DRAFT Specification No…….. lR;eso t;rs GOVERNMENT OF INDIA MINISTRY OF RAILWAYS SPECIFICATION FOR GUIDELINES TO SET-UP THE TEST BED OF TESTING OF REPAIRED/OVERHAULED 3-PHASE TRACTION MOTORS OF WDG4 / WDP4 LOCOMOTIVES. FEBRUARY 2011 Issued by Motive Power Directorate Research, Designs and Standards Organisation Manak Nagar, Lucknow-226011 1.0 Introduction ALCO locomotives are rebuilt at DMW/PTA. It has been decided that repairing/ overhauling of traction motors for 4000/4500 hp AC-AC WDG4 and WDP4 locomotives are also to be carried out at DMW/PTA. In view of this test facilities shall be required to verify the characteristic of these repaired /overhauled traction motors. A general guidelines for installation and commissioning of test bed for testing of repaired/overhauled traction motors of WDG4/WDP4 locomotives at DMW/PTA have been framed. Objectives: 2.1 This guidelines covers the technical requirements for setting-up the test facilities for conducting routine testing of 3-phase traction motor type 1TB2622 and ITB2525 of M/s Siemens make or equivalent Traction motor of other manufacturers used in 3phase Diesel Electric Locomotives of Indian Railways. The scope of technical requirement of this guidelines covers the design, manufacturing, supply and commissioning of the equipment for test set-up at DMW/PTA for conducting routine testing of the motor. The system should be suitable to deliver 2500V to test the motor. Specified schematics for test set-up in given in Annexure-I. 2.2 The proposed test bed shall be such that the existing set-up shall be suitable for ROUTINE TEST comprising of short duration temperature rise test, No-Load test, short circuit test, vibration test & Noise test etc. as per IEC 60349-2 of above said motors under uncoupled conditions without any modification in the existing ones. The test parameters of already tested motors is given at Annexure-II for reference 2.3 At a latter date, if it is required to upgrade the test bed, for conducting full load test (Part of type test as in IEC) it should be possible to do so by minimum adjustment in the existing set-up and by commissioning of additional equipment along with various interfaces. In that case the test bed shall be comprised of four quadrant active front drive during upgradation for load tests. The test parameters at testing (Part of type test) of already tested motors is given at Annexure-III for reference. 2.4 The equipment required for carrying load test (Part of type test as in IEC) of the motors shall be taken up in 2nd phase after successful completion of the project for conducting routine testing of the motors. 2.5 The offered equipment shall be designed to comply with the latest issues of the appropriate International Electro-technical Commission Standards (IEC) or Indian Standards (BIS) standards. The same may be indicated in the offer. 3.0 Scope of Supply: 3.1 This guidelines defines the supply of transformer and their associated auxiliary equipment / accessories, off-circuit tap changer and earthing bus bars. The successful tenderer shall supply the necessary equipment and undertake the testing and commissioning of the test bed on turnkey basis. 3.1.1 The scope of Transformer include s: • The tap changer • The marshalling kiosk • The Primary phase CTs • The Primary neutral CTs • The Secondary neutral CTs • All multicore / multipair cabling between those items • All multicore / multipair cabling between other equipment such as WTI’s, cooling pumps and fans. The Primary and Secondary currents should be indicated with appropriate meters. 3.1.2 The scope will also include the provision of separate Earthing connections to the main tank, each cooler bank, the Primary neutral Earthing connection, cocoordinating rod Earthing connections, the Secondary neutral Earthing connection for the transformer. 3.2 This guidelines also defines the supply of VFD drive suitable for driving the 3-phase Motor to be tested rating upto 1.4MW / 2.5KV. It shall also consist of control desk, from which the control of all the testing parameters can be controlled, monitored / measured and recorded. 3.3 Switchgear Equipment: Since the supplier has to supply the test bed on turnkey basis, the supplier shall supply suitable switchgear equipment for satisfactory operation and protection of the overall system. 3.4 Surface Plates for Traction Motor Test Bed to be supplied by the tenderer. 