be possible to achieve when the ambient temperatures are below 12
°C, allowing the gas turbine to generate sufficient power, reference figure 6.3.
In addition, pump discharge PT-450444 will be used as a process variable input to the Control and Process Shutdown System (CPS) to trip the pump to full stop in the event the high high pressure set point is activated. Furthermore, the CPS has to monitor and record the pressure and duration.
The CPS shall report the following for each year of operation:
Total duration of all pressure excursions that are above the design pressure of 270 barg, and below a 20% overpressure threshold of 359.1 barg.
Total duration of all pressure excursions that are above the 20% overpressure threshold of 324 barg, and below a 33% overpressure threshold of 359.1 barg.
This can be achieved if the pump operates above its design speed or in an event of the discharge being closed. Figure 13 shows the pressure excursion graphic displayed on the screen in the CCR and can be found in the screen for pump “C” and “D”.
Figure 15 Pressure Excursion Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 85 of 158
The ability to reduce the pump speed to idle whilst running the turbine has several operating advantages. Primarily it will reduce restart time in the event of a process trip or the need to reduce flow for operational reasons.
The CRT may trip the turbine to idle speed using the push button XHS-450453.
On detection, the CPS logic will send a signal to the Solar Turbine Control Panel
(TCP) to slow down the turbine to idle speed. When the turbine has reached idle speed status, the TCP will send a signal to “Cool down Indication” XI-450410 and close XV-450446 and XV-450501 after a 30 second time delay.
As XV-450446 closes, FIC-450445 will open under PID control to protect the pump from damage at low flow rates. “Permissive to Restart Feed Forward” XI-
450454 will be given under the following conditions:
XV-450446 and XV-450501 are closed
Turbine operates in idle mode
The TCP will keep the turbine running in idle mode for 180 minutes, before it trips the turbine to full stop. If CRT presses “Request to Restart Feed Forward” push button XHS-450455 during this period, the CPS logic will send a signal to the
TCP to restart the turbine to idle. When the turbine has reached idle status, the
Solar Turbine Control Panel will send a signal to the CPS logic to bring the turbine automatically to the feed forward status and change “Speed Set Point
Controller” SIC-450453 from automatic to manual mode. This will bring the unit back on line again and the speed controller set point can be adjusted as necessary to suit the requirement.
If the CRT does not press “Request to Restart Feed Forward” push button XHS-
450455 during this period, the Solar Turbine control Panel will send a signal XI-
450411 to indicate that the “Gas Turbine is totally stopped” to the CPS.
4.13.1 Normal Shutdown
Following shutdown and valve isolation of the Deaeration Tower, XXV-441040 should be checked for leakage by using FCV-441001 drain valves. It is not desirable to allow leakage into, and filling, of the tower as this causes high stresses on the structural supports under severe weather conditions.
If leakage is found, either a double block and bleed should be set up on the inlet, or FCV-441019 and downstream manual valve should be left open to drain the tower overboard.
Excessive contact with oxygen will rapidly deplete the sensing elements of the analysers AT-441018 and AT-442019 when these sensors are active. Therefore the analysers should be de-energised to extend sensor life.
A planned shutdown of the de-aeration package can be initiated from the CPS:
Tag Number
P-44201A/B
XV-441024
XV-441028
XV-441040
XXV-441040
Description
Stripping Gas Blowers
Nitrogen Top-up Line
Instrument Air Top-up Line
Methanol Supply Line
Seawater Inlet Line
Action
Stopped
Closed
Closed
Closed
Closed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 86 of 158
The system control valves can be moved to their shutdown positions thus.
Valve Tag No.
FCV-441001
FCV-441019
FCV-441021
PCV-441023
FCV-441027
TCV-442014
Shutdown
Position
Closed
Open
Closed
Closed
Closed
Open
Description
Seawater Inlet Valve
Overboard Dump Valve
Stripping Gas Vent Valve
Nitrogen Top-up Valve
Instrument Air Inlet
Stripping Gas Exchanger Bypass
Following shutdown of the deaerator package confirm the chemical injection valves are closed as detailed below. Refer to P&ID L-8000-GP-0043.00
:
Valve No.
HV-441002
HV-441121
Description
Antifoam
Calcium nitrate
Signature
HV-441008
HV-441019
Scale Inhibitor
Oxygen Scavenger
The deaerator package is now shutdown. However, the system trace heating should not be isolated until the deaerator has been drained and vented.
Additionally, each of the drain valves within the seawater pipework should be opened to ensure that no liquid is present.
The only subsea condition that will cause the water injection trees to close in is loss of hydraulic fluid, typically due to umbilical snagging.
VACUUM CONDITIONS ON SHUTDOWN
When the water injection pumps’ shutdown and discharge valves are closed, the reservoir pressure is such that water will be drawn into the formation, causing a vacuum to be pulled in the flexible risers. To prevent this condition, injection well wing valves are closed following shutdown of the injection pumps. Additionally, the risers are reinforced with steel liners to cope with vacuum conditions.
ISOLATION FOR MAINTENANCE
The water injection pumps are only provided with a single discharge isolation valve due to space limitations. The water injection pumps must therefore be shut down and locked out to achieve positive isolation for maintenance. The water injection wells are not capable of back-pressuring the FPSO and therefore work may be carried out without closing the turret isolation valves. The subsea well wing and master valves must be closed to prevent pulling a vacuum and drawing air into the system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 87 of 158
DEPRESSURISATION OF WATER INJECTION SYSTEM
Step
1
2
3
Procedure
Shutdown of main pump using operating procedure
Ensure all well injection wing valves are closed.
Monitor annulus pressure on PI-105923n to ensure that it remains within allowable operating range (0-310 barg)
Close UIMV
Close SCSSV
4
5
6
7
8
Re-open UIMV
Trend WHCIP on PI-105922n
Carry out flowline depressurisation back to FPSO using turret drain valve.
9 Continue to trend WHCIP for 1 hour after full depressurisation
10 Close UIMV & AIMV
Signature
SHUTDOWN NOTES:
On shut-down of the water injection system there are four key considerations:
The potential for a vacuum condition in the water injection system due to reservoir under-pressure.
Hydraulic surge due to closure of the wing valves, with the potential for exceeding the over-pressure allowances on some components, if the system is operated at above maximum steady state injection rate limits.
Closure of the wing valves against the main water injection pumps, leading to a transient under-pressure in the well which could damage the downhole sand screens.
Excessive wear of the water injection wing valve if it is closed against the main pump.
The inclusion of a carcass in the water injection risers and subsea flexible jumpers allows for vacuum conditions to exist in the system without the potential for collapse of the internal liner in these components. However, the system should be operated with the intention of minimising the potential for this condition.
This is primarily aimed at reducing the time taken to restart the system, but also provides assurance against collapse of the polyethylene liner within the water injection flowlines.
A similar philosophy to that used on the system start-up will be employed for a planned shutdown. Therefore, the main pumps will initially be shutdown whilst maintaining the water supply by using the produced water booster pumps or seawater lift pumps. This will be followed by closure of all wing valves and then shutdown of the produced water booster pumps or seawater lift pumps.
For an unplanned shut-down the water injection tree wing valves will be automatically closed on loss of al l water injection pumps.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 88 of 158
4.13.2 Emergency Shutdown
In the event of an ESD/HIPS, the system is shutdown in the same way as for a normal shutdown with the exception that XXV-441002 (seawater inlet) is also closed. Once the cause of the shutdown has been investigated and rectified, the valves can be reset. XXV-441040 and XXV-441002 must be reset manually while the other valves are auto-reset. Additionally, there is a water injection PSD, refer to C&E L-8000-JC-0002.24.
An emergency shutdown affects the subsea tree valves as follows:
Yellow Shutdown
Red Shutdown
IWV closes
UIMV closes
AMV closes
XOVT closes as Yellow Shutdown above, but in addition -
SCSSV closes
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 89 of 158
The CRT may initiate a Normal Shutdown from the CCR or LER. The gas turbine will trip to idle speed, which will be indicated on the start up graphics. When the turbine remains in idle speed for 180 minutes, it will be totally stopped. If the CTR initiates “request to restart feed forward”
XHS-450455 before this time, the CPS logic will bring the pump automatically back on line.
The CRT may Fast Stop the turbine using XHS-450456 from the CPS
(see Control System Stop , below). The CPS logic will send a signal to
TCP S511-1 to trip the turbine to full stop. When the turbine comes to a full stop the CPS system will turn off the fuel gas superheater and shut valve XV-850005 instantaneously, XV-450446 and XV-450501 will close after a 30 second delay. (Note this does not depend on a return of a turbine full stop signal. This will happen on detection of ‘Fast stop the turbine’ XHS-450456). As XV-450446 closes, flow rate through the pump reduces and FIC-450445 will open under PID control to protect the pump from damage at low flow rates.
The operator may Emergency Stop the turbine from the TCP in the LER or from two different locations outside of the skid. The TCP will total stop the turbine, the Solar Turbine Control Panel will send a signal to the CPS and will be indicated on the start up graphics.
The turbine can be stopped from the CCR or LER, push buttons on the skid or by the control system. The system has the following stop functions:
Normal Shutdown from the CCR or LER, or Trip Turbine to Idle Speed from the CCR - the turbine will trip to idle speed, run for 3 hours and total stop
Manual Emergency Stop from the LER or from skid pushbuttons - the turbine will total stop
Control System Stop
Back-up Active Shutdown
Turbine Enclosure Fire Detection
Turbine Overspeed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 90 of 158
4.14.1 Normal Shutdown or Trip Turbine to Idle Speed
Normal shutdown involves a cool down period in which the engine runs at idle speed for a preset time before the fuel is cut off and the engine coasts to a stop.
This can be done as follows:
By activating the “Normal Stop” switch (S111) on the Turbine Control
Panel, or
“Request to trip turbine to idle” from the Central Control Room.
This will be indicated by “Cool down” on the start-up screen for the pump in the
CCR. The Solar/Silvertech control systems will trip the gas turbine to idle speed, reset speed controller to 70% of turbine design speed, run for 180 minutes and total stop. The pump can be brought back on line by ac tivating the “request to restart feed forward” button on the start-up screen for the turbine in the central control room. After the engine coasts to a stop and the rundown timer expires, a preset lubrication cycle will be initiated.
When the gas turbine is brought to idle speed or a total stop, the CPS will initiate the following for the water injection pump P-45001D:
Tag Number
P-45001D
XV-450446
XV-450501
Description
4 th Water injection pump
Pump discharge valve
Pump discharge equalisation valve
Action
Stopped
Closed after a timer delay of 30 seconds
Shut
The system control valves can be moved to their shutdown position thus:
Tag Number Description Action
FCV-450445 Pump minimum flow valve Open
4.14.2 Manual Emergency Stop
The manual emergency stop is initiated by depressing the local, remote, or skidmounted emergency stop switch. When the stop is initiated, the start/run latch in the microprocessor is reset and the fast stop latch in the backup control is set.
Fuel valves and guide vanes are closed and the bleed valve is opened. The backup system controls lubrication oil for engine rolldown and post-lube. An emergency stop does not include a cool down period, which allows the engine to run with no load for a preset period before the engine is stopped. The emergency stop shutdown should only be used when plant conditions require an immediate shutdown. This can be done by:
Activating the “emergency stop” switch (S112-A or S112-B) on the
Turbine Control Panel in the LER, or by
Activating o ne of the two “emergency stop” switches (S522 or S522A) on the skid.
“Gas Turbine to Full Stop” will indicate on the start-up screen for the pump in the
CCR. The engine shuts down immediately with no cool down cycle. After the engine stop, the post lubrication cycle will be initiated.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 91 of 158
When the gas turbine is brought to a total stop, the CPS will initiate the following for the water injection pump (P-45001D):
Tag Number
P-45001D
XV-450446
XV-450501
Description
4 th Water injection pump
Pump discharge valve
Pump discharge equalisation valve
Action
Stopped
Closed after a timer delay of 30 seconds
Shut
The CPS will initiate the following for the water injection pump P-45001D driver:
Tag Number
XV-850005
XS-850003
Description
Fuel Gas Valve
Fuel Gas Heater ETP 85002
Action
Closed
Trip
The system control valves can be moved to their shutdown position thus:
Tag Number Description
FCV-450445 Pump minimum flow valve
Action
Open
4.14.3 Control System Stops
There are two main types of control system stops, depending on the severity of the malfunction and urgency to stop the GT or pump:
cooldown stop (cooldown non-lockout & cooldown lockout)
fast stop (fast stop non-lockout & fast stop lockout)
If an unsafe operating condition is detected by the control system, the control system will initiate a shutdown. Depending upon the severity of the shutdown, the control system will initiate either a cooldown stop or a fast stop. If the control system stop was initiated due to a condition that is self-correcting, the engine can be restarted after the condition returns to normal. If the control system stop was initiated due to a condition that is not self-correcting, contact maintenance personnel to perform corrective actions.
The Cooldown Stop unloads the driven equipment and allows the engine to idle for a cooldown period before shutting off fuel. The Fast Stop immediately shuts off fuel and unloads the driven equipment.
A Lockout inhibits control system operation. The control system cannot initiate a start until the malfunction is reset. Lockout-type malfunctions are generally more severe and require attention before the system can be restarted. Non-lockout malfunctions typically result from an operation disruption or an abnormal condition. Non-lockout malfunctions can be reset when conditions return to normal.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 92 of 158
Cooldown Stop
If a cooldown stop has been initiated, the engine is shut down in the same manner as a normal stop. There are two types of cooldown stops; cooldown nonlockout and cooldown lockout.
Cooldown Stop Non-lockout (CN) – Cooldown non-lockout shutdowns reduce engine speed to idle for a preset cooldown period before initiating a shutdown. Cooldown non-lockout shutdowns include operator-initiated normal stops, operating conditions that reached a shutdown limit because maintenance was not performed, a momentary disruption that causes an outof-limits condition, and operating conditions that exceed alarm levels but are not serious enough to cause any immediate damage. The turbine control system will automatically acknowledge and reset the cooldown non-lockout shutdowns and the turbine can then be started from the CCR without corrective action. Cooldown stop nonlockouts include normal stops as well as stops responding to alarms not serious enough to cause immediate damage.
These conditions include operation out of sequence, or a momentary out of limit condition.
Cooldown Stop Lockout (CL) - Cooldown lockout shutdowns reduce engine speed to idle for a preset cooldown period before initiating a shutdown.
Cooldown lockout shutdowns typically result from a component failure and not because operating conditions have exceeded alarm or shutdown levels.
Cooldown lockout shutdowns may not present immediate danger, but corrective action must be taken to avoid damage resulting from a component failure. When lockout shutdowns occur, the turbine can not be started until the shutdown is acknowledged and reset using the local acknowledge and reset switches.
Cooldown stop lockout shutdowns typically result from a component failure and not because operating conditions have exceeded alarm or shutdown levels.
Cooldown stop lockout malfunctions include:
sensor failure lube tank level low lube tank overpressure
Fast Stop
If a fast stop has been initiated, the engine is shut down in the same manner as an emergency stop. There are two types of fast stops; fast stop lockout and fast stop non-lockout.
