CS075481/BPDG/1.0 March 2015 Appendix C – Standard Details Appendix C/ – Standard Details GENERAL NOTES: 6000 MAX 155 CENTRES SPECIFICATION: 152x152x37 UC POSTS WITH POINTED TOP ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE SPECIFIED. PALISADE FENCING GATE FRAME 90x50x3.5 RHS ALL STEEL PALISADE FENCE SHALL BE SECURITY TYPE GP18 IN ACCORDANCE WITH BS 1722 : PART 12 AND HOT DIP GALVANISED IN ACCORDANCE WITH BS EN ISO 1461. ANTILIFT GATE HANGING DETAIL ALL ROLLED STEEL SECTIONS SHALL BE OF STEEL GRADE S275 TO BS EN 10025 : 1993 UNLESS OTHERWISE SPECIFIED. 1800 SLIDING LOCKING BAR 6mm THK SLAM PLATE TRIANGULAR GUSSET PLATE GROUND LEVEL 525mm MINIMUM EMBEDMENT INTO 600x600x1100mm CONCRETE FOOTING 300 1100 DROP BOLT ALL BEDDING CONCRETE FOR VERTICAL FENCE POSTS TO BE MASS CONCRETE MINIMUM GRADE ST2 TO BS 8500-1. TYPICAL 1.8m HIGH 6m WIDE PALISADE GATE (1:50) (TYPICAL EXTERNAL VIEW) INSTALLATION GUIDANCE: PALISADE FENCING 2750 MAX 155 CENTRES 102x44x7.5 RSJ A 40x40x6 RSA RAIL 1800 225 3.0mm THICK CORRUGATED PALES FIXED TO RAILS AT 155mm CENTRES 1800 225 ALL CONNECTIONS SHALL BE BOLTED IN ACCORDANCE WITH BS 1722 : PART 12. OPTIONAL ITEMS REQUIRED FOR ADDITIONAL SECURITY ARE TO BE SPECIFIED IN A PROJECT SPECIFIC FORM A/B 600 40x40x6 RSA RAIL 100 100 ALL BOLTS SHALL COMPLY WITH BS 3692 AND SHALL BE STRENGTH GRADE 8.8. NUTS SHALL BE STRENGTH GRADE 8 AND WASHERS SHALL CONFORM TO BS 4320. ALL BOLTS, NUTS AND WASHERS SHALL BE ZINC COATED. GROUND LEVEL TO LIMIT DEFLECTION IN FENCE RAILS, THE BOTTOM HORIZONTAL RAIL SHALL BE SUPPORTED SO THAT AFTER TIGHTENING OF THE BOLTS, ALIGNING AND PLUMBING TO THE FENCE THERE IS A SLIGHT UPWARD CAMBER. THIS SUPPORT SHOULD BE REMOVED ONLY ONCE THE CONCRETE HAS SET. 102x44x7.5 RSJ WITH POINTED TOP 40x40x6 RSA RAILS TOP AND BOTTOM CONCRETE MINIMUM 3.0mm THICK x 70mm WIDE CORRUGATED 'W' FENCING PALES AT EQUAL CENTRES, WITH TRIPLE POINTED TOPS WITH SPLAYED HEADS POINTING OUTWARDS CONCRETE: C30/37, AC-4, DC-4, AGGREGATE: 20mm (MAX.) SULPHATE AND CHLORIDE RESISTANT DISTANCE TO COAST: 2km, SITE ALTITUDE: 100m AMSL WIND SPEED: 25m/s, ENVIRONMENT: TYPICAL OPEN COUNTRYSIDE GROUND CONDITION: AVERAGE FOR PLANTED (ROOT) FOUNDATION WATER TABLE: WELL BELOW THE FOUNDATION, AND SITE IS NOT SUSCEPTIBLE TO FLOODING GROUND LEVEL ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES NR/SP/OHS/011: PREVENTION OF DAMAGE TO AND DANGER FROM SURFACE AND BURIED SERVICES. NR/PRC/MPI/CI0024: CONTROL AND USE OF METAL PINS AND SPIKES ON NETWORK RAIL INFRASTRUCTURE NR/PRC/MPI/CIOO26 PROCESS: FOR LOCATING BURIED SERVICES PRIOR TO GROUND PENETRATION. FENCES JOINED TO EXISTING FENCES, WALLS OR OTHER STRUCTURES TO PROVIDE A COMPLETE BARRIER TO PERSONS OR ANIMALS AS APPROPRIATE. FENCES SHALL BE ACCURATELY SET OUT AND ERECTED TO PROVIDE A SMOOTH ALIGNMENT IN PLAN AND ELEVATION, FOLLOWING THE CONTOURS OF THE GROUND AS CLOSELY AS IS PRACTICABLE. THE LINE OF THE FENCING SHALL BE CLEARED OF ALL IMPENDING VEGETATION AND TRIMMED TO REMOVE ANY IRREGULARITIES TO ENABLE FENCE INFILL PANELS TO BE ERECTED AT A CONSTANT DISTANCE FROM THE GROUND. 17.12. 2014 01 Rev Date P.J. FIRST ISSUE Name Description of Revisions S.C. Rev' Check Client TABLE 1 50 MAX. 1100 525 50 MAX. SAFETY, HEALTH & ENVIRONMENT RISK ASSESSMENT 525mm MINIMUM EMBEDMENT INTO 600x600x1100mm CONCRETE FOOTING 600 A TYPICAL 1.8m HIGH PALISADE FENCE (1:50) SECTION A-A (1:50) (TYPICAL EXTERNAL VIEW) DESIGNERS' NOTE - CDM REG. 13(2)(b) THE FOLLOWING ARE SIGNIFICANT HAZARDS WHICH MIGHT AFFECT THE HEALTH AND SAFETY OF THOSE UNDERTAKING THE WORKS OUTLINED IN THIS SET OF DRAWINGS ON RAILWAY STRUCTURES OR THOSE AFFECTED BY THESE ACTIVITIES. A SITE SPECIFIC RISK ASSESSMENT SHOULD ALWAYS BE UNDERTAKEN PRIOR TO COMMENCING ANY OF THE WORKS DESCRIBED ON SITE. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 IT IS ASSUMED THAT A COMPETENT CONTRACTOR IS AWARE OF THE RISKS ASSOCIATED WITH GENERAL CONSTRUCTION ACTIVITIES UNDERTAKEN WITHIN THE RAILWAY ENVIRONMENT. RISK CONTACT WITH OVERHEAD WIRES OR BURIED SERVICES STAGE C SPECIFIC METHOD STATEMENT AND RISK ASSESSMENT TO IDENTIFY AND DETAIL PROTECTION TO ALL SERVICES, BURIED AND OVERHEAD. DAMAGE TO ROOTS OR PROTECTED TREES C SPECIFIC METHOD STATEMENT TO DETAIL PROVISION FOR ROOT PROTECTION OF TREES DURING WORKS. INJURY TO ADJOINING LANDOWNERS C ADJOINING LANDOWNERS TO BE INFORMED AHEAD OF WORKS. FAILURE OF FENCE DUE TO SUB-STANDARD MATERIALS D/C CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE MANUFACTURER. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title 1.8m HIGH 6m WIDE PALISADE GATE & FENCE DETAILS SECURITY LEVEL 1 & 2 Drawn By Name Checked By Name Approved By Name Scale APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER Signature: Name: Title: FAILURE OF FENCE DUE TO SUB-STANDARD INSTALLATION D/C Date: NOTE : C=CONSTRUCTION, D=DESIGN CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE INSTALLER. E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. P.JENYON S.CHAMBERS J.SHERIDAN N/A Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Sig. ELR N/A Drawing No. 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/001 01 GENERAL NOTES: SPECIFICATION: 203x203x60 UC POSTS WITH POINTED TOP 6000 MAX 155 CENTRES GATE FRAME 100x60x5.0 RHS ALL STEEL PALISADE FENCE SHALL BE SECURITY TYPE SP30 IN ACCORDANCE WITH BS 1722 : PART 12 AND HOT DIP GALVANISED IN ACCORDANCE WITH BS EN ISO 1461. ALL ROLLED STEEL SECTIONS SHALL BE OF STEEL GRADE S275 TO BS EN 10025 : 1993 UNLESS OTHERWISE SPECIFIED. ANTILIFT GATE HANGING DETAIL ALL BOLTS SHALL COMPLY WITH BS 3692 AND SHALL BE STRENGTH GRADE 8.8. NUTS SHALL BE STRENGTH GRADE 8 AND WASHERS SHALL CONFORM TO BS 4320. ALL BOLTS, NUTS AND WASHERS SHALL BE ZINC COATED. 