3.5 Cables and Cable accessories to connect all the equipment under the scope of supply of tenderer. Distance from supply points to the equipment & test plant shall be provided by DMW. 3.6 Instrumentation Power Analyzer Insulation Tester High Voltage Tester Multimeter(s) Temperature Scanner Tachometer with speed sensors Vibration Measurement meter Noise Level Meter DC Current Source 1-ph Variac of 28-Amps & Current source of 50 Amps, having voltage, and current measuring instruments 4.0 Transformer 4.1 References IEC 60529: Degrees of Protection Provided by Enclosures IS 2026-1: Power transformers: Part 1 (General) IS 2026-2: Specification for power transformers: Part II Temperature-rise IS 2026-3: Specification for power transformers: Part III Insulation levels and Dielectric tests IS 2026-4: Specification for power transformers: Part IV Terminal markings, tapings and connections 4.2 Definitions CMR - Continuous Maximum Rating – capable of delivering the maximum applied load constantly Primary - The high voltage winding of the transformer and any components (e.g. CTs, Bushings) associated with it. 4.3 Secondary - The low voltage winding of the transformer and any component (e.g. CTs, Bushings) associated with it. The Input voltage System: The indicative rating/requirement of the transformer proposed for the test-set up is furnished as below. The tenderer may offer its own design to cater to the requirement during in the offer. System Voltage (available at input supply from SEB): 11 kV Rated Voltage : 12 kV • Size of step : 5% • Nominal position Tap : 3% • Number of tapping positions : 5% Rated Frequency : 50 Hz Design Fault Levels 3ph : 25 kA for 1 Sec Design Fault Levels Ph-E : 25 kA for 1 Sec Rated lightning impulse-withstand voltage (peak value) to earth: 95 kV Minimum Electrical Clearances Basic electrical clearance (Phase-Earth) : 160-mm Phase to Phase clearance : 250-mm Insulation height (Pedestrian access) : 2440-mm Safety working clearance (vertical & horizontal): 2600-mm 4.4.1 Requirement of the Transformer: 4.4.1 Technical Conditions: .1 The transformer shall be converter duty with one winding in the primary side & multiwinding phase shifted at secondary, suitable to feed the VFD, required to test the motor. .2 The transformers shall be suitable for installation outdoors and shall comply with IS2026. Cooling shall be type ONAN / OFAF or ONAN / ONAF. The design of accessories shall be coordinated so that the thermal rating of the unit shall not be limited by these accessories. .3 Transformers under this guidelines shall be suitable for frequency range between 20Hz to 70Hz to test the motor, three phase units with electrically separate Primary and Secondary windings. They shall typically have a combination of natural / forced cooling. .4 The windings shall be able to withstand without damage the thermal and dynamic effects of external short circuit levels. The transformer shall be designed to ensure that leakage flux does not cause overheating in any part of the transformer. Avoidance of over-fluxing at the most onerous operating conditions, especially on cyclic overloading condition, is essential. .5 Rated Power: The temperature rises associated with maximum power ratings and overloads for 11.5 kV, suitable voltage to run the motor under test, transformers are expected to be within the limits specified in IS: 2026. The designs submitted should comply with the temperature rise limits specified in IS:2026, Part 2, when operating under ONAN and OFAF (or ONAF) conditions on any tapping position. Control of Voltage shall be done using an off-load tap changer. .6 The guaranteed losses of transformer shall be stated in the tender. These losses shall also be considered during evaluation of the tender. .7 Creepage distances shall be a minimum of 25mm per kV at the rated voltage. 4.4.2 General Conditions: .1 The equipment shall be compliant with IS-2026 Power Transformers where appropriate unless otherwise varied in tender document. Any variations from this Standard shall be listed. .2 The transformer and all associated components shall be designed to be suitable for use at the defined cyclic rating, without exceeding any defined parameters, at an ambient temperature of 45 degrees C. .3 The transformer and all the ancillary equipment (e.g. CTs, instruments etc.) forming part of the transformer of similar design shall have been type tested by the manufacturer or testing authority in accordance with the relevant IS or IEC standards before delivery. Copies of the relevant type test certificates shall be submitted with the offer. .4 The transformer shall be supplied with suitable and sufficient anchorage points (painted yellow) for the attachment of work positioning and fall arrest lanyards for use when working at height. .5 All labels shall be clearly visible from the normal operating position and shall indicate the function of the component, not merely a reference number. The transformer and all connections shall be capable of operating at any tapping