(ii) EDUCATION AND TRAINING EQUIPMENT Declaration of Conformity: Directives (where applicable) 89/392/CEE as amended by 91/368/EEC 89/336/CEE 72/23/CEE We declarethat the following unit complieswith the aboveEEC directives: R633 Refrigeration Cycle Demonstration Unit For and on behalf of P.A. HILTON LIMITED 4,~;._AA ~ TechnicalDirector P .A. HILTON LIMITED HorsebridgeMill, King's Sombome, Stockbridge,Hampshire,S020 6PX, England. Tel No. National Romsey(01794) 388382 International +44 1794 388382 Fax No. +44 1794388129 E-mail: sales@p-a-hilton.co.uk (i) POLICY STATEMENT After Sales Service We, P.A Hilton Ltd., attach considerable imJX)rtanCein being able to retain die confi(k;nce and goodwill of our clients in offering an effective after sales service. Every effort is made to answer clients COrIesponOODCC promptly and to JXOvide a rapid follow up of spares and repi.:ement parts by maintaining comprehensive stocks of COIDJXments usually available ex-stock. Shouldour clients encounterany difficulty in ~g that as a first step dley COIU.:tdle Hilton ~tative repesentative.write direct to P.A. Hilton LId. or maintaininga Hilton prodtx;t we would ask in their country or. in me absenceof a 1<x:a1 In the extreme~ a problem may arisein the operatiooof equipmentwbkh could seriouslydisrupt a teachingor ~h ~hedule. In suchcircwnstancesrapid advicefrom the man~ is desirable and we wish our clients to know that HiltoDs' will acceptfrom them a tlansfer chargetelephonecall from anywherein the wcxld. We ask our clients to treat d1is service as an emergerx:y service only and to use it sparingly and wisely. Pleasedo be aWaleof the time diff~ that may exist and. before making a tclelitone call. make notesof die POblemyou wish to describe. English is a prefen'edlanguage.Our telephonenumberis "Romsey(01794) 388382" and the felephme is oonnally mannedbetween0800 and 1700 hrs GMr every day. Advarx:enotice of an impendingfelepixmecall by Fax would be appreciated. ~h productmanufacturedby P.A. Hilton Ltd., is testedunderoperatingconditionsin our permanent instaUationsbefore~-~!ch. VisitorSto ~mdge Mill are encouragedto operateand evaluateour equipmentwith initial guidancefran a Hilton en~. INDEX ~ SCHEMATIC DIAGRAM 1 VALVE POSITIONS DIAGRAM 2 SYMBOLS AND UNITS 3 INTRODUCTION 4 The Refrigeratiooor Heat Pump Cycle 4 The ValX>urCompressionCycle 4 INSf ALLA nON AND COMMISSIONING THE mLTON REFRIGERATION CYCLE DEMONSTRATION UNIT: 6 10 Useful Data 10 Specification 11 Description 13 OPERATING PROCEDURE IS Nonnal Operation IS EvaporationPnx:ess IS CondensationProcess 16 Shutting Down the Unit RefrigerantPumpDown 16 17 Oil Return 11 Air Venting 18 MAINTENANCE: 19 High PressW'e Cut Out 19 Thennometers 19 Minjanue Cin:uit B~ (MCB) 20 ResidualCunent Circuit Breaker(RCCB) 20 Testing the RCCB 20 20 Checkingfor Leaks 20 Chargingor Rechargingwidt Refrigerant 21 CAPABILITIES OF THE REFRIGERATION CYCLE DEMONSTRATION UNIT: 23 1. Demonsb'ation of die Vspour Com}Xession Cycle 24 2. The PressmeTemperatmeRelationship 27 3. Demonstrationof PumpingOver 30 4. Demonstrationof Charging 31 s. Demonsttationof Effect of Air in a RefrigelationSystem 32 6. Effect of EvaJX)rating and Condensing Temperatures on the Refrigeration Rate 3S 7. Effect of CompressorPressureRatio OIl SystemPerformance 39 8. Detenninationof Overall Heat TransferCoefficient 43 9. Generationof a RefrigerationCycle Diagram 47 10. Measurementof dIe Effect of ConoonsingTemperatureon Com~r Power Input 51 OBSERVAllON SHEET (Blank) 53 R141b SATURA nON PRESSURE v TEMPERATURE GRAPH 54 R141bP~SURE-ENTHALPY DIAGRAM ss R141b COSHH DATA S6 WIRING DIAGRAM. R633 58 WIRING DIAGRAM - 11O-130V Transformer 59 APPENDIX: A. Optional R633A Digital Temper:ature Indicator - Fitting B. Optional R633B Digital Wattmeter- Fitting Instructions Instructions 61 67 1 of-' .c :) "Qj ~ "II D ~ +- ~ 4) ... = 0) it 2 NORMAL OPERATION r SHUTDOWN 3 SYMBOLS AND UNITS Svrnool Pc Pressureof Refrigerantin Condenser kNm-2 P. Pressureof Refrigerantin Evaporator tNm-1 me Water Mass Row 1i1. Water MassF1owRate through Evaporator it Temperatureof Water enteringEvaporattl' oc ~ Tem~ oc 1, Temperatureof Water leaving Condenser ~ f,. Temperatureof Water enteringCondenser ~ ts Evaporating Tempel8t1n"e oc .. Temperaturein Condenser oc t, CompressorDischargeTemperature oc Is CondensedLiquid TemperabJre oc u Overall Heat TransferCoefficient W m-~K-1 Rate dU'OughCondenser of WaterleavingEvaporator Presentationof Numerical Data In dlis manual, numerical quantities obtained during experiments,etc., are expressedin a nondimensionalmanner. That is, me physical quantity involved hasbeendivided by me units in which it has beenmeasured. As an example: 10' pNm-1 . 150 This indicatesthat or p = 150 x 10' N m-2 alternatively p = ISOkN m°2. . Absolute pressure =Gauge reading + aunospheric pressure 4 INTRODUCTION Tbe Refriaeratk»D or Heat PumD Cycle: A refrigerator is defined as a m~hine w~ prime function is to remove heat from a low temperature region. Since energy cannot be deSU'OYed. die heat Iaken in at a low temperature plus any other eneJ'gy inJX1tm~t be dissipated to die SUn'()Undings.H the tempezabJreat which die heat is dissipated is high enough ro be useful, e.g. for SpIM:;e heating, the ~hine is then called a heat pump. By selectivedesignof the componentsthe cycle may be optimisedeidler for heat pump applications or for refrigeration applications. Indeed unckr certain applicationsboth useful functions may be performedby one machinewhere circumstancespenniL For example,in a dairy where refrigeration is requiredfor milk cooling and storageand hot water is requiredfor OOuIeor tank washing. The aausius Statementof the SecorKILaw of Thennodynamicsstatesthat heat will not passfrom a cold to a ootter region without the aid of an "externalagency". Thus. a refrigerator will require an "externalagency",i.e. an input of high gradeerergy, for it to operate. This energy input may be in me foon of w<X'k. cx a heat transferat a high temperature. The most C<XDmon type of refrigerator or heat pump ~ a WORK INPUT and operates00 die VAPOUR COMPRESSION CYa.E. t The Vapour Compression Cycle The work input to the Vapom CcmpressionCycle drives a compressorwhich maintainsa k>wpressure in an EVAPORATOR and a higher pressurein CONDENSER. The temperatW'eat which a liquid will ev8lX>rate (or a va[X)urwill coodense)is dependenton die pressure,thus if a suitablefluid is introducedit will evaporateat a low temperatm'e in the low pressure evapora1Or (taking in heat) and will condenseat a higher remperatW'e in die high pressurecondenser (rejectingheat). The high IXeSStD'e liquid fomted in the condenser must then be returned to the evaporator at a controlled rate. Thus. the simple vapour compressionrefrigerationcycle has four main components. (1) An evaporatorwhereheatis takenin at a low tempe1'ature as a liquid evaporatesat a low p-essure. (2) A compressorwhich usesa work input to redI.K:e the ~ure .. pressure of die vapourbeingtransferred to die condenser. in the evaporatorand increasethe (3) A cOIxienserwhere the high pressurevapourcondenses.rejecting heatto its surroundings. (4) A flow control device which controls die flow of liquid 00ck to die evaporatorand which brings about die pressurereduction. The refrigeratioocycle is most interestingfrom the thennodynamicview poinL It is one of the few ~tical plants which operateson a true thennodynamiccycle and involves (a) Nucleateboiling and filmwise condensation. (b) Steadyflow processes,i.e. dn'ottling,compressionand beatexchange. (c) Row conttOl. (d) The thermodynamicproperties,i.e. pressure,specifICvolume, temperature,specific enthalpy and specifICenttOpy,of a pure substanceat all conditionsbetweensub-cooledliquid and super-heated vapour. Ald\Oughthe vapourcompressioncycle is simple to thosewho are familiar widt it many studentsfind great difficulty in visualising and understandingdte eventsoccurring within the various components. 5 With dtis in mind P.A. Hilton Ltd., designeddie RefrigerationCycle DemoosuatiooUnit in which die major pan of the cycle takesp~ inside glasschambersand can dlereforebe observed. The unit is a valuable~hing aid for studentsin a widerangeof co~ trainingto first degreeat a Universityor PolyteClmic. from craft andteChnician 6 IN~ ALLA nON AND COMMISSIONING Removeme unit from its p.:king caseand carefully examineit for damage.If any is foulKi. notify tile insurersimmediately. Standthe unit on a table at a convenientheight aM cl~ adlain. to an elec1ricalsupply, a water supply and Do not standthe unit in a positionwhere it will be in strongdirect sunlight for long periods. This may result in high chamberpressureswith the subsequent lossof the refrigerant charge through the safetYvalves. (i) The tmit is fitted with two long life fluorescentlampswhich for shippingare ~ In orOOrto fit the lamps the rear panel of the m.:hine must be removed. separately. Ensuredlat die m&:hineIS NOT CONNEcrED 10 nIB MAINS ELEC1RICAL SUPPLY and removedie hexagooalbolts and one Dut secmingdie rear panel Note that die bolts are 8mm acrossflats and the COn'ectsize spanneris recommended. The lamp socketsare locatedinternally and are under die two vertical slots in ~ unit panel. Carefully remove me lamps from their packing ma1erialand imezt diem in me white plastic socketson the left hand and right hand sidesof me panel. SUR>Ort the socketsby handas tm lamps are inserted. While me rear panel is removed ensure mat die Residual C1DTCOt CiIcuit Breaker switch situated on DIN rail the right side of the panel is in die ON positioo. The unit will have been left in d1e ON position when shipped but transit vibration or shock loading can ~ the switched to jwnp to me OFF position. (0) Connectdie mainswater supply to die water inlet at the rear of die unit using the diagooainylon reinforcedhose. When facing the rear of the machine the water ~ ~ on the extreme left or thepanel. It ~ recommendedthat the water supply is red through an isolatingvalve that can be turned ofTwhenthe unit is not in use. In older to increasethe stability of the condenser water ftowmeter and evaporator water flowmeter the conttol valveson thesedevicesare fitted to the dischargeside of the flowmeter. Henceif externaldamageresultsin the flowmeter tubesbeing brokenan externalisolating valve will be req~ to stop the flow of water from the unit (ill) Connectdie remainingwater coupling at the rear of the panelto a suitabledrain using the dear plastic pipe provided. (iv) 220/240V Units Replacethe rear panel BEFORE connectingthe unit to the mains suWly. The power supply cable will be foWld emergingfrom die rear panel. Connectdie cable to a suitable fixed power supply via a fused outlet (for 5 Amps) which canplies with die ~ regulatioos. Brown cable LIVE or LINE Bloocable NEtn'RAL EARTHor groond GreenlY ellow cable Note that fcx safeoperationthe greenlY ellow cableshouldbe ~ted earthingpointthatcomplieswith thelocalregulations. to a low impedance 7 110/I20V Units The unit hasan internally fitted transformerwhich is suitablefor input voltagesof between110 and 130 Volts (110 to 130V in 5 volt steps). The integral SUWlyl~ must be coonected10d1e nearestsuitablevoltage tennina1sand mis can ooly be ~hieved by first removing tIx: rear panel from the unit. The transfonneris locatedon the right handside of the unit when looking at the rear of the machine. Before connection to dte transf<l'D1eJ',die l()Cal mean voltage between Line aOONeulI8l should be measured. by a competent person, widt a suitable meter. Until dte transfonner hu been connec~ internally as described below die sUWly leOOSHOULD NOT BE CONNECTED TO THE LOCAL ELECTRICAL SUPPLY. The BROWN cableof die supply 1eOO is conn~ted to the 130V tenninal of the transformerafter testingat the factrry. Once the local supply voltagehasbeenmeasureddIe brown cable should be removed fmn die 130V tem1ina1and should be conn~ted to the nearestlabelled voltage tCJmjnalon the tramfooner. S~ Figure 3 on Page9. The Blue cable is alreaIy coonectedto the OV terminal on me b'ansfonner. The Green/Yellowcable is connectedto die Eard1ternlinal on die ttansfc:lm~. The rear panel may now be repla::ed. The externalfree end of die supply Ie.t may now be coonectedto the local elecbical supply. Connect the cable 10 a suitable fixed power sUWly via a fused outlet (for 10 Amps) which complies with the local regulations. Brown cable Blue cable GreenlYellow cable UVECR'LINE NEU1RAL EARm CR'ground Note that for safe operation die GreenlYellow cable should be connectedto a low impedance earthingpoint that complies with the local regulations. (v) The standard instrumentation kit includes five OOCto SOOCthermometers aOOtwo -lOOC U>llOOC thennometers. One of the -100c to ll00C dtennometershould be inseJ'tedin the central thennometerJXx:ket located in the condensertop plate and the other in the compressordischargeJXx:ket~. The remaining dtermometersshould be insertedin dte evaporator~ plate JXx:ketand the four identical ev8lX>r8fOr and conde~ cooling water JXx:ke~at dte ends of the evapora~ and condensercoils. It is recommendedthat in order to imlXOvethe resolutionof the thennometersa few drops of light machineoil is OOded to ~h thennometerp<x:ket.This will help to improvethennaIcontact betweenthe thennometersarKIthe pockets. (vi) If theinSb'Umentation upgradehasbeen~ in AppendixA in this manual. at a laterdatethe fitting of the kit is detailed (viI) A ~oomatic diagram of the machine COIDJX)nentS is supplied 00 an A3 (4~m x 297mm approximately)sheetand a diagramshowing die valve positionsfor ~ration is suppliedon an A4 (297mm x 2O8mmapproximately)sheet. Two L shapedclearp~tic schematicholoorsaresuppliedto contain me diagramsand thesemay either be suspendedon a cord and hung on a wall adjacentto the unit CX'alternativelyclipped to the top of the uniL 8 If die djagramsare to be fitted to die panel then it will be ~-!!!