3000 SLIDING LOCKING BAR 6mm THK SLAM PLATE ALL CONNECTIONS SHALL BE BOLTED IN ACCORDANCE WITH BS 1722 : PART 12. TRIANGULAR GUSSET PLATE 300x300mm INSITU CONCRETE SILL. MIX ST2 GROUND LEVEL ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE SPECIFIED. PALISADE FENCING OPTIONAL ITEMS REQUIRED FOR ADDITIONAL SECURITY ARE TO BE SPECIFIED IN A PROJECT SPECIFIC FORM A/B 1300 300 ALL BEDDING CONCRETE FOR VERTICAL FENCE POSTS TO BE MASS CONCRETE MINIMUM GRADE ST2 TO BS 8500-1. 100 DIA DUCT FOR EARTHING TAPE ON INSIDE OF COMPOUND DROP BOLT 925mm MINIMUM EMBEDMENT INTO 900x900x1300mm CONCRETE FOOTING 900 CONCRETE: C30/37, AC-4, DC-4, AGGREGATE: 20mm (MAX.) SULPHATE AND CHLORIDE RESISTANT DISTANCE TO COAST: 2km, SITE ALTITUDE: 100m AMSL WIND SPEED: 25m/s, ENVIRONMENT: TYPICAL OPEN COUNTRYSIDE GROUND CONDITION: AVERAGE FOR PLANTED (ROOT) FOUNDATION WATER TABLE: WELL BELOW THE FOUNDATION, AND SITE IS NOT SUSCEPTIBLE TO FLOODING (TYPICAL EXTERNAL VIEW) 50x50x6 RSA RAIL 127x76x13 UB POSTS WITH POINTED TOP A FENCES SHALL BE ACCURATELY SET OUT AND ERECTED TO PROVIDE A SMOOTH ALIGNMENT IN PLAN AND ELEVATION, FOLLOWING THE CONTOURS OF THE GROUND AS CLOSELY AS IS PRACTICABLE. THE LINE OF THE FENCING SHALL BE CLEARED OF ALL IMPENDING VEGETATION AND TRIMMED TO REMOVE ANY IRREGULARITIES TO ENABLE FENCE INFILL PANELS TO BE ERECTED AT A CONSTANT DISTANCE FROM THE GROUND. 17.12. 2014 01 Rev Date P.J. FIRST ISSUE Name Description of Revisions S.C. Rev' Check Client TABLE 1 50x50x6 RSA RAILS TOP AND BOTTOM 475 475 2750 MAX 155 CENTRES TO LIMIT DEFLECTION IN FENCE RAILS, THE BOTTOM HORIZONTAL RAIL SHALL BE SUPPORTED SO THAT AFTER TIGHTENING OF THE BOLTS, ALIGNING AND PLUMBING TO THE FENCE THERE IS A SLIGHT UPWARD CAMBER. THIS SUPPORT SHOULD BE REMOVED ONLY ONCE THE CONCRETE HAS SET. FENCES JOINED TO EXISTING FENCES, WALLS OR OTHER STRUCTURES TO PROVIDE A COMPLETE BARRIER TO PERSONS OR ANIMALS AS APPROPRIATE. CONCRETE TYPICAL 3.0m HIGH 6m WIDE PALISADE GATE (1:50) 127x76x13 UB INSTALLATION GUIDANCE: PALISADE FENCING ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES NR/SP/OHS/011: PREVENTION OF DAMAGE TO AND DANGER FROM SURFACE AND BURIED SERVICES. NR/PRC/MPI/CI0024: CONTROL AND USE OF METAL PINS AND SPIKES ON NETWORK RAIL INFRASTRUCTURE NR/PRC/MPI/CIOO26 PROCESS: FOR LOCATING BURIED SERVICES PRIOR TO GROUND PENETRATION. SAFETY, HEALTH & ENVIRONMENT RISK ASSESSMENT DESIGNERS' NOTE - CDM REG. 13(2)(b) MINIMUM 3.0mm THICK x 70mm WIDE CORRUGATED 'W' FENCING PALES AT EQUAL CENTRES, WITH TRIPLE POINTED TOPS WITH SPLAYED HEADS POINTING OUTWARDS 3000 3000 3.0mm THICK CORRUGATED PALES FIXED TO RAILS AT 155mm CENTRES 300x300mm INSITU CONCRETE SILL. MIX ST2 380 100 50x50x6 RSA RAILS THE FOLLOWING ARE SIGNIFICANT HAZARDS WHICH MIGHT AFFECT THE HEALTH AND SAFETY OF THOSE UNDERTAKING THE WORKS OUTLINED IN THIS SET OF DRAWINGS ON RAILWAY STRUCTURES OR THOSE AFFECTED BY THESE ACTIVITIES. A SITE SPECIFIC RISK ASSESSMENT SHOULD ALWAYS BE UNDERTAKEN PRIOR TO COMMENCING ANY OF THE WORKS DESCRIBED ON SITE. GROUND LEVEL 100 50 1300 50 MAX. 925 CONTACT WITH OVERHEAD WIRES OR BURIED SERVICES 925mm MINIMUM ENBEDMENT INTO 600x600x1300mm CONCRETE FOOTING 600 SECTION A-A (1:50) A INTERMEDIATE SUPPORTS WITH 100mm EMBEDMENT INTO CONCRETE SILL TYPICAL 3m HIGH PALISADE FENCE (1:50) (TYPICAL EXTERNAL VIEW) Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 IT IS ASSUMED THAT A COMPETENT CONTRACTOR IS AWARE OF THE RISKS ASSOCIATED WITH GENERAL CONSTRUCTION ACTIVITIES UNDERTAKEN WITHIN THE RAILWAY ENVIRONMENT. RISK GROUND LEVEL Property and infrastructure STAGE C SPECIFIC METHOD STATEMENT AND RISK ASSESSMENT TO IDENTIFY AND DETAIL PROTECTION TO ALL SERVICES, BURIED AND OVERHEAD. DAMAGE TO ROOTS OR PROTECTED TREES C SPECIFIC METHOD STATEMENT TO DETAIL PROVISION FOR ROOT PROTECTION OF TREES DURING WORKS. INJURY TO ADJOINING LANDOWNERS C ADJOINING LANDOWNERS TO BE INFORMED AHEAD OF WORKS. FAILURE OF FENCE DUE TO SUB-STANDARD MATERIALS D/C CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE MANUFACTURER. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title 3.0m HIGH 6m WIDE PALISADE GATE & FENCE DETAILS SECURITY LEVEL 3 Drawn By Name Checked By Name Approved By Name Scale APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER Signature: Name: Title: FAILURE OF FENCE DUE TO SUB-STANDARD INSTALLATION D/C Date: NOTE : C=CONSTRUCTION, D=DESIGN CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE INSTALLER. E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. P.JENYON S.CHAMBERS J.SHERIDAN N/A Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Sig. ELR N/A Drawing No. 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/002 01 GENERAL NOTES: SPECIFICATION: 1500 MAX 155 CENTRES ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE SPECIFIED. 152x152x37 UC POSTS WITH POINTED TOP PALISADE FENCING GATE FRAME 90x50x3.6 RHS ALL STEEL PALISADE FENCE SHALL BE SECURITY TYPE GP18/SP30 IN ACCORDANCE WITH BS 1722 : PART 12 AND HOT DIP GALVANISED IN ACCORDANCE WITH BS EN ISO 1461. ALL ROLLED STEEL SECTIONS SHALL BE OF STEEL GRADE S275 TO BS EN 10025 : 1993 UNLESS OTHERWISE SPECIFIED. ANTILIFT GATE HANGING DETAIL ALL BOLTS SHALL COMPLY WITH BS 3692 AND SHALL BE STRENGTH GRADE 8.8. NUTS SHALL BE STRENGTH GRADE 8 AND WASHERS SHALL CONFORM TO BS 4320. ALL BOLTS, NUTS AND WASHERS SHALL BE ZINC COATED. 