position on load. .6 Manuals shall be provided which clearly indicate any special considerations and procedures for use, maintenance, trouble shooting etc. .7 The normal operating condition of transformers on the power system is to maintain the secondary voltage constant for either, variations in load on the secondary winding, or variations in voltage applied to the primary winding. (i.e. to boost the voltage by operating the tap changer). .9 Tap changers shall provide facilities for remote tap position indication, tap change in progress indication and tap-change raise and lower complete indication. .10 Cable boxes: The transformer shall have cable boxes at both the primary as well as secondary windings .11 Open Terminal Bushings: On primary winding unit, the HV terminations shall usually be outdoor bushings, with a smaller bushing insulator for the Primary neutral. The Tenderer must specify the types of bushing to be used. On primary winding unit the primary neutral is not bought out as its insulation level is uniform. .12 Marshalling Kiosk: The Marshalling Kiosk will provide the point at which all alarms, trips, controls, indications, and CT outputs from the main transformer, the earthing or auxiliary transformer and the pump are terminated and ferruled ready for connection with multi-cores to the relay panels. A tank mounted or cooler support structure mounted weatherproof local marshalling kiosk is required on transformer. Paint finish to be the same as the main transformer. .13 Cooling System: The arrangement of cooling systems should be normally either ONAN/OFAF or ONAN/ONAF types. Coolers are required with detachable radiators, valves for oil filtering, motors, fans, pumps, and related control gear associated with a forced cooling system. 5.0 Variable Frequency Drive (VFD): Variable speed AC drive also referred as Variable Frequency Converter (VFC) or Variable Frequency Drive (VFD) or Variable Speed Drive (VSD) is used for converting ac input power into a controlled output variable ac voltage or current of variable frequency of 3-phase Induction motor testing. Power Converter and Inverter: It shall consist of line side 3-phase uncontrolled bridge rectifier using power diodes / thyristors for AC to DC conversion and the drive shall be based on IGBT technology & the VFD output shall be PWM waveform. Rating of the Drive: The rating of the drive offered by the tender shall be suitable for future expansion (or excel the test requirement) to load the motor for temperature rise test and evaluating the load characteristic, no-load characteristics & lock rotor test upto 70Hz at different frequency. The method to be followed for testing of the motor shall be as per IEC-60349-2 5.1 Reference for Standards: 5.1.1 The design, manufacture and testing of Inverter Panels for AC Drives shall be carried out as per the latest applicable BIS, International Standard, Indian Electricity Rules, Code of Practices and requirement of Chief Electrical Inspectorate of the State Govt. However, for ready reference some of the Standards are listed below. IEEE 519 - Recommended Practice and requirement for harmonic control in power systems. IS 1248 - Direct acting indicating analogue electrical measuring instruments and their accessories. IS 1885 - Part 7 - Semi Conductor Devices IS 1885 - Part 27 - Power Electronics IS 3700 - Essential ratings and characteristics of semi conductor devices. IS 6619 - Safety code for semi-conductor rectifier equipment. IS 13947 - Low voltage switchgear and control gear. electrical 5.2 Requirement of VFD Drive 5.2.1 Technical Requirement: .1 Closed loop vector control (entire speed range) drive to be used with features as specified: The general requirement of the VFD drive is indicative as below. In case the tenderer proposes different design for the proposed test set up to cater to the requirement the same shall be furnished in the offer. a. Speed control 0.01%, dynamic 0.2%sec, torque lin. <2%, torque rise time ~2 ms. b. Starting Torque: 150 %, Frequency stability: +0.1%. c. Overload: 110% load for 60 seconds. Once in every 10 minutes. d. The ratio of peak inverse voltage to peak voltage of the drive shall be more than 2.5 (under normal operating conditions). e. Drive Design temperature: 45 ºC. f. Speed range: 1 % to 270% of the normal speed of the motor. .2 AC Output: Current waveform should be approx. sinusoidal to provide step less speed variation for the operation of traction motors. .3 AC drives should be designed / supplied for an output frequency range of 1Hz to 160Hz. .4 The efficiency of the drive at rated voltage and load should not be less than 97.5%. .5 The drive supplied should be with input reactor for reduced harmonics as per IEEE159. VFD module and the input reactor should be of same make. .6 The Bidder shall provide Type and expected life of DC link capacitors used in the system. 