Fast Stop Lockout (FL)
Fast stop lockout shutdowns initiate an immediate shutdown of the engine and prevent package operation until the shutdown is acknowledged and reset using the local acknowledge and reset switches.
In addition to using the local acknowledge and reset switches, fast stop lockout shutdowns initiated due to a microprocessor failure, fire detection, backup overspeed, or pressing of emergency stop switch will require the backup relay system to be reset. Fast stop lockout shutdowns are the most severe shutdown types and require corrective action before the package can be restarted.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 93 of 158
Fast stop lockouts respond to conditions that can cause serious damage if operation continues. Investigation for damage is required. Corrective action may be required before restart. These conditions include high bearing temperatures, high T5 temperature, node failure, transmitter failures, pump high thrust bearing temperature, gearbox high thrust bearing temperature, pump high vibration and gearbox high temperature.
WARNING: When a fast stop shutdown has been initiated due to fire detection, the post-lube oil pump will remain energised for a preset rundown period. After the preset rundown period expires, the post-lube oil pump will be de-energized for 20 minutes. After the 20 minute time period expires, the post-lube pump will cycle on and off for a preset post-lube period. If unsafe conditions still exist, the operator must manually abort the post lube cycle by opening the contactors for the post-lube and back-up lube oil pumps.
Fast Stop Non-lockout (FN)
Fast stop non-lockout shutdowns initiate an immediate shutdown of the engine. Fast stop non-lockout shutdowns typically result from a disruption in operation due to abnormal operating conditions and may not require corrective action.
The turbine control system will automatically acknowledge and reset the fast stop non-lockout shutdowns and the turbine can be re-started from the CCR without corrective action.
Fast stop non-lockouts respond to conditions that can cause damage if operation continues. The conditions are caused by a momentary disturbance in the system or an occasional sequencing related malfunction. Momentary conditions typically include engine overspeed, flameout and high vibration
(engine). Sequencing-related malfunctions include fail to crank, ignition fail, fuel valve check fail, yard valve fail, and pre-lube fail.
4.14.4 Backup Active Shutdown
The backup active shutdown is enabled if there is a microprocessor failure, fire, backup overspeed, or manually initiated Emergency Shutdown (ESD). The backup system immediately shuts off fuel, opens system valves to eliminate driven equipment load, and controls lubrication oil for engine rolldown and postlube. After a backup active shutdown, the backup system must be reset with the
BACKUP RESET keyswitch. The ACKNOWLEDGE and RESET switches must be pressed before the package can be restarted.
Microprocessor Fail
A microprocessor fail malfunction is detected by the controller. When microprocessor failure is detected, a fast stop is initiated and backup control is activated. Fuel valves and guide vanes are closed, the bleed valve is opened, and the gas driven equipment is unloaded. The backup system controls lubrication oil for engine rolldown and post-lube.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 94 of 158
4.14.5 GT Enclosure Fire Detection
When fire is detected, the backup system immediately sets the fast stop latch in backup control. The shutdown sequence proceeds as with the manual emergency stop except enclosure fans, are stopped, and lube continues for engine rolldown. If the PLC is functioning after the 20-minute hold, a post-lube cycle is completed.
4.14.6 Turbine Backup Overspeed
The turbine overspeed malfunction is sensed by the backup overspeed detection module. The magnetic pickup speed sensor is independent from primary control sensor. The backup overspeed monitor detects overspeed that indicates the normal control and protect systems are not operating. When overspeed is detected, the fast stop latch in the backup control is set and the stop sequence proceeds as with manual emergency stop.
Water injection pump P-45001D is provided with discharge double block and bleed isolation and suction single isolation. The other three water injection pumps P-45001 A/B/C are only provided with discharge single isolation. To achieve positive isolation for maintenance of water injection pumps P-45001
A/B/C, a blank flange is to be fitted to the discharge non-return valve, when the water injection pump P-45001D is in operation.
WARNING: In case of an instrument air failure and if maintenance on the turbine fuel gas system is required, an entrapped pressure will occur and care should be taken on opening up the system for maintenance.
To achieve positive isolation for maintenance of the turbine:
Valve HV-520503 for the warm up line to flare has to be closed
Valve HV-804807 for the instrument air has to be closed
HV-815500 & HV-815501 for the cooling medium system have to be closed.
The demineralised water line to the wash cart should be emptied of water when the temperature falls below 5 deg C, to prevent freezing in the pipe, by opening valve HV-803709 (P&ID: 37W022F0146-A-8000-GP-0090.01-2C). There are two sets of drain water traps underneath both the HVAC (two traps) and combustion air Intakes (one trap) that are not winterised. A TQ has been raised to have these winterised.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 95 of 158
Use the following procedures to start up and shut down the video display computer and TT4000 software.
Start-Up of Computer
1.
2.
Switch on power to computer to start up Windows program.
When prompted to begin login: a. b. c.
Press Ctrl+Alt+Delete
Type user name Operator
Type password 1111 (four ones) and press Enter.
Start-Up of TT4000
1.
2.
3.
4.
5.
6.
From desktop, double-click TT4000 Designer icon.
From menu bar, click File.
From File pull-down menu, click Open Project.
Click C:\Jobs\70981\70981.ttprj.
From tool bar, click green Run button (right arrow).
NOTE: Project may take several minutes to load.
If “Server Busy” window pops up, click on Retry button.
Shutdown of TT400
1.
2.
3.
4.
5.
Move pointer arrow to bottom of screen. From Desktop Taskbar, click
TT4000 Designer Application button.
From toolbar, click red Stop button (square).
NOTE: Project may take several minutes to stop.
If “Server Busy” window pops up, click on Retry button.
From File pull-down menu, after Project has stopped, click Close Project.
When Project has closed, click Close button (X) at top right corner.
Shutdown of Computer
1.
2.
3.
4.
From Desktop taskbar, click Start button (bottom left corner).
From menu listing, click Shut Down (bottom of listing).
Select Shut down the computer and press Enter.
Wait for message. It is now safe to turn off your computer to appear.
Finally, switch off power to computer.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 96 of 158
The water injection system subsea is normally controlled and monitored from the operator workstation console within the CCR. The subsea control system is designed to be a ‘stand alone’ system to the normal process control system
(CPS), with a simple data hand-off system which allows the CPS to monitor any subsea data points as required.
The Master Control Station (MCS) provides appropriate well status indication to the CPS only if the CPS requests the information over the data hand-off system.
The information passed to the CPS is not employed by the CPS but is passed directly to the production information system. Any information displayed on the
CPS is indirectly obtained via the production information system.
Other topsides equipment supplied are the Hydraulic Power Unit (HPU), which provides the appropriate hydraulic pressures for subsea distribution, and the
Topside Umbilical Termination Unit (TUTU), which provides the interface between the umbilical systems and the platform cabling and piping. There is one TUTU for the Schiehallion Central, West & Gas Disposal Well (GDW) developments, and a second TUTU for the Schiehallion North and Loyal developments.
Two dynamic umbilicals are used to transport the electrical power, control signals and hydraulic supplies to the subsea systems. ROV installed and recoverable
Electro/Hydraulic/Chemical (E/H/C) jumpers are used to distribute the various supplies to the Subsea Control Modules (SCM) mounted on the Xmas Tree (XT).
The SCM is mounted on the XT via an ST001 ‘John Brown’ standard interface.
The SCM utilises through-base hydraulic and electrical connections which connect to the XT mounted E/H/C supplies stabplate and the Xmas Tree valves and instrumentation.
From the Umbilical Termination Assembly (UTA) or manifold, an E/H/C supplies jumper connection to each Xmas Tree. This jumper includes the following.
A dual power pair and a dual communications pair to the SCM.
A dual HP/MP hydraulic hoses to the SCM.
One multi-core cable for readback at the SCM of up to 3 off 4-20mA sensors on the manifold (valve position sensor, pressure and temperature sensor).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 97 of 158
5.1.1 Interlocks
Interlocks serve to reduce valve wear. Interlocks when the MCS is in
OPERATOR mode are:
Wing valve cannot be opened unless the Upper Master Valve is open
Upper Master Valve cannot be opened or closed unless Wing Valve is closed
SSSV cannot be opened unless upper master valve and wing valve are open
SSSV cannot be closed unless the upper master valve is closed.
Note: When the MCS is set to SUPERVISOR mode, these interlocks can be overridden with the exception of the opening of the SCSSV, which can still only be opened if the wing valve and the upper master valve are open.
For the SCSSVs that share the same valve function, the upper master valves and wing valves on both trees must be open to enable the
SCSSV to be opened.
The SCSSV must not be opened until a positive indication of flow is obtained from the injection well venturi flow measurement. This protects the valve from being opened against a high differential pressure which could cause damage to the valve. Once flow is indicated, identifying that the pressures have equalised and the flapper type valve has opened, hydraulic pressure should be applied by opening the valve from the control system.
Water injection maintains reservoir pressure to minimise loss of productivity and maintain reservoir above the bubble point. The subsea water injection system is normally controlled and monitored from the operator workstation within the CCR. The subsea control system is a stand-alone system to the normal (topsides) process control system.
The Master Control System (MCS) can provide the CPS with well information if requested from the CP.
INDICATIONS, ALARMS AND TRIPS SUBSEA
Location Tag No.
Swivel - upstream of the water injection PG 450 803 manifold
Swivel - upstream of the 10” ball valves FE 180 800A
FE 180 800B
(Central Riser)
FE 182 800A
FE 182 800B
(West/North/Loyal Riser) dP sss929n xtree - venturi meter at the inlet to the xtree block xtree - downstream of the wing valve PTT sss922n
Instrument Type
Pressure Gauge
Flow Element
Flow venturi xtree - downstream of the cross over valve (tree) COVT
PT sss923n
Pressure/ Temperature
Transmitter
Pressure Transmitter
Table 11 Locations of Instruments on the Water injection system
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 98 of 158
The following table explains what the setting is for each instrument on the xtree.
Instrument
PTT d/s IWV
Design
PTT d/s IWV
Design
PT
@ XOUT
Design
FT
Design
PI on MP hydraulic supply
Design
PI on HP hydraulic supply
Design pressure
0/ 380 bara temperature
-30/ 80
C pressure
0/ 380 bara flowrate
0/ 331m 3 /d pressure
0/ 569 bara pressure
0/ 569 bara
Setting on the Alarms
HiHi Hi
Indicates that the pressure nearly at the design pressure of the system
Indicates that the pressure is approaching the design pressure
Indicates that the temperature near the maximum design temperature of the risers
Annulus pressure near the maximum operating pressure none none none
Indicates that the temperature approaching the maximum design temperature of the risers
Annulus pressure approaching operating pressure none none none
Lo
Indicates the pressure is getting near to the riser drawing a vacuum
Indicates that the temperature approaching the minimum design temperature of the risers
Annulus pressure near min. operating pressure none
Low pressure on
MP hydraulic supply; valves are closing , and should be closed under controlled manner
Low pressure for the HP hydraulic supply, close the valves in controlled manner
LoLo
Indicates that the riser has drawn a vacuum
Indicates that the temperature near the minimum design temperature of the risers
Annulus pressure near min. operating pressure none
Valves closing.
Hydraulic valves should be closed
Valves closing.
The valves should be closed.
Table 12 Indication of Alarm Setting on the Xtree
For alarms set on each xtree see Doc: Schedule of Alarm Settings, Doc No: S-9000-GY-9200.
The settings for normal operation of the water injection system are:
Deaeration Tower
FIC-441001
FIC-441019
PIC-441021
Stripping Gas Regeneration
Set by FIC-441019
945 m 3 /hr (minimum flow)
5 barg
FIC-441027
TIC-442014 & 5
FIC-441001
Water Injection Pumps P-45001A/B/C
98 - 140 kg/hr
150
C
40 – 60 litres/hr
FIC 450145
FIC 450245
FIC 450345
750 m 3 /hr design
750 m 3 /hr design
750 m 3 /hr design
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 99 of 158
These parameters can be monitored on the inlet and outlet of the pump.
Monitoring
P-45001D suction pressure
P-45001D discharge pressure
P-45001D flow rate
P-45001D minimum flow valve position
P-45001D main discharge valve position
P-45001D bypass valve position
Device Location
PI-450441
PI-450443
FIC-450445
ZI-450445
Remote
Remote
Remote
Remote
ZLH/ZLL-450446 Remote
ZLH/ZLL-450501 Remote
Figure 16 Pump D Monitoring
Ref. P&ID: 37W022F0146-l-8000-GP-0046.03-2C
The Turbine Control Panel (TCP) in the LER controls the turbine, the gearbox and pump P45001D.
The CCR controls the turbine control panel, valves on the valve access platform and the fuel gas system.
The following hardware connections exist between TCP and CCR:
Permissive to start turbine from TCP
Request to start turbine from CCR
Trip gas turbine to idle speed from CCR
Cool down indication from TCP
Request to fast stop the turbine from CCR
Speed control of the turbine from CCR
Ready to load indication from TCP
Fast stop indication from TCP
Turbine Full Stop from TCP
Monitoring of pre-selected operating data for turbine, gearbox and pump will be carried out by using a serial link between TCP and CCR.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 100 of 158
The Solar TCP in the LER has the following functions:
Lamps:
Ready light illuminated indicates that the turbine is ready to start.
Starting & Local/Remote split-type, dual-function indicator. The correct mode is selected by rotating the Off/Local/Remote switch. Normal operation is remote.
Cool down light illuminated indicates that Normal stop switch has been pressed.
Stopping light illuminated indicates that normal, emergency or control system stop has been initiated.
Alarm Summary light illuminated indicates an alarm condition. The light remains on until condition is cleared and system is reset.
Shutdown Summary light illuminated indicates that the shutdown was initiated manually or automatically. The light remains on until control system is reset.
Back-up Active light illuminated indicates that the backup relay system has been activated by the following events:
Failure of microprocessor
Detection of fire
Detection of engine overspeed by backup overspeed monitor
Pressing of emergency stop switch.
The backup relay system will maintain lube oil pump operation to avoid possible damage to the engine or driven equipment.
Switches:
Off/Local/Remote switch can be in the following positions:
Off: start sequence is inhibited.
Local: Turbine can be operated from the LER, but this is FORBIDDEN.
Remote: Turbine should only be operated from CCR, normal operation. The
Turbine MUST NOT be operated from the LER.
Rotating the switch to the off position when the unit is operating will initiate a control system stop of the engine with no cool down cycle.
The key to the panel is held in the CCR and is only released under a Permit to
Work.
Th e key is only required if “Cool-down Lockout “ or “Fast Stop Lockout” occur, and for maintenance.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 101 of 158
Pushbuttons:
Emergency stop: This initiates immediate engine shutdown, with no cool-down cycle.
Horn Silence: This initiates the silence Audible Alarm Horn after an alarm or shutdown has occurred. Additional alarm or shutdowns will re-activate the alarm horn. To re-activate the horn silence, the button has to be pressed.