-ry to die ~ of d1epanel. to fit me four clips suwlied Auach the 4 spring cli~ to the ~ of 1be.-nel using the 8 self-tapping~WS povided. Note that 8 small pre-drilled holesexist on the ~ of ~ panelto a:ceIXthe ~ws. The clips shouldbe fitted wid! the OPEN end king toward the fratt of die panel. The L shapedclear plastic schematicooldersare dIeDslid underthe spring clips. In order to utilise the plastk COV~for the unit the L shapedschemabcholdezsmay be removed and stored under the unit panel 9 1 2 4 3 Amendments 2 MAINS FL TER ADDED 10.9.97 JB A B c SlFPL y m -130Y SO/60Hz SEe HA" ~ The ~ier is req.jred to deliver goods strictly ~cordi-9 to drowing. Componentinspection is the suppliers responsibiity R8IIIDveoil sharp edges a~ burrs. Limits unless otherwise stated TITLE: 110 MTL: FIIIISH: - Fractions * 1/6" Decimals * 0.25 mm 130V TRANSFORMERWIRINGDlRGRAM aAGRAH F~ [Drawnby P. A. HL TON l TO JB [ IDimensions: mm Checked by: @Q Projection' Issue: 2 Date:4.3.96 DRG. No. Scale. KINGS SOMBORNEHAMPSHIRE TERttNAL KEY - no/rig. 1 ENGLAND I 633365 10 THE HD..TON REFRIGERAnON CYCLE DEMONSTRAnON UNrr USEFUL DATA Condenser: Wal« coil surf~ area: O.O32m3 E VSDOratOC Water coil surfacearea: 0.032012 Specific beatcapacity of Wafa'(c,>: 4.18 kJ tg"1 K-1 Refri~erant: R141b 1,1,-dicbloro-1- flooroetbane Quantity: approximately800 cm' (awroximately 1 kg) 11 SPECIFICADON Compreaor Hennetic type ~pressor with inlegrall/2 H<X'5eIX>wer mOtor drawing aPJX"Oxirnately810 Watts. The com~ is a single cylinder reciprocatingtype with a displacementof 17.4 cubic centimetres. Condenser Vertical, dlick walled high suengtb glass cylinder widt f1arM ends to give tension free connection to nickel plated brass end plates with P.T.F.E. seals. Cooling surface - 9 coils of 6.3 mm dia ~ b1be through which wala: fk>ws. fitted to Oppel'end plate. Cooling area 0.032 m2. Ball valve at the baseof d1ecoDdena' allows refrigerant charge to be contained within me condenser for demonstration PUllX>8eS. Evaporator Aoo(k';d type -constnx:tionsimilar to concknserbut widt COppt2'tube surface specially treated to promote nucleate boiling. Expansion Valve Float operatedneedlevalve fitted in condensert.se plate. Charging Valve Fitted to base of ev8{XXalor usedto intnxluce or di.:barge refrigeranL Sight Glass Fitted in pipe betweenexpansionvalve and evaporator- to show generation of vapourbubblesaftertheexpansion valve. Oil Return Capillary Combinedwith integralball valvesto allow oil to be simply reblrlltAito the compresscxin a conttoUedmanner. Instruments (StandardUnit) Pressure28U2eS - - Two Range -100 to +2S0 kN m"2 gauge. To indicateevaporatorand condenserpressures. ThermometerS-Seven Five, RangeO°C to 50°C x ISOmmlong, glass. Two, Range-10 to 110°Cx ISOmmlong, glass. Fitted in masspocketsto iJxIicatewater inlet and outlet tem~wres 81 condenserand at evapora1.«,evaJX>rabon tem~b1re, condensation temperatureand compressordischargetemperature. Row meters. Two Taperedglasstube type, widt stainlesssteel indicator float, ~h fitted widt a conb'Olvalve. Range 0 to 50 gramme S.I, To indicate and conttol water flow rate dtroUghevaporatorand condensercoils. ODtiOnal UD2T8de Instrumentation: (Not suppUed unless specifically ordered) Temperature Indicator A multi way digital temperature indicaUX' fitted widt 8 stainless steel sheathed type K thennocouples to replaw.:e the 7 standard dJermometers and to measure in addition the condensed liquid temperature at station is (see ~hematic diagram). The digital temperablre indicator repI.:es the blanking plate in dte centre of the standard lIInel and may ~y be fitted by the customer or if purchased with dte standard unit can be a factory fitted option. Wattmeter A digilal wa1Uneterdesigned 10 iOOicatcme true IX>werconsumption of me compressor. The watbneter rep~es me blanking plate in me centre 12 of die StaDdaIdpanel and may easily be fined by the CUSfDm~.or if purchased widt the standard unit can be a f~tory fitted 0IKia1. SAFETY No moving parts. Intemally mounted relief val~ ~t to 2SOkN m"2 gauge fitted to cOIxIen= aOOevaporator. High ~ure cut out fitted to stop compress<rif condenserpessme exceOOs 220 kN m"2gauge. Main switch is a combineddouble pole Ininjat1Jre~t breakerand overl<>lMi cut out 3OmAimbalanceResidualCurrent Circuit Breakerfitted. ~ Consauctedfrom GR.P. - attractivemoonstooewipe clean finish. DIMENSIONS Height Width Depth Weight 7romm 7romm 43(knm ro kg 22OVunits (+lOtg for 110V units) CAUTION This wnt ~ ~n specifically designedto opeJ'ateat low pressure00 R141band no other refrigerant shouldbe chargedinto die systemas damageto the comples.D'<X'oda: ~~ts will be die resulL 13 DESCRIYnON (pleaserefer to me schematicdiagramon Page 1) All COlDJX)nents are mounted 00 an attractive durable glass reinf<XCedplastic panel. The evaporatoris a v~ glasscylinder with pla1edmetal end plates. A helical coil of copperwbe conveyswater mrough a pool of refrigerant in the cylinder. The compressordraws vapour from the evaporatortherebyredocingpressurein the evaJXJrafnr and this causesthe refrigerant to boil at a low temperature. In order to boil, or changephasefroo1a liquid to a Vap)ur, heat is ~ and d1isis extractedfrom the water passingmrough the coppercoil and to a lesserextent from the surroundings. As heat bas been extta;ted froo1the water its temperabJre is reduced. The com~ is an hermetic type similar to those found in many domestic refrigemta'S. The com~or is inside the hermeticallysealedcasingand is directly coupledto an elecbic motor. VaJX)Urfrom die evaJX)rat(X'is drawn into me compressor casing and then into the CODJK'es8(X' itself where its Jl'essure is raised before being discharged to the condenser. Having had work done on me gas its tem~ is iocreased as well as its pressure. The cooden.a- is also a vertical gJasscylinder fitted with plated metal end plates, the upper one supportinga helical coil of tubethroughwhich cooling waterflows. The hot high pressurevapourfrom the COrDpreSSt)f cools and condensesas it ttansfersbeat to the cooling water inside the nickel plated c~ coil As beat is transfenedto the cooling water itS temperatureis increased. The cooled high pressureliquid collects in die tx>ttomof the con~nser and its level cootroIsa float operatedex~on valve. This valve reach~ an equilibrium position and discharg~ refrigerantliquid back to die ev8iX>ratorat die samerate as it is fonned. As the warm high pressureliquid passesthrough die valve seatingits presswe~ to that in die evaporatOrand its temperaturemust fall to the saturationtempemwreat the lower pressure. The fall of tempemnueis accompaniedby the f(X'Inationof vapour bubblesand thesemay be ~n througha sight glass fitted in the pipe returning the liquid/vapour mixnIre to the evalX>rator. On entering the evaJX)rat(X" the low pressureliquid aOOvaJX}urseparate.the liquid passinginto the "pool" for re-evaporation.while the vapour mixes with the vaJX}urproducedby the boiling ~tion of the water coil. The vapour mixture then returns to the compressorto repeatthe cycle. In the standardunit instrumentationis provided to measure: (i) The tem~rature and pressureof die refrigerant vapourin die evaporatorand condenser. (ii) The tem~rature of die water entering and leaving die coils in d1eevaporatorand condenser. (ill) The water flow rates throughbodi coils. (iv) The tem~rature of die oot gas leaving the canpessor. All temperaturesare measuredon die standardunit using red spirit dlennometers. An optional digital temperatW'e upgradekit is availablethat allows measurementof the temperatureof the condensedliquid te as well as the above list of temperatures. With the addition of this optional upgradedie completecycle diagrammay be plotted on an R141b pressure-enthalpy diagram. An isolating valve is fitted at the condenseroutlet and this may re cl~ed to ~onstrate a technique used in refrigeration maintenaocewhere the refrigerant charge is collected and contained in the conde~ or in most CMesa specialisedliquid receiveradjocentto the condenser. 14 This ~hnique is imJX)rtantin onk:r to demOOSb'ate how to pevcnt ~ escapeof refrig~t maintermnce. during In common with all refrigeration and heat pump systemsthe unit containsa small amountof oil for lutxication of ~ CaDpessa. During normaloperation~e oil. in die fOODof mist andoil/refrigerant ~Iution is carried from the compessor to the condenserand ultimately to die evap<J'atorwhere it collects. In order to return this oil to the com~ casingin a controlledmannera valve at the base of the evaporalorconnectsan oil return capillary to die suction side of the com~ via a ~nd valve. For ~rator safety the refrigerant used ~ a veIy low ~ for a given temperabue(V8IX>Uf pressureat 2OOCis 0.81 Bar amolute). In addition die unit is fitted with a pres8\D'e switch to nun off the C<XDpressa' if dIe condenser~ exceeds220 kN m-z. For IMided safety and to allow operation by students, both the coodcosecand eVaJ)(Xatorare fitted with relief valves mountedinside the instrumentpaneL In order to vent any air inUoducedinto d1esystemduring demonstrationa t.ll valve is sinJatedon d1e condensertop plate. This allows air to be ventedvia a pipe to the inside of d1epanel IS OPERATING PROCEDURE (please refer to Figure 1 - SchematicDiagram, and Figme 2 R633 Valve Positionsdiagram) - To assiStin unOOrstanding ~ration. item namesand relevant items on the two scoomaticdiagrams suppliedare refelTedto in bold type in the following sections.For example.Refrigerant Pump Down on Figure 2 and Condenseror Evaporator etc on Figure 1. The five baD valves shown on the two schematicdiagramshave beeninsIalled for ~ Figure 2 (Page2) diagramshowsthe four standardvalve combinations. ~ The vent valve on die condenseris namally only openedbriefly to vent air from the systemaId this is referred to elsewhere. Note mat when the mrlt is shut down the ball valves should AlL be in the closed positioo. This preven~ the refrigerantmigrating to the lowest temperaturepart of the systemdue to vapourpressure effects and in most ~s dtis would be the compressorcasing as this will respondmost rapidly to variations in ambienttemperature. Normal Ooeration To start the unit first turn on the cooling water supply and the mains supply to the unit Open the valves indicatedin Figme 2 (Page2) for Normal Operation. 11risallowsvapourto be<b'awn from dIeevaporatorby thecompr~r returnto theevaporator from thecondenser. andfor ~ liquid to Twn on the watersupply to the unit and adjust the control valveson the evaporator water nowmeter and condenser water nowmeter to give approximately20-30 gls flow rate. Turnon themainswitchandthecom~ will stanandthetWointemallampswill light If the optional temperature indicator is fitted then the display on this will also illuminate. Evaporation ~e&1 As dIe compressorruns dIe condenserpressurep. will rise and dIe evaporatorpressureP. will fall. If dIe water supply temperawreis high (aPJK'Oximately 16°Cor more) dIen the boiling oction shouldbe reOOilyvisible from sev~ points on the submergedeV8p(X'a1or coil. In order to promoteevalXJrabon from the coil surfacethe coil has been specially treatedto provide many bubble nucleationsites. If the water temperanue is low then the ev8lX>ratorpressure will need to reach a lower value and roiling may occur from single sites on the coil, from me surface of me liquid adjacent to the coiJ/surface interface or from the -.seplate of the evaporator. To indoce further evaporationfrom odler sites open the ball valve at the baseof the ev8lX>r8tOf.00 NOT open the charging valve as this will allow air to enter the system. Opening the ball valve at the baseof die evaporatCl'will causedie oil rewm capillary to becomepart of the evaporatorand the resulting large increasein heat transfer surface area relative to die small volwne of liquid in the capillary will result in vapour appearingfrom me baseof die chambec. This techniqueis also usedwhen completing refrigerant pump down. During normal opera&n oocenucleationhasbeenKtivaled from otha' sites within the chamberdlen the ball valve at the baseof the chambermay be closed. 