3000 SLIDING LOCKING BAR ALL CONNECTIONS SHALL BE BOLTED IN ACCORDANCE WITH BS 1722 : PART 12. 6mm THK SLAM PLATE TRIANGULAR GUSSET PLATE OPTIONAL ITEMS REQUIRED FOR ADDITIONAL SECURITY ARE TO BE SPECIFIED IN A PROJECT SPECIFIC FORM A/B 300x300mm INSITU CONCRETE SILL. MIX ST2 GROUND LEVEL ALL BEDDING CONCRETE FOR VERTICAL FENCE POSTS TO BE MASS CONCRETE MINIMUM GRADE ST2 TO BS 8500-1. 1300 300 INSTALLATION GUIDANCE: PALISADE FENCING 100 DIA DUCT FOR EARTHING TAPE ON INSIDE OF COMPOUND TO LIMIT DEFLECTION IN FENCE RAILS, THE BOTTOM HORIZONTAL RAIL SHALL BE SUPPORTED SO THAT AFTER TIGHTENING OF THE BOLTS, ALIGNING AND PLUMBING TO THE FENCE THERE IS A SLIGHT UPWARD CAMBER. THIS SUPPORT SHOULD BE REMOVED ONLY ONCE THE CONCRETE HAS SET. 925mm MINIMUM EMBEDMENT INTO 600x600x1300mm CONCRETE FOOTING 600 ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES NR/SP/OHS/011: PREVENTION OF DAMAGE TO AND DANGER FROM SURFACE AND BURIED SERVICES. NR/PRC/MPI/CI0024: CONTROL AND USE OF METAL PINS AND SPIKES ON NETWORK RAIL INFRASTRUCTURE NR/PRC/MPI/CIOO26 PROCESS: FOR LOCATING BURIED SERVICES PRIOR TO GROUND PENETRATION. FENCES JOINED TO EXISTING FENCES, WALLS OR OTHER STRUCTURES TO PROVIDE A COMPLETE BARRIER TO PERSONS OR ANIMALS AS APPROPRIATE. FENCES SHALL BE ACCURATELY SET OUT AND ERECTED TO PROVIDE A SMOOTH ALIGNMENT IN PLAN AND ELEVATION, FOLLOWING THE CONTOURS OF THE GROUND AS CLOSELY AS IS PRACTICABLE. THE LINE OF THE FENCING SHALL BE CLEARED OF ALL IMPENDING VEGETATION AND TRIMMED TO REMOVE ANY IRREGULARITIES TO ENABLE FENCE INFILL PANELS TO BE ERECTED AT A CONSTANT DISTANCE FROM THE GROUND. CONCRETE TYPICAL 3.0m HIGH 1.5m WIDE PALISADE GATE (1:50) CONCRETE: C30/37, AC-4, DC-4, AGGREGATE: 20mm (MAX.) SULPHATE AND CHLORIDE RESISTANT DISTANCE TO COAST: 2km, SITE ALTITUDE: 100m AMSL WIND SPEED: 25m/s, ENVIRONMENT: TYPICAL OPEN COUNTRYSIDE GROUND CONDITION: AVERAGE FOR PLANTED (ROOT) FOUNDATION WATER TABLE: WELL BELOW THE FOUNDATION, AND SITE IS NOT SUSCEPTIBLE TO FLOODING (TYPICAL EXTERNAL VIEW) 17.12. 2014 01 Rev Date P.J. FIRST ISSUE Name Description of Revisions S.C. Rev' Check Client TABLE 1 SAFETY, HEALTH & ENVIRONMENT RISK ASSESSMENT 1500 MAX 155 CENTRES 178x102x19 UB POSTS WITH POINTED TOP GATE FRAME 90x50x3.6 RHS ANTILIFT GATE HANGING DETAIL DESIGNERS' NOTE - CDM REG. 13(2)(b) THE FOLLOWING ARE SIGNIFICANT HAZARDS WHICH MIGHT AFFECT THE HEALTH AND SAFETY OF THOSE UNDERTAKING THE WORKS OUTLINED IN THIS SET OF DRAWINGS ON RAILWAY STRUCTURES OR THOSE AFFECTED BY THESE ACTIVITIES. A SITE SPECIFIC RISK ASSESSMENT SHOULD ALWAYS BE UNDERTAKEN PRIOR TO COMMENCING ANY OF THE WORKS DESCRIBED ON SITE. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 1800 SLIDING LOCKING BAR 6mm THK SLAM PLATE TRIANGULAR GUSSET PLATE GROUND LEVEL 1100 525mm MINIMUM EMBEDMENT INTO 600x600x1100mm CONCRETE FOOTING 600 TYPICAL 1.8m HIGH 1.5m WIDE PALISADE GATE (1:50) (TYPICAL EXTERNAL VIEW) T: +44 (0) 161 488 1500 IT IS ASSUMED THAT A COMPETENT CONTRACTOR IS AWARE OF THE RISKS ASSOCIATED WITH GENERAL CONSTRUCTION ACTIVITIES UNDERTAKEN WITHIN THE RAILWAY ENVIRONMENT. RISK CONTACT WITH OVERHEAD WIRES OR BURIED SERVICES STAGE C SPECIFIC METHOD STATEMENT AND RISK ASSESSMENT TO IDENTIFY AND DETAIL PROTECTION TO ALL SERVICES, BURIED AND OVERHEAD. DAMAGE TO ROOTS OR PROTECTED TREES C SPECIFIC METHOD STATEMENT TO DETAIL PROVISION FOR ROOT PROTECTION OF TREES DURING WORKS. INJURY TO ADJOINING LANDOWNERS C ADJOINING LANDOWNERS TO BE INFORMED AHEAD OF WORKS. FAILURE OF FENCE DUE TO SUB-STANDARD MATERIALS D/C CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE MANUFACTURER. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title 3.0m & 1.8m HIGH 1.5m WIDE PALISADE ACCESS GATE DETAILS Drawn By Name Checked By Name Approved By Name Scale APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER Signature: Name: Title: FAILURE OF FENCE DUE TO SUB-STANDARD INSTALLATION D/C Date: NOTE : C=CONSTRUCTION, D=DESIGN CERTIFICATE OF CONFORMITY IN ACCORDANCE WITH BS 1722 TO BE PROVIDED BY FENCE INSTALLER. E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. P.JENYON S.CHAMBERS J.SHERIDAN N/A Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Sig. ELR N/A Drawing No. 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/003 01 5. 6m LIGHTING 8m LIGHTING A DUCT A B DUCT PLAN (1:20) B HINGED COLUMN TO BE INSTALLED TO FALL AWAY FROM TRACK FOR MAINTENANCE PURPOSES. THE TOP SURFACE OF THE FOUNDATIONS SHALL BE SET TO LEVEL WITH A TOLERANCE OF +/- 5mm. NO POINT SHALL HAVE A SAG GREATER THAN 3mm FROM A 2m STRAIGHT EDGE. 7. REFER TO ABACUS DRAWINGS FOR DETAILS 8. FOR FURTHER DETAILS OF CIVIL ENGINEERING WORKS REFER TO :- NR/L3/CIV/140-MODEL CLAUSES. FOR FURTHER DETAILS OF TECHNICAL APPROVAL OF DESIGN, CONSTRUCTION & MAINTENANCE OF CIVIL ENGINEERING INFRASTRUCTURE REFER TO :- NR/SP/CIV/003. GENERAL NOTES: 1. ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. 2. DO NOT SCALE THIS DRAWING. 3. GROUND UNDER CONCRETE FOUNDATION TO BE WELL COMPACTED PRIOR TO LAYING CONCRETE. ANY SOFT SPOTS TO BE EXCAVATED OUT AND BACKFILLED WITH TYPE 1 FILL WELL COMPACTED IN 150MM LAYERS. 