5.2.2 General Requirement .1 The output current of the drive shall be sized on the basis of full load current of motor. It may need to be oversized to accommodate application requirements such as high starting, overload or accelerating torque. It shall also be able to accelerate the load from zero to full speed under specified voltage and frequency variation. .2 The Drive shall be based on Microprocessor based Digital controller with digital & analogue input / output cards to fulfil the controlling of system. .3 Auxiliary power supply: 415V AC, 3-phase, 50 Hz supply shall feed Control transformer, panel cooling, motor cooling, panel illumination, panel and motor space heaters etc. Suitable switchgear ( Fuse unit or MCCB) shall be provided for isolation. .4 Control supply :Control supply voltage shall be considered 110V / 220V AC. All logic control wiring, indication lamps, control contactors, Local control station wiring, and discrete DCS I/O shall be at Control supply voltage. .5 Drive should be suitable for Switching Duty of 5 starts per hr in normal operation and 6 starts per hr in trial run. .6 Acceleration and de-acceleration time: Up to 3000 seconds independently adjustable. .7 All the drives should be with varnished PCBs. Operator Display & control for parameterization of drive to be provided on panel door. .8 Open Circuit mode: The drive shall be operational in open circuit mode i.e. disconnected from the motor for start-up adjustments and troubleshooting. 5.3 Operation features of the drive: The drive shall have the following features as mention below: .1 Soft start with adjustable time acceleration. .2 Speed reversal locking for unintended direction of rotation. .3 User programmable carrier frequency for optimum harmonic distortion and switching losses. .4 Auto tuning feature to configure Drive parameters according to Motor rating and characteristics. .5 Operator display unit shall be multi-line alphanumeric keypad for on line simple English text message for cause of fault, fault diagnostics, parameterisation, configuration, and control. It shall store History of last 30 faults with real time stamp and actual value recorded at the time of fault. The operator display unit shall display the cause of fault in English text message not in code, so that fault can be identified & resolved to reduce the down time of system. .6 Power loss ride thru – in case of momentary supply failure, the drive shall be able to run load by using kinetic energy of rotating motor. .7 Flux optimisation – to reduce energy consumption and reduce motor noise level when motor running at below nominal load. .8 Independently adjustable set point up and down ramps. .10 Serial bus Communication cards with MODBUS / PROFIBUS DP Protocol to connect with DCS. 5.4 Harmonics .1 De-rating (if required) due to harmonic currents shall be considered to ensure rated load without exceeding rated temperature rise under worst supply condition. .2 Tenderer shall recommend any power de rating for the motor when operated with the drive in order to account for the harmonic content of the drive output. .3 Chokes and Filters: Distance of the motor with the drive can be more than 100 metres. Necessary hardware e.g. chokes / filters in load side etc. if required, shall be supplied on the basis of calculation of peak voltages at motor terminals. .4 Modes of operation: Panel shall be provided with 2 way selector switch for Remote / Panel / Field (Local) mode selection. It will be possible to change the reference only from the place of selection of operation. .5 PC software for Configuration: A PC based, Windows 2000 / XP / NT compatible software tool suitable for configuration, parameterisation, upload /download data, tuning, diagnostic purpose, trouble shooting. The PC shall be connected to drive’s RS232 / RS 485 port. Necessary hardware and complete documentation shall be included in the scope. 5.5 Type of Protection on the Drive Panel: Following protection shall be provided on the drive. .1 Earth fault protection’ and ‘Surge protection’ .2 The ‘short circuit rating’ of panel should be more than available short circuit capability of connected ac line. .3 Capability to skip / exclude frequency bands that may cause mechanical resonance. .4 The fault detection system shall shutdown the rectifier and inverter firing circuit and output during fault signal. The operator display unit shall identify the abnormal condition, which caused shut down of the drive system. 