Acknowledge: This initiates the acknowledgement of alarms or shutdown and activates the Reset switch, which allows the system to be reset when an alarm or shutdown becomes inactive.
Reset: This initiates clearing of alarms or shutdown indicators, and the reset control system.
Start is permitted only if shutdowns are inactive and the control system has been reset.
Lamp Test: This initiates illumination of all indicator lights. If all of the lights are illuminated it indicates that all of the light circuits are intact.
Other Switches:
Back-up Reset: Rotary, two-position (off, on) switch, rotated clockwise to reset the back-up relay system. The back-up relay system cannot be reset until after the acknowledge and reset buttons are pressed. The back-up light will indicate when the back-up relay system has been reset.
Normal Stop: This initiates the cool down stop sequence. The engine speed is reduced to idle speed. Idle speed is maintained for a pre-selected cool down time before fuel gas is shut off and the engine shuts down.
Start: The Start switch on the local panel has been disabled and can only be started from the CCR.
Auto/Manual: Split type, dual-function switch, with individual indicator lights, illuminates to indicate mode selection. This switch should ALWAYS be in Auto.
Decrease: This initiates a decrease of speed from the LER, this is FORBIDDEN.
Increase: This initiates an increase of speed from LER, this is FORBIDDEN.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 102 of 158
Engine Gauge Panel
The engine gauge panel has the following instruments: o Lube Oil Filters Differential Pressure Gauge
Indicates differential pressure across the engine lube oil filter. o Lube Oil Pressure Gauge
Indicates lube oil header pressure. o Engine Compressor Discharge Press Gauge
Indicates engine compressor discharge pressure. Operating pressure varies based on engine speed and inlet air temperature. o Lube Oil Temperature Gauge
Indicates lube oil header temperature. o Gas Fuel Pressure Gauge
Indicates the pressure of fuel gas prior to the primary shutoff valve. o Turbine Starting Horn
The Horn sounds the alarm for a preset period to alert the operator that a start sequence has been initiated. The Alarm is silenced when the preset time period expires.
Figure 17 Solar Local Control Panel
Ref. P&ID: 37W022F0146-l-8000-GP-0090.04/05/06/07-2C.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 103 of 158
Figure 18 Solar Local Control Panel (showing emergency stop)
The following parameters can be monitored for the gas turbine:
Monitoring
Permissive to start
Start/Restart to Idle from CCR
Ready to Load
Trip to idle from CCR
Trip to Idle from CCR
Trip gas turbine to full stop.
Fuel Purge
Start Initiate
Starting
Purge Crank
Ignition
Light Off
Running
On Load
Stopping
Post Lube
Fast stop remote from CCR.
Power turbine speed
Gas turbine air inlet
Gas turbine inlet filter delta P
XI-450456
SI-450405
TI-450422
PDI-450401
Gas turbine inlet filter delta P PDI-450402
Gas turbine compressor discharge pressure PI-450432
Gas turbine T5 average
Gas turbine T5 max-T5 average
Fuel gas rate
Fuel gas pressure
Fuel gas temperature
Normal stop
Power turbine BRG 5-X-axis
TI-450433
TI-450434
FI-850005
PI-450433
TI-850099
XI-450419
YI-450415X
Device
XI-450407
XI-450440
XI-450430
XI-450409
XI-450410
XI-450411
XI-450412
XI-450413
XI-450414
XI-450415
XI-450416
XI-450417
XI-450418
XI-450420
XI-450421
XI-450422
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Location
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 104 of 158
Monitoring
Power turbine BRG 5-Y-axis
Power turbine axial
Power turbine trust bearing
Power turbine BRG 4-X-axis
Power turbine BRG 4-Y-axis
Gas producer NGP PV
Power turbine BRG 3-X-axis
Power turbine BRG 3-Y-axis
Power turbine BRG 2-X-axis
Power turbine BRG 2-Y-axis
Power turbine BRG 1-X-axis
Power turbine BRG 1-Y-axis
Gas producer axial
Gas producer trust bearing
Device
YI-450415Y
YI-450412
TI-450450417
YI-450407X
YI-450407Y
SI-450406
YI-450408X
YI-450408Y
YI-450409X
YI-450409Y
YI-450410X
YI-450410Y
YI-450411
TI-450431
The following parameters can be monitored for the gearbox:
Location
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Monitoring
Thrust Brg Outboard Temp RDN
Thrust Outboard Brg Temp
LSS NDE End Bearing Temp
Axial
Accelerator
HSS DE End Bearing Temp
Bearing HSS Y Axis
Bearing HSS X Axis
Bearing LSS Y Axis
Bearing LSS X axis
LSS DE End Bearing Temp
Thrust Inboard Brg Temp RDN
Thrust Inboard Bearing Temp
Device
TI-450414B
TI-450414A
TI-450412
ZI-450405
XI-450408
TI-450410
YI-450405Y
YI-450405X
YI-450406Y
YI-450406X
TI-450413
TI-450415B
TI-450415A
HSS NDE End Bearing Temp TI-450411
The following parameters can be monitored for the start motor:
Location
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Monitoring
Start motor voltage
Start motor current
Start motor speed
Device
XI-450424
XI-450423
SI-450407
The following parameters can be monitored for the accessory gearbox:
Location
Remote
Remote
Remote
Monitoring
Accessory Gearbox
Device
XI-450428
Location
Remote
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 105 of 158
The following parameters can be monitored for the lube oil:
Monitoring
Lube Oil Header Temperature RDN
Lube Oil Header Temperature
Lube Oil Header Pressure RDN
Lube Oil Header Pressure
Lube Oil Filter DP
Lube Oil Pre Post Pressure
Lube Oil Tank Temperature
Lube Oil Tank Pressure
Lube Oil Tank Level
Accessory Gearbox bearing drain temp
Gas Producer Bearing Drain temp
Gas Producer Bearing Drain Temperature
Device
TI-450424
TI-450425
PI-450434
PI-450435
PDI-450405
PI-450436
TI-450426
PI-450437
LI-450401
TI-450427
TI-450428
TI-450429
Power Turbine Bearing Drain Temperature
Scavenge Pump Pressure
Back-up Lube pressure Test
TI-450430
PI-450438
PI-450439
The following parameters can be monitored for the enclosure:
Monitoring
Enclosure Primary Vent Fan
Enclosure Temperature
Enclosure Back-up Vent Fan
Enclosure Pressure
Enclosure Filter DP
Device
XI-450426
TI-450432
XI-450427
PI-450420
PDI-450404
The following parameters can be monitored for WI pump P-45001D:
Location
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Location
Remote
Remote
Remote
Remote
Remote
Monitoring Device
WI DE Vibration
WI Pump DE Vibration
WI Pump DE Seal Pressure
WI Pump NDE Seal Pressure
YI-450400X
YI-450400Y
PI-450416
PI-450417
WI Pump DE Journal Bearing Temperature TI-450405
WI Pump NDE Journal Bearing Temperature TI-450406
WI Pump NDE Vibration
WI Pump NDE Vibration
WI Pump I/B Thrust Bearing Temperature
WI Pump O/B Thrust Bearing Temperature
YI-450401Y
YI-450401X
TI-450407
TI-450408
WI Pump Balance Return Line Temperature TI-450409
Location
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
WI Pump Speed
Pump HP (Indicated in MW)
SI-450404
XI-450425
Remote
Remote
Figures 19-21 show the graphic display screens for the gas turbine where the following parameters can be monitored:
Pump power
Enclosure pressure & temperature
Enclosure vent fan on/off
Enclosure Filter DP
Gas turbine not running or running. When the speed of turbine is less than 5% of the design speed, this will be indicated as not running
Gas turbine air inlet filter DP
Operating data in the fuel gas system.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 106 of 158
Figure 19 4 th Water Injection Pump Gas Turbine Graphic Display
Figure 20 Gas Turbine Monitoring & Lube Oil System Graphic Display
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 107 of 158
Figure 21 Gas Turbine to 4 th Water Injection Pump Gearbox Graphic Display
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 108 of 158
The de-aerator HIPS shutdown valves XXV-441002 and XXV-441040 must be manually reset following activation.
Note: When the seawater inlet shutdown valve XXV-441002 is used as part of an isolation, the air supply to the actuator should be locked off and disconnected.
A high-high level HIPS is installed on the inlet to the deaerator tower to prevent the column overfilling. The support pallet steelwork is adequate for the occasional (less than once a year) flooding of the tower, however, no appraisal for fatigue has been performed. Therefore, it is important that each flooding occasion is logged.
The HIPS is arranged as a level transmitter initiated a one-out-of-two voting system acting on two independent ESD valves and located on the inlet to the vessel. The HIPS level transmitters and shutdown valves are driven via the hardwired ESD system.
The deaerator also has a primary protection system in the form of a high high level shutdown switch acting on the upstream shutdown valve, XXV-441040, via a dedicated CPS solenoid. The primary shutdown system operates via the software based CPS system.
The HIPS comprises the following:
HIPS Transmitters High-high Setpoint
LT-441013
LT-441014
HIPS ESD Valves
3050 mm
3050 mm
First Valve
Second Valve
XXV-441002
XXV-441040 (via a dedicated ESD solenoid)
Primary Protection Transmitter High-high setpoint
LT-441032 2600 mm
Primary Protection Shutdown Valve
Upstream Valve XXV-441040 (via a dedicated CPS solenoid)
The HIPS is installed on the deaerator as the vessel relief valves are not designed for full seawater flow relief.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 109 of 158
PSD Resets
Field inputs which have caused a trip, after the measurement goes healthy, require to be reset in the PSD system. This is achieved at the operator workstations as follows:
1. On “Main System” graphic select “PSD”, this will display “PSD
Shutdown/Reset Page”.
2. On this page all process systems status will be displayed, i.e. input trip, output trip etc. On this page against each process system there is a reset pushbutton. If all field inputs for the process are healthy, the reset can be pressed and the status of input trips should change from red to green.
Note: Any field inputs which require a start-up override, and are therefore active due to plant not running, require a start-up override applied before the reset is pressed.
SUBSEA AND WATER INJECTION TREES
Refer to Cause and Effect S-9000-GC-9002
Input Cause
Red Shutdown
Yellow Shutdown
Water Injection Pumps Trip
Input
F&G or Manually from CCR
F&G or Manually from CCR
PSD
Action
Closes all wells, wing valves, master valves, annulus valves, SCSSV and crossover valve.
Closes all wells, wing valves, master valves, annulus valves, SCSSV and crossover valve.
Closes wing valves.
Table 13 ESD actions on tree valves
Alarm
Deaerator tower de-aerated seawater
LAH-441010
Deaerator tower de-aerated seawater
LAL-441010
Deaerator tower seawater inlet
FAH-441001
Deaerator tower seawater inlet
FAL-441001
Deaerator tower seawater outlet
FAH-441019
Deaerator tower seawater outlet
FAL-441019
Deaerator tower pressure
PAH-441003
Deaerator tower pressure
PAL-441003
Deaerator tower temperature
TAH-441008
Deaerator tower temperature
TAL-441008
Departed seawater outlet oxygen content
AAH-441018
Departed seawater outlet chlorine content
AAH-441017
Input
LT-441010
LT-441010
FT-441010
FT-441010
FT-441019
FT-441019
PT-441003
PT-441003
TT-441008
TT-441008
AT-441018
AT-441017
Action
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 110 of 158
Alarm
Purge system pressure PAH/L-441034
Purge system liquid leak
LAH-441033
Blower inlet pressure PAH-441021
Blower inlet pressure PAL-441021
Blower inlet hydrocarbon analyser
Blower P-44201A dp PDAH-442027
Blower P-44201A dp PDAL-442027
Blower P-44201B dp PDAH-442004
Blower P-44201B dp PDAL-442004
Blower P-44201A temp TAH-442002
Blower P-44201B temp TAH-442005
Blower outlet flowrate FAH-442008
Blower outlet flowrate FAL-442008
Heat exchanger outlet temp TAH-442014
Heat exchanger outlet temp TAL-442014
De-oxidiser V-44201 temp TAH-442015
De-oxidiser V-44201 temp TAL-442015
De-oxidiser V-44201 dp PDAH-442016
De-oxidiser outlet O2 content AAH-442019
Methanol Inlet flowrate FAH-442025
Methanol Inlet flowrate FAL-442025
Instrument air inlet
(process) mass flow FAH-441027
Instrument air inlet
(process) mass flow FAL-441027
Input
AT-441017
PS-441034
AT-441017
LS-441033
PT-441021
PT-441021
AT-441026
PDT-442027
PDT-442027
PDT-442004
PDT-442004
TT-442002
TT-442005
FT-442008
FT-442008
TT-442014
TT-442014
TT-442015
TT-442015
PDT-442016
AT-442019
FT-442025
FT-442025
FT-441027
FT-441027
Action
Purge controller in field
Purge controller in field
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
CPS
Alarm
Deaerator Tower Seawater
Level LAHHH-441013
Deaerator Tower Seawater
Level LAHHH-441014
Deaerator Tower Seawater
Level LAHH-441032
Deaerator Tower Seawater
Level LALL-441015
Deaerator Tower Temperature
TAHH-44107
Blower Inlet Pressure
PAHH-441020
Blower Inlet Pressure
PALL-441020
Blower Outlet Flowrate
FAHH-442009
Blower Outlet Flowrate
FALL-442009
De-oxidiser V 44201 Temperature
TAHH-442018
De-oxidiser V-44201 Temperature
Thermostats (in series)
Heater Tube Sheet Terminal Box
De-oxidiser V-44201
Heater Element Temperature
De-oxidiser outlet Temperature TAHH-441030
De-oxidiser Outlet Oxygen Level AAH-442019
Input
LT-441013
LT-441014
LT-441032
LT-441015
TT-441007
PT-441020
PT-441020
FT-442009
FT-442009
TT-442018
TS-442017
TS-442016
TT-441030
AT-442019
Action
ESD
ESD
PSD
PSD
PSD
PSD
PSD
PSD
PSD
PSD
MCC
MCC
PSD
CPS
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 111 of 158
6.2.1 Pump P-45001A Alarms & Actions
Alarm
GEC Purgepak PM 45001A
(mounted on front of UCP) PAL-450163
Injection pump P-45001A
DE journal bearing vibration high
YAH-450100 x/y
Injection pump P-45001A
DE journal bearing vibration high sensor fail YA-450100 x/y
Injection pump P-45001A
NDE journal bearing vibration high YAH 450101 x/y
Injection pump P-45001A pump NDE journal bearing vibration high sensor fail
YA 450101 x/y
Injection pump motor
PM-45001A motor
DE journal bearing vibration High
YAH-450102 x/y
Injection pump motor
PM-45001A DE journal bearing vibration high sensor fail
YA-450102 x/y
Injection pump motor
PM-45001A NDE journal bearing vibration high
YAH-450103 x/y
Injection pump motor PM-45001A NDE journal bearing vibration high sensor fail
YA-450103 x/y
Injection pump P-45001A
DE journal bearing
TAH-450105
Injection pump P-45001A
DE journal bearing temperature sensor fail
TA-450105
Injection pump P-45001A
NDE journal bearing
TAH-450106
Injection pump P-45001A
NDE journal bearing temperature sensor fail TA-450106
Injection pump P-45001A
I/B thrust bearing TAH-450107
Input
PT-450163
YT-450100X/Y
YT-450100X/Y
YT-450101X/Y
YT-450101X/Y
YT-450102x/Y
YT-450102x/y
YT-450103 x/y
YT-450103 x/y
TT-450105
TT-450105
TT-450106
TT-450106
TT-450107
Injection pump P-45001A
I/B thrust bearing temperature sensor fail TA-450107
TT-450107
Action
EPS
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
(contd)
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 112 of 158
6.2.1 Pump P-45001A Alarms & Actions (continued)
Alarm
Injection pump P-45001A
O/B thrust bearing TAH-450108
Input
TT-450108
Injection pump P-45001A
O/B thrust bearing temperature sensor fail TA-450108
Injection pump P-45001A balance return line temp TAH-450109
Injection pump motor PM-45001A air circuit temperature TAH-450110
TT-450108
TT-450109
TT-450110
TT-450110 Injection pump motor PM-45001A air circuit temp sensor fail TA-450110
Injection pump motor PM-45001A DE journal bearing temp high TAH-450111
Injection pump motor PM-45001A DE journal bearing temp sensor fail
TA-450111
Injection pump motor PM-45001A NDE journal bearing temp high
TAH-450112
Injection pump motor PM-45001A NDE journal bearing temp sensor fail TA-450112
Injection pump motor PM-45001A winding temp high
TAH-450113
Injection pump motor PM-45001A winding temperature sensor fail
TA-450113
Injection pump motor PM-45001A winding temperature high
TAH-450114
Injection pump motor PM-45001A winding temperature sensor fail
TA-450114
Injection pump motor PM-45001A winding temperature high
TAH-450115
Injection pump motor PM-45001A winding temperature sensor fail
TA-450115
Injection pump P-45001A DE seal pressure high
PAH-450116
TT-450111
TT-450111
TT-450112
TT-450112
TT-450113
TT-450113
TT-450114
TT-450114
TT-450115
TT-450115
PT-450116
Action