4. CONCRETE TO BE DESIGNED MIX IN ACCORDANCE WITH BS8500-2. COMPRESSIVE STRENGTH CLASS C32/40 DESIGN CHEMICAL CLASS DC-2Z MAX. AGGREGATE SIZE 20mm CHLORIDE CLASS CI 0.40 CONSISTENCE CLASS S3 CONCRETE BLINDING TO BE DESIGNATED MIX GEN 1 IN ACCORDANCE WITH BS 8500-2. REINFORCEMENT TO BE GRADE 500 BAR IN ACCORDANCE WITH BS4449, OR MESH FABRIC IN ACCORDANCE WITH BS4483. COVER TO ALL REINFORCEMENT TO BE 50MM. MASS CONCRETE FILL TO BASE TO BE COMPRESSIVE STRENGTH CLASS C16/20. 6880 4910 6. PLAN (1:20) NOTE: LIGHTING POSITION MAY VARY TO SUIT SITE LOCATION THE VERTICAL EDGE OF THE CONCRETE FOUNDATION SHALL BE FORMED TO A CLASS F2 FINISH IN ACCORDANCE WITH SECTION 80 CLAUSE 80.033 OF THE SPECIFICATION. THE TOP OF THE FOUNDATION SHALL HAVE A SWEPT BRUSH FINISH WITH FLOATED EDGES, 100mm WIDE. APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER Signature: Title: Name: Date: 8m LIGHTING 6m LIGHTING 17.12. 2014 1000 1000 01 Rev FIRST ISSUE Name Description of Revisions S.C. Rev' Check Client GROUND LEVEL Property and infrastructure 500 500 GROUND LEVEL Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 1000 CABLE ENTRY (150X50) MASS CONCRETE FOUNDATION GRADE ST2. CONCRETE TO BE RAMMED AS FILLING PROCEEDS. CABLE ENTRY (150X50) T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. 1200 1450 1250 Date P.J. Project Title MASS CONCRETE FOUNDATION GRADE ST2. CONCRETE TO BE RAMMED AS FILLING PROCEEDS. INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title WITH CONCRETE ON 25mm SAND BLINDING 300 WITH CONCRETE ON 25mm SAND BLINDING 6m & 8m LIGHT DUTY HINGED LIGHTING COLUMN FOUNDATION DETAILS 300 SECTION A-A (1:20) TYPICAL 6m ABACUS T061RLS LIGHT DUTY LIGHTING COLUMN FOUNDATION DETAILS SECTION B-B (1:20) TYPICAL 8m ABACUS T081RLS LIGHT DUTY LIGHTING COLUMN FOUNDATION DETAILS Drawn By Name Checked By Name Approved By Name P.JENYON S.CHAMBERS J.SHERIDAN N/A Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Sig. ELR N/A Drawing No. 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/004 01 5. 6m LIGHTING COLUMN A A DUCT NOTES: 1. ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. 2. DO NOT SCALE THIS DRAWING. 3. GROUND UNDER CONCRETE FOUNDATION TO BE WELL COMPACTED PRIOR TO LAYING CONCRETE. ANY SOFT SPOTS TO BE EXCAVATED OUT AND BACKFILLED WITH TYPE 1 FILL WELL COMPACTED IN 150MM LAYERS. 4. CONCRETE TO BE DESIGNED MIX IN ACCORDANCE WITH BS8500-2. COMPRESSIVE STRENGTH CLASS C32/40 DESIGN CHEMICAL CLASS DC-2Z MAX. AGGREGATE SIZE 20mm CHLORIDE CLASS CI 0.40 CONSISTENCE CLASS S3 CONCRETE BLINDING TO BE DESIGNATED MIX GEN 1 IN ACCORDANCE WITH BS 8500-2. REINFORCEMENT TO BE GRADE 500 BAR IN ACCORDANCE WITH BS4449, OR MESH FABRIC IN ACCORDANCE WITH BS4483. COVER TO ALL REINFORCEMENT TO BE 50MM. MASS CONCRETE FILL TO BASE TO BE COMPRESSIVE STRENGTH CLASS C16/20. B PLAN (1:25) 6. THE TOP SURFACE OF THE FOUNDATIONS SHALL BE SET TO LEVEL WITH A TOLERANCE OF +/- 5mm. NO POINT SHALL HAVE A SAG GREATER THAN 3mm FROM A 2m STRAIGHT EDGE. 7. REFER TO ABACUS DRAWINGS FOR DETAILS 8. FOR FURTHER DETAILS OF CIVIL ENGINEERING WORKS REFER TO :- NR/L3/CIV/140-MODEL CLAUSES. FOR FURTHER DETAILS OF TECHNICAL APPROVAL OF DESIGN, CONSTRUCTION & MAINTENANCE OF CIVIL ENGINEERING INFRASTRUCTURE REFER TO :- NR/SP/CIV/003. 3175 PLAN (1:25) 2370 RIGID DUCT 8m LIGHTING COLUMN B THE VERTICAL EDGE OF THE CONCRETE FOUNDATION SHALL BE FORMED TO A CLASS F2 FINISH IN ACCORDANCE WITH SECTION 80 CLAUSE 80.033 OF THE SPECIFICATION. THE TOP OF THE FOUNDATION SHALL HAVE A SWEPT BRUSH FINISH WITH FLOATED EDGES, 100mm WIDE. NOTE: LIGHTING POSITION MAY VARY TO SUIT SITE LOCATION HINGED COLUMN TO BE INSTALLED TO FALL AWAY FROM TRACK FOR MAINTENANCE PURPOSES. 3200 2035 APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER Signature: Title: Name: Date: 17.12. 2014 01 6m LIGHTING P.J. FIRST ISSUE Name Description of Revisions S.C. 8m LIGHTING Rev Date Rev' Check 1505 1505 Client DOOR DOOR GROUND LEVEL GROUND LEVEL Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Project Title 500 500 Capita Property and Infrastructure Ltd. 1450 1200 CABLE ENTRY (150x50) 1200 1450 CABLE ENTRY (150x50) MASS CONCRETE FOUNDATION GRADE ST2. CONCRETE TO BE RAMMED AS FILLING PROCEEDS. MASS CONCRETE FOUNDATION GRADE ST2. CONCRETE TO BE RAMMED AS FILLING PROCEEDS. ON 25mm SAND BLINDING ON 25mm SAND BLINDING 600 SECTION A-A (1:25) TYPICAL 6m ABACUS T067RLH HEAVY DUTY LIGHTING COLUMN FOUNDATION DETAILS 600 SECTION B-B (1:25) TYPICAL 8m ABACUS T087RLH HEAVY DUTY LIGHTING COLUMN FOUNDATION DETAILS INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title 6m & 8m HEAVY DUTY HINGED LIGHTING COLUMN FOUNDATION DETAILS Drawn By Name Checked By Name Approved By Name P.JENYON S.CHAMBERS J.SHERIDAN N/A Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Sig. ELR N/A Drawing No. 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/005 01 NOTES 1. ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. DO NOT SCALE THIS DRAWING. 2. GUARD RAIL TO BE IN ACCORDANCE WITH NETWORK RAIL DOCUMENT NR/GN/SIG/11210 APPENDIX 2G05 3. ALL COMPONENTS TO BE SECURED WITH EPOXY IN ACCORDANCE WITH MANUFACTURERS SPECIFICATION. 4. GUARD RAIL TO BE GREY - RAL 7047 5. FOR FURTHER DETAILS OF CIVIL ENGINEERING WORKS REFER TO :- NR/L3/CIV/140-MODEL CLAUSES. FOR FURTHER DETAILS OF TECHNICAL APPROVAL OF DESIGN, CONSTRUCTION & MAINTENANCE OF CIVIL ENGINEERING INFRASTRUCTURE REFER TO :- NR/SP/CIV/003. 6. HANDRAIL SHALL BE CAPABLE OF WITHSTANDING A HORIZONTAL FORCE OF 400N/m ACTING AT THE HEIGHT OF HANDRAILS IN ACCORDANCE WITH NETWORK RAIL COM[ANY STANDARD NR/SP/OHS/069 1000 50mm OD (40mm ID) GRP POSTS. 