16 Unlessdie supply water temperatureis high men altera1ionof ~ evaIJ<nIOrwater flow rate will have a relatively small eff~t on die ev8lXJrarDr pressme. Howeverif die evaporatorwater flow is twned off completelythen the evaporatorpressurewill reduce slowly until evaporation OCCID'S from some other ~ smfa::e using beat tI3Dsfmed from die sunuundings. CondensadoaProcess The vapouris dI3wn from the eVaJX)lata' into the compressorand both ilS pressureand temperatureare raised. The hot high pressurepassesdtroughthe insuJatedpipe to the condenser. The temperanueof the p leaving the com~ may be measuredby d1ethermometerin pocket tr. Note mat if the COOlpreSoD' is run for long periods widl die coodenserJX'essutehigh then the temperaturehere can reach SOOC. As die gaspassesthrough the insulatedpipe therewill be someheat loss and after an initial warming up period of operatioo this will result in the gas being partially de-supethcated before it enters the co~. In fa:t just after starting,whenthe unit is cold. the gasenteringthe condenserchambermay evenbe partially condensedand dropletsof liquid, will be seendrippingfrom the top plate. The gas entering the condemer under n<X'D1al opezatioowill be in a superheatedcondition and wiD initially desuperbeatand then condenseon the water cooled coils. Adjusunent of thecontrol valveon thecondenser water nowmeterwill allowthecondc~ ~ to be iocreased or decreased. To increase the condenser pressure reduce the cooling water now rate. To reduce the condenserpressure increasethe cooling water now rate. The condenserpressurewill also be effectedby the inlet temperawreof the cooling water. F<X'the samewater flow rate the condenserpressurewill be lower if the inlet cooling water temperawreis lower. The inlet water temperaturewill thereforelimit the minimwn ~hievable coodenserpressure. As me liquid ex~ds through the float controlledvalve at the baseof the condensersomeevalJ<Xation of the liquid beginsto occur immediatelydownsueamof d1evalve. The valve is physically ~hed to the 00seplate of the condenserand dIereforesome of the heat requiIedto bring aboutthis phasechangeis ex~ted from die liquid at dIe baseof die condenser.This has the effect of sulx:oolingdie liquid below the saturationtemperatureassociatedwith the measured pressureshown on the condenserpressure gauge. If the optional temperature indicator is fitted then an additional thennocoupleIs is supplied to be fitted in the baseof the condenserchamber.Heocethe subcooledliquid temperawremay be measured and this togetherwith the otrer measuredtemperablreS and p-essuresallows a completerefrigeration cycle diagramto be plotted on the pressure-eothalpy diagram ~lied. The experimentalJl'()CeduIesdelailed elsewhereinvolve operation of the various 00ll valves and variationof the condenserpressurein or~r to achievevariousoperatingconditions. Thesepl{x:edures are detailedin the individual experimentalprocedures. SbuttineDown the Unit In order to shut down the unit it is recommenOOd d1a1if die refrigerantchargehasbeenpumpeddown (transferredto die condenserchamber)then the valve at die baseof the condenseris openedand the systemallowed to return to a normal rwming condition before the m~hine is fmally shut down. 17 Normal running condition is widl aPJK'Oximately 2o-25mmof liquid in the bottom of the condenser chamberand dle float valve maintainingthis level constanL Oncenormal operatingconditionshavebeen~hieved menme main switch shouldbe turnedoff. The compressorwill stop and me lights on the unit will be extinguished. If the optional temperature indicator has been fitted the display on this too will be extinguished. Turn off die cooling water suWly to die unit It is recommendeddlat die (water) control valves are left open so that if die usersuppliedexternalisolating valve leakswater will be allowed to run to drain and will be noticed more readily. In addition, if conditionsare suchthat the water supply is likely to freeze dlen leaving die control valves on the flowmeterSopenmay not prevent die glasstubesbeing broken but it will makebreakageless likely. Oncethe unit b$ beenturnedoff then me ball valveson me unit shouldbe closedto mimic me shutdowncondition. SeeFigure2 (page2). This will prevent the large volume of refrigerant containedin the evaporcUormigrating into the compressorcasingdue to vapourpressurechanges.The small volume of liquid in the condensermay migrate to the compressorunder certain ambientconditionsbut this is no causefor concern. Refri2erant Pumo Down This is a procedureoften usedin industrial and commercialrefrigerationpractisewheredie refrigerant chargeis condensedand collectedeidier in the condenseritself or more commonly in a liquid receiver. In die RefrigerationCycle DemonstrationUnit R633 die condenserand liquid receiver are combined in die sameglasscylinder. In order to carry out pumpingdown dte unit shouldhavebeenoperatingnormally f<X"severalminutes widt an evaporatorand condensercooling water flow rate of approximately40 gS.l. By settingthe valvesas shownin me Refrigerant Pump Down diagramin Figure 2 (Page2) me flow of condensedliquid from the base of me condenseris stoppedand liquid will thereforecontinueto collect in the condenserchamber. As liquid b'ansfersfrom the evaporatorthe level will fall and less of the evaporatorcoil surf~e will be effective in evaporatingthe liquid. The evaporationrate will reduceand the processwill become slower. This effect may be offset as the liquid level becomesvery low by opening ONLy the ball valve at the baseof the evaporator. This will havethe effect of utilising the capiljary surfaceareaand ambientair temperatureto evaporate additional liquid. If before pumping down the unit hasbeenoperatedfor a prolongedperiod. the liquid collectedat the base of the evaporatOrmay appearthicker and less viscous. It may also appearslightly yellow in colour. The liquid remaining in the evaporatOris primarily the oil d1athas been carried over in the fOmt of mist and refrigerantoil mixwre from the compressor. The oil will not evaporate at me pressures ~bieved by me compressor and thereforeit mustbe physicallyreturnedto mecompressor casing. Note that me unit should ~ SHUT DOWN when me refrigerant charge is in the PUMP DOWN condition as under certain ambient conditions it is possible for the charge to migrate to the compressor casing. Oil Return (Only when in Pumped Down Condition) Once the unit has been pumped down as described aoove, the oil may be returned to the compressor by setting the ball valves to the positions as shown for Oil Return in Figure 2 (page 2). The condenser 18 cooling water aM evaJX)ratorwater flow rates are left as for normal nD1ningand me unit remaim switched00. The only pam from me evapa-atorto the compressoris via the capillary tube. The oil in the baseof the evaporatorwill start to flow mrough the capillary blK:t to the com~ casing. The evaporator chamber may be at low JXeSSureand therefore the oil return process will be slow due to the low differential pressure. This may be increased and the ~ speeded up if a small amount of refrigerant liquid is OOmittedto the evalXJ[ator by briefly opening the ball valve at the base of the condenser. However DO NOT leave this valve open. Once the oil has beenreturnedto die CODlpresD'casingd1endie ball valves may be ~ position for normal operation as shown in Figm'e2 (page2). to dx:; Once die operating coOOiuons have rewrned to noonal and the liquid level in the conde~ is apJX'Oximately2O-2Smm tOOntOOunit may be eithez shut oown as described ai)Ove or adjusted for further experiment. Air Ventin2 A vent valve is siwatedon dle top of the con<knseraIK1this allows air that bas beenadmittedto the systemto be safely ventedinto the void inside the insb'Umentpanel Air d1atenters me system usually from the charging valve as part of an experiment will be swept into the com~ by d1eflow of vapoor from me evaporator and from here to the coodenser where it will collect around the condenser coils. The air will remain in this area and effectively present an insulating barrier to vapour ttamfer. condensation and hence heat transfer. The nett result will be a chamber pressure that is far greater than should be the case for the condensing temperature ~ indicated. Unl~ demonstratingd1eeffects of air in a coodenserit will be necessaryto vent the air from die system. The oil utilised in die compresSa'is hygroscopicand air admittedto die systemis likely to bring widt it water vapour. This should thereforebe ventedfrom die system. To vent air from the condenser it is necessary 10increase the condenser pressure 10app-oximately 50kN m-1aboveabnospheric pressure. With the unit nmning n<X'Dlally, cl~ diecontrol valveon thecondenserwater nowmeter.Thiswill cause die condenser pressure to rise. The time taken to rea;h 5c:k.Nm-1above abnospheric pressure will depend upon die local ambient temperature and the amount of time that the unit has been running. Once 5OkNm-1is reachedthe vent valve should be ~ ~ned and gas will be heardto enter the void inside the panel. Close the valve well before the gaugepressurereaches0 kN m-1. 19 MAINTENANCE Hi2b Pressure Cut Out At regular intervals and accordingto the local safety regulationsthe high pressurecut out shouldbe testedas follows: Start dte unit as detailed for normal operation in the operating procedure 00 Page 15 and operatewidt a modezatecooling water flow to both dte condenserand evaporaroras detailed. Allow die unit to warm up and then cl~ the control valve on the condenserwater nowmeter. This will causethe condenserpressureto rise. At approximately22OkN m"1the compressc.' shouldbe shutdown by the internal high pressurecut out An audibleclick shouldbe heardfrom the cut out device. If the compressordoesnot turn off automaticallyat a oressureof 230kN molthen turn off the unit at the main switch. It will then be necessaryto adjust the pressure switch as detailed below. If the compress<rdoes turn off automatically,~n me control valve on the condenserwater nowmeter and me condenserpressurewill immediatelyreduce. Once me pressurereducesto app-oximatelyInN m4 the C<XDpre8s(x' should automa1ical1y restan. Adiusunentof Hiv.h PressureCut out The following J:roCedure should only be carried out by a competentpersonand the compressorhigh pressurecut out must never be set to operate at a pres.ure exceeding220kN m-l (or any reason. Isolate d1e unit from die mains and remove the rear panel. The high JX'CSSuIe cut out is located above the compressor casing on the internal panel surf~e. The cut out is connected by a coiled copper capillary tube to the condenser p~ure gauge. The cut out hastwo adjustingscrewson its top surfacewhich may be coveredby a plastic cap secured by a single screw. Removethe plastic top cover and to adjustthe cut out pressureturn the screwwith the larger range. The cut out devicesare commercialdevicesand the pressureindicatedon the scale may not matchthe cut out pressureindicatedby the pressuregaugewhich is of much higheraccmacy. Only b1rnthe screw a small incrementat a time and then retest in order to obtain an estimateof its effect. By dlis methodthe cut out pressuremay be ~t to 22OkNm-2. The smaller range scale usually labelled "DIFF" indicates tOOdifference between me cut out and restart pressures. This should usually be set at aPIl"Oximately l2OkN m-z in order to ensure that me starting l()1ki on me com~ is minimised After adjustmentthe ~ cov« should be replaced. Tbermometers Due to the relatively small temperature differences between water inlet and outlet temperabJreS.it is advisable to calIbrate the thermOOleten by pla:ing diem all in a container of watel'. All of ~ dtennometersshould be marked in S<XDe way for identifICationand one ~1eCtedas dte re.ference.Alternatively, if a known standardis availabledtis should be used. Stir the water for aIx>I1t2 minutes and record the indicated temperanlres on each of the thennometeJ'S. This should give a table of small differences from the "reference" thennometer. 