Protection Systems D i F Design Fundamentals d t l Transmission Line Protection FRCC System Operator Subcommittee - Spring Seminars 2011 - Objectives • Review Definitions • Review Purpose of Relays (Protection Systems) • Review 5 Design Attributes protection systems • Review Types of transmission line protection • Review Communications Based Schemes • Review Protection Redundancy vs Backup 2 1 Purpose of Relays (what ?) • NERC Definition of “Protection System”: “Protective relays, associated communication systems, voltage and current sensing devices, devices station batteries and DC control circuitry. • Merriam- Webster definition of “Relay”: “an electromagnetic device for remote or automatic control that is actuated by variation in conditions of an electric circuit and that operates in turn other devices (as switches) in the same or a different circuit.” • Power P System S t Relaying R l i textbook t tb k definition d fi iti off “Relay”: “R l ” “equipment that detect abnormal power system conditions, and initiate corrective action as quickly as possible in order to return the power system to its normal state”. 3 Purpose of Relays (why ?) • Silent sentinels that “watch” the power system - Relays are continuously monitoring the system to detect abnormal condition on Power System, and initiate corrective actions as quickly as possible in order to return the power system to normal state state. • Minimize power system equipment damage • Minimize danger to people • Provide automatic response (no human intervention) • Remove electrical stress from other equipment • The power system – one big machine electrically connected • Provide a quick response to remove faulted equipment • Restore the power system to a “normal state” • Increase reliability of the overall power system 4 2 Minimize the damage Minimize the effects of faults 2003 Northeast Blackout 2/26 UFLS Event - 3 phase fault - Failed 138 kV switch in Miami - Disabling of all local protective relay equipment while troubleshooting - Led to Delayed clearing of a fault -Fault remained on the system for: approximately 1.7 seconds Resulting effect on frequency 3 Design Attributes of Relays • 5 Attributes inherent to protection system design • Reliability li bili (2 ( components - dependability d d bili and d security) i ) • Selectivity of Relays (zones of protection) • Relay Speed • Simplicity • Economics/Cost 7 Design Attributes of Relays (cont) Reliability contains two components: Dependability – “the degree of certainty that a relay or relay system will operate correctly” when called upon to trip – Easy to ascertain dependability by testing Security – “relates to the degree of certainty that a relay or relay system will not operate incorrectly” say when there is no fault or fault is outside the zone. – Not easy to ascertain, due to wide range of conditions that might be presented to the relay and control systems. Can’t be predicted. – How does FRCC track and learn from occurrences ? Misoperations ! 8 4 Reliability of Relays Reliability’s 2 components: Dependability – Two independent redundant systems increase certainty, backup, secondary, multiple redundant schemes. Redundancy will be discussed later. Security Two independent series systems - will not operate incorrectly 9 IMPROVE DEPENDABILITY • Primary Relay scheme is dedicated to a specific zone of protection. A Primary relay scheme operates with no intentional time d l delay. • Redundant Relay scheme does the exact same function as the primary and provides redundant protection • Back-up Relay Scheme is usually time delayed. It will typically remove more of the system elements than required by operation of the primary relay scheme. 5 Dependability: Backup, primary, secondary, redundancy Security 6 Design Attributes of Relays (cont) Selectivity – Minimum system disconnection for isolation of faulted equipment - Zone of Protection Generally a zone of protection is designed for each system element. The faulted element is isolated. Some cases more than one elements is combined in one zone of protection. DEDICATED RELAYS FOR EACH ZONE Transmission line Generators Substation Bus Capacitor bank Reactor Circuit Breaker Transformers Dist. Feeder Combined Elements: Two or more of the above elements. 