50mm OD (40mm ID) GRP POSTS. A A B PLAN ON FOUNDATION (1:20) B PLAN ON FOUNDATION ALTERNATIVE POST FIXING DETAIL (1:20) 50mm OD (40MM ID) GRP RAILS. 600 GROUND LEVEL 17.12. 2014 01 Rev Date P.J. FIRST ISSUE Name Description of Revisions S.C. Rev' Check Client GROUND LEVEL DEPTH TO SUIT FORMATION LEVEL 500 MASS CONCRETE FOUNDATION GRADE ST2, 400x400x700mm DEEP. CONCRETE TO BE RAMMED AS FILLING PROCEEDS & TOP TO BE CHAMFERED AT 1:40. BASE MOUNTED GRP POST FIXED WITH 4 NO. M12 GALVANISED STEEL RESIN ANCHORS, OR IN ACCORDANCE WITH MANUFACTURERS SPECIFICATION. DEPTH TO SUIT 1100 50mm OD (40mm ID) GRP POSTS. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title 1000 FILLED WITH CONCRETE ON 25mm SAND BLINDING 2000 ALL EXCAVATED 225 MATERIAL TO BE REINSTATED IN 150mm COMPACTED LAYERS 225 SECTION A-A GRP GUARD RAIL ELEVATION (1:20) APPROVED FOR CONSTRUCTION - NETWORK RAIL CIVIL ENGINEER 450 SECTION B-B ALTERNATIVE POST FIXING DETAIL (1:20) INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title HEAVY DUTY GRP HANDRAIL DETAILS Drawn By Name Checked By Name Approved By Name S.CHAMBERS J.SHERIDAN Title: N/A Sig. Date Sig. Date Sig. Date Sheet AS SHOWN @ A3 Site Coordinates Signature: P.JENYON ELR N/A Drawing No. Name: Date: 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Revision 075481/CV/006 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Road width varies Existing Ground Type 3 granular sub-base material (subject to designers requirement) Finished road level Existing Ground 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Tensar TriAx used to create mechanically stabilized layer (subject to detailed design) Geotextile weed membrane Proof rolled formation Overall depth of access road to be site specific Property and infrastructure STONE ACCESS ROAD DETAILS (Subject to site specific design) Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Note: All soft spots encountered are to be removed and replaced by 6F2/6F5 material in accordance with specification for Highway Works' series 600. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title Alternate option N.R. approved manufacturer surfacing (i.e. Truck Pave). TYPICAL ROLLED STONE ACCESS ROAD DETAILS Drawn By Checked By Approved By L.Z. J.W. J.W. Scale Site Coordinates Name Name Name L.ZEMAN J.WHITE J.WHITE Date Sig. Date Sig. Date Sheet 1:10 @ A3 N/A Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 007 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES 30mm thick AC 10 close surf 100/150 to BS EN 13108-1 50mm thick HRA 30/14 f surf 40/60 chip 8/14 to BA EN 13108-4 Refer to table A for sub-base and capping layer 60mm thick AC 20 dense bin 100/150 to BS EN 13108-1 60mm thick AC 20 dense bin 100/150 to BS EN 13108-1 150mm thick AC 32 dense base 100/150 to BS EN 13108-1 Refer to table A for sub-base and capping layer Type 1 granular sub-base material to S.H.W. 800 Capping layer - class 6F5 (or 6F2) capping material Lotrack 2800 geotextile (or equivalent) Sub formation level Type 1 granular sub-base material to S.H.W. 800 Capping layer - class 6F5 (or 6F2) capping material Lotrack 2800 geotextile (or equivalent) Subgrade CBR (%) Subgrade CBR (%) ACCESS TYPE 2 Sub formation level ACCESS TYPE 3/4 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Table A: Foundation thickness based on selected subgrade CBR values pavement and track form designed in accordance with HD26/06 foundation class 2. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure SUB BASE ONLY DESIGN SUBGRADE CBR (%) 2.5 3 4 5 7 10 15 T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. SUB BASE (TYPE 1) mm 450 420 360 320 290 250 200 TOTAL THICKNESS mm 450 420 360 320 290 250 200 Project Title SUB BASE AND CAPPING DESIGN SUBGRADE CBR (%) 2.5 3 4 5 7 10 15 SUB BASE (TYPE 1) mm 350 320 270 240 220 180 150 CAPPING (SERIES 600) mm 250 240 220 210 190 170 150 TOTAL THICKNESS mm 600 560 490 450 410 350 300 NEW CARRIAGEWAY CONSTRUCTION STANDARD DETAIL INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL ASPHALT CONCRETE ACCESS ROAD DETAILS Drawn By Checked By Approved By L.Z. J.W. J.W. Scale Site Coordinates Name Name Name L.ZEMAN J.WHITE J.WHITE Date Sig. Date Sig. Date Sheet 1:20 @ A3 N/A Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 008 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Depth of Pavement Finished level Concrete slab Grade PAV2 1200g polyethylene Proof rolled formation Type 1 GSBM Capping (6F2 or 6F5) 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Subject to detail design. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL CONCRETE HARDSTANDING / ACCESS ROAD DETAILS Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet NTS @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 009 Rev 01 GENERAL NOTES: Galvanized mild steel barrier guard rail complete with guard rail system to be installed strictly in accordance with manufacturers details. 600 600 100mm wide 8mm Thick stiffener 412 412 Notes: 127x76 UB A Depth to suit formation level Mass concrete foundation grade ST2. Concrete to be rammed as filling proceeds. 25mm sand blinding A 12mm Thick base plate - see detail Depth to suit formation level 1. Fishtailed end unit to be fixed to all barrier ends. 2. Post centres as per manufacturers detail, but a minimum of 2m centres. ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Galvanized mild steel barrier guard rail complete with 127x76UB post and base plate. Guard rail system to be installed strictly in accordance with manufacturers details. Mass concrete foundation grade ST2. Concrete to be rammed as filling proceeds. on 25mm sand blinding ARMCO BARRIER RIDGID DUCT DETAIL ROOTED ARMCO BARRIER DETAIL (PREFERRED OPTION) 17.12. 2014 01 450 450 Galvanized mild steel barrier guard rail complete with 127x76UB post and base plate. Guard rail system to be installed strictly in accordance with manufacturers details. Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Property and infrastructure 12mm Thk. base plate c/w Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 127x76 UB 12mm Thick base plate - see detail B 330 60 B 45 412 600 SECTION A-A PLAN ON FOUNDATION E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS 100mm wide 8mm Thick stiffener 250 Drawing Title ARMCO BARRIER DETAILS Concrete Base/Apron Drawn By ARMCO BARRIER DETAIL FIXED TO CONCRETE BASE/APRON SECTION B-B ARMCO BARRIER BASE PLATE DETAIL L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet NTS @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 010 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES YPL Street Furniture Bollards installed at 1.5m centres Bollards installed at 1.5m centres Unit 9 Royal Business Park King Street Pontefract Lifting handle YPL Economy Telescopic Post Heavy duty galvanised 100x100 steel section (YPLECO) WF8 4AH Tel: 00(44) 1977 600999 Email: Sales@ypl-streetfurniture.co.uk Removable steel bollard 1000 610 (YPL889 Galvanised or YPL010m powder coated) top bollard G.L. 20mm clean chippings compacted 150 5mm box section, galvanised. 6mm base plate complete with water outlet G.L. 300 Concrete to be grade ST4 to BS 8500 and BSEN 206. Grass: +50mm (with 50mm chamfer) Asphalt conc.: -60mm Concrete: integral with slab 150 200 Bollard 50mm chamfer G.L. 785 200 450 minimum of concrete Hinged cover plate Concrete to be grade ST4 to BS 8500 and BSEN 206. DROP BOLLARD 200 200 Concrete to be grade ST4 to BS 8500 and BSEN 206. TYPICAL CONCRETE BASE REMOVABLE BOLLARD 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Bollards installed at 1.5m centres 915 1300 Bollards installed at 1.5m centres Marshalls Bridgford T: +44 (0) 161 488 1500 INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Bottom 500mm to be given 3 coats of RIW and set into C25 concrete bases 200mm minimum surround. Drawing Title BOLLARD DETAILS Drawn By 270 dia L.Z. Checked By Approved By PRECAST CONCRETE BOLLARD E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title 500 455 Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure with concrete. Painted with yellow and black banding. Ground level NOTES 1. All dimensions in millimetres. 2. Concrete markers and bollards to be ST4 concrete to BS.5328 PT2 3. Bollards to have smooth plain white concrete finish or beadalite finish if required. Property and infrastructure Bollard constructed PERMANENT STEEL BOLLARD Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet NTS @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 011 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES 50x150mm Flat top P.C.C edging kerb each side of road Proposed Road level ST2 Concrete 200mm 50mm 150mm min. 200mm Existing landscape 200mm EDGING KERB 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client 150 125 20 Finished road level ST2 Concrete 125mm Finished road level 150 125x150mm dropped Bullnosed lightweight recycled polymer kerb (Durakerb or similar approved product) Property and infrastructure 150 150 min 75 150 70 60 50 125x255mm half battered lightweight recycled polymer kerb (Durakerb or similar approved product) 50 25 Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure For road construction details refer to typical details Capita Property and Infrastructure Ltd. 275 ST2 Concrete 350 DROPPED KERB Not for use on public highways HALF BATTER KERB T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title LIGHTWEIGHT KERBING DETAILS (DURAKERBS) Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:10 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 012 Rev 01 GENERAL NOTES: 305 x 150mm CD dished channel 125 x 150mm P.C.C. bull nosed kerb type BN to BS EN 1340 150 150 300 15 15 ST1 concrete bed and haunch 60 60 Kerb face 125 x 255mm P.C.C. half battered kerb type HB2 to BS EN 1340 ST1 concrete bed and haunch Kerb face -25mm as vehicular crossing - 6mm as pedestrian crossing 300 15mm min mortar (see note 4) 15mm min mortar (see note 4) 200 125 60 150 15 150 ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES ST1 concrete bed and haunch 305 125 555 200 50 x 200mm P.C.C. flat top edging type EF to BS EN 1340 70 180 50 x 150mm P.C.C. flat top edging type EF to BS EN 1340 445 X = min 25 max 65 dowel holes 230 380 ST1 concrete bed and haunch 100 15 60 100 230 C'way X 115 415 25 160 80 DISHED CHANNEL TYPE CD ST1 concrete bed and haunch 250 15mm min mortar (see note 4) 60 NB. Where insufficient haunching/backing is available, vertical dowel holes are moulded into the unit. dowel bars should then be put into the unit & anchored securely. KERB TYPE BN (BULL NOSED KERB 125x150mm) 50 KERB TYPE HB2 (HALF BATTERED KERB 125x255mm) 250 17.12. 2014 01 Rev 15mm min mortar (see note 4) Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client 15mm min mortar (see note 4) HIGH CONTAINMENT KERB WITH DOWEL HOLES EDGING TYPE EF 50mm upstand (Edging 50x200mm) EDGING TYPE EF Flush (Edging 50x150mm) Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title NOTES 1. Do not scale off this drawing. 