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
CPS
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
(contd)
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 113 of 158
6.2.1 Pump P-45001A Alarms & Actions (continued)
Alarm
Injection pump P-45001A DE seal pressure high pressure sensor fail PA-450116
Input
PT-450116
Injection pump P-45001A
NDE seal pressure high
PAH-450117
Injection pump P-45001A
NDE seal pressure high sensor fail
PA-450117
Injection pump motor PM-45001A coolant leakage level
LAH-450120
Injection pump P-45001A lube oil reservoir temperature TAH-450128
Injection pump P-45001A lube oil reservoir temperature TAL-450128
Injection pump P-45001A lube oil reservoir temperature sensor fail TA-450128
Injection pump P-45001A lube oil cooler outlet temperature
TAH-450131
Injection pump P-45001A lube oil supply pressure PAL-450134
P-45001A lube oil supply pressure sensor fail PA-450134
PT-450134
PT-450134
P-45001A lube oil supply pressure sensor fail PA-450135 PT-450135
P-45001A lube oil filter differential pressure PDAH-
450136
P-45001A lube oil filter differential pressure sensor fail
PDA-450136
P-45001A lube oil reservoir level LAL-450139
P-45001A lube oil reservoir level sensor fail LA-450139
P-45001A suction pressure alarm PAL-450141
P-45001A suction pressure alarm PAH-450141
P-45001A discharge pressure alarm PAL-450143
P-45001A discharge pressure alarm PAH-450143
Pump DE journal bearing vibration YAHH-450100 x/y
Pump NDE journal bearing vibration YAHH-450101 x/y
Pump DE journal bearing vibration YAHH-450102 x/y
Pump NDE journal bearing vibration YAHH-450103 x/y
Pump DE journal bearing vibration YAHH-450105 x/y
Pump NDE journal bearing vibration YAHH-450106 x/y
Motor Air circuit temperature TAHH-450110
Motor DE journal bearing TAHH-450111
Motor NDE journal bearing TAHH-450112
Motor winding temperature TAHH-450113
Motor winding temperature TAHH-450114
Motor winding temperature TAHH-450115
Lube oil supply pressure PALL-450135
PT-450117
PT-450117
LT-450120
TT-450128
TT-450128
TT-450128
TT-450131
PT-450136
PT-450136
LT-450139
LT-450139
PT-450141
PT-450141
PT-450143
PT-450143
YT-450100
YT-450101
YT-450102
YT-450103
YT-450105
YT-450106
TT-450110
TT-450111
TT-450112
TT-450113
TT-450114
TT-450115
PT-450135
Action
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
CPS
CPS
CPS
CPS
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ECP
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 114 of 158
6.2.2 Pump P-45001B Alarms & Actions
Alarm
GEC Purgepak PM-45001B
(mounted on front of UCP) PAL-450263
Injection pump P-45001B DE journal bearing vibration high
YAH 450200 x/y
Injection pump P-45001B DE journal bearing vibration high sensor fail
YA 450200 x/y
Injection pump P-45001B NDE journal bearing vibration high YAH 450201 x/y
Injection pump P-45001B NDE journal bearing vibration high sensor fail YA 450201 x/y
Injection pump motor PM-45001B
DE journal bearing vibration high
YAH-450202 x/y
Injection pump motor PM-45001B
DE journal bearing vibration high sensor fail YA-450202 x/y
Injection pump motor PM-45001B NDE journal bearing vibration high
YAH-450203 x/y
Injection pump motor PM-45001B
NDE journal bearing vibration high sensor fail YA-450203 x/y
Injection pump P-45001B
DE journal bearing TAH-450205
Injection pump P-45001B DE journal bearing temperature sensor fail TA-450205
Injection pump P-45001B
NDE journal bearing TAH-450206
Injection pump P-45001B NDE journal bearing temperature sensor fail TA-450206
Injection pump P-45001B
I/B thrust bearing TAH-450207
Injection pump P-45001B I/B thrust bearing temperature sensor fail
TA-450207
Injection pump P-45001B
O/B thrust bearing TAH-450208
Injection pump P-45001B O/B thrust bearing temperature sensor fail TA-450208
Injection pump P-45001B balance return line temperature
TAH-450209
Injection pump motor PM-45001B air circuit temperature
TAH-450210
Injection pump motor PM-45001B air circuit temperature sensor fail
TA-450210
Injection pump motor PM-45001B DE journal bearing temperature high
TAH-450211
Injection pump motor PM-45001B DE journal bearing temperature sensor fail
TA-450211
Input
PT-450263
YT 450200X/Y
YT-450200X/Y
YT-450201X/Y
YT-450201X/Y
YT-450202x/Y
YT-450202x/y
YT-450203 x/y
YT-450203 x/y
TT-450205
TT-450205
TT-450206
TT-450206
TT-450207
TT-450207
TT-450208
TT-450208
TT 450209
TT-450210
TT-450210
TT-450211
TT-450211
Action
EPS
ECP Mounted hardwired available in CCR via Data Link
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
CPS
ECP Mounted hardwired available in CCR via Data Link
Ditto
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted hardwired available in CCR via Data Link
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 115 of 158
6.2.2 Pump P-45001B Alarms & Actions (continued)
Alarm
Injection pump motor PM-45001B
NDE journal bearing temperature high
TAH-450212
Injection pump motor PM-45001B NDE journal bearing temperature sensor fail
TA-450212
Injection pump motor PM-45001B winding U temperature high
TAH-450213
Injection pump motor PM-45001B winding U temperature sensor fail
TA-450213
Injection pump motor PM-45001B winding V temperature high
TAH-450214
Injection pump motor PM-45001B winding V temperature sensor fail
TA-450214
Injection pump motor PM-45001B winding W temperature high
TAH-450215
Injection pump motor PM-45001B winding W temperature sensor fail
TA-450215
Injection pump P-45001B
DE seal pressure high
PAH-450216
Injection pump P-45001B DE seal high pressure sensor fail
PA-450216
Injection pump P-45001B
NDE seal pressure high
PAH-450217
Injection pump P-45001B
NDE seal high pressure sensor fail
PA-450217
Injection pump motor PM-45001B coolant leakage LAH-450220
Injection pump P-45001B lube oil reservoir temperature
TAH-450228
Injection pump P-45001B lube oil reservoir temperature TAL-450228
Injection pump P-45001B lube oil reservoir temperature sensor fail TA-450228
Injection pump P-45001B lube oil cooler outlet temperature TAH-450231
Input
TT-450212
TT-450212
TT-450213
TT-450213
TT-450214
TT-450214
TT-450215
TT-450215
PT 450216
PT 450216
PT 450217
PT 450217
LT 450220
TT 450228
TT 450228
TT 450228
TT-450231
Injection pump P-45001B lube oil supply pressure PAL-450234
Injection pump P-45001B lube oil supply pressure sensor fail
PA-450234
Injection pump P-45001B lube oil supply pressure sensor fail
PA-450235
PT 450234
PT 450234
PT 450235
Action
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 116 of 158
6.2.2 Pump P-45001B Alarms & Actions (continued)
Alarm
Injection pump P-45001B lube oil filter differential pressure PDAH-450236
Injection pump P-45001B lube oil filter differential pressure sensor fail
PDA-450236
Injection pump P-45001B lube oil reservoir level LAL-450239
Injection pump P-45001B lube oil reservoir level sensor fail LA-450239
Injection pump P-45001B suction pressure alarm PAL-450241
Injection pump P-45001B suction pressure alarm PAH-450241
Injection pump P-45001B discharge pressure alarm PAL-450243
Injection pump P-45001B discharge pressure alarm PAH-450243
Pump DE journal bearing vibration
YAHH-450200 x/y
Pump NDE journal bearing vibration
YAHH-450201 x/y
Pump DE journal bearing vibration
YAHH-450202 x/y
Pump NDE journal bearing vibration
YAHH-450203 x/y
Pump DE journal bearing vibration
YAHH-450205 x/y
Pump NDE journal bearing vibration
YAHH-450206 x/y
Motor air circuit temperature TAHH-450210
Motor DE journal bearing TAHH-450211
Motor NDE journal bearing TAHH-450212
Motor winding temperature TAHH-450213
Motor winding temperature TAHH-450214
Motor winding temperature TAHH-450215
Lube oil supply pressure PALL 450235
Input
PT 450236
PT 450236
LT 450239
LT 450239
PT 450241
PT 450241
PT 450243
PT 450243
YT-450200
YT-450201
YT-450202
YT-450203
YT-450205
YT-450206
TT-450210
TT-450211
TT-450212
TT-450213
TT-450214
TT-450215
PT-450235
Action
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
CPS
CPS
CPS
CPS
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ECP
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 117 of 158
6.2.3 Pump P-45001C Alarms & Actions
Alarm
GEC Purgepak PM-45001C
(mounted on front of UCP)
PAL-450363
Injection pump P-45001C DE journal bearing vibration high
YAH-450300 x/y
Injection pump P-45001C DE journal bearing vibration high sensor fail
YA-450300 x/y
Injection pump P-45001C NDE journal bearing vibration high
YAH-450301 x/y
Injection pump P-45001C NDE journal bearing vibration high sensor fail
YA-450301 x/y
Injection pump motor PM-45001C DE journal bearing vibration high
YAH-450302 x/y
Injection pump motor PM-45001C
DE journal bearing vibration high sensor fail
YA-450302 x/y
Injection pump motor PM-45001C
NDE journal bearing vibration high
YAH-450303 x/y
Injection pump motor PM-45001C
NDE journal bearing vibration high sensor fail
YA-450303 x/y
Injection pump P-45001C
DE journal bearing
TAH-450305
Injection pump P-45001C DE journal bearing temperature sensor fail
TA-450305
Injection pump P-45001C NDE journal bearing
TAH-450306
Injection pump P-45001C NDE journal bearing temperature sensor fail
TA-450306
Injection pump P-45001C
I/B thrust bearing
TAH-450307
Injection pump P-45001C I/B thrust bearing temperature sensor fail
TA-450307
Injection pump P-45001C
O/B thrust bearing
TAH-450308
Injection pump P-45001C O/B thrust bearing temperature sensor fail
TA-450308
Injection pump P-45001C balance return line temperature TAH-450309
Input
PT-450363
YT 450300X/Y
YT-450300X/Y
YT-450301X/Y
YT-450301X/Y
YT-450302x/Y
YT-450302x/y
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
YT-450303 x/y
YT-450303 x/y
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
TT-450305
TT-450305
TT-450306
TT-450306
TT-450307
TT-450307
TT-450308
TT-450308
TT-450309
Action
EPS
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
CPS
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 118 of 158
6.2.3 Pump P-45001C Alarms & Actions (continued)
Alarm
Injection pump motor PM-45001C air circuit temperature
TAH-450310
Injection pump motor PM-45001C air circuit temperature sensor fail
TA-450310
Injection pump motor PM-45001C DE journal bearing temperature high
TAH-450311
Injection pump motor PM-45001C DE journal bearing temperature sensor fail
TA-450311
Injection pump motor PM-45001C NDE journal bearing temperature high
TAH-450312
Injection pump motor PM-45001C NDE journal bearing temperature sensor fail
TA-450312
Injection pump motor PM-45001C winding U temperature high
TAH-450313
Injection pump motor PM-45001C winding U temperature sensor fail
TA-450313
Injection pump motor PM-45001C winding V temperature high TAH-450314
Injection pump motor PM-45001C winding V temperature sensor fail TA-450314
Injection pump motor PM-45001C winding W temperature high
TAH-450315
Injection pump motor PM-45001C winding W temperature sensor fail
TA-450315
Injection pump P-45001C
DE seal pressure high
PAH-450316
Injection pump P-45001C
DE seal pressure high sensor fail
PA-450316
Injection pump P-45001C
NDE seal pressure high
PAH-450317
Injection pump P-45001C
NDE seal pressure high sensor fail PA-450317
Injection pump motor PM-45001C coolant leakage LAH-450320
Injection pump P-45001C lube oil reservoir temperature
TAH-450328
Input
TT-450310
TT-450310
TT-450311
TT-450311
TT-450312
TT-450312
TT-450313
TT-450313
TT-450314
TT-450314
TT-450315
TT-450315
PT-450316
PT-450316
PT-450317
PT-450317
LT-450320
TT-450328
Action
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted hardwired available in
CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 119 of 158
6.2.3 Pump P-45001C Alarms & Actions (continued)
Alarm
Injection pump P-45001C lube oil reservoir temperature TAL-450328
Injection pump P-45001C lube oil reservoir temperature sensor fail TA-450328
Injection pump P-45001C lube oil cooler outlet temperature
TAH-450331
Input
TT-450328
TT-450328
TT-450331
Action
ECP Mounted
Annunciator
ECP Mounted
Annunciator
Injection pump P-45001C lube oil supply pressure PAL-450334
Injection pump P-45001C lube oil supply pressure sensor fail PA-450334
Injection pump P-45001C lube oil supply pressure sensor fail PA-450335
Injection pump P-45001C lube oil filter differential pressure PDAH-450336
Injection pump P-45001C lube oil filter differential pressure sensor fail PDA-450336
Injection pump P-45001C lube oil reservoir level LAL-450339
Injection pump P-45001C lube oil reservoir level sensor fail LA-450339
Injection pump P-45001C suction pressure alarm PAL-450341
Injection pump P-45001C suction pressure alarm PAH-450341
Injection pump P-45001C discharge pressure alarm PAL-450343
Injection pump P-45001C discharge pressure alarm PAH-450343
Pump DE journal bearing vibration
YAHH-450300 x/y
Pump NDE journal bearing vibration
YAHH-450301 x/y
Pump DE journal bearing vibration
YAHH-450302 x/y
Pump NDE journal bearing vibration
YAHH-450303 x/y
Pump DE journal bearing vibration
YAHH-450305 x/y
Pump NDE journal bearing vibration
YAHH-450306 x/y
Motor air circuit temperature TAHH-450310
Motor DE journal bearing TAHH-450311
Motor NDE journal bearing TAHH-450312
Motor winding temperature TAHH-450313
Motor winding temperature TAHH-450314
Motor winding temperature TAHH-450315
Lube oil supply pressure PALL-450335
PT-450334
PT-450334
PT-450335
PT-450336
PT-450336
LT-450339
LT-450339
PT-450341
PT-450341
PT-450343
PT-450343
YT-450300
YT-450301
YT-450302
YT-450303
YT-450305
YT-450306
TT-450310
TT-450311
TT-450312
TT-450313
TT-450314
TT-450315
PT-450335
ECP Mounted hardwired available in CCR via Data Link
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
ECP Mounted
Annunciator
CPS
CPS
CPS
CPS
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ESD via ECP
ECP
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 120 of 158
Ref. P&IDs: 37W022F0146-A-8000-GP-0090.05/06/07-2C
37W022F0146-A-8000-GP-0090.03-2C
Alarm Input
P-45001D pump vibration common alarm
P-45001D pump temperature common alarm
P-45001D pump seal pressure common alarm
Gearbox high temperature common alarm
Gearbox vibration alarm
P-45001D lube oil common alarm
Gas producer temperature common alarm
Fire & Gas common alarm
Gas producer vibration common alarm
Gas turbine other common alarm
Power turbine temperature common alarm
Power turbine vibration common alarm
Gas turbine start-up common alarm
Gas turbine common alarm
Alarm Summary (Package)
Gas turbine fast stop lockout alarm
Shutdown summary status (Package)
Gas turbine fast stop non lockout alarm
Gas turbine cool down lockout alarm
Gas turbine cool down non-lockout alarm
P-45001D Suction low pressure alarm
P-45001D Suction high pressure alarm
P-45001D Discharge low pressure alarm
P-45001D Discharge high pressure alarm
Water Injection Rate Low
Action
XA-450400 CPS
XA-450401 CPS
XA-450402 CPS
XA-450403 CPS
XA-450404 CPS
XA-450405 CPS
XA-450406 CPS
XA-450407 CPS
XA-450408 CPS
XA-450409 CPS
XA-450410 CPS
XA-450411 CPS
XA-450412 CPS
XA-450413 CPS
XA-450418 CPS
XA-450414 CPS
XA-450419 CPS
XA-450415 CPS
XA-450416 CPS
XA-450417 CPS
PI-450441 CPS
PI-450441 CPS
PI-450443 CPS
PI-450443 CPS
FIC-450445 CPS
NOTE: XA-450400 to XA-450412 are customized alarm groups. Predefined alarms in the LER are displayed in the CCR.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 121 of 158
Figure 22 Lube Oil System Common Alarm Graphic
Figure 23 Gearbox Temperature & Vibration Common Alarm Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 122 of 158
Figure 24 Pump Temperature, Pressure & Vibration Common Alarm Graphic
Figure 25 Gas Turbine Common Alarm Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 123 of 158
Figure 26 Power Turbine Vibration & Temperature and
Gas Turbine Start-up Common Alarm Graphic
Figure 27 Gas Producer Vibration & Temperature and
Fire & Gas Common Alarm Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 124 of 158
SUCTION DISCHARGE
Figure 28 Water Injection Pumps P-45001C&D Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 125 of 158
The LER gathers information on pump and turbine controls and shutdowns, and fire & gas systems. There is also a connection to the ESD system in the LER via hardwires from the CCR. The fuel gas system ESD isolation is connected directly to the existing ESD system.