5.6 Display Indications on the Drive Panel / Operator Display Short circuit in converter and inverter Instantaneous over current Breaker trip. Thermal overload. Stall protection and Locked rotor. I2t monitoring for power devices and motor. Phase imbalance. Single phasing. AC under voltage / over voltage protection. DC link over voltage. Control and regulated power supply failure. High temperature protection. Communication fault. Transformer protection trip. External emergency off. Over speed / under speed. Stator motor temperature by motor modelling. 5.7 Wiring Details of Drive: Wiring of power cable and control cables will be laid separately. All power cables sizing from drive to motor shall be recommended by tenderer. All the control wiring shall be done by stranded copper wires of minimum 1.5 mm2, cross-section. All signal cables shall be 0.75 / 1 mm2 screened type. All the wires will be ferruled at both the ends. Adequate cabling space shall be provided for external cable termination. Inter-module wiring will be colour coded as far as possible. Proper wiring, shielding, grounding should be done in the panel to minimize noise and interferences. 5.8 Bus bars Details: All metallic parts, components etc. shall be connected to main earth bus bar. Main earth bus bar shall be connected to plant earth grid by minimum 60 x 10 mm copper bus bar. Bus bars should be of Electrolytic grade copper or aluminium type. It should be suitably supported to avoid stress on the terminals. Support points shall not be used for power tapping. 5.9 Wherever required, Live parts shall be suitably shrouded with transparent acrylic sheets. 5.10 Terminal Board Details: All external power and control circuit connections shall be brought on readily accessible spring press screw less connectors at the bottom of the cubicle. Ample space shall be provided at the bottom up to a height at least 250 mm for connecting the Power & Control Cables and for easy accessibility. 5.11 Each functional module should have its own terminal board and panel should be complete with the inter-connections between them. Terminals shall be of springpress screw less type. 5.12 All the terminating points shall be brought on the front of the Panel. The reference voltages / signals should be displayed on digital operator station to facilitate faultfinding. 20% extra spare terminals should be provided for customer’s interlocking with down stream equipment. 5.13 Cooling system: The system shall be designed for continuous operation at site ambient condition with forced cooling for drive. The arrangement shall preferably be such that the ventilation air passes only through transistor heat sinks in a separate duct so as to prevent dust deposition and consequent tracking. 5.14 Indications & Fault Monitoring on Control Desk Panel: The panel should be provided with Status of the Indication Lamps - Power ON, Drive Ready, Motor Running, Remote Breaker trip and 2 Spares. Meters should display true RMS value of inverter drive input and output currents. All faults and running parameters like current, speed; KW etc. shall be displayed on operator display unit on the front panel. Following Controls switches shall be provided on the front of the panel. 5.15 A lockable mushroom head red colour push button –to operate and turn to release type Emergency Stop PB to isolate incoming supply. Start (green)-Stop (red) PB. Speed raise-lower (Blue and yellow). 2-way selector switch (16 A rating) for DCS / Panel / Local mode. Indicating meters: Meters of 96 x 96 mm Flush mounted on front panel. AC Ammeter with selector switch on control desk panel. AC Voltmeter with selector switch on control desk panel. Constructional Details of the Panel: Panel shall be floor mounted, freestanding, cubicle made of cold rolled sheet steel, suitable for indoor (IP4X). The preferred thickness of sheet steel shall be 2 mm except for all the covers and base plates of 1.5 mm thickness. The base channel would be 3.0 mm thick. Panel shall have suitable lifting hooks. Louvers with filters shall be provided on the panel doors. Drawing pockets on the doors for keeping drawings will be provided. All doors shall be hinged and provided with electro-mechanical interlocking so that power cubicles can not be opened until power source is disconnected. Similarly interlock system shall ensure that power can’t be switched on until all power cubicles are closed. All power and control components shall be easily accessible from panel front. If use of rear doors are made necessary, it shall be clearly indicated in the offer. All metal surfaces shall be painted as per RAL 7032 of DIN (Pebble Grey) before thorough cleaning/ rinsing and degreasing of the panel All unpainted steel parts shall be suitably treated to prevent rusting. 