2. All dimensions in millimetres unless otherwise stated. 3. Unless specified otherwise steel dowel bars shall be used where kerb bedding / backing is laid separately. If used dowel bars shall be 300mm long 20mm diameter mild steel at 450mm centres. 4. Mortar only to be used when kerb laid on cured concrete. Designation (i) mortar to be used. 5. All kerbs to be precast concrete. INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title PRE-CAST CONCRETE KERBING DETAILS Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:20 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 013 Rev 01 NOTES: 1. All dimensions in millimetres unless noted otherwise. Do not scale this drawing. 2. For futher details, refer to manufacturer. AQUA. Belmont House, Garnett Place, Skelmersdale, Lancashire, WN8 9UB. Tel 01695 51933. Email. sales@aquafab.co.uk. Fax. 01695 51891. Web. www.aquafab.co.uk Entry to be Galvanised solid lid with frame site specific CL (Cover Level) Finished ground level X 17.12. 2014 01 X Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Incoming pipes 300 IL site specific Incoming pipes Entry to be 100 100 Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 100 Depth to be site specific Entry to be Incoming pipes backfill. site specific HDPE chamber Clean 20/40mm single sized aggregate or 40mm gravel surround Concrete base slab SECTION X-X T: +44 (0) 161 488 1500 PLAN ON SOAKAWAY E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL AQUA SOAKWAY DETAILS TYPICAL SOAKWAY DETAIL NON TRAFFICKED AREAS For non-vehicle traffic only. Subject to detail design & liason with manufacture based on Aqua Thieel chamber. Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:20 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 014 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Class B solid engineering bricks, concrete blocks or precast concrete cover frame seating rings 750mm sq clear opening D400 (min) ductile iron cover and frame bedded on mortar with a mortar haunch GL 750 1050 diameter manhole rings changing to 1050 soakaway rings Geotextile filter membrane shall be provided to the top, bottom and all sides of the soak away pit. Geotextile membrane to be Lotrak 2300 or Polyfelt TS50 or approved equivalent. 750 Clean 20/40mm single sized aggregate or 40mm gravel surround / base infill to soakaway. Top stone Geotextile Geotextile 17.12. 2014 01 L.Z. First issue Name Description of Revisions J.W. IL Rev Date Rev' Check Geotextile 3500 Geotextile Geotextile Geotextile Client Property and infrastructure BL 450 Geotextile GEN 3 concrete ring foundations for the soakaway rings T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title Geotextile Geotextile 300 (min) Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 1050mm diameter PCC Soakaway rings with 75mm diameter holes 300 (min) Clean 20/40mm single sized aggregate or 40mm gravel surround / base infill to soakaway. INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL SOAKWAY DETAIL TRAFFICKED AREAS TYPICAL SECTION THROUGH SOAKAWAY Drawn By Subject to detail design. L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:20 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 015 Rev 01 GENERAL NOTES: Kerb ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Vertical saw cut to existing Binder course Existing Carriageway Vertical saw cut to existing Surface course. Joint to be painted with hot bitumin (Cl 706) Surface course Binder course 300 Existing Carriageway Proposed carriageway profile 130 100 Existing material to be planed or removed with hand tools 60 Or as directed by Engineer 40 300 Base course Surface course Binder course Base course Capping layer The edge of existing carriageway to be cut back 300mm to sound face or as directed by the Engineer Where this dimension is in a taper section and varies from 0 to 750mm then concrete may be used in lieu of Base course Concrete to be C7.5, wet lean concrete to Cl 1030 with 75mm slump, placed with vibrating poker 425 CONSTRUCTION DETAILS ADJACENT TO EXISTING CARRIAGEWAY (LONGITUDINAL TIE-IN DETAIL) CLAUSES REFER TO THE SPECIFICATION FOR HIGHWAY WORKS Existing Carriageway to be planed min 100 CUT FIL L Sub-base Surface course regulating material Sub-base Binder course regulating material Existing carriageway profile Base course regulating material REGULATING COURSE IN AREA OF BUILD UP ON EXISTING CARRIAGEWAY (TRANSVERSE TIE-IN DETAIL) 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Transition joint location Shown on plan 3000 Surface course Binder course Base course Sub-base Existing Footway 75 75 Reinforcement 1000 Concrete surface 300 Property and infrastructure Surface course Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure Binder course T: +44 (0) 161 488 1500 Sub Base 10 Detail design Sub-base 200mm Transition slab 1 20mm mild steel bars 1m long at 300 centres. TRANSITION JOINT BETWEEN CONCRETE AND ASPHALT CONCRETE SURFACING E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title All joints to be saw cut and sealed FOOTWAY TIE-IN DETAIL INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TIPICAL HARDSTANDING / ACCESS ROAD TIE-IN DETAILS Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet NTS @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 016 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES 35 150 * 60 * Dimensions marked thus 100 - load class A15 150 - load