Ref. Cause and Effect: L 8000-JC-0002.24, L-8000-JC-0002.38
Input Cause
Injection pump P45001D suction pressure PAHH-
450442
Injection pump P45001D suction pressure PALL-
450442
Injection pump P45001D
Discharge pressure PAHH-
450444
Injection pump P45001D discharge pressure PALL-
450444
Injection pump P45001D low low flow FALL-450446
Injection pump P45001D Fuel gas system temperature
TAHH-850005
Injection pump P45001D Fuel gas system temperature
TALL-850005
Injection pump P45001D fuel gas system temperature
TALL-850006
Injection pump P45001D fuel gas system pressure PAHH-
850005
Input
PT-450442
PT-450442
PT-450444
PT-450444
FT-450446
TT-850005
TT-850005
TT-850006
PT-850005
Action
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, open overboard dump valve
XV-450445, trip fuel gas heater ETP-
85002 and fast stop gas turbine
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
1 out of 2 voting (TT-850005 and TT-
850006). Intertrip to water injection system, close dischargeXV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
1 out of 2 voting (TT-850005 and TT-
850006). Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Intertrip to water injection system, close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 126 of 158
Input Cause
Injection pump P45001D fuel gas system pressure PALL-
850005
Gas turbine trip to full stop, by fast or emergency stop.
Intertrip from existing fuel gas system.
Intertrip from water injection system
Input
PT-850005
Solar
CUST553
Intertrip
Intertip
Action
Intertrip to water injection system close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Intertrip to water injection system close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005 and trip fuel gas heater ETP-
85002.
Intertrip to water injection system close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Close discharge XV-450446, equalisation XV-450501, fuel gas XV-
850005, trip fuel gas heater ETP-
85002 and fast stop gas turbine.
Figure 29 Trips and Interlocks Graphic
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 127 of 158
Figure 30 Water Injection System Interlocks Graphic (1)
Figure 31 Water Injection System Interlocks Graphic (2)
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 128 of 158
Refer to Cause and Effect L 8000-JC-0002.24
Input Cause
Injection pump P-45001A suction pressure PAHH-450142
Injection pump P-45001A suction pressure PALL-450142
Injection pump P-45001A balance line TAHH-450109
Injection pump P-45001A discharge pressure PAHH-450144
Injection pump P-45001A discharge pressure PALL-450144
Injection pump P-45001A low-low flow FALL-450146
Injection pump P-45001B suction pressure PAHH-450242
Injection pump P-45001B suction pressure PALL-450242
Injection pump P-45001B balance line TAHH-450209
Injection pump P-45001B discharge pressure PAHH-450244
Injection pump P-45001B discharge pressure PALL-450244
Injection pump P-45001B low-low flow FALL-450246
Injection pump P-45001C suction pressure PAHH-450342
Injection pump P-45001C suction pressure PALL-450342
Injection pump P-45001C balance line TAHH-450309
Injection pump P-45001C discharge pressure PAHH-450344
Injection pump P-45001C discharge pressure PALL-450344
Injection pump P-45001C low-low flow FALL-450346
Yellow Shutdown
Input Action
PT-450142 Trip pump A via HV switchboard and close discharge XV-450146
PT-450142 Trip pump A via HV switchboard and close discharge XV-450146
TT-450109 Trip pump A via HV switchboard and close discharge XV-450146
PT-450144 Trip pump A via HV switchboard and close discharge XV-450146
PT-450144 Trip pump A via HV switchboard and close discharge XV-450146
FIT-450146 Trip pump A via HV switchboard and close discharge XV-450146
PT-450242 Trip pump B via HV switchboard and close discharge XV-450246
PT-450242 Trip pump B via HV switchboard and close discharge XV-450246
TT-450209 Trip pump B via HV switchboard and close discharge XV-450246
PT-450244 Trip pump B via HV switchboard and close discharge XV-450246
PT-450244 Trip pump B via HV switchboard and close discharge XV-450246
FIT-450246 Trip pump B via HV switchboard and close discharge XV-450246
PT-450342 Trip pump C via HV switchboard and close discharge XV-450346
PT-450342 Trip pump C via HV switchboard and close discharge XV-450146
TT-450309 Trip pump C via HV switchboard and close discharge XV-450346
PT-450344 Trip pump C via HV switchboard and close discharge XV-450346
PT-450344 Trip pump C via HV switchboard and close discharge XV-450346
FIT-450346 Trip pump C via HV switchboard and close discharge XV-450346
Trips water injection pumps
P-45001A/B/C/D and closes discharge valves
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 129 of 158
Valve
Water injection wing valve water injection master valve water injection annulus valve cross-over valve
SCSSV
Master Xtree
1
3
5
7
9
Slave Xtree
2
4
6
8
10
Table 14 Tree valve Closure Sequences
These sequences are typical for tree shutdown and follow directly from 1 to 10:
The master xtree shutdown would be in the sequence of 1,3,5,7,9 and the slave xtree in the sequence of 2,4,6,8,10.
The IWV sequence of valve closure would always be 1 followed by 2.
The UMIV valve closure could be 3 followed by 4 or 4 followed by 3.
The AMV valve closure: 5 and then 6 or 6 and then 5, etc.
The same typical and alternative shutdown sequences apply to all of the following tables. Table 15 shows the shutdown sequences for West and Loyal injection centres, which have two slave xtrees to a master xtree.
Valve Master Xtree First Slave
Xtree
1 2
Second Slave
3 Water injection wing valve water injection master valve water injection annulus valve cross-over valve
SCSSV
4
7
10
13
5
8
11
14
6
9
12
15
Table 15 Sequence of Master and Slave Xtree Shutdown
on Red ESD for West and Loyal Water Injection Drill Centres
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 130 of 158
6.6.1 Yellow ESD shutdown
The causes for a Yellow ESD shutdown for the water injection system are variable. On a Yellow ESD, the following order of valve shutdown would occur.
Sequence of
Valve closure
1
Time Delay after valve closed (s)
30
Valve Tag Number
IWVsss934n
2
3
4
15
15
90
Water injection wing valve water injection master valve water injection annulus valve cross-over valve
UIMVsss933n
AMVsss935n
XOVTsss937n
Table 16 Sequence of Valve Shutdown on Yellow ESD
On a Yellow ESD, the sequences of master and slave xtree closure are shown in
Tables 17 & 18 below:
Valve
Water injection wing valve water injection master valve water injection annulus valve cross-over valve
Master Xtree
1
3
5
7
Slave Xtree
2
4
6
8
Table 17 Sequence of Master and Slave Xtree Shutdown
on Yellow ESD for Central and North Water Injection Drill Centres
Valve Master Xtree First Slave
Xtree
1 2
Second Slave
Water injection wing valve water injection master valve water injection annulus valve cross-over valve
SCSSV
4
7
10
13
5
8
11
14
3
6
9
12
15
Table 18 Sequence of Master and Slave Xtree Shutdown
on Yellow ESD for West and Loyal Water Injection Drill Centres
6.6.2 Water Injection Pump Trip PSD
On a water injection pump trip PSD only the IWV on the xtree will shut. The sequence of master and slave xtree will be as before, namely the master xtree closing first followed by the slave xtree(s).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 131 of 158
The design flowrates for existing drill centres and water injection wells are:
Design Flowrate (mbpd) maximum well flowrate design drill centre flowrate allowable drill centre flowrate
Table 19 Design Water Injection Flowrates
Pressure Parameters
Location
Schiehallion
Central
50
140
154
Schiehallion
West
50
100
96
Schiehallion
North
50
100
149
FPSO riser base
Schiehallion Central
West
North
Loyal
Design Pressure (barg) MAOP*
(barg)
323 315.7
323
323
323
323
312
314
316
322
Loyal
30
30
87.5
Transient Surge Pressure
(barg)
347.3
343.3
345.4
347.8
354.9
* This is equivalent to the maximum allowable operating pressure @ LAT of 276 barg.
Table 20 Pressure at the Water Injection Manifold
Temperature Parameters
Temperature: - Minimum
- Maximum
28 degC
60 degC
- Normal Discharge 63 degC
Shutdown
Normal Shutdown: Usually involves closing the wing valve
Process Shutdown: Wing valve closed
Start-up
The normal well start up sequence is:
Open subsurface safety valve (SCSSV)
Open water injection master valve (UMIV)
Monitor pressure indicator on the xtree
Open injection wing valve (IWV) when pressure across valve is equal.
Additional Well Start-up
To start a second or subsequent well, the sequence is:
open subsurface safety valve
open injection master valve
monitor pressure indicator on the xtree
open injection wing valve when pressure across the valve is equal.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 132 of 158
PUMP OVERHEATING / SEIZURE
Fault:
Pump operating below minimum flow
Correction:
Review pump-operating parameters with the pump vendor. Dismantle and repair unit and flow correct procedures during future operation.
HIGH BEARING TEMPERATURE
Fault:
Oil level too low or high
Correction:
Refer to Lubrication for correct level, and adjust as necessary
Fault:
Oil viscosity too high
Correction:
Use oil of recommended grade
Fault:
Excessive pump thrust
Correction:
Replace / overhaul pump cartridge
REDUCED PUMP OUTPUT FLOW
Fault:
Minimum flow line open or partially open.
Correction:
Review minimum flow circuit and make corrections to ensure proper operation.
Fault:
Impeller passages obstructed.
Correction:
Replace / overhaul pump cartridge.
Fault:
Pump internals worn on close running clearance surfaces
Correction:
Replace / overhaul pump cartridge.
VIBRATION AND NOISE
Fault:
Cavitation as air or gas comes out of entrainment at first stage impeller.
Correction:
Check pump design requirements. Make necessary changes or adjustment to system to create more pressure at pump suction.
LOSS OF DISCHARGE PRESSURE AFTER START UP
Fault:
Air pocket in suction line.
Correction:
Open all vents eliminate air from pumping.
LOSS OF DISCHARGE PRESSURE AFTER START UP
Fault:
Insufficient suction pressure causing product to vaporise in the pump.
Correction:
Check pump design requirements and proceed to make necessary changes or adjustments to system and create sufficient pressure.
NO DISCHARGE PRESSURE. FAILURE TO DELIVER LIQUID AT START
Fault:
Speed is too low – turbine or engine drives.
Correction:
Refer to the driver vendor information and take the recommended action.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 133 of 158
Certain operating conditions constitute abnormal turbine engine operation.
Identification of the following malfunctions will help in determining package maintenance or repair requirements.
Engine Compressor Surge
If engine compressor surge occurs, do not wait for controls to actuate - PRESS
STOP SWITCH IMMEDIATELY. Transient conditions in fuel or air systems can cause the engine to surge as described by these sounds and conditions:
Surge in the lower speed range could be indicated by engine failure to accelerate coupled with increased exhaust temperatures and a sound of buffeting or fluttering air
Surge in the higher speed range could be indicated by a loud roar and/or popping noises plus engine failure to accelerate to rated speed.