13 7 ZONES OF PROTECTION Note: Not to be confused with “Zone 1” , “Zone 2”, “Zone 3”, to be discussed later 15 SPEED: minimize the damage 8 Design Attributes of Relays (cont) Speed – Attribute to remove a fault as quickly as possible 2/26/08 – FRCC UFLS Event The initiating event was a three phase fault on a failed 138 kV switch at a transmission substation located West of Miami, Florida. The disabling of all local protective relay equipment while troubleshooting a transmission switch led to delayed clearing of a fault that developed on the switch. The fault remained on the system for approximately 1.7 seconds. • “delayed clearing” – Typical clearing time - primary protection – 0.067 0 067 seconds – Typical local backup clearing time – 0.255 seconds The depressed voltages in the area of the fault led to protective equipment trips of the two Nuclear generating units at Turkey Point as well as the loss of additional fossil generation at that and other sites in the Region . 17 Design Attributes of Relays (cont) Speed – definitions “Instantaneous” – relay operates without intentional time delay (inverse time delay characteristic) “Time Delay” – an intentional time delay is inserted between relay decision and operation “High-Speed” – relay operates in less than 50 mS S typical i l (3 cycles) l ) “Ultra High Speed” – relay operates in 4 mS or less (non-standard but currently typical 18 9 What design attribute is this ? Design Attributes of Relays (cont) Simplicity – Fewer components and attributes in a design result in: • A system with fewer potential Human and Equipment Performance issues • Usually more cost effective, both immediate and life-cycle • Easier to troubleshoot when issues occur 20 10 Design Attributes of Relays (cont) Economics - Protection & Control systems typically range from 10 – 15% of the cost of the equipment they protect, down from 15 – 20% jjust ten – fifteen yyears ago g p prior to uprocessor technology coming to market. The more equipment you install the more money is required – cost benefit vs dependability and security equation – You use overlapping pp g zones / backup protection etc. Critical equipment you install Fully redundant systems 21 Are we done yet ? We’re just getting started ! Any Questions on Design Attributes 22 11 Transmission Line Protection Road Map to the End • TLP Options: • Overcurrent relays – Instanstaneous – Time delay • Directional Overcurrent • Non-pilot – Step Step-Distance Distance Relays – Zones 1, 2 & 3 • Pilot Protection • Carrier types and communication at a high level • Cover some relay types • Define – “Primary Protection” – “Backup Protection” – “Redundancy • “Redundancy” • Communication Outages 23 The Goal of Line Protection To detect transmission line faults and initiate isolation of that line fault 3-5 cycles. cyc es A fault au t du duration at o o of longer o ge time t e (8 plus cycles) can cause instability. Typical Transmission line Substation A Substation B 12 Overcurrent Protection • • • • Only looks at line current Simple – setting (normal load +25%) Does not see faults “behind” - no fault current C Can coordinate di t with ith relays/fuses l /f downstream d t – Add time delay – Coordination for all types (10 types) of faults becomes difficult (phase to phase, phase to ground, 3 phase etc.) Radial Load Substation A Ohm’s Law: V=IxZ I = V/Z Relay trip when I = set current flow Distance or Impedance Relay • As the protected system gets more complex • Available changes in configuration (network) • Changes in generating patterns • Wider variation in fault current than radial • Can’t just use current monitoring for reliable protection • We need to look at current AND voltage 13 Distance or Impedance Relay Look at Current and Voltage to detect fault V = 100 V Conclusion: if we know voltage and current we can estimate the impedance If we know the conductor and construction (impedance per mile of transmission line is fairly constant) t t) Ohm’s Law: V=IxZ Z = V/I THE LINE CONDUCTOR AND CONSTRUCTION IS SAME, DISTANCE IS PROPORTIONAL TO IMPEDANCE We can estimate a where a fault is based on measured voltage and current on the line Distance or Impedance Relay How to know if line has a FAULT?? • We know the properties of the transmission line – Length – Impedance • We know the current on the line from the substation • We know the voltage on the line bus at the substation • Ohms Law – V = I x R or V = I x Z (for Impedance) • We can identify a set of “Z”s for faults and set the relay to pick-up 14 Step Distance Relaying Its hard to pinpoint the “end” of the line “Z” – use “zones”…… The “art” art of Relaying – Company PHILOSPHIES may vary Zone 1 Zone 2 80% 120% Zone 3 Typical setting of zones 120% of combined 29 Step Distance Line Protection why 80%, 120% etc • Create Zones of Protection • Z1 = 80% line impedance no time delay dela • Z2 = 120% line impedance time