20 Th~ differencesmay be added(B'subtlaCtedfrom dJe~ as awropriare. If greater~uracy is requiredmenthe watermay be gently warmedandmediff~nces notedat ~vera1 temperatures. In d1is case a graph of indk-lt~ against difference should be plotted for ~h th~omeleJ' . H the optional temperature indkator hasbeenfitted then d1eaOOve differa1<:ecalitntion will not be necessaryas all dJermocouples are switchedin turn through to the sameiOOicatoruniL Miniature Cb-cuit Breaker (MCB) The Main Switch on ~ front of the ~el is an MCB and will cut-out in the event of an ov~ICMld causedby a shoo circuit 01'a shortto earth. If this shouldcut-out.the unit shouldbe discoonectedfrtxn the supply and the causeof the overloadinvestigatedby a com~tent ~rson. Residual Current Circuit Breaker (RCCB) This is situatedinsidethe paneland will isolatethe unit whenthe incomingandoutgoingcurrentsdiffer by more than 3OmA,as in a leakageto earth situation. Testin2 the RCCB The RCCB shouldbe testedby a competentpersonat intervalsthat comply with the local regulations. Remove the rear panel and switCh on the mUL The RCCB will be found on the right hand side of the unit WOOD looting into the rear of the unit Pressdie button malked 'Test' or 'T' on die RCCB, but 00 NOT TOUCH ANYTfnNG ELSE INSmE THE UNIT. The largelever on the RCCB shouldh1IDfrOO1d1eON ('r) to OFF ('0') position immediatelyand me unit isolatedfrom die supply. If dris ck>es not OCCm', die RCCB is faulty and~ to be repaired/repla:edby a qualified electrician. Return die lever to die ON ('I') ~ition and the unit should be switchedon again Repia::e the rear panel. ~ This may be cleaned with a mild detergent and then JX}llshedwith a soft clodt. Abrasive cleaners must not be used. The pJasticdust cover provided shouJdbe kept in }X>sitionwhen the unit is not in use Cbeckinl for Leaks If a leak in the refrigerant circuit is suspected. e.g. if d1ereis a loss of refrigerant from the system, me following procedlD'e should be adopted: (A) If tOOreis refri9.erantin the system: ~e die unit in a WanDplaceuntil its temperaturerea:hes32-3SoC.The pressurethrooghoutdie systemwill now be aboveabnosphericaJKIdie leak may be loca1edei~ by (i) Applying a Sb'Ongsmp or detergentsolution to all joints, (ill Using an electronicleak detector. (B) If there is no refrl2erantin the System: Pressuriseme systemto SOkN m""wim air by applying a manualpump.e.g. motOrcar tyre ~p. to me charging valve at me baseof the evaporator. The leak may then be locatedas in A. 21 Cbarg2 or Recharge Under nonnal conditions me vapour press\U'eof die refrigerant does not reach abnospheric pressure Wltil die liquid is at a temperatme of approximately 32°C. In order. merefore.to make charging me unit simpler. the one bip can supplied by P.A. Hilton LId containsa small amolDltof Niuogen gas in order to raise me internal press\D'eartificially. Before chargingit is recommendedthat me unit is set up in me following way: Start die unit as detailed for normal operation in die operating procedure on Page 15 and operate widl a moderatecooling water flow to bodl die condenserand evaporatoras detailed. Allow the evaporatorpress1D'e to reduceand then position the ball valvesfor shutdown condition (see Figure 2 - Page2) and bJrn off the compressor. Note that if the unit is not chargedand containsair then it may be necessaryto vent this from the condenservia the vent valve on the condensertop plate. The unit is now~y for charging. The chargecan only be releasedfrom the can by using the brasschargingvalve (VCl7/2) suppliedin the accessaieskiL Unscrewdie small brasshexagonalnut from die chargingvalve and screwdiis onto die dtreadon die top of the can. Screw die rest of the charging valve (VC27fl.) into the straight connector on die refrigerant chargingline (C45/2), also suppliedin die accessorieskit Removethe brasscap from the fixed charging valve at the baseof the evaporatoron the R633 uniL Note that the angled end of the refrigerantchargingline hasa b~ pin in the.centreof the connector. This end should be connectedto the fixed charging valve on the baseof the evaporatOr.When d1e connectoris screwedtight the pin depressesthe centreof the fixed charging valve and allows access to the evaporator. The can should be inverted and me two componentsof the brasscharging valve should be screwed togetherby rotating me can. SeeFigure 4, Page22. When the componentsof the chargingvalve are screwedtogemerme refrigerantwill flow into me chargingline dueto me nittOgenpressurein d1ecan. Open me ball valve at me baseof me evaJX>rator and me refrigerantwill flow into the evaporator. Switchon die writ and d1iswill againreducedie evaporatorpressureand assistdie flow of die refrigerant into die evaJX)rator. When the liquid level in the evaporatOris abovethe level of the tOpcoil close the ball valve at the base of the evaporatOr. Allow die unit to run under nonna! operatingconditions until die liquid level in die condenserhas stabilised. Ensurethe liquid level is still abovedie top coil of die evapomtol. If this is not die case then open the ball valve at die 00seof die evaporatorbriefly until d1erequired level is ~hieved. Unscrewthe charging line from the can and this will close the valve in the can. The ball valve at die baseof the evaporatorcan be briefly openedto draw in any liquid remaining in die chargingline. The chargingprocedureis likely to result in someair enteringthe system. To removethe air follow the procedurefor Air Venting describedon Page 18. 22 0,. Tr~Can RMX74/1 - Figure 4 rn Bras.C~gi'1g Valva VC27/2 B Refrigerant Charging Line CI.5/2 IN c~~ Valw With Centre Pin Angled Comector With Central Pn 23 CAPABILmESOF THE REFRIGERATION CYCLE DEMONSTRATION UNIT Demonstration of vaJX)m'compressioo refrigeration or heat pump cycle widt visual observation of the important ~. 2. Investigation/demonstmtion of d1esaturation pressure-temperature relationship during evapoIation and con~nsation. 3. Demonstration of "plDlping over" or "pumping down" into the condenser. 4. Demonstrationof charging. 5. Demonstrationof effect of air in a refrigeration system. 6. Detenninationof effect of evaporatingand condensingtemperamreson me refrigeration rate and condenserheat output 7. Investigationof die effect of compressorpressureratio on systemperfonnance. 8. Deterntinationof overall heattransferbetweenR141band water in the evaporatorand condenser. With the addition of the optional temperature indicator:- 9. Generationof a refrigerationcycle diagram on a pressure-enthalpy chart. With the addition of the optionalwattmeter:10. Measurementof me eff~t of condensingtemperatureon compressorpower input. 24 1. DEMONSTRA nON OF VAPOUR COMPRESSION REFRIGERA nON OR REA T PUMP CYCLE The ex~cnt shouldbegin wid! the unit at rest.havingbeenleft in die shutdown (SeeFigure2, Page 2) condition for sometime in order for all of the compo~nu to be at a similar ambienttempelabD'e. Open the ball valveson the cylinders as for normal operation (SeeFigure 2, Page2) but do oot bIrD on die unit and do not bIrD on die water supply to the evaporatorand condensercoils. The stu<kntsshouldnOtCthat all of die systemremperaUJreS and pressmesare "awroximately similar" (assumingmat d!e unit has DOtbeen left standingin mght swilight and that d!ere is liquid visible in bod! the conde~ and evaporator). Turnon theunit andwatersuppliesasootailedfor norrna1 ~on 00 Page15. (i) Note mat as the com~ draws vapour from me evaporaror the ~ in me evapora1m'faDs. Similarly as the V8lX>uris compressed by the comiX'CSD' and Imssedto me COIKJen=-die ~ in me condenser rises. (ii) As the pressurein the evaporaUX' falls the liquid will begin to boil due to the reducOO pressure. The boiling actim is the refrigerantchangingfrom its liquid phasethrough to a V81X>1D" ~. Referenceshouldbe madeto the PressureEnthalpydiagramon Page55 or the largee~uJaIed diagram(C57/10) suppliedin the accessorieskit In order to changephaseat constantlX'e8Sure, energyis required to increasethe endlalpy of me vaJX>ur.This energy is takenfrom the water passingthroughthe evaP<X8fOr coil and. depending uJX>n the water inlet tem~rature and the local ambienttem~rabJre,the surroW1ding atmospbete. If the water supply temperatureis high (awroximately 16OCor m<Xe)dlen the roiling ~tion should be reOOilyvisible from severalpoin~ on the submergedevaporatorcoil. In order to promoteev8IXJrationfrom the coil surf~e the coil bas been specially treatedto provide many bubble nucleationsites. If the water temperawreis low then the evaporatorpressurewill needto reacha lower va1~ and boiling may occur from single sites on the coil, from die surf~ of the liquid adjacentto die coil/surfaceinterfaceor from the baseplateof die evaporator. To indoce funher evaporationfrom other sitesopen the ball valve at the 00seof the evapcntDr. DO NOT open the charging valve as this will allow air to enter the system. Openingthe ball valve at the baseof the evaJX)rator will causethe oil rewm capillary to become part of die evaporatorand the resulting large iocreasein heatttansfersurfacearearelative to die small volume of liquid in the capillary will result in vapour ~g from the base of die chamber. If the capillary bJbeis touchedunder theseoperatingconditionsthen the smfacewill feel cold. WOOnthe v8lK>urbubbles are being prodtx;edfrom me evaporaUX'coil within the evaporator chamberthen heat is being exb'Xted from me cooling water flowing through the coil. If the evaporatorinlet water tempelabJretl is examinedafter several minutes operation and this is comparedwith the water dischargetemperature~ the dischargetemperatm'eshould be fouOOto be slighdy lower than the inlet tem~. In <X'derto increasethe apparent temperabJre difference,the evaporatorwater flow rate may be reduced. If die evaporatOr cooling water flow rare is ~ completely then it is likely that roiling from die water coil will stop and die evaporator pressW'Cwill reduce ftn'ther until anothez soun:e of heat is found. This is most likely to be the base plate as heat is conducroo from the outside air. In 25 addition, dependingupon me local ambient conditions,water vapour will also condenseon die outside surfaceof me glasscylinder and baseplate. The changein phaseof me water vapourto a liquid will in itself IX'Oviooheat to causeevaporationof die refrigerant in me chamber. In addition, if the evaporatorcooling water flow is stoppedthen the rate of condensationfonning on the condensercoils will also reducedue to me reducedvapourgenerationrate in the evaporataand me reducedvolumettic efficiency of the compressorand increasein specific volume of me vapour generatedin the evaporatorchamberat low pressure. (ill) With the evaporatorand condenserwater again flowing as describedin the normal operation conditions on Page 15 the condenserpressureshouldbe observed. The condenserpressmewill be seento be higher than that of the evaporator. This is obviously due to the compressor. The ratio of condenserpressureto evaporatorpressure.PJP.. is known as the compressorPressureRatio. This will vary ID1derdifferent operating conditions and may be investigated. After the W1ithas been nmning for several minutes under nonna! conditions the condenser cooling water inlet temperabD'eand the discharge temperawre should be compared. It will be found that the dischargetemperature1, is greaterthan the inlet temperaturer.. This is due to the heat given up by the hot high pressuregas entering the condenserfrom die compress<X". Dependingupon operatingconditioosand die length of time the unit hasbeenoperating,the gas enteringthecondensermay be in a superheated condition. (Referto the pressureenthalpydiagram on Page55 m'the encapsulateddiagram (C57/10)suppliedin the accessorieskit). If in the superheated condition, initially the gaswill desuperheat and its temperaturewill reachthe saturation temperaturecorrespondingto the chamberpressme. At this point the vapour will condenseonto the water cooled coil and this will drip down to the baseof the chamber. It is die cooling and condensingphasechangethat suppliesthe heat to raise the cooling water temperature. If the chamberis at a temperatlD'e abovethat of the swroundingatmospherethen an unquantified amountof heatwill be given up to the atmosphere.Howeverthis should be small relative to the heat given to the cooling water. (iv) If the condensercooling water flow rate is reducedthen the condenserpressurewill rise rapidly relative to the time taken for the evaporatorpressureto reducewhen the evaporatorwater supply was tlD'nedoff. It will also be noted mat the meantemperatureof the vapour in the condenser~ will also rise. If the temperarurepocketprotruding into the chamberis condensingvapour men the temperawre recordedat this point should correspondto the saturationtemperatmeof the refrigenmt at me indicatedpressure.Note d1atthe indicatedpressureis gaugepressure and the pressuresreferred to on thepressure..enthalpy diagramsareabsolutepressures. In order to allow the dtermometerpocket and thennometerto reacha representativetemperattlre it will be necessaryto hold the pressureconstantfor a brief period after eachrise in condenser pressure. (v) The high pressureliquid leavesthe condenserthrough the expansion valve which is conb'Olled by a simple float at the baseof the condenser. 