If surge occurs, shut down the engine immediately to prevent the rapid buildup of damaging temperatures. After the engine has coasted to a stop, attempt to restart as usual. If a surge occurs a second time, contact Solar Turbines
Customer Service.
Explosive Atmosphere
Dangerously explosive accumulations of natural gas, fuel fumes, oil tank vent leakage, or solvent fumes must be avoided at all times. This is achieved by proper ventilation, elimination of leaks, and by confining the use of solvents to appropriate maintenance facilities
Permissive to start the Turbine is not given
Fault: Permissive not given by Turbine to Start
Correction: Check Status on TCP in LER, clear alarms & reset Control System
Fault: XV-450446 not Closed. XV-450501 not Closed. XV-850002 not Open
Correction: Check that the Status on the valves and Correct the Faults.
Combustion Air Intake System Differential Pressure High
Fault: Inlet blocked
Correction: Clear
Fault: PBR/HVX bags need change out. Check local pressure transmitter
Correction: Change
Fault: Object blocking face of PBR/HVX filter bags
Correction: Clear
Fault: Object blocking the face of the vane separator
Correction: Remove
Fault: Wrong type of filter bags have been fitted
Correction: Change
Fault: Pressure transmitter misreading or connections are damaged
Correction: Replace
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 134 of 158
Combustion Air Intake System Differential Pressure Low or Zero
Fault: Access door to PBR/HVX filter bags is open
Correction: Close
Fault: PBR/HVX filter bags missing or damaged
Correction: Fit or Replace
Fault: Seals on filter bags or access door not in place or damaged
Correction: Replace
Fault: Pressure transmitter not functioning. Instrument pipework damaged
Correction: Replace
Fault: Drain hoses damaged or leaking on vane separator
Correction: Clear / Replace
Fault: Interface flange joints leaking Seal
Correction: Seal
Fault: Ducting or flexible damaged or punctured
Correction: Repair.
Contamination Downstream of Intake Filter Elements
Fault: Access door to PBR/HVX filter bags if open
Correction: Clean/close
Fault: PBR/HVX filter bags missing or damaged
Correction: Replace
Fault: Wrong type of filter bag fitted
Correction: Replace
Fault: Seals on PBR/HVX filter bags or access door are damaged/leaking
Correction: Replace
Fault: Downstream duct flanges are damaged or leaking
Correction: Seal
Fault: Drain hose connections to vane separator are damaged/leaking
Correction: Clear/replace
Fault: Instrument pipe work connections are leaking
Correction: Replace
Intake Filter House Doors not Functioning Properly
Fault: Hinges binding due to improper lubrication and maintenance
Correction: Clean and lubricate
Fault: Door incorrectly adjusted
Correction: Adjust as necessary
Fault: Broken seal
Correction: Replace as necessary
Fault: Dirt around bottom seal
Correction: Clean and adjust as necessary
Gas Turbine Enclosure Doors not Functioning Properly
Fault: Hinges binding due to improper lubrication and maintenance
Correction: Clean and lubricate
Fault: Door incorrectly adjusted
Correction: Adjust as necessary
Fault: Broken seal
Correction: Replace as necessary
Fault: Dirt around bottom seal
Correction: Clean and adjust as necessary
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 135 of 158
Gas Turbine Enclosure Ventilation System Differential Pressure High
Fault: Inlet blocked
Correction: Clear
Fault: GT2 filter panel dirty
Correction: Replace
Fault: Wrong type of filters fitted
Correction: Replace
Differential Pressure Low or Zero
Fault: Fitted access cover loose
Correction: Replace
Fault: Door GT2 filter missing
Correction: Replace
Fault: Wrong type of filters fitted
Correction: Replace
Fault: Seals on filters or cover missing or damaged
Correction: Replace
Fault: Interface flanges leaking
Correction: Seal
Loss of Fan Performance
Fault: Fan stopped
Correction: Check electrical supply and connections
Fault: Filters blocked
Correction: Replace filter
Fault: Motor operating in reverse
Correction: Rewire phases of fan
Fault: Vent dampers not fully open
Correction: Reset dampers
Fault: Flexible bellows failed
Correction: Check all bellows
Fault: Enclosure doors open
Correction: Shut doors
Fan Unit Vibrating
Fault: Bearing requires lubrication
Correction: Lubricate
Fault: Loose motor fixings
Correction: Tighten or replace
Fault: Damaged fan blade
Correction: Replace fan blade
Fault: Foreign material in fan unit
Correction: Clear debris
Fault: No power to damper/ vent dampers closed
Correction: Check circuit/ open dampers
Combustion Exhaust Gases leaking from Assembly Joints
Fault: Fixing hardware loose or missing
Correction: Tighten or replace hardware as necessary
Fault: Gaskets between joints deteriorated or not working properly
Correction: Replace gaskets or if not working properly tighten
Fault: Compensator worn or deteriorated
Correction: Replace parts
Sudden Vibration or Noise
Fault: Thermal growth restricted
Correction: Check mounts and bearings for ease of movements
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 136 of 158
APPENDIX A - VALVE POSITION TABLES
CSO Car Seal Open
D/S Downstream
LC Locked Closed
LO Locked Open
U/S Upstream
Valve Position Table No.1
Refer to P&ID L-1000-GP-0043.00
Valve Tag
Number
Description
HV-441001 XXV-441040 D/S drain valve
HV-441004
HV-441005
HV-441121
HV-878031
FCV-441001 U/S drain valve
FCV-441001 D/S drain valve
V-44101 inlet calcium nitrate injection block valve
V-44101 inlet biocide injection block valve
Start-up
Position
Closed and blanked
Closed and blanked
Closed and blanked
Open
Closed and blanked
Normal
Operation
Closed and blanked
Closed and blanked
Closed and blanked
Open
Closed and blanked
HV-878032
HV-878033
V-44101 outlet biocide injection block valve
V-44101 outlet biocide injection bleed valve
HV-441112 V-44101 outlet biocide injection block valve
HV-441003 V-44101 inlet anti-foam injection
HV-441080 Z-44101 instrument air supply
HV-441020 PSV-441005 U/S block valve
HV-441021 PSV-441005 D/S block valve
HV-441023 PSV-441006 U/S block valve
HV-441022 PSV-441006 D/S block valve
HV-441024 PSV-441005/6 bypass (globe valve)
HV-441025 PSV-441005/6 bypass
Closed
Closed and blanked
Closed
Closed
Open
LO*
LO*
LC*
LC*
Closed
Closed
Closed
Closed and blanked
Closed
Closed
Open
LO*
LO*
LC*
LC*
Closed
Closed
HV-441017
HV-441019
HV-441026
HV-441100
HV-441012
Booster pumps P-43001A/B/C to V-44101
O
2
scavenger injection point
V-44101 drain to overboard
V-44101 outlet scale inhibitor injection
FCV-441019 U/S drain valve
Open
Closed
Closed
Closed
Closed and blanked
Open
Closed
Closed
Closed
Closed and blanked
HV-441013 FCV-441019 D/S drain valve
HV-441014 FCV-441019 D/S block valve
HV-441016 V-44101 outlet
Closed and blanked
Open
Closed
Closed and blanked
Open
LO
* Valves mechanically interlocked to ensure that either PSV-441005 or PSV-441006 is on line
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 137 of 158
Valve Position Table No.2
Refer to P&ID L-1000-GP-0044.00
Valve Tag
Number
Description
HV-441066 PCV-441023 U/S block valve
HV-441065 PCV-441023 D/S block valve
HV-441063 PCV-441023 D/S block valve
HV-441061 PCV-441021 U/S block valve
HV-441062 PCV-441021 D/S block valve
HV-441070 FCV-441027 U/S block valve
HV-441068 FCV-441027 D/S block valve
HV-442001 P-44201A inlet
HV-442006 P-44201A outlet
HV-442007 P-44201B inlet
HV-442012 P-44201B outlet
HV-442024 FI-442025 U/S drain valve
HV-442021 FI-442025 D/S block valve
HV-442026 X-44201 tube side vent
HV-442027 X-44201 tube side drain
HV-442031 V-44201 vent valve
Start-up
Position
Open
Open
Open
Open
Open
Open
Open
CSO
CSO
CSO
CSO
Closed and blanked
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Closed
Open
Open
Open
Open
HV-442029 V-44201 manual vent (globe valve)
HV-442030 V-44201 manual blowdown (ball valve)
HV-442035 V-44201 outlet
HV-442039 X-44201 outlet
HV-442041 TCV-442014 block valve
HV-442040 TCV-442014 block valve
Valve Position Table No.3
Refer to P&ID L-1000-GP-0046.01
The following valve position table covers the line-up of water injection pump P-45001A:
Valve Tag
Number
Description
HV-450100 Instrument air supply block valve
HV-450101 Air supply to 4-way block valve
HV-450135 Air supply to discharge valve
HV-450136 Air supply to minimum flow valve
HV-450137 Spare air supply valve
HV-450138 Spare air supply valve
HV-450121 Lube oil tank T-45001A drain
HV-450104 Oil cooler X-45001A cooling medium supply
HV-450106 X-45001A cooling medium supply drain valve
Start-up
Position
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Normal
Operation
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Normal
Operation
Open
Open
Open
Open
Open
Open
Open
CSO
CSO
CSO
CSO
Closed and blanked
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Closed
Open
Open
Open
Open
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 138 of 158
Valve Tag
Number
Description
HV-450105 X-45001A cooling medium return
HV-450109 X-45001A cooling medium return line drain
HV-450139
HV-450110
HV-450111
HV-450113
HV-450114
HV-450115
HV-450116
-
HV-450123
HV-450132
HV-450144
HV-450141
HV-450142
HV-450125
HV-450126
HV-450127
HV-450128
HV-450134
HV-450133
HV-450129 FCV-450145 D/S block valve (overboard dump line)
X-45001A D/S lube oil drain valve
PDIT-450136 block valve
PDIT-450136 block valve
F-45001A vent valve
F-45001A drain valve
F-45002A vent valve
F-45002A drain valve
F-45001A/2A equalising valve
HV-450117 Lube oil line to PCV-450137
HV-450140 RO-450160 U/S block valve
HV-450118 PIT-450134 (lube oil supply) block valve
HV-450119 PT-450135 (lube oil supply) block valve
HV-450103 PIT-450117 (NDE seal pressure) block valve
HV-450102 PIT-450116 (DE seal pressure) block valve
HV-450143 Balance return line drain
HV-450122 Water inlet block valve
HV-450130 Water inlet drain valve
PIT-450141 (water inlet) block valve
HV-450124 PT-450142 (water inlet high/low trip) block valve
HV-450131 Water inlet vent valve
Discharge line vent
Discharge line vent
Discharge line drain
Discharge line drain
PIT-450143 (discharge line) block valve
PT-450144 (discharge high/low trip) block valve
FIT-450145 block valve
FIT-450145 block valve
Discharge line drain valve
Discharge line drain valve
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO
Start-up
Position
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Open
Open
Open
Normal
Operation
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Open
Open
Open
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 139 of 158
Valve Position Table No.4
Refer to P&ID L-1000-GP-0046.01
The following valve position table covers the line-up of water injection pump P-45001B.
Valve Tag
Number
Description
HV-450200 Instrument air supply block valve
HV-450201 Air supply to 4-way block valve
HV-450235 Air supply to discharge valve
HV-450236 Air supply to minimum flow valve
HV-450237 Spare air supply valve
HV-450238 Spare air supply valve
HV-450221 Lube oil tank T-45001B drain
HV-450204 Oil cooler X-45001B cooling medium supply
HV-450206 X-45001B cooling medium supply drain valve
HV-450205 X-45001B cooling medium return
HV-450209 X-45001B cooling medium return line drain
HV-450239 X-45001B D/S lube oil drain valve
HV-450210 PDIT-450236 block valve
HV-450211 PDIT-450236 block valve
HV-450213 F-45001B vent valve
HV-450214 F-45001B drain valve
HV-450215 F-45002B vent valve
HV-450216 F-45002B drain valve
F-45001B/2B equalising valve
HV-450217 Lube oil line to PCV-450237
HV-450240 RO-450260 U/S block valve
HV-450218 PIT-450234 (lube oil supply) block valve
HV-450219 PT-450235 (lube oil supply) block valve
HV-450203 PIT-450217 (NDE seal pressure) block valve
HV-450202 PIT-450216 (DE seal pressure) block valve
HV-450243 Balance return line drain
HV-450222 Water inlet block valve
HV-450230 Water inlet drain valve
HV-450223 PIT-450241 (water inlet) block valve
HV-450224 PT-450242 (water inlet high/low trip) block valve
HV-450231 Water inlet vent valve
HV-450232 Discharge line vent
Start-up
Position
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Open
Open
Open
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Normal
Operation
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Open
Open
Open
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 140 of 158
Valve Tag
Number
HV-450244 Discharge line vent
Description
HV-450241 Discharge line drain
HV-450242 Discharge line drain
HV-450225 PIT-450243 (discharge line) block valve
HV-450226 PT-450244 (discharge high/low trip) block valve
HV-450227 FIT-450245 block valve
HV-450228 FIT-450245 block valve
HV-450234 Discharge line drain valve
HV-450233 Discharge line drain valve
Start-up
Position
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO
Normal
Operation
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO HV-450229 FCV-450245 D/S block valve (overboard dump line)
Valve Position Table No.5
Refer to P&ID L-1000-GP-0046.01
The following valve position table covers the line-up of water injection pump P-45001C.