delay• Z3 = 120% line impedance and 120% of next zone; with a time delay – backup next zone 15 Limitations of Step Distance Line Protection • Problem: can’t clear both ends of the line instantaneously for faults near one end • As loading increases the “Z” viewed by the relay may cross into the “Z” trip area of the relay setting • Harder to coordinate multi-terminal and parallel line • So far – all information for “tripping decision” has come from one substation Pilot Protection • Provides instantaneous protection over entire line section • 2 modes “blocking mode” (integral to line) or “tripping tripping mode” mode (independent comm channel) • Communicate information from one terminal to the other terminal (in the zone of protection) • Communication methods: – – – – Power line carrier Microwave Fiber optics Pilot cable • Speed up remote end clearing time 16 Pilot Protection • Schemes can be classified as: – Directional Comparison – Phase comparison – Pilot wire Depending on type of sensing used • Further described as : – Blocking – Unblocking – Transfer trip Depending on how transmitted signal is used • Transfer trip is further categorized as: – Direct – Permissive underreaching – Permissive overreaching Types of Communication Channels 1. Power line carrier – On/Off, FSK Reliable, expensive, noise, freq. availability 2. Pilot wire – dedicated 2 wire copper circuit Expensive 3. Leased line – digital or audio tone Dedicated channel, low installation cost Reliability, ongoing costs 4. Microwave – digital or analog Capacity, C it low l noise/location, i /l ti weather th 5. Fiber optic – digital Noise immunity/network delays, cost 34 17 Current Differential 87L 87L Communication channel Basic End to End Communication Scheme 21 21 18 Permissive Overreaching Transfer Trip 1. LOCAL END DETECTS FAULT, SEND PERMISSIVE TRIP 2. REMOTE END RECEIVES PT, IF REMOTE SEES FAULT, IT TRIPS AND SENDS PT TO OTHER END 3. CONSIDER FAULT INSIDE AND OUTSIDE Directional Comparison Blocking 1. LOCAL END DETECTS FAULT, DOES NOT SEND BLOCK TRIP 2. REMOTE END SEES FAULT AND IT DID NOT RECEIVE BLOC FROM REMOTE, IT TRIPS. ALSO, IT DOES NOT SEND BLOCK. PASSIVE PERMISSION 3. FAULT CLOSE BY AND OUTSIDE, BLOCK IS SENT AND TRIP IS BLOCKED. 4. CONSIDER FAULT INSIDE AND OUTSIDE 19 Loss of Blocking Communication Example #1 Adjacent line fault with Blocking scheme Channel To Ranch 1) No communications on Cedar- Corbett 230 kV line Possible temporary 2) Fault on Cedar – Deltrail 230 kV line (close to Cedar) remedy: Study opening line 3) Corbett terminal sees fault on Deltrail line (zone 2) at a distribution sub, which should only allow 4) Corbett terminal does not receive blocking signal instantaneous zone 1 trips. 5) Corbett breakers 8W45 and 8W99 trip high speed 6) Both Cedar and Corbett will trip for any zone 2 fault Loss of Communication Example # 2 close in fault on line with blocking scheme Channel To Ranch 1) No communications on Cedar- Corbett 230 kV line 2) Fault on Cedar – Corbett 230 kV line (close to Cedar) 3) Cedar sees zone 1 fault - trips 8W62 & 8W48 instantaneously 4) Corbett terminal sees fault on zone 2 and trips high speed Internal – NO issue 5) Breakers 8W45 and 8W99 at Corbett trip 6) All faults on Cedar-Corbett line will still be cleared high speed 20 Communication Based Schemes Pilot Protection, Protection Differential, Differential and Directional comparison comparison. DCB DCB, POTT cover in a little bit detail, Mention DUCB, PUTT, DUTT. Discussion / Simulation 41 Road Map Continued • Pilot Protection Schemes • Directional Comparison, – POTT – PUTT/DUTT – DCB – DCUB CURRENT DIFF POTT- next 21 FRCC Handbook Procedure 43 REDUNDANCY Protection system components (below) make up a protection system. In some cases, for redundancy two system are provided. A complete “Chain” of components make up a system. AC Current Source AC Voltage Source Protective Relay Communication Channel - DC Control Circuitry Auxiliary Relay DC Source Trip Coil 44 22 REDUNDANCY Non-redundant system Single DC P Power supply l 45 REDUNDANCY Fully-redundant system Diverse DC power supply 46 23 Typical DC Control Circuit 47 Protection System Outages If a protection system (chain of components) does not meet all of the requirements described above above, then the protection system is not redundant. From an operations standpoint – - is the remaining protection “redundant” back up - Is the remaining protection “back-up” - Understand what “secondary” means - What elements will be tripped for a fault in the affected protection zone 48 24 49 • Questions ? 25