26 As soonas the liquid passesthroughthe expansionvalve iU pressuredropsto awroximately the pressIU'e inside the eV8lXX8fOr.This ~ me liquid to immediaIelystart to changephasefrom liquid to V81XXJr.As in the evaporatm'cragy is requiredto bring about me phasechangeand someof this is taken from the baseplate of the condensera the expansionvalve is ~hcd to the hue plate. ExtrlK:tingbeatfrom me baseplateredIx:esits te~ and this in bIrDreducesthe tem~nue of the condenserliquid at me baseof the condenser.This resultsin ~ liquid being "sub cooled" below its satUIationtempelatm'e. If the optional temperature indicator is fitled ~ an IKiditional thennocouple r. is supplied to be fitled in the base of the colxleDSQ"chamber. Hence the sub cooled liquid tem~ may be measured and this together with the other measured remperattlreSand pressures allows a complete refrigeration cycle diagram to be plotted on the pfeSSW'C-enthalpydiagram supplied. In the condensertrerefore the refrigerantchangesfrom superheatedvapouron entry. through to sanuatedvapourthen to sabJratedliquid and ultimately to sub cooJedliquid before it leavesthe condenserchamber. As ~ refrigezant~ along the pipe leaiing from the exlBn8ioovalve to the eValJ(Xator beat will be exb'.:ted from the SUn'Oundings and ~ liquid will be further convertedto a v8fX)Ur.The si,ht ,- just beforeenb'yto theevaporator allowstheliquid/vaJX)ur mixtureto be ~ed. 27 2.. PRESSURE TEMPERATURE RELATIONSHIP The relationshipbetweensanuationpressureand temperaturemay be observedin both me evaporator and condenser. However as variation in the evaporatingtemperat1D'e is small for aU but extreme changesin cooling water flow me condenserIX"Ovides a moregraphicillustration. As the conoonser contains refrigeJ'ant in all stages from superheatedvapour through to sub cooled liquid the dlermometer pocket ~ only records temperatures close to saturation when die pocket is showing signs of condensed liquid Therefore it is recommended that die pressure temperature relationship in the condenser is investigated as the condenser pressure increases. If the pressuretempemturerelationshipis investigatedby reducing the condenserpressurethen the ft thennometerpocket will be at a tempenuurethat is higher than the surroundingvapour due to its thermalinertia. Thereforeno vapour will condenseon the pocketand an inCOIreCt temperaturewill be measured. Note that dJepressures referred to on dJepressure-enthalpy chart and on the p-essure-temperaturechart on Page 29 are "absolute" values. Absolute pressure = Pressure gauge value + Local abnospheric pressure Procedure: (i) Start the unit for normal operation as shown on Page 15 but iocrease the condenser cooling water flow to the flowmeter maximum (50 g S.l). The pressure at which the condenser stabilises will depend upon the water inlet temperawre. (ii) Allow die unit to run for approximately IS minutes in order to reach a uniform operating temperature. Then record die condenserpressmePc, evaporatorpressurePe' die condensing temperature~ and die evaporatingtemperaturer,. (ill) ReducedIe cooling water flow by a small incrementso that dIe condenserpressureincreaseby approximately10-2CBcN m-z. This amountwill vary depending upon dIe coolingwaterinlet temperature. Allow the unit to stabilisefor a few minutesand againrecord the aboveparameters. (iv) Re~ the procedureup to the maximumcondenserJX'eSSure requiredor to the high pressurecut out value of 22OkNm4 Typical resultsare shown in the table below. Local Aunospheric~: lOlkN mol Condenser Pressure Pc I kN m-1 gauge CondenserPressure Pc I kN m-1-absolute Condensing temperature E vaporatol' Pressure E vaporata Pressure Evaporating temperature ../~ P.I kN m°7. gauge PG I kN m4 absolute .,/OC -41 -31 -21 -11 +4 +49 ~ 70 80 90 105 150 15.0 19.5 24.0 27.0 31.0 41.0 -68 -69 -69 -69 -69 -69 33 32 32 32 32 32 6.S 4.0 4~ 4.0 4.0 4.0 28 Note that tem~ have been estimatedto d1enearestO.soC~ing die SIaOOard 1benDOIDC1m SUWIied. Whezcthe opdoul temperature indicator is fitted ~~ may be ~ to d1e nearestO.loC. The resultsare ploUCdin graphicalfonn on Page29. Note that the standardJD'eSSUIe gauge~y of tl % of gaugefull ..::a)ehasbeat shown as 00Ued lines abouta mean. The absolute.:curacy of the dlermometers(m-~(XIa} tem~ iDd-k.J1O!' and thmnocouples)plus readingerrorswill also .sd to any disc~ies. 8 (f) . ~ 0 0 N 1 ffit r~ ~ N _f3 III .1.~ ~ ~ ~ 0 0 .l.,~T ~ UO!:J8.1D.:J8S 0 Ll) t_W N}( I a.lDssa.ld f5 0 0 to.. g ~ 0 ~ tV) a 0 N 0 ~ 0 29 30 3. DEMONSTRAnON OF "PUMPING OVER" OR "PUMPING DOWN" INTO mE CONDENSER Duringmaintenance of refrigemOOopJaob.partkularly when repl-=ementof com~nb is involved. it is convenient to transf~ the ~gerant to me conck.nser.This ba the ~vantage of saving me refrigerantfor f1D1heruse and also may avoid the needof ev~ua1ionprior to rechargink. In addition.for ecologicalreasons followingme guidelinesof d1eMontreal~l. refrigerantis in manycountriesoowa criminaloffence. ~ ventingof This is a proc.edureoften used in indusbial and commercialrefrigeration~tise where the entire refrigerant charge is condensedand collected either in die corKlenseritself or more commooiy in a liquid receiverco~ted to the condenser.Once the chargebas beenplrDped into the condenseror liquid receiverthenwork may be carriedout on the systemwidiout losinglargequantitiesof refrigerant to atmosphere.For ecological~ following die guidelinesof die Montteal Protorol, the venting of refrigerantis in many countriesnow a criminal offence. In the RefrigerationCycle Demonsb'81ion Unit R633 d1ecoOOe~ and liquid receiver are combined in d1esameglass cylinder. In order to carry out pumpingdown, dIe unit should havebeenoperatingnormally for ~veral minutes widt an evaporatorand condensercooling water flow rate of approximately40 gS.I. By setting me ball valves as shown in me Refrigerant Pump Down mode (~ flow of condensedliquid from the expansionvalveat the ~ will thereforecontinue to colle(:t in me condenserchamber. Fig1De 2 of the conoonSel: is ~ - Page2), me and liquid As liquid ttansfecsfrom the evapcnror, the level will fall and lessof the evaporaur coil surf~ will be effective in evaporalingthe liquid. The evaporatioorate will reduceand die processwill become slower. This effect may be offset as the liquid level becomesvery low by opening(ONLY) the baD valve at the baseof the evaporaU>r. This will have the effect of utilising die capillary surface area and ambient air temperawre to eVa(X)rate additiona1liquid. If, beforepumping down, the unit basbeenoperatedfor a prolmged period, die liquid collectedat d1e baseof the evaporaUX'may appearthicker and less viscoos. It may also appearslightly yellow in colour. The liquid remaining in die eva!X)ratoris primarily the oil d1athas been carried over in die form of mist and refrigerantoil mixture from the com~. The oil will not evaporateat die pessures .:hieved by d1ecanpressor and tOOreforeit must be physically rewmed to die compressorcasing. Note that the unit should ~ SHUT DOWN when the refrigerant charge is in the PUMP DOWN condition as under certain ambient conditions it is possible for die charge to migrate to the compreS&:Jr casing. ~: In an industrial plant, isolating valves are usually fitted between all major components. As ~ as the refrigerant has been b'ansferred to the condenser (or liquid receiver) the valves may be closed. trapping the liquid. The defective comlX>nentcan dIeDbe serviced or repJ.lK:edwid¥>Ut losing the refrigerant charge. At me end of the demonsb'8tionthe opportunitymay be takento reblrn the oil collectedin the baseof me evaporatorto die condenser.The procedurefor this is given underOil Return on Page 17. However,if oil is not to be returnedto the compressorat this stage,~ mIl valves should be set for normal operation (SeeFigwe 2, Page2) and me refrigerantallowed to rewrn to the evaporator. 31 4. DEMONSTRATION OF CHARGING Due to die restrictionsof die Montreal Protocol it is not recommendedd1atthe refrigerant chargeis removed from the machinefor any ~n other than essentialrepair. If chargeremoval is necessaryd1enrechargingmay be "demonstrated"if convenientto 00 so. Chargingfrom a Hilton suppliedone nip can should follow the Chargingor RechargingjX'OCedure on Page21. Note that any refrigerantremovedfrom the machineshouldbe storedin a screw topped metal can to preventevaporationand to stop moistme being absorbedby the oil in solution. Any refrigerantstoredin sucha can may be drawn ~k into the evaporatorby connectingthe charging line to the charging valve in a similar way to the standardchargingprocedurebut then immersingthe open end in the liquid inside the container. If the unit is turned on for normal operation then the pressuredrop in the evaporatorwill causethe refrigerant to flow into the evaporator. Note that air is likely to needventing from the condenser. 32 s. DEMONSTRA nON OF mE EFFECT OF AIR IN A REFRIGERA nON SYSTEM When air is presentin a refrig~oo plant. it will O(X'Inallybe sweptfrom the evaporata by me flow of refrigerant vapourand will becomettappedin the con(k;D.W'. For a combinationof reasons.the air will ~ the com~ delivery IX'CSSIJre to rise. reducingdie coefficient of peifonnance.arxl increasingthe power input for a given duty. The ilx:reaseof pressureis due to (i) The total pressure in the coodensu is approximately equal to die sum of the refrigeJ'aDtsatumtion pressure~ the pressure of die air Jl'CseDt(Dalton's Law of partial pressures). and (ii) The air tendsto be swept towards die heat transfersurfaces.fonning an insuJatinglayer which reduces~ heat b'ansfercoefficient. This in Ulm drives up die temperaturedifferencerequjred for a given heat transferrate and this results in a higher refrigerant sabJratiootemperatureand pressure. The effect of air in the systemmay be demonsttatedas follows: Procedure: (i) Start the unit for normal operation and adjust the evaJX)ratorcooling water flow rate so dlat the evaporator pressure is below abnospheric pressure. Unless the cooling water temperablre is v«y high this is likely to be the case in all conditions. Ensure that the unit is free of air and if o«.essary follow the air vendng procedtDe shown 00 Page 18. (ii) Run the lmit for ~veral minutesin order to reachnormal operatingtemperattD'es men record all systemtemperatures,pessures and flow rates. Also visually note the condensationrate on me corKlensercooling coils. (ill) Connectthe angl~ endof the charginglire (C45/2)suppliedin the~es valve at the baseof the evaporator. kit to the charging (iv) Observe ~ evapc:ntor pressuregauge and ~ open the ball valve at the base of me evaporator. The evaporatorpressuregaugewill indicate an increasein JXessurefollowed by a return to its original value. The condenserpressuregauge,however,will increaseand remain at the new value. (v) Re~ openingof d1eball valve until the condenserJXessure hasapproximatelydoubledfrom its original val~. Note that if the condenserpesswe ~~ 22OkNmo1then me high presswecut out will operateand the experimentwill have to be repeatedfran an air free conditioo. When air is admitted 10 the evaj)(X'a1Orit initially adds 10 the pressure within the evaporator ~cording 10 Daltoo's Law. However it is almost immediately swept dlrough into die comlX'eSSOfby the flow of refrigezant v8lX>ur. The mixbD'e then passesdlrougb 10 the comJX'CSSOr am ultimately to die condenser where it can go no further d~ to the liquid at die base of the condenser. In addition. the conlinuous flow of refrigerant vapoW' towards the condenser cooling coil causes die air to remain around the coil region. The reduced rate of cooOOnsationshould be observed as well as die increase in condenser pressure. Record aU system temperatures. pessures and flow rates. Typical resultsare shown in the following table. 33 Local AtmosphericPressure:lOlkN m-1 TestNo. 1 Air Free 1.With Air Evaporala GaugePressure p ~ I kN mo2 -69 -66 Absolute EvaporatorPressure p ~ I kN mo2 32 35' t,/OC 400 5.5 EvaporatorwateJ'flow m.1 g S.l 20.0 20.0 Evapora1fX water inlet ~/OC 11.0 11.0 Evapora1(X'water outlet ~/OC 9.5 10.0 Evaporatingtemperature Condenser Gauge Pressure Po 1kN m-2 -21 59 Absolute Condenser Pressure Pol kN m-2 80 160 25.5 30.5 4.0 4.0 CondensingTemperature Condenserwater flow r./OC IDa 1 g S.l Condenserwater inlet t./OC 12.0 12.0 Condenserwater outlet t,/OC 22.0 20.3 The results are plotted on a temperabJre-pressuregraph on Page 34. » :-. = =: 2' ., 00 » ~ 2' ., tD ~ tD a "= tD ., ~ 34 0 ~ m-2 CN 8 ~ ~ .., ~ Q) CD :AJ - CD ~ Q) ~ (Q ~ 0 ~ -. 0W W.., (") :AJ Q) .. -~ CD .. -n"C c -n =0 I ~ ..