Valve Tag
Number
Description
HV-450300 Instrument air supply block valve
HV-450301 Air supply to 4-way block valve
HV-450335 Air supply to discharge valve
HV-450336 Air supply to minimum flow valve
HV-450337 Spare air supply valve
HV-450338 Spare air supply valve
HV-450321 Lube oil tank T-45001C drain
HV-450304 Oil cooler X-45001C cooling medium supply
HV-450306 X-45001C cooling medium supply drain valve
HV-450305 X-45001C cooling medium return
HV-450309 X-45001C cooling medium return line drain
HV-450339 X-45001C D/S lube oil drain valve
HV-450310 PDIT-450336 block valve
HV-450311 PDIT-450336 block valve
HV-450313 F-45001C vent valve
HV-450314 F-45001C drain valve
HV-450315 F-45002C vent valve
HV-450316 F-45002C drain valve
F-45001C/2C equalising valve
HV-450317 Lube oil line to PCV-450337
HV-450340 RO-450360 U/S block valve
Start-up
Position
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Normal
Operation
Open
Open
Open
Open
Closed
Closed
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Closed and blanked
Open
Open
Closed and blanked
Closed and blanked
Closed and blanked
Closed and blanked
Closed
Open
Closed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 141 of 158
Valve Tag
Number
Description
HV-450318 PIT-450334 (lube oil supply) block valve
HV-450319 PT-450335 (lube oil supply) block valve
HV-450303 PIT-450317 (NDE seal pressure) block valve
HV-450302 PIT-450316 (DE seal pressure) block valve
HV-450343 Balance return line drain
HV-450322 Water inlet block valve
HV-450330 Water inlet drain valve
HV-450323
HV-450324
HV-450331
HV-450332
HV-450344
HV-450341
HV-450342
HV-450325
HV-450326
PIT-450341 (water inlet) block valve
PT-450342 (water inlet high/low trip) block valve
Water inlet vent valve
Discharge line vent
Discharge line vent
Discharge line drain
Discharge line drain
PIT-450343 (discharge line) block valve
PT-450344 (discharge high/low trip) block valve
HV-450327 FIT-450345 block valve
HV-450328 FIT-450345 block valve
HV-450334 Discharge line drain valve
HV-450333 Discharge line drain valve
Start-up
Position
Open
Open
Open
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO
Normal
Operation
Open
Open
Open
Open
Closed
LO
Closed and blanked
Open
Open
Closed and blanked
Closed
Closed and blanked
Closed
Closed and blanked
Open
Open
Open
Open
Closed
Closed and blanked
LO HV-450329 FCV450345 D/S block valve (o’board dump line)
Valve Position Table No.6
Refer to P&ID L-1000-GP-0046.02
Valve Tag
Number
Description
HV-450001 Injection water to V-43001 drain valve
HV-450002 Injection water to V-43001
HV-450003 F-43001A/B to P-45001A/B/C
HV-450005 Water make-up to 2 nd stage separator V-21201
HV-450012 P-45001A discharge to AT-450020
HV-450007 P-45001A discharge to AT-450020 low point drain
HV-450006 P-45001B discharge to AT-450020
HV-450013 P-45001B discharge to AT-450020 low point drain
HV-450014 P-45001C discharge to AT-450020
HV-450008 P-45001C discharge to AT-450020 low point drain
HV-450009 P-45001A/B/C discharge AT-450020
HV-450010 P-45001A/B/C discharge AT-450020 low point drain
Start-up
Position
Closed and blanked
Closed
Open
Closed
Open
Closed & blanked
Open
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Normal
Shutdown
Closed and blanked
Closed
Open
Closed
Open
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Open
Closed and blanked
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 142 of 158
Valve Position Table No.7
SUBSEA VALVE LINE-UP (sample summary – not complete)
Position Signature/Date Tag No.
CW11/N
SCSSV-105931N
LIMV-105921N
UIMV-105933N
AMV-105935N
IWV-105934N
XOVT-105937N
CHI-105926N
Closed
Open
Closed
Closed
Closed
Closed
Set at a value of 2.3
(i.e. 23% or 1.7 turns)
CW12/P
SCSSV-105931P
LIMV-105921P
UIMV-105933P
AMV-105935P
IWV-105934P
XOVT-105937P
CHI-105926P
Closed
Open
Closed
Closed
Closed
Closed
Set at a value of 2.3
(i.e. 23% or 1.7 turns)
Central WI Manifold
ROVV-180921
ROVV-180922
ROVV-180923
ROVV-180924
Open
Open
Closed
Closed
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 143 of 158
th
REPORT NO: S/UTG/ /02
SECURITY CLASSIFICATION: UNCLASSIFIED
ISSUE DATE: 11/04/20
MAIN TITLE : Schiehallion FPSO
SUB TITLE : 4th Gas Turbine Exhaust Dispersion Study
CLIENT:
PRINCIPAL RECIPIENT:
BP Exploration - Schiehallion
COMMISSIONED BY:
ISSUING DEPARTMENT/DIVISIONS: UTG
PREPARED BY: AUTHORISED FOR ISSUE BY:
______________
Chris Savvides
________________
Vincent Tam
ACKNOWLEDGEMENT RECORD PAGE: Yes
ABSTRACT :
This report describes the results of the study for the dispersion of hot exhaust gas from the proposed
Water Injection 4 th Gas Turbine, on the Schiehallion FPSO. The study consisted of the following:
Assessment of the turbine exhaust temperature distribution on helicopter and crane operations for two turbine locations and various exhaust orientations
Quantify the temperature and air quality (NO
2,
and CO concentrations) for the chosen location and configuration and assess impact on Helideck, crane and personnel at different locations on the FPSO where they could be normally present.
The results showed that with the current Gas Turbine location, forward of the Crane pedestal at frame
40, with the exhaust discharging at an elevation of 55m and pointing forward, there should be minimal impact on the Helideck, Crane operations, or to air quality.
KEYWORDS : Turbine Exhaust, Dispersion
DISTRIBUTION: End of the Report
FOR EXTERNAL CLIENT LISTING: No
UTG JOB NO: UTG:
Original report held at Britannia Data Management (BDM), 628 Western Avenue, Park Royal, London, W3
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 144 of 158
SUMMARY
This report describes the results of the study for the dispersion of hot exhaust gas from the proposed Water Injection 4 th Gas Turbine, on the Schiehallion FPSO. The study consisted of the following:
Assessment of the turbine exhaust temperature distribution on helicopter and crane operations for two turbine locations and various exhaust orientations
Quantify the temperature and air quality (Nitrogen dioxide - NO
2
and Carbon Monoxide – CO, see
Footnotes 1 & 2 ) concentrations for the chosen exhaust location and configuration and assess impact on Helideck, crane and personnel at different locations on the FPSO where they could be normally present.
The results showed that with the current Gas Turbine location, forward of the Crane pedestal at frame 40, with the exhaust discharging at an elevation of 55m and pointing forward, there should be minimal impact on the Helideck, Crane operations or to air quality.
The Schiehallion FPSO has been operating off the west of Shetland since 1998. Due to the requirement of water injection, a 4 th Gas Turbine will need to be installed to provide the extra power.
As part of safety requirements, the hot plume characteristics from a gas turbine need to be assessed and quantify so as not impair Helideck, crane or other operations. There is also a requirement to demonstrate that the air quality meets UK regulations. This report summarises the findings of the computational study to find the best location and orientation of the 4 th Turbine
Exhaust so that the effects of the hot exhaust plume would have a MINIMUM impact on the
Helideck, crane operations and at other manned areas.
The fluid flow software FLACS has been used for the plume dispersion calculations. BP has extensively used FLACS for a lot of projects involving dispersion and gas accumulation calculations. It has been validated for a number of large-scale experimental data.
1 Sulphur Dioxide is not considered because Sulphur is not present in the Schiehallion fuel gas supply.
2 Particulate matter is not considered, as the level present in the Taurus 70 exhaust gas is very low
(to be quantified by Solar).
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 145 of 158
Objectives
The main objectives of this analysis were to:
Assess the impact of the exhaust plume of the proposed 4 th Gas Turbine on Helideck and
Crane operations. Identify the location and orientation of the turbine exhaust that would have minimum impact on Schiehallion operations
Quantify the availability of the Helideck and Crane based on the wind conditions and temperatures distribution and also assesses the effect of the exhaust gases on the manned areas for the different locations and exhaust orientations. For Helideck operations, it is a requirement that the isothermal line at 20m directly above the Helideck is less than +2 degrees above the ambient temperature (Footnote 3 )
Quantify the air quality (NO
2 and CO) levels in manned areas for the final Gas Turbine location.
The study of the exhaust dispersion using Computational Fluid Dynamics requires an accurate representation of all the major structure and equipment, the wind and exhaust parameters. An accurate computer model of the Schiehallion FPSO Installation was already available (used previously for explosion hazards). This was constructed based on the as build PDMS CAD model
[1, 2]. Details of the Gas Turbine and exhaust were incorporated into the model.
The new water injection Gas Turbine is a Taurus 70 from Solar Turbines Incorporated. Exhaust flow rates, temperatures and gas analysis are for full load output of 6700 -7800 kW, depending on ambient temperature.
3 The Civil Aviation Authority (CAA) paper 99004 Section 4.1.4 includes a sentence stating “CAP
437 requires that notification to operators be given if temperatures in excess of 2
C above ambient are liable to exist above the Helideck. Section 4.2.3 also states “Minimisation of the impact of hot exhausts (see Section 4.1.4) has generally been regarded as keeping the Helideck free of excess temperature, at least to a reasonable height (say greater than 20m above deck level). Ideally, in conjunction with flight operations planning, approach and take-off flight paths should also be considered.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 146 of 158
The following Turbine Data [3] has been used in the simulations:
Load Case
1
2
Turbine Load
Exhaust Flow
Rate kg/s
100% at 5
100% at 23 o o
C
C
27.7
24.9
Exhaust Gas
Temperature, o
C
488
506
NO
2
Concentration mg/m 3
74.03
72.78
CO
Concentration mg/m 3
53.65
52.69
Table 1: Turbine Exhaust Conditions (see Footnote 4 )
During the course of this study 3 different exhaust diameters were used (1000, 900 and 800mm).
For the final results the exhaust diameter used is 900 mm
The exhaust gas is specified as a non-reacting mixture of gas and air with a molecular weight of
28.
The CFD analyses performed are 3-dimensional, steady state, turbulent simulations of the flow of a non-reacting mixture of ambient air and hot gases. Buoyancy forces due to the gas/air mixture density and temperature variations are incorporated directly.
Two locations on the FPSO were considered for the Gas Turbine. Both locations were on the
Starboard side
The lay-down area on Pallet 8 (Frame 35) just forward of the Blast Wall separating the
Living Quarters from the Process areas.
The lay-down area on Pallet 7 (Frame 40) forward of the aft Crane Pedestal
Several different orientations of the turbine exhaust have been tried for each of the two locations namely:
Discharging vertically up
Discharging to starboard
Discharging 45 degrees forward-starboard
Discharging forward, at 0, 10, 20 and 45 degrees to the horizontal
4 The NO
2
exhaust analysis figures relate to Solonox Combustion. For this analysis it is assumed that all oxides of nitrogen are considered to be nitrogen dioxide (NO
2
). This is a worst case assumption, which in practice means that calculated NO
2 levels would be slightly higher than actual levels. This will (together with other factors discussed later in this document) provide assurance that air quality will meet regulatory requirements.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 147 of 158
For the preliminary investigations to evaluate the location and orientation of the turbine exhaust, only winds at 6 m/s from Forward and Starboard (0-45 degrees) were considered as these would have a direct impact on the Helideck operability, which was the primary reason for this evaluation.
For the final assessment, results were obtained for all wind directions at 6 and 12 m/s so that the impact of the exhaust temperatures and NO
2
levels on the Crane boom, Crane cabin and other manned areas is assessed. Table 2 lists all the weather conditions and the probability of occurrence for the Schiehallion FPSO [4].
0 - 2.5 2.5 - 7.5
Wind Speed, m/s
7.5 - 12.5 12.5 - 17.5 >17.5 % Probability
Wind Direction relative to vessel
Angle from Forward
10-30
40-60
70-90
100-120
130-150
160-180
190-210
220-240
250-270
280-300
310-330
340-360
% Probability
0.00%
0.00%
0.71%
0.71%
0.83%
1.18%
7.8%
1.18%
0.83%
1.18%
0.59%
0.35%
0.24%
1.65%
0.35%
1.89%
2.60%
3.90%
8.97%
39.6%
8.26%
5.90%
2.13%
2.24%
0.83%
0.83%
10.27%
5.67%
1.42%
0.47%
0.12%
0.35%
0.12%
0.00%
0.71%
1.42%
4.13%
9.45%
34.1%
0.00%
0.00%
0.00%
0.24%
1.42%
5.55%
16.3%
7.56%
1.18%
0.24%
0.12%
0.00%
0.00%
0.00%
0.00%
0.00%
0.00%
0.12%
0.47%
2.2%
1.30%
0.35%
0.00%
0.00%
0.00%
0.00%
1.8%
0.4%
3.3%
5.0%
10.4%
25.6%
100.0%
28.6%
13.9%
5.0%
3.4%
1.3%
1.4%
Table 2: Wind Frequency (Port 0-180, Starboard 180-360)
For Helideck operations, it is a requirement that the isothermal line at 18m directly above the
Helideck is less than +2 degrees above the ambient temperature
The temperature of the Crane boom (wire rope & lubricant, warning lights, load sensors) should not exceed 85 o C [5]
The UK air quality regulations objectives (NO
2
and CO only) are defined in the Environment
Agency (EA) Guidance Notes [6] and are shown in Table 3 below:
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 148 of 158
Pollutant
NO
2
NO
2
CO
Reference period
Hourly mean
Annual mean
8 hour mean
Limit Value
200
g/m 3
40
g/m 3
11.6 mg/m 3
Limit Value to be met by
31 Dec 2005
31 Dec 2003
Table 3: Environmental Quality Standards – Protection of Human health [table 1 Ref 6]
Initially the 4 th Gas Turbine was to be located on the lay-down area, Pallet 8 (Frame 35), just forward of the Blast Wall. The distance of the discharging exhaust to the centre of the Helideck would have been approximately 40 metres. The elevation of the exhaust was restricted to 47m, as a higher exhaust would have interfered with Crane operations.
Preliminary investigations, examining different orientations of the exhaust, have shown that due to its proximity to the Helideck and also the restriction on the elevation of the discharge, the temperatures above the Helideck (hovering height) would be greater than +2 degrees C, which would restrict safe helicopter operations for winds from the Forward to 20 degrees Starboard.
From the wind frequency table 2, this would have made the Helideck unavailable for almost 30% of the time.
This factor was one of a number of reasons why the Pallet 8 location was changed to the Pallet 7 location.
The second location for the Gas Turbine, the lay-down area on Pallet 7 (Frame 40) forward of the aft Crane Pedestal was then examined. This location is some 60 metres from the Helideck. From the results of the preliminary investigations for the first location, it was decided that the exhaust discharge should be forward and at an elevation at least above the Crane boom. The forward discharge allows the exhaust gases extra distance away from the Helideck, while the extra elevation, firstly eliminates any problems with hot gases on the Crane boom and cabin and secondly the exhaust is not in the lee of recirculation areas.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 149 of 158
The final location and orientation of the turbine exhaust is:
Location
Orientation
Diameter
E=115m N=375m Elevation=55m
Discharging Forward at 10 degrees up from the horizontal
900mm
For this location and orientation a full set of results is presented for the 2 cases listed in Table 1.
All wind directions and wind speeds of 0, 6 and 12 are presented. These represent about 85% of all weather conditions. The other 15% are for higher wind speeds. One result for a 20 m/s wind from the Forward direction gave similar results to the 12 m/s case.
For this load case, the gas Turbine is operating at 100%, with an exhaust flow rate of 27.7 kg/s and a temperature of 488 o C. The results are presented in Table 4. The temperatures are given in degrees Celsius above the ambient temperature. The NO
2
concentrations are given in
g/m 3 .
Living Quarters refers to the area behind the Blast Wall and Process deck, areas forward of the
Blast Wall at elevations between 32 and 50m
The results show the following:
Helideck operations might be affected by winds from 10 degrees from
Starboard at 12 m/s or higher (8-10% of the time). The temperature is only 3 degrees above ambient just slightly above the requirements.