5.16 Type of protection of the Panel: Panel shall confirm IP42 protection. The panel shall also have effective protection against Electromagnetic emissions. The panel shall be totally enclosed and dust, vermin proof. Panel shall have proper separation between HV and LV side for Human safety inside the panel. 5.17 Marking: Identification labels: All the main and sub-assemblies of the Panel shall bear proper identification labels / tags. Information like rating, drive name, drive number shall be inscribed on the nameplate and fixed on panel front. 6.0 Technical requirement of surface plate of Motor Test Bed: Technical requirement of supply of commissioning of material motor test bed are as follows: Cost iron surface plate shall be preferred to mount the traction motor for conducting various tests. The surface plate shall be confirms to IS: 2285-1991. The surface plate shall be made from close grained plain cast iron conforming to Grade FG: 220 of IS: 210-1978. C.I. Surface Plates shall be made from one piece casting. The finished surface plate shall have smooth machine finished for grade 3 flatness accuracies. Flatness determination shall be done by grid method as per clause 4.3.1 of IS: 12937-1990 Indian standard on Engineering Metrology “Methods of Testing Straightness, Flatness, and Perpendicularity”. Flatness accuracy shall be checked by Electronic level. Computer print out of the contour of top working surface shall be furnished. Size of the Surface plate shall be of 2500-mmx 2500-mm in size. Special features of grid slots for location, tapped holes, and T-slots shall be provided on working surface to meet the dimensions of the Traction Motor. Envelope dimension of the motor to be tested is given in Annexure-IV. It is for reference. These envelop dimension may vary with the motors of other manufacturers, so tenderer may have to supply necessary fixtures for fixation of other motor having different dimensions on the surface plate. Installation of surface plate at site is in the scope of supplier. Necessary modifications on the civil structure for installation of the complete ‘drive system’ required for the test bed is in the scope successful tenderer. 7.0 Evaluation / Qualification Criteria of the Firm / Tenderer: The tenderer shall be experienced in manufacturing of major equipment of the system like VFD drive Panel and Transformer having the capability to produce minimum 1MVA rating of these equipments. Firm / tenderer shall also be manufacturer of motors of industrial use with a capability & exposure for combined testing of motor & drive system together. Documentary proof for the above cited experience shall be submitted. 8.0 QAP and Inspection Plan : The tenderer should have a well-defined Quality Assurance Plan (QAP) for major equipment (like VFD drive System, Transformer and switchgear) offered for installation of the proposed test bed. He will furnish a copy of such QAP documents along with the rating during submission of the offer. If the tenderer proposes to obtain sub-assemblies/ components/ material from a sub-contractor, QAP documents of sub-contractor shall also be submitted by the tenderer. The QAP shall also include test procedure/standards and acceptance limits followed during stage manufacturing of these major equipment. The submitted QAP will require approval of IR. Proper test procedure for proposed system through the offered equipment system shall also be submitted by the successful tenderer for approval by IR before execution of the work. 9.0 Warranty: The supplier shall offer warranty against any manufacturing defects/commissioning noticed on the test bed or on the equipment offered for a period of 12 months from the date of commissioning & 18 months from the date of despatch which ever is earlier. Any inadequacies or unsatisfactory performance on equipment due to design or manufacturing or commissioning noticed after set up of test bed during the warranty period shall be rectified /replaced by the firm free of cost. In such cases the warranty may be extended after modification with mutual consent between the Firm and IR. Firm to support the system for the expected life of atleast 5 years of the system. 10.0 Literature and Maintenance Instructions: The approved supplier shall supply sufficient copies of manuals for operation, complete Drive maintenance and overhaul. The approved supplier shall provide training to the personnel free of cost with sufficient number of days at place of commissioning (i.e. DWW/PTA) till they become expert to handle the complete drive independently for testing of the motors. Firm should also nominate few expert to assist these personnel for testing of first 15 nos. of motors at DMW/PTA. *********