(J) ~ o~ -. ~O'. + 0 0 '< .., >-, (") c: (") (Q"C CD CD < G)-I Q) CD c: 3 CD c: .., CD (J) (J) ""D 35 6. EFFECT OF EVAPORATING AND CONDENSING TEMPERA~ REFRIGERAnON RATE AND CONDENSERREAT OUTPUT ON THE The effect of evaporatingtemperatmeon die refrigeration rate can be investigated.but due to d1e limited effect on evaporatingtemperatureof all but very largechangesin cooling waterflow it is more graphic to investigatecondensingtemperaturefirst. If time pennits. the correspondingeffects of evaporatingtemperaturemay then be investigated. The effect of increasingme condensingtemperatureon many refrigeration systemsand heatpwnps is a reduction in me heat dischargedfrom me condenserand in many casesa smaller reduction in the refrigerating effect at the evaporator. Similar reductionswill be observedif the evaporatingtemperatureis lowered The effocts are due pimarily to the reduction in volwnetric efficiency of the compressorat high pressureratios (PJPJ and the reduction in specific volume of the refrigerant gas as the evaporating temperaturereduces. An investigationof die effectsof pressureratio are given in the following experiment A simple explanationfor this is that for eachsuctionstrokeof die compressora lower massof gas(for the samevolume) is drawn in to the cylinder to be compressed. The effect of increasingcondenserpressuremay be investigatedin the following manner. Once air free increasethe condensercooling water flow to the flowmeter maximum (50 g S.l). The pressureat which the condenserstabiliseswill dependupon the water inlet temperature. (ii) Set die evaporator water flow to approximately 20-30 g S'l and allow the unit to run for approx,irnately15-20 minutes. The time taken to stabilisewill dependupon the local ambient conditions and the cooling water inlet temperature. (ill) Record all the systemparametersas illustrated in the table on Page36. (iv) Reduce the condensercooling water flow rate until the condenser pressure increasesby approximately5-10 kN mo1,Allow the unit to stabiliseand againrecord the parameterson Page 36. (v) Repeatfor increasingcondenserpressuresto dIe minimum readablevalue on dIe condenserwater flowmeter is ~bed, or the condenserpressurereaches200 kN roo"gaugepressure. 36 OBSERVA nONS Local AtmosphericPresswe:lOlkN m-2 Test No. 1 2 :t 4 5 Evaporaux'GaugePressure Pel kN m-2 -68 -69 -69 -69 -69 AbsoluteEvaporalOr Pressme Pel kN m-2 33 32 32 32 32 6.5 4.0 4.0 4.0 4.0 20 20 20 20 20 IJ.,O 11.0 11.0 E V8IXX8UX' Temperature EvaporaUX'Water Row Ra&e t,/OC di./ gin S.l Evapor8tcrWater InJetTemp. it/OC 11.0 11.0 Evaporat(X'Water Outlet Temp. ft/1IC 10 10 It) IG 10 CondensedLiquid Temp. ../IIC 4 Condenser Gauge Pressure P./ tN m-2- -41 .31 -21 -II AbsoluteCondenser Pressure P./ tN m-2- 60 70 80 90 105 CompressorDischarge - - Temp. - - t,/1IC Condenser Temperawre r./OC 15.0 J9.5 24,0 27.0 31.0 m./ gin S*l 50.0 10.0 4.0 2.0 1.0 Condenser W &tel' Flow Rate CondenserWater Inlet Temp. r./ac 11.0 11.0 11,0 11.0 11.0 Condenser Water Outlet Temp. r,/1:C 12.0 16.5 22.0 26.5 31.5 CompressorPowerInput W/Waus Note d1a1the temperaturesrecorded have been estimatedto the nearest0.5°C using die standard thennometerS supplied. If the optional temperature indicator is fitted with the thermocouplesensors then the temperaturesmay be recordedto the nearestO.l°C. 37 SPECIMEN CALCULA nONS FOR TFST NO.2 EVAPORATOR Rate of Heat Transfer to Water in EvaJX)rator: <J. = <J. = m. C, (t1 - tz) 20.0 x 10-3x 4.18 x 10' x (11.0 - 10.0)W Q. =83.6W - CONDENSER Rate of Heat Transferto Water in Condenser: Qc = mcc, (" - tJ Qc = 10.0X 10-3X 4.18 x 103x (12.0 - 11.0)W Q=222.2W c - DERIVED RESULTS EvaporatingTemperature t,/OC 6.5 4.0 4.0 4.0 4.0 CondensingTemperature ~/OC 15.0 19.5 1A.O 27.0 31.0 Heat Transferin Evaporator Q./W 83.6 83.6 83.6 83.6 83.6 Heat Transfer in Condenser Oc/W ~ 229.9 183.9 129.6 85.7 The graph on Page38 has been drawn from theseresults. It will be seen that the heat transfer at the condenser decreasesas the condensing temperature increases. The a1x>vetest may be repeatedat odler evaporatingtemperatures. ~: In order to expanddie rangeof experimentandto investigatewider variationsin evaporatorand condensertemperaturesit is possibleto supply WaDDed water to die wlit. Howeverunlessme internalpipe connectionsof die unit are modified dlis will havedie effect of supplyingwarmed water to both the condenserand evaporatorcoils. This will tend to increasebodl condensing and evaporatingtemperatures. 39 7. ~GA nON OFTHE EFFECTOF COMPRESSOR PRESSURE RAno ON SYSTEM PERFORMANCE The effect of increasingthe condensingtemperaturefor a constantgiven evaporatingtemperatureis to increasethe compressionratio PJP. that the compressoris requiredto deliver. Due to die effects of valves and die necessarypiston to cylinder bead clearancesdie volumetric efficiency of reciprocatingcompresSOIS tendsto fall with increasingpressureratio. Volumetric efficiency = Actual Volume Delivered CompressorSwept Volume In terms of a refrigeration system. Volumebic efficiency = Mass flow of refris:erantx Soecific volume of refris:erantat inlet CompressorSwept Volume Henceif dte volurneb'icefficiency falls widt increasingpressureratio then the effect will be a reduction in the effective massflow of refrigerant. The massflow of refrigerantthrough the compressorrelates directly to dte amount condensingon the condensa-coil and this in turn relates to the rate of heat b'ansferto dte cooling water. In addition me above equationindicatesme effect of reducing me specific volume of the refrigerant entering me compressorby lowering me evaporatingtemperature. The effect of pressure ratio on system performance may be investigated by the following method which is identical to that used in Experiment 6 on Page 35. Once air free increase the condenser cooling water flow to the flowmeter maximum (50 g S.l). The pressure at which the condenser stabilises will depend ulX>nthe water inlet temperature. (ii) Setthe evaporatorwater flow to approximately30 g S.land allow the unit to run for approximately 15-20minutes. The time takento stabilisewill dependupon the local ambientconditionsand the cooling water inlet temperature. (ill) Record all the systemparametersas illustrated in the table on Page40. (iv) Reduce the condenser cooling water flow rate until the condenserpressure increasesby aP{X"Oximately 5-10 kN mol. Allow the unit to stabiliseand againrecord the parameterson Page 40. (v) Re~ for increasingcondenserpressurestD the minimum readablevalue on the condenserwater flowmeter is reached,or the condenserpressurereaches200 kN m-zgaugepressure. 40 OBSERVA nONS Local Atmospheric Preaure: 101 kN m4 Test No. 1 1. 3 4 s EvapoI31a'GaugePressID'e Pel tN m-2 -68 -69 -69 -69 -69 Absolute Evaporator Pressure PeI tN m-2 33 32 32 32 32 6-"' 4.0 4.0 4.0 4.0 20 20 20 20 20 11.0 11.0 EvaponI(X'Tem~ Evapora1aWater Row Rate t,/OC Ih. I gin S.l Evaporaf« Waf.« InJetTemp. it/OC 11.0 11.0 EvaporalakWater Outlet Temp. ta/-C 10 10 10 10 10 CondensedLiquid Temp. re/OC 11,0 Condenser Gauge Pressure p.1 tN m-2 -41 -31 -21 -11 4 AbsoluteCondensez ~sure p.1 tN m-2 60 70 8C 90 IOS 15.0 19.5 24.0 27.0 31.0 50.0 10.0 4.0 2.0 1.0 Cu.u~~ Discharge Temp CondenserTmnpelabJre Condenser Watel' Row Rate r.,/OC ../OC di./ lID Sol CondenserWater Inlet Temp r./OC 11,0 11.0 11.0 11.0 11.0 CondenserWater Outlet Temp 's/OC 12.0 16.5 22.0 26.5 31.5 CompressorPower Input W I Watts Note that the temperaturesrecorded have been estimatedto the nearestO.5°C using the standard thermometerssupplied. If the optional temperature indicator is fitted with the thermocouplesensors then the tempe~ may be recordedto the nearestO.I°C. 41 SPECIMENCALCULAnONS FOR T~T NO.3 EVAPORATOR Rate of Heat Transfer to Water in EvaJX)rator: iii. C, (11- ~ Q. . 20.0X 10-3X 4.18X 10'X (11.0- 10.0)W Q. = -I3..6W Q. = CONDENSER Rate of Heat Transfer to Water in Condenser: Qc = "c C, (r, - tJ Qc = 4.0x 10-' x 4.18 x 10' x (12.0 - 11.0)W Qc =18.3..2W - COMP~_SDR Note that dIe pressmemtio shouldbe derived using Absolutepres8W'e not GaugePressures. Delivered PressureRatio =Pc/P. 32/80 =-2.5 DERIVED RESULTS CompressorPressmeRatio p./p. 1.82 2.19 2.5 2.81 3.28 Heat Transfer in Evaporator Q./W 83.6 83.6 83.6 83.6 83.6 Heat Transfer in Condenser Q./W 200 229.9 183.9 129.6 85.7 Theseresults are presentedgraphically on Page42. In order to investigatevolwneuic efficiency it would be necessaryto measurethe rotational speedof the compress<X' and to know the mass flow of the refrigerant. With an hermetic compressor measurementof the compressorrotational speedis not possible. In order to allow this and odler relatedparametersto be measuredand investigatedP.A. Hilton Ltd can offer the R713 Refrigeration Laboratory Unit and RC713 Computer Linked Refrigeration Laboratory Unit. P.A. Hilton Ltd or their local representative will be pleased to supply information on these and other available refrigeratiol1/beat pump units. 43 8. DE~ATlON OF OVERALL HEAT TRANSFER BETWEEN R141b AND WATER IN mE EV APORA TOR AND CONDENSER The Overall Heat TransferCoefficient (U) is die heatttansferrateper unit areaof heatttansfersurface when a temperaturedifferenceof ooe degreeexists betweendie hot and cold fluids. In die evaporator,die refrigeranttemperatureis sensiblyconstant,but die water temperaturefalls as it passesthrough the coils. In die condensersomedegreeof superheating~ be presentwhen the gas entersthe condenserglasschamber. However the quantity of heat delivered due to the superheating will be small relative to that attributableto the condensingphasechange. Examination of the high pressureline of the cycle diagramgeneratedin ExperimentNo.9 on Page47 will confirm this. In oroor to analysethe overall heatb'aIlSfercoefficient a representativetemperaturedifferencemust be determinedthat representsthe driving force for heat transferbetweenthe refrigerant and the water. The temperaturedifferenceto be usedin this caseis the "Logarithmic Mean" which is given by where9... = Temperawre differencebetweendie two fluids at inlet, 9..-1ot = Temperature differencebetweendie two fluidsat outlet. and A dleoreticalanalysisof dle logarithmic meantemperatmedifferencemay be found in mosttext books on heat transferand will not dlereforebe expandedin dlis manual. Once air free increasedie condensercooling water flow to a mid range value. The pressureat which the condenserstabiliseswill dependupon the water inlet temperature. (ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately 15-20minutes. The time takento stabilisewill dependupon the local ambientconditionsand the cooling water inlet temperature. (ill) Record allllie systemparametersas illustrated in the table on Page44. 44 OBSERVATIONS Local AUDOspheric ~: lOlkN m.~ Test No. 1 Evaporata GaugePressure Pel tN mea -68 AbsoluteEvaporatorPressure p.1 kN mea 33 Evaporata'Temperature EvaporaI« Waf« Flow Rate t,/OC die I gin S.l 11.0 EVaporaI«Water Outlet Temp. 'a/OC 10 CondensedLiquid Temp. "lac CondenserGaugePressW'e p.1 tN m-2 -41 AbsoluteCondenser ~ p.1 tN m-2 ro Condenser Tempelature Condenser Water Flow Rate 5 t,IOC r-/OC Ib./ gin 8"1 15.0 so.o CondenserWaf« Inlet Temp. ~/ac 11.0 CondenserWater Outlet Temp. r,/OC 12.0 Compressor Power Input 4 20 rs/OC Discharge Temp. - 3 6.5 Evaporata Water Inlet Temp. Compreso 2. W I WatU Note that the tem~rabJres recordedhave been estimatedto me nearest0.5°C using me standard mennometerssupplied. If the optional temperature indicator is fitted with the themtocouple~nsors then the temperaturesmay be recordedto the nearestO.I°C. 45 For the Evaoorator RaICof Heat Transferto Wata' in EvaJX)rator: Q. Q. - t,) S IN. C, (t1 S 20.0x 10-' x 4.18x 10' x (11.0- 10.0)W Q. :.83.6W e~ - 11.0- 6.5 e~ = 10.0 - 6.5 = 4.5- 3.5 8- . In~ 3.5 ~K Q U=A&: u . ~ 83.6'--, W.-2 ~~ u =~ For - - the g-l w..-2c' Condenser Rareof Heat Transf~ to Water in Coode~ Q~ = *~ c, (" Q~ - - tJ 50.0x 10-' x 4.18x 10' x (12.0- 11.0)W Q~ = . W 8~ . 15.0- 12.0 8-- . 15.0- 12.0 . 8- . 4.0 - 3.0 ID~ 3.0 ~K 3.0K 46 Heat Transfer Rate u=~ A8. u. u = ~ Wm-2K-l 47 9. GENERATION OF A REFRIGERATION CYCLE DIAGRAM ON A PRFSSUREENTHALPY CHART Note this procedure can ONLY be undertaken by the following detailed method with the optional temperature indicator fitted to the R633 unit as the temperature of the refrigerant liquid in the condenseris required for one state point on the cycle diagram. However the procedure may be modified for use with the standard thermometer set. SeePage48. The fitting JX'OCedUIe for the optional temperatureIndicator kit, if not already fitted. is given in Appendix A. Details of the kit are availablefrom P.A. Hilton Ltd. or their local representative. The vapour compressionrefrigeration cycle is of paramountimportancein tentls of food and drug preservation,air conditioning, and heatpumps. In order to analysethe systemperformancein tentlS of die diermodynamiccycle it is common for engineersto record systempressW'eS and temperawres and dien to plot the various statepoints on a pressure-enthalpy chart of the wm'king fluid. The working fluid in me Hilton RefrigerationCycle DemonstrationUnit SeriesR633 is R141b. This has me chemicalname 1.1.