class B125 200 - load class D400 Linear drainage channel (subjec to detail design) Min C25/30 concrete bedding and haunch. LINEAR DRAINAGE UNIT DETAIL ASPHALT PAVEMENT * Top of channel 3mm below pavement Concrete hardstanding * Channel width * * Slotted ductile iron grating refer to loading classes Concrete hardstanding Linear drainage channel (subjec to detail design) * Slotted ductile iron grating refer to loading classes 185 Varies Top of channel 3mm below pavement Dimensions marked thus 100 - load class A15 150 - load class B125 200 - load class D400 Min C25/30 concrete bedding and haunch. LINEAR DRAINAGE UNIT DETAIL CONCRETE PAVEMENT 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL LINEAR DRAINAGE CHANNEL DETAILS Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:20 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 017 Rev 01 160 430 160 150 210 ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES 150 210 330 750 500 150 400 800 150 GENERAL NOTES: 150 350 150 150 375 Formation drainage slot PLAN OF P.C. COVER SLAB FOR 500mm * 350mm GRATING AND FRAME PLAN OF P.C. COVER SLAB FOR 430mm * 370mm GRATING AND FRAME NOTES Joint between kerb and frame filled and pointed with polyester resin mortar 10 Formation drainage slot Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client 2. Gratings shall be available with either left or right hand hinges as viewed when facing the kerb. Hinged end to be nearest on-coming traffic. The grating shall be captive within the frame. Varies 330 min Carriageway 50 17.12. 2014 01 1. End hinged ductile iron gully grating and frame to BS EN 124:1994 Class D400 (see note 5) bedded on polyester resin mortar 10 to 20mm thick. See Note 1 150 Formation Level Formation drainage slot 375 650 Concrete ST4 cast in-situ raising piece rebated as necessary and finised smooth and even. Portland cement is to be used when the ambient temperature can be expected to fall 150 Property and infrastructure 3. All in-situ concrete to be medium workability / 75mm slump. Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 4. Precast concrete gully cover slab ST4 with minimum cement content 300 kg/m3 and 0.60 maximum water/cement ratio. Workability to suit method of manufacture. Capita Property and Infrastructure Ltd. T: +44 (0) 161 488 1500 Bend as required Flexcell joint 150mm diameter outlet 5. Dimensions of opening on upper face of PC cover slab shall be the same as the clear opening at the underside of the frame. Tolerance is permitted on all other cover slab dimensions 450*750*150 concrete street gully to BS5911 Part 6 E: Special.Projects@Capita.co.uk Project Title INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title CONCRETE ROAD GULLY FOR ACCESS ROAD Stopper & chain Flexcell joint Drawn By L.Z. Checked By 150mm bed and surround concrete ST4 150mm bed and surround concrete ST4 Approved By Scale CONCRETE ROAD GULLY J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1 :10 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 018 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Additional access shafts dependent upon Separator size and manufacturer Finished Level External construction Manhole cover classification dependant upon location 1500 diameter PCC rings required for maintenance access on separators with a cover of 1.25m and over 1220*685 multiple cover required 17.12. 2014 01 Positioned on filter access unit Rev 200mm thick R.C. capping slab reinforced with 2 layers of A393 mesh 1 top + 1 bottom (40mm cover) 1000 over hang all round 75mm thick layer of polystyrene Profile of P.I. is indicative only. Concrete surround to tank in accordance with manufacturers installation instructions Date L.Z. First issue Name Description of Revisions J.W. Rev' Check Client 1000 over hang all round NOTE Property and infrastructure Concrete to capping slab to be grade C35/20 with a minimum cement content of 330kg/m3 and a maximum free water/cement ratio of 0.55. Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title TYPICAL SECTION THROUGH OIL SEPARATOR IN TRAFFICKED AREA INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS Drawing Title TYPICAL OIL SEPARATOR Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:50 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 019 Rev 01 GENERAL NOTES: ALL WORKS TO BE COMPLETED IN ACCORDANCE WITH THE REQUIREMENTS OF NETWORK RAIL COMPANY PROCEDURES Surface to be reinstated to match existing 500 Finished ground level 20mm Single size stone 17.12. 2014 01 Rev Date L.Z. First issue Name Description of Revisions J.W. Rev' Check 150 Client pipe (pipes to be laid with perforations at invert). Terram 1000 lining or similar approved product. Filter material 10mm clean pea gravel. Property and infrastructure Special Projects, 2nd Floor Clemence House, Mellor Road, Cheadle Hulme. SK8 5AT Web: www.capita.co.uk/infrastructure 150 T: +44 (0) 161 488 1500 E: Special.Projects@Capita.co.uk Capita Property and Infrastructure Ltd. Project Title 50 INFRASTRUCTURE ACCESS POINTS BEST PRACTICE DESIGN GUIDE STANDARD DETAILS 150 150 600 FILTER DRAIN DETAIL Geotextile filter membrane on 50mm thick layer of sand bedding. Drawing Title FILTER DRAIN DETAILS Drawn By L.Z. Checked By Approved By Scale J.W. J.W. Name Name Name L.ZEMAN J.WHITE J.WHITE N/A Date Sig. Date Sig. Date Sheet 1:10 @ A3 Site Coordinates Sig. ELR N/A 1 Chainage of 17.12.14 17.12.14 17.12.14 1 N/A Drawing No. 075481 / CV / 020 Rev 01