The maximum temperature at the crane boom would be less than 20 degrees for all weather conditions. This is well within the requirements
There will be concentrations higher than 40
g/m 3 for the forward, and up to 10 degrees from
Starboard. The concentration increases almost linearly for higher wind speed. Wind directly from the aft of the FPSO will produce high levels of NO
2
concentration at the Turret area and the forward Crane cabin (300 and 240
g/m 3 respectively). The frequency of the wind from the aft is very low, of the order of 1%.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 150 of 158
Simulation
Number
Wind
Direction relative to
FPSO heading
Wind
Speed m/s
HELIDECK
NO
2
Temp
Deg C
CRANE
BOOM
Temp
Deg C
Crane Cabin
Living
Quarters
Process
Deck
NO
2
Concentration
060000 No Wind
060600
061200
062000
360600
260605
261205
260610
261210
260622
261222
260645
261245
260667
261267
260690
261290
260613
160622
161222
160645
161245
160667
161267
160680
161280
160690
161290
160600
161200
161213
FWD
FWD
FWD
BWD
STB 5
STB 5
STB 10
STB 10
STB 22.5
STB 22.5
STB 45
STB 45
STB 67.5
STB 67.5
STB 90
STB 90
STB 135
PORT 22.5
PORT 22.5
PORT 45
PORT 45
PORT 67.5
PORT 67.5
PORT 80
PORT 80
PORT 90
PORT 90
PORT 100
PORT 100
PORT 135
6
12
20
6
12
6
12
6
6
12
6
6
6
12
6
12
6
12
6
12
6
12
12
6
12
6
12
6
12
6
40
100
120
40
80
+3
40
120
160
240
Fwd crane
+5
+5
+3
Fwd crane
+15
+15
+5
+5
+8
+10
+17
60
80
120
80
Table 4: Load Case 1 - Temperature and NO
2
Concentrations on the Helideck, Crane and other areas
60
120
300
Turret
40
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 151 of 158
For this load case, the gas Turbine is operating at 100%, with an exhaust flow rate of 24.9 kg/s and a temperature of 506 o C. The results are presented in Table 5.
Simulation
Number
Wind
Direction relative to
FPSO heading
Wind
Speed m/s
HELIDECK
NO
2
Temp
Deg C
CRANE
BOOM
Temp
Deg C
Crane Cabin
Living
Quarters
Process
Deck
NO
2
Concentration
070000 No Wind
070600
071200
270690
271290
170622
171222
170645
171245
170667
171267
170690
171290
270605
271205
270610
271210
270622
271222
270645
271245
270667
271267
FWD
FWD
STB 5
STB 5
STB 10
STB 10
STB 22.5
STB 22.5
STB 45
STB 45
STB 67.5
STB 67.5
STB 90
STB 90
PORT 22.5
PORT 22.5
PORT 45
PORT 45
PORT 67.5
PORT 67.5
PORT 90
PORT 90
6
12
6
12
6
12
6
12
6
12
6
12
6
12
6
12
6
12
6
12
6
12 +4
40
100
40
80
Table 5: Load Case 2 - Temperature and NO
2
Concentrations on the Helideck, Crane and other areas
+5
+15
+15
+5
40
120
60
80
80
60
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 152 of 158
As can be seen from the table, all the results are nearly identical to the previous load case.
Conclusions are similar to the load case 1.
In addition to the UK air quality regulations’ objectives, EA Guidance Note H1 [6] also tabulates long term and short term Environmental Assessment Levels (EALs) for a wide range of substances. The short term and long term EALs for NO
2
and CO are compared with typical exhaust gas quantities in Table 6 below. An indication of the required dilution factors for the exhaust gases (mixing with fresh air) for each contaminant is noted where contamination levels reach an acceptable level.
Substance Contaminant Acceptable level of Contaminant Dilution Factor Required to level at exhaust gas outlet
74,031
g/m 3
(Short-term and Long-term EALs) reach acceptable air quality
NO
2
CO
74,031
g/m 3
53,650
g/m 3
53,650
g/m 3
40
g/m 3
Long-term EAL (Annual mean)
200
g/m 3
Short-term EAL (Hourly mean)
350
g/m 3
Long-term EAL (Annual mean)
10,000
g/m 3
Short-term EAL (Hourly mean)
1851
370
5.365
153.3
Table 6: Dilution Factors required to reduce exhaust gas contamination to an acceptable level.
Observation of the results shown in Table 6 above shows that a greater dilution of exhaust gases
(with fresh air) is required to achieve acceptable NO
2
levels than for CO. Thus, it is valid to model the NO
2
levels only and infer that acceptable levels of CO will be achieved if acceptable levels of
NO
2
are reached. The Environmental Assessment Levels (EALs) for NO
2
and CO shown in Table
6 above are lower than the Occupational Exposure Limits (OELs) for NO
2
and CO set by the
Health & Safety Executive HSE in their document EH40/2002 [7]. A comparison of the two limits is shown in Table 7 below.
3
4
Row
1
2
Limit Description
HSE Defined OEL
Long-term exposure limit (8-hour TWA ref period
Environment Agency Defined EAL
Long Term
5
Limit in Row 1 above divided by Limit in row 2 above
HSE Defined OEL
Short-term exposure limit (15-minute ref period)
Short Term
6 Limit in Row 4 above divided by Limit in row 5 above
NO
2
5,700
g/m 3
40
g/m 3
Annual Mean
142.5
9,600
g/m 3
200
g/m 3
Hourly Mean
48.0
CO
35,000
g/m 3
350
g/m 3
Annual Mean
100.0
232,000
g/m 3
10,000
g/m 3
Annual Mean
23.2
Table 7: Comparison of EAL and OEL figures for NO
2
and CO.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 153 of 158
The reasons for the differences between EALs and the OELs limits is explained in a section titled
“Derivation of Environmental Assessment levels for Air” in Appendix D of the Environment Agency
Guidance Note H1 [6]. A copy of this section is included in Appendix 1 of this document. This shows how a factor of safety is applied between the HSE defined OEL or maximum exposure limit
(MEL) if there is a specific concern about the pollutant (e.g. a carcinogen) and the environmental assessment level (EAL). The long and short term EALs for NO
2
were based upon the Expert
Panel on Air Quality Standards (EPAQS) guideline values. Also, the short term EAL for CO was based upon the EC Daughter Directive 99/30/EC. However, for these exceptions the philosophy of a large safety factor between OELs or MELs and EALs still applies.
An exhaust emissions study has already been carried out on the Schiehallion FPSO in May 2000 by Lindsay Ross (BP Occupational Health). This compared site readings with HSE OELs, rather than Environment Agency EALs objectives. The measurement instrument used by Lindsay to measure NO
2
levels during this survey was not capable of reading NO
2
levels less than 0.5 ppm
(1900
g/m 3 ). It is not possible, therefore, to determine a precise impact of the exhaust from the two LM6000 gas turbines at different locations on the FPSO. Only one reading taken by Lindsay exceeded the 0.5 ppm measurement threshold value during his survey, but that reading was taken directly at the point of emission from a fire pump diesel engine. The main conclusion of the survey was that all emission measurements were very low and well within the respective OELs with the majority being below the limit of detection of the equipment used.
Use of the EA EAL values rather than HSE OELs does provide a level of assurance that air quality on the Schiehallion FPSO will be much better than required to meet occupational health requirements. The EA Guidance Note H1 [6] describes how operators can show that their proposals represent the Best Available Techniques (BAT) to prevent and minimise pollution from an installation. Use of the modelling approach for the 4 th WI pump’s GT exhaust can be demonstrated to meet this requirement. There are arguments for and against use of safety factors implicit in the use of EALs, as follows:
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 154 of 158
FOR USE OF SAFETY FACTORS:
Safety factor will cover impact of any errors caused by use of CFD model, e.g. the model does not take into account the impact of the FPSO motion and the tendency for locations on the vessel to move into areas of higher NO
2
levels than modelled.
CFD modelling does not take into account the emissions generated by exhaust from the existing two LM6000 gas turbines on Schiehallion. Use of EALs with target emission levels an order of magnitude below OELs provides assurance that there will be little, if any impact on occupational health issues for personnel on the FPSO.
A review of the NO
2
contour plots does show that for some combinations of wind speed and direction (20 metres per second with forward wind - 0 degrees), that NO
2
levels near the accommodation air inlets may reach a level of 60
g/m 3, which is above the
Long Term EAL for NO
2
. This level is considered acceptable, because the frequency of its occurrence is low (< 1% wind speed exceeding 17.5 m/s from wind directions
350º, 0º and 10º was observed in 9 months data collected between 1 st February 2000 and 17 th October 2000. Similarly, for an aft wind, NO
2
levels of up to 300
g/m 3 were observed. Again the frequency of this wind direction is very low (< 0.5% occurrence during the period 1 st February 2000 and 17 th October 2000). Any relaxation of the approach used could result in unacceptable NO
2 levels in the accommodation and/or at the turret.
AGAINST USE OF SAFETY FACTORS:
Use of a large safety factor increases the complexity and cost of the exhaust arrangement. It might be possible to reduce the safety factor because there is: 1) no local population living close to the installation, other than off duty hours in the accommodation; 2) there will be recovery periods between exposures; and 3) personnel on the FPSO will not include sensitive individuals, e.g. children, the elderly or those with diseases such as asthma.
On balance, the arguments are in favour of retaining the use of the large safety factors.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 155 of 158
This area is currently free of pressurized hydrocarbon gases. The introduction of the Gas Turbine
GT would change that. As there is only one pipe for the gas into the Turbine, it is possible to control the consequence of a potential gas explosion to an acceptable level by controlling the connection locations and the pipe routing.
The dimensioning explosion based pallet filled condition gave an overpressure of over 4 bar if the process deck is grated (i.e. when gas is allowed to accumulate above between the tank top and process deck). If this can be avoided then maximum overpressure would be reduced to about 1 bar. Further, if the volume of flammable gas can be reduced, maximum explosion overpressure would be further lowered. Our view is that if the recommendations below are implemented, then the maximum overpressure at the blast wall would be l below the blast wall capacity of 0.5 bar, and no further explosion analysis is required.
We reviewed the layout of the fuel gas line. The good points of the layout are: The fuel gas line is routed high, and high integrity joints are used to connect pipe sections which appears to have been kept to a minimum.
It is recommended to route the fuel gas line input into the skid on the outboard side (rather than the inboard side). This will allow any potential leaks to be dispersed away from the vessel. Our understanding from our discussion with the Schiehallion project is that in the unlikely event of the connection failing, then the release direction would be along the length of the pipe, i.e. the released gas from the fuel gas line would impact on the plating on the side of the Turbine skid and disperse mainly outboard, and the fuel gas from the skid would be directed outboard and again disperse outside the vessel.
It is also recommended that:
Plating the Gas Turbine skid around the fuel gas entry into the skid or ensure that a gas leak within the Gas Turbine skid cannot be dispersed below the process deck (if the process deck cannot be plated). This can be done using a flange guard
Ensure there is adequate explosion venting in the Gas Turbine module enclosure. We recommend that one of the panels of the Turbine should fail quickly under explosion load; the starboard panel (facing outboard) should fail, while the top panel should remain. This panel should be restrained (say by a chain) to avoid missile hazards. The design should ensure the integrity of the fuel gas line is not affected.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 156 of 158
The proposed location of the 4 th Gas Turbine, forward of the Crane pedestal at frame 40, with the exhaust discharging at an elevation of 55m and pointing forward at an angle of 10 degrees above horizontal, should have minimal impact on either the Helideck or Crane operations
There should be no additional explosion hazard, provided the gas from the fuel line is dispersed above the process deck
The air quality will remain within acceptable health guidelines (see following discussion).
Schiehallion FPSO Final Design, Gas Accumulation and Explosion Studies,
UTG Sunbury Report SPR/OIT/012/97, December 1997
Schiehallion FPSO Updated Explosion Analysis Study, UTG Sunbury Report
S/UTG/155/00, December 2000
Weather Data, supplied by Schiehallion Project
Gas Turbine Data, supplied by Solar Turbines Inc
Crane boom limitations, supplied by Sparrows.
Environment Agency Guidance Note H1. Integrated Pollution Prevention and
Control (IPPC) – Environmental Assessment and Appraisal of BAT.
EH40/2002. Occupational Exposure Limits 2002.
IPPC Version 3.1, July 2002 89
Derivation of Environmental Assessment levels for Air
For many substances which are released to air EQSs have not been defined. Where the necessary criteria are absent then the Regulators have adopted interim values known as
Environmental Assessment Levels (EALs). The EAL is the concentration of a substance which in a particular environmental medium the Regulators regard as a comparator value to enable a comparison to be made between the environmental effects of different substances in that medium and between environmental effects in different media and to enable the summation of those effects. Ideally EALs to fulfil this objective would be defined for each pollutant:
based on the sensitivity of particular habitats or receptors (in particular three main types of receptor should be considered, protection of human health, protection of natural ecosystems and protection of specific sensitive receptors, e.g. materials, commercial activities requiring a particular environmental quality;
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 157 of 158
be produced according to a standardised protocol to ensure that they are consistent, reproducible and readily understood;
provide similar measure of protection for different receptors both within and between media;
take account of habitat specific environmental factors such as pH, nutrient status, bioaccumulation, transfer and transformation processes where necessary.
A suite of EALs derived in this consistent manner is not currently available, therefore, interim values based on published information have been adopted. The list below shows the sources from which information has been obtained. For consistency, risk based values proposed by the World Health Organisation or given in the IRIS database have been excluded.
Currently some 460 substances or groups of substances are authorised by the
Regulators for release to the environment and many of these may be released to air.
However, established environmental criteria (other than a limited number of EQSs) are available for only a small fraction of this number. For example, in the case of releases to air, EPAQS have produced guideline values for only six substances (Ozone, Benzene,
Carbon Monoxide, Sulphur Dioxide, Particles and 1,3 Butadiene, nitrogen dioxide, PAHs and lead) and the WHO Air Quality Guidelines contain values for 27 substances.
Information sources :
Expert Panel on Air Quality Standards (EPAQS)
EC Air Quality Directives - limit values and guidelines
World Health Organisation Air Quality Guidelines for Europe (1987, 1995)
Other International Organisations (e.g. United Nations Economic Commission for Europe)
Other National Organisations (e.g. US IRIS data base)
Health and Safety occupational exposure limits.
Expert judgement
Ideally, EALs for those substances where there are no existing criteria would be derived direct from toxicological data on the effects of the pollutant on a particular receptor.
However, an assessment of this type would be a very substantial undertaking which could only be considered over an extended timescale. One approach to overcoming this problem is to make use of occupational exposure limits which provide an assessment for a specific receptor (i.e. adult human workforce) of the toxicological effects of a pollutant.
These values might then be progressively revised as further information and resources allow. Indeed a similar approach to this was followed by the then Factory Inspectorate in
1968 when a large number of occupational standards were adopted from the American
Conference of Governmental Industrial Hygienists (HMSO 1968) which has since been progressively revised by the Health and Safety Executive on the basis of new information and UK experience.
Z-8000-BB-4076 Rev Z1 20 January 2005 Page 158 of 158