-Dichloro-l-fluoroed1ane. A pressure-enthalpy chart for this substanceis shownon Page55. A detaileddescriptionof die variousparametersdisplayedand obtainablefrom pressure-endtalpy charts will be found in most text books on thermodynamicsand thereforewill not be expandedupon in this manual. In order to plot a cycle diagramfor the unit the following procedureshould be adopted. Procedure: (i) Start me unit fOf normal operation as shownon Page 15 and ensuredtat me unit is air free by venting air from the condenseras describedunder air venting on Page 18. Once air free increasethe condensercooling water flow to a mid range value. The pressureat which the condenserstabiliseswill dependupon the water inlet temperature. (ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately 15-20minutes. The time takento stabilisewill dependupon the local ambientconditionsand the cooling water inlet temperature. (ill) Recordall the systemparametersas illustrated in the table on Page49. (iv) In order to demonsttatethat the cycle variesfor different operatingconditionsit is recommended that die condenserpressureis variedby adjusbnentof die condensercooling waterflow rate. The unit should be allowed to stabiliseand die systemparametersrecorded. The proceduremay also be repeatedat different evaporatingtemperaturesand the resultsplotted on a pressure-enthalpy chart as describedbelow. The results from die following table are shownplotted on PageSO. The statepoints a. b and c on the diagramon Page50 are locatedin the following manner:(i) Pointa is at theintersection of theevaporator chamber pIeSSm-eP. = 32 kN mozabsolute andthe evaporating temperature Is= 4.0OC. (ii) Point b is at the intersectionof the compressorchamberpressurePG= 70 kN compressor discharge temperature ~ = 41.7OC. m°2.absolute and the 48 (ill) Point c is at the inte~tion condensedliquid tem~ of the compressorchambel'pressurePc= 70 kN m-1~lute r. = 19.5OC. and d1e (iv) The expansionis assumedto be adiabaticand dtereforea ~ of constantenthalpymay be drawn vertically oown from IK'int c to intersectwidt the evarxratnr presSUIeline Pc. Consideringthe processesd1a1are happeningat eachSta1epoint in turn:(i) At JX)inta die v8lX>urfrtm die evaporBt«is drawn into the compe.-,r and me pressureis raised from P. to Pc. It is evident from die line of constantentropyintersectingwith JX)inta (1.9 kJ kg-I K-1) that die compession is not isentropic as die pressurerise is completedat an entropy of aPJXQximately1.92 kJ kg-l K-1. If required the isentropic efficiency of compressionmay be evaluated. (ii) The vapour leaving the com~ at point b is superheated as it is to the right of the saturated vapour line. The vapoorcools slightly in the pi~ to the condenserand then in the condensertksu~rl1eatingand colxlensingtake p1a;:eat essentiallyconstantpressure. (ill) At point c me liquid at die baseof me condenseris slightly sub cooled due to me effect of me cooling water tempembirebeing below the saturationtemperatureof me conde~ chamber pressure(water tem~ 11.6to 16.7OC.Sawrationtemperanueat Pc= 70 kN m-1= 21.7°C). In addition ~me sub cooling in this unit arrangementis addeddue to the expansionvalve being physically attachedto the condenserbaseplate. The temperaturedrop causedby me expansion conductsheat through me baseplatefrom me condensedliquid reducing the liquid temperature furdler. (iv) The JXessuredrop causedby me expansionbrings me refrigerantinto the valX>ur!1iquid mixtm'e region betweenme saturatedliquid and satlD'8tedvapourlines. The mixture of vapourand liquid may be seenin the sight glassadj~t to the evaporator. The liquid/vapom mixbJIemay be seenreturning to the evalJ(X'atOr through the fitting in the tOp plate. Note that mough me experimentmay only be carried out in the aOOvedetail utilising the optional temperatureindicator. statepoints a and b may be determired using the standardthermometerS. The temperatureof dIe conOOnsed liquid may. however.be estimatedfrom dIe saturationpressurein the condenserif it is assumeddlere is no sub-<:ooling.In dIe aboveexampler.. dIe condensedliquid tem~. is measuredas 19.5oC.but dIe saturationtemperawreat 70 kN m-zpressureis 21.7OC. Cearly somesub-coolinghasoccurred. 49 OBSERVAnONS Local AttnospbericPressure:lOlkN m-2 1 Test No. Evaporala GaugePressure p. I kN m4 -69 Absolute Evaporator Pressure P. I kN m4 32 Eva{X)ratCKTemperature ts/OC Ib.I gill S-l 4.0 Evaporara Water Flow Rate 20 Evapofata Water Inlet Temp it/OC 11.2 Evaporata'Water Outlet Temp ~/OC 9.7 CondensedLiquid Temp. ../OC 19.5 Condenser Gauge~ PcI tN m-l -31 Absolute Condenser Pressure PcI tN m-l 70 Compressor Discharge Temp. t.,/OC 41.7 CondenserTemperablre ../OC 19.5 dlc / gin S.l 10.0 CondenserWater Inlet Temp. r,./OC 11.6 Condenser Water Outlet Temp. ~/OC 16.7 Condenser Water Row Rate CompressorPower Input W I Watts 2. 3 4 5 ~ !~ Q) '0 n =- CD 13 so I.A 0 w w 0 0 t-.) \.It 0 t-..) 0 0 - ~v. =0 =- . . -6" ;O ~ _0 ~o = c.. =. -6" '<~ _v. ~o ~~ Vt 0 0 VI VI 0 0\ 0 0 0\ "" 0 .,..J 0 0 -.0 i ~ ~ 0 :... w 0 0 "" ;;'f 'j~ G' ~r"i:t ~ ~ ~ 0 "" 0 "0\ § ~ . 0 c. -V ~: ..~ - ~~ ~ -.J ;i N .. w ~.:; l ::r~P :~ - - m ",,~' ~ ~ - 'c '8 ~ ~ i;:~ 9~ ..~ ~E 1-.»8 ~ ! 1 ~~ fij- m ~ ~ -t.,) loA 000 A; ..,°.. l~11 rl"r1 ,~ 1\ { ~,r\ Oa - Co 'oc INI ~~I.09 00 i.I- ~ .ft I~ * " ~ "v- f\ ~ ~ 't~J -N ""-0 . ~t -N V-O ~ ~~ " \. i::1:' ~ v ~:'. - ", 1 1~ ' ,\ :~ ,\ .. , -, ," 1\ w . V\O\~-0 \ r: ~-::: .~ '.~ ~ I.~ A\ \" Pressionabsolue/ Absolute pressure(bar) 0 W \\.:..\ I" \ 'i~ 0 ~ ~=-,~, ;If:::to:tt1- ~ - 0 'w w~ 00 1 1I '-0 --- w ~ 0000 ~I \'1 V\O\ ~ ~ 0 0 N v0 ~ 0 0 ~ v. 0 ~ 0 0 ~ v. 0 u0 0 "'" "'" 0 0\ \oft 0 51 10. MEASUREMENT OF mE EFFECT OF CONDENSING TEMPERATURE ON COMPRFSSOR POWER INPUT Notethis procedurecan~ be undertakenby the followingmethodwith the ootionaldi2ital wattmeterfitted to the R633unit. The fitting procedurefor the optional wattmeter kit. if not alreadyfitted, is given in Appendix B. Details of the kit are availablefrom P.A. Hilton Ltd. or meir local re~tative. The vapourcompressionrefrigerationcycle is utilised in both refrigerationand heatpump awlications. In a refrigeration situation the eff~t of high ambienttemperaturewill be to both ~rease the loan on the refrigeration system(due to heat leakagejntq the cold spacethrough thennal insulation) and to increasethe condensingtemperaturein order to reject heat from the system. In a heatpump applicationthe useful heatfrom the condenserwill be more easily utilised for heating applicationsif rejectedat a high temperature. In bodl cases,increasingdie condensinglX'Cssureresul~ in a greaterwork requirementfor die compresscx. In addition, die increased compression ratio will in most cases result in a reduction of system efficiency due to a reduction in volumetric efficiency. This is due to die necessary clearance required for compressor valve opening and machining tolerances. At die end of a compression stroke this clearance value is COOStant but at high pressure will contain a higher mass of unb'ansferred gas dIaD at low pressure. In addition,due to commercialfactors,the motors usedin mostdomesticrefrigerationcompressorswill be of a relatively low elec1rlcalefficiency. Henceelec1rlcalresistanceheatingeffects in the windings will be relatively high under all operatingconditions. Procedure: (i) Start the unit as for normal operation as shown on Page15 and ensurethat the unit is air free by venting air from me condenseras describedunder air venting on Page 18. Once air free increasethe condensercooling water flow to maximum (50 g/s). The pressureat which the condenserstabiliseswill dependupon the water inlet temperatm'e. (ii) Set the evaporatorwater flow to a mid range value and allow me unit to run for awroximately 15-20minutes. The time takento stabilisewill dependuponthe local ambientconditionsand me cooling water inlet temperature. (ill) RecorddJecompressorpower input shown OIl the digital wattmeterand the condensingpressure Pcas illustrated in dJetable on Page52. (For referenceit is recommendedthat studentscarefully touchthecompressorcasingto experience the heat loss from die compressordue to electrical heating effects. This representselectrical energy wasted by the system. Care should be exerc~ed as the comoressor casioa will be !!QI.) (iv) Adjust the condensercooling water flow to a lower valueand againallow the systemto stabilise. Re~ d1eaboveobservations. (v) The proceduremay be repeatedup to the maximum condensingpressureif local cooling water conditionspermit S2 OBSERVAnONS Local AtmosphericPressure: kNmo2 Test No. Evaporala GaugePre~ Pel tN mol Absolute Evaporator Pressure Pel tN mol Evaporata T~penIuIC E Vaporatm' Watrl' Row Rate - EvaporaIO'Waf« Outlet Temp. ~/OC CondensedLiquid Temp. "/OC CondenserGaugePreaure p./tN m4 Absolute Condenser Pressure p./tN m4 Temp. - Condenser T emperahlre Condenser Water Flow Rate 190 274 302 4 5 ",/OC ,,/oc Ib./ gin S'1 Condenser Water Inlet Temp. ~/OC CondenserWater Outlet Temp r,/OC Compressor 15 3 Ih. I lID 8-1 ts/OC Discharge 1 "/OC Evaporara Wat« In1etTemp. Compressor - 1 Power Input W I Watts Note that the val~ observedwill dependupon the local conditions,the p-essuresset and the local supply voltage and frequerx:y. As indicatedabove,the power required to drive the com~ is increased. increasesas ~ condensingpressme S3 OBSERVAnONS Local Atmospheric~: kNm-7. 1 TestNo. Evaporata' GaugePressure Pel kN m-2 Absolute EvaporatorPressme p.1 kN m-2 Evaporat(X'Temperature Evapotat(X'Water Flow Rate .,/OC m. I gin S-1 EvaporatorWater Inlet Temp. "/OC EvaporatorWater Outlet Temp t,/OC CondensedLiquid Temp- r./OC Condenser Gauge Pressure p~I kN m-2 Absolute Condenser Pressure p~I kN m-2 Compres~ DischargeTemp. t.,/OC Condenser Temperawre ~/OC CondenserWater Flow Rate Ib.I gin S.1 CondenserWater Inlet Temp r./OC CondenserWater Outlet Temp t,/OC CompressorPower Input W / Watts 2 3 4 5 54 rn ~ 2' ., ~ C'. = = --3 tD a ~ ., ~ 2' ~ ~ 0 0 ~ 0 (.a) 0 ~ tn 0 m 0 ..., 0 0 U1 0 ~ 0 0 Saturation r-m , ~ (11 0 1-'.' m m-2 ~ ~ n-{+~ Tl t1. n-111 LL ti TI ~ a f1 m ++i ~ ~ ~ = z t < = 0 V\ \0 0 '1"\ '1"\ 0 0 \I") 0 In 'o:t' 0 0 ~ 0 ~ ~ 0 0 M <:> It"\ N 0 0 N 0 -In ! - 0000 \CV\ 000 \O\t'\ ~ ~ ~ 0\; "#' 0\; 0'; (f'I N- o~ \, 011'\ N- ~~ ..1 ~~ -I "" ...a l i I~ ! ill~ ~tl X 'S.J ~ I~ - i -0 ~ \OV\.qoM ~! \, I '. m l' 0 ~ (.l8q) 3.1ns~.ld N ~t - 0 00 0 0 -~~~- -tv / 3RlosQU'UO!St3Jd N00 '" . J~ ~; N-::00 - 0 '55 0 r--- 0 V\ \0 0 0 10 0 V\ V\ 0 0 '1"\ OJ) - ~ o~ VI~~ c. "; .c = O~ 0~~ .c. "; .c - 0= VI~ ~ 0 0 ('f') 0 V\ N g N - 0 Ir) S6 SPECIFIC RISKS . Contact with liquid will causeseverefrost bite . Decomposesin a fire to give toxic and corrosive fumes . Containen may bunt if overheated . Risk of asphyxiation at high concentration IDENI1F1Ct770N 1. LI 1.1 SYDOBymS l,l,-Dichloru-l-O=roethaDe. R-141b Uses Plastic fOim blowing aaalt,SOlveDt 2. COMPOSmON Substance Impurida 3. PHYSIC4LPROPERTIES At2G-C liquid 3.1 PbysicalSUte colo1U': colourless 0d01U': slightly etherial Tempentura melting point: -lO3.S-C boiliDl point: 32.0-C critical taDper8ture: 20S.C 3.2 (.rubstanCeJor impurities giving a hazard) 1,I ,-dichloro-l-Qooroethane DOne ~tiOD ~.1Ure: CAS EINCS 1717-00-6 404-080-1 Health & Safety Data Sheet SOO-C 3.J pH DCutr81 3.4 Solubility in ~ at20.C: 0.54%by weight in solvCDts: misciblewith aliphatichydrocarbons. aromatlcs,ketoaes.chkwiDated derivatives a1¥i~ 3.5 Vapour pressure at 2Q8C: 0.81 bar at SO.C: 3.6 Deasity (liquid) at 2S.C: (vlpOur) at 32.C: 5.011 kIfm) 3.7 Other data criticalpressure: 43.4bar 4. 4.1 STORAGE AND HANDLING SpedalstoraceaDd StorebetWeeI1 0- andSO-Cin awell v~rilated~ baDdUac precaadoDS ~t storedin.sp«ial1yreinforced dnDDS. 4.% PacklDgmaterials Avoid alloys with 2% or moreof magnesiumor aluminium.Avoid plastics. Usesteelor polyethyleue dr1Dns. 4.3 DecompolltioD prvducu Stableat ambienttemperabl1'e, but willlDfcrlo thermal decompositionat elevatedtemper8tures to give off hydrochloricand hydrofllWric acidsaDdpossiblypbol8~ 4.4 DaQcroas reacdODS Withnakednameor hot metal~ 4.5 lDdJvtduaJpmeDdoD and pAtecd"e measures Gloya- 4.6 Sped" protecdve mcuara Va1ri1arcthe workiD&area. No aom,. nama. 4.7 Meuara after IpWqe 0r Ieak8Ie If in m ~loscd If this materialis redistributedfor sale,detailsof its hazardsand recommendedmethodsof safe handlingshouldbe passedon to all users. .83bIr 1.24.,cm) loula r=ommeaded AvoidliquidcoDtKt HRP Refrigerants Ltd. Gellibirion Industrial Estate Pontypridd Mid Glamorgan CF37 5SX withskiD - eyes aDd theiDh8Iati~ of~. No aaked -rea. YCDn18le or WaI' tt:1!oCOaIaiDCd bratbiDI ~ (risk or -.hyxi8lioa/llK)xia).Allow to eT8pOrIIcor pump into salecoatIiIICr. Prevalt.!rom mtailla ~ bucmCUISetc. In caseof emergencytelephone" 01443 842255 57 SPECIFIC RISKS . Contact with liquid will causeseverefrost bite . Decomposesin a fire to give toxic and corrosive fumes . Containers may burst if overheated . Risk of asphyxiation at high concentration DestnacttoD of coDtamiDated coDwDer ...8 4.9 Ret\un to supplia-. Other recommeDdatioDS Storeat a tanperaturebelow SO-Cin a y~latM away from all ~~ of heator ignition. 5. 5.1 IGN1110N AND EXPLOSION F1ash poiDt none 5.1 Auto-ignition temperature none S.J Special fire or explosioD hazards area, Non-flammableproduct Thermal decompositiongives off toxic fumesoChydrochloricand hydrofluoric acids and phosgene. 5.4 Extinction Not applicable 5.5 Particularmeasura during OR-fighting Wear self-containedbreathingapparatusand full acid resistantprotectiveclothing. 5., Other recommendations Protect.containersfrom heat~urces. Cool with water to avoid ov« pressurisation.EDsureproductdoesnot come into contactwith nakedflamesor hot metal surfaces. 6. TOXlCOLOGICtLINFORMATION CAS EINCS 1717-00-6 404-080-1 Health & Safety Data Sheet If this materialis redistributedfor sale,detailsof its hazardsand recommendedmethodsof safe handlingshouldbe passedon to all users. Employersshouldbe awarethat this productis ~lvent abusable. 7. Vapour 2,500 ppm for 30-60minuteswin causevertigo, drowsinessand respiratoryproblems. May causeincreased sensitivity of myocardiumabove 12,500ppm. Uquid Repeatedandproloaaedskin contactwill produce dermatosis. Eye contactwill lead to irritation. rednessand moderateconjunctivitus. FIRST AID PROCEDURES Skin contact Washwith copiousamolmts ofwater'. Inhalation Removeto freshair. ApplyoxygeniCbreathing is difficult. Consulta doctor. EyeCODtact Wash1!DQ!.~a~ely with copiousamolmts of water. Consult an opbtbalmologist. 8. SPECIAL PRECt U110NS FOR WASTEDISPOSAL This matcria1is subj«t to the resttictioasof the EnvironmentalProt=tiol1 Act and shouldoot be Va1tedto atmosphere.W.. materialcan be ~ to HRPR. Movancnt of refri&~ for ~1amation or destIuctioDis subj~t to the Duty of CareIlK! requiIeIlppropt.ate documentationCora contro~ Wde. HRP Refrigerants Ltd. Gellihirion Industrial Estate Pontypridd Mid Glamorgan CF37 5SX In caseof emergencytelephone 01443 842255 S9 '3 2 1 4 Amendments 2 MAINS FILTER ADDED 10.9.97 JB A NEW 3 CORE POWER CABLE FROM TRANSFORMERSECONDARY 2'OV TO MA~S FILTER LENGTH 1000 mm () r--- .. j LINE t )1 -0 HA~ -. IFLTER ~ ~~IP£A~ LOCAl ~PL Y V~ TAGE A~ CON~CT BROWNWIRETO ~AREST va. TAGE TAPP~ PaNT. SET TO 130V ~ r- ; ~I ~I ~ HAt-IJFACTURE 1 . 1 i: 1 ~:1 m r- ~ B I Q ~o~~~1 <@ (2}1 IllJ--,m . @} 1111 @ IW ~I ...1 10 1m @I -<I ~. r-1 i. . . .. 1 . .. ~~.~:.. ."J. c OR~L 3 CORE POWERCABLE DSC~CT FROM HAINS FL TER LINE IN RE ROOTE TO PRt1ARY SIDE CF TRANSFORMER ~PLY to -mY 5O/~ SEE MAN WlRNG CMAGRAHFOR TERMNAL KEY The supplier is reqUred to deliver goods stri:lly accord'W'lgto dramg. Compcx-.ent inspection is the suppliers responsibility. ReIOOveall sharp edges and blSrs. Limits unless otherwise stated TITLE: 110 - 130V TRANSFORMER -- MTL: FINISH: I DrcwnbY: ..B Checked iDimensions mm I °Y @c::J Fractions .t 1/6'. Decimals .t 0.25 mm Projection: Issue: 2 WIRING Dote:4.3.96 DRG. No. DIRGRAM Scale.- no/rig. 1 --- HA~SHIRE ENGLAND P. A. HLTON LTD KINGSSOMBORNE 633385 61 APPENDIXA OP'nONAL DIGITAL TEMPERATURE INDICATOR R633A If£I-I"iNG INSTRUcnONS 62 -- -- VjQllK mQJCator ~l in the centre of the Wlit. The addition of the digilal temJ'eraLureindicator not only increases die resolutioo of tem})el3ture measuremenmfrom to.soC to O.IOC but a thennocouple sensor is provided to record the temlJeJ'a1Ures of the liquid in the baseof the condenserchamber The refrigerant additiOnal teJnj)elatures R141b allow PCessure-enthaIpy a complete vapour re. comPlession cycle diagram to be nrn.i..~_.. - diagram. - Oncethe level has beenmeasuredor marked,position the ball valves for shutdown (SeeFigure 2 R633 Valve Positions)and hJm the unit off. Turn off and disconnectthe unit from the water supply. Isolate the unit from its electrical supply and then remove the bolts and one nut securing the rear panel. Storethe bolts, nut and washersin a containeras thesewill be requiredfor refitting the panel. Removethe thermometersfrom their pocketsandstorethesesafely. Note that if the original installation recommendations were followed dlere will be someoil in ~h of die dlennometerpockets. With the help of an assistantlay the machineon its back and locatethe 3mm (1/8") diameterblanking rod in a pipe fitting in the 00seof the condenserchamber. This is the locationfor the 1s thennocouple. 1 63 Ensuremat the liquid level is below the level of the blanking rod and that the condenserpressureis either at or below atmospheric pressure. Using a close fitting spannerremovethe nut securingdIe blanking rod. Take the 0 3mm x 8Smm long diennocouple (!MIS/IO) and using a 0 3mm compressionolive (PF4/67)and die original nut. insert the diennocouplein die chamberto a depdi JUST BELOW that of the measuredliquid level. Rewm me unit to an upright position. Thosewim accessto a vacuumpump may eXb'actany air from the systemby connectingto me internal pipe leading from me vent valve on top of the condenser chamber. Note that the oil in the unit is hygroscopic(absorbswater vapourfrom the air) and the unit shouldDOt be left open to atmospherefor long periods. Fit the 7 shon rod type thermocouples(IMlS/l6) in placeof the original thermometers.For the present time the thermocoupleconnectingleadscan be left ttailing at the front of the panel. Remove die 92mm x 92mm blank insttument case from the panel by releasing die retaining screws from inside die machine panel and withdrawing die case from die front of the unit. The digital temperatw'eindicator and multi way selecta-switch are two separateitems. A separate2 coretbennocouple cableis suppliedto makemelink betweenmemo FirSt install the 10 way selector(]MIS/50) at the bottom of the 92mm x 92mm panel orifice. This is retainedby wire springsandclips whichpressagainstthefascia.Referto FigureA on Page65. The indicator (!MIS/53) is fitted abovethe multi way selectorand retainedby jacking screwswhich bear on me rear of the panel fascia. Refer to Figure B on Page65. Make the 2 core thermocoupleconnectionin accordancewith the wiring diagramon Page71 The Brown or Green (+) wire runs from COMM I to indicator terminal 25 "VI". The Blue or White (-) wire runs from the terminal on die right of COMM 1 to indicator ternrinal26 "COM", Apply the label "Oc" to the fa:e of the indicator to the right of the digital display. Apply the yellow label "TemperattJreIndicator" to the panel fascia. Electrical Installation The 3 core IX>wersupply lead for die optional ternperattJre indicator and separateoptional wawneter is factory fitted to the following tenninalson the DIN rail connectorson the right handsideof die unit adjacentto the input IX>werlead. Their free endsare identified ~ follows: - 49 (Eard1 ColourGreen+ Yellow suipe) FromDIN Rail 5 47 (Line - Colour Red) From DIN Rail 8 48 (NeuU'al Colour Black) From DIN Rail 13 - ~ units already fitted widt a wattmeter (R633B) will use the ~k. of loose JinkssuWlied to tap into the wattmeterIK>wersupply. Refer to the wiring diagramon Page71. Unitsnot fitted wim mewattmeterwill useme free wireslabelled47 (Line - Cololn' Red) and 48 (Neub'al- Colour Black) directly. 64 The free end of d1elead will havebeenprotectedwith tenninal covers. Theseshooldbe removedand the 3 wires given 1 turn throughme ferrite ring suppliedand ~1Ued ooarto the indicator. The red and b1a;kcablesshooldbe connectedto the following terDlinalson the digital temperatW'e indicator. Note that as ~ digital temper8bJre indicator is double insulated.the green/yellowearth wire is not usedin this application. 18 L Line renninal securesRed wire 47 17 N Neuttal terminal securesB1a:k wire 48 The themtocoupleleadsmay now be ~red to the thennocoupletenninalson the multi way switch oox. Note fran the wiring diagramon Page71 that ~h of the 10 switcOOdchannelcoonectiooson the rear of the oox has4 terminals. However.in eachcaseonly the left baOO pair of eachgroup of four areutilised. Note that due to a new EuropeanStandard,sometype K d1ennocoupie w~ insulation and od1ersgreenand white to identify the polarity. will utilise brown andblue For ~b tbennocouplethe brown or green~itive lead is connectedto the tenninal marked 1 in ~b group of four. The blue or white negativelead connectsto me next terminal on the RIGIrr of me tenninal maIked 1 in eocbgroup of four. The remainingtennina1sin eachgroup of four are not used. Note that only channelsI to 8 (CHI, CH2, aD...CH8) are utilised. The remainingchannels,9 and 0, are not utilised for dlis option kiL Start with ~ merm<x:ouple (refer to the schematic diagram) and pass this lead dtrough a convenient hole in me unit panel (e.g. where me cooling water pipe passes through the panel). The thennocouplc wires are coloured: Greenor Browo(+) JX)sitiveto CHI White or Blue (-) negativeto right band side of CHt Note that the remaining 2 pairs of thennocouple tenninals, i.e. CH9 and CHO. on the digital temperature indicata' are useable. Any type K (Nickel-Chrome, Nickel-Aluminium) thermocouple may be conneA:!ed to these terminals and used in the same manner as those suWlied if other areas of interest exist NOTE that if local regulations require, or any doubt exists concerning correct connection of the instrument, the unit should be inspectedby a competent electrician before supplying power to the unit. Refit die unit back paneland restoredie elecbical supply and water supply. Start the unit as for normal operation following the procedureon Page IS and verify that when the main switch is turnedon the digital temperahlreindicator lights. The rotary selectorswitch connectsthe indicated thermocouplenumrer to the digital display. Note that the unconnecteddtennocouplechannelswill give readingsthat have no meaning(full scale negativeor full scalepositive) unlessa dtennocoupleis flued by dte user. The digital temperat1D'eindicator has five fmtCtiODkeys on its front fascia. These are used only during manufocbJre to configure the instrument Pressing me keys may disturb d1e displayed value. The display will revert to normal after a 60 second delay. In order to improve dtennal cont.:t widt die thermocoupleprobesit is recommendedthat a small quantity of light oil is put into eachdtennocouplepockeL The unit is ~rated in die nonnal way ~rding to the recommendedlJ:()COOures. 6S PA~L FIGURE A ~ USE A SUITABLE FLAT SCREWDRIVERTO PUSH AND ROTATE THE ClP ONTO THE TWO BRASS STUDS ON THE SlOE OF THE SWITCH CASE. THE OPPOSITE SVE FITTED IN THE SAME MANNER BUT INVERTED 66 This page is intentionally blank 67 APPENDIX B OFrlONAL DIGITAL W ATfMETER R633B ttrl-rING INSTRUcnONS 68 »--ESCRIPfION Thewattmeteris fitted to die panelfasciain p~ INST ALLA of a blackDIN ~, nON ; Removethe 145 x 65 DIN caseby s1a:keningthe fascia pinch ~ws. holdersand p$s die empty caseforward through the fucia. Fit the wattmeterin the vacated~ Rotate to releasethe screw widt dte screwtenninaJsat the lower side towardsthe tmit base. A 3 core power supply lead for dIe optional wattmeter and separateoptional digital temperature indicator is factory fitted to dIe following terminals00 dIe DIN rail connectionson die right handside of dIe unit adj~ent to dIe power input lead. Their free endsare identifIed as follows: 49 (Earth - ColourG~ + Yellowstripe) FromDIN RailS 47 (Line - ColourRed) FromDIN Rail 8 48 (Neub'al-ColourBlack) FromDIN Rail 13 Thoseunits alreadyfitted with a digital temperature indicator (R6J3A) will ~ die JmCk of loose links supplied to tap into the IX>wersupply. Refer to the wiring diagram on Page 71. H the tempezanue indiCa1CK gets in me way, unclip and push forward. Units not fined with the digital temperature indicator will usethe threeunusedwires within the loom identified as follows: 69 - 49 (Earth ColourGreen+ Yellow stripe) 47 (Line Colour Red) 48 (Neuttal- Colour BJack) - Before connecting to me watbneter,pass mese3 wires 1 turn through the ferrite ring supplied and securenear to me watbneter. The lOOmmred link from watuneterTenninall L to 3 AC V is usedin all cases. The baseboardis pre-drilled with 4 off pilot holes 2mm dia. to receive the 2Ommlong self-tapping screws(SFl/118). Theseshouldbe usedto securethe currenttransformer(E3/108) in position. Refer to diagramon Page70. Remove the compressorelectrical connectionscover. Detach the red line wire 31 and cut enough adjacentcable ties to enablethis wire to passthrough the centreof the current transformerand back to the compressor.Reconnectthe red line wire 31 to its original terminal on the compress<l'and refit the cover. Connect the 1200mm long red wires from the current transformer 51 and 52 terminals to the conespondingterminalson the wattmeter. Twist thesetogetherto form a twisted pair of wires. Route them throughthe releasablecableties securingthe loom to the fascia,and passthe pair 2 bJIDSthrough the ferrite ring. Tidy the loom using the cable ties IX"Ovided. NOTE that if local regulations require, or any doubt exists concerning correct connection of the instrument, the unit should be inspectedby a competentelectrician before supplying power to the unit. Refit d1erear paneL Fit die tarel "Wattmeter"to me fascia in me spaceaboveme Wattmeter. Restoreelectricalpower. Switch on the main switch and verify the wattmeteris indicating. Minus valueswill appearif S1 and S2 are reversed.i.e. S1 on the cWTenttransfonneris connectedto S2 on the wattmeter,and vice versa. Or alternativelyif the direction of the compressorpower supplythrough the core of me transfonneris reversed,the samenegativevalues will be seen. 70 .. N !! I §i~i~ 5~"'1 i ~' , , "i" I I Ii.;.-n CIJ:D~ :11 !: I'"; - J.I i ..I I'! : i~ p 8p ~ i ~p ~ -Iu.-W"aiW--' Ila~~III! " .. I ~ 1t\.!1 ~ 0( ~ @ ~oO I-W cl- e @ iii ~t: ~~ WW ..1~~ ~~ ,~ i ~i : IL,% : I! 1 I§ ~~ \ I i", ~. I!!i !! ~"AZ ~"~ SJ.~ S1J.YM AG" ZI. ~ AG, ~ $"AS ScIIY 8 9 AGJ. {" UIoH W8 ~S S ~c Qw 1-1~~ ~)I~ ~'t IIIi 11 ~~ ii ...1 ~~ Oil t t t .. t 1 I I I I I I I I I I I , I I I I - ... - EJ...J 8_lI i~ ~i ~ yo A .."~ - aE -I~ - i~ @~ ~ ! '- i ~! Ii i~ .~ A ~ ~ \11;1 i ~ ~I I '\ §~ '" 0 !*.;;.. . !~.. ~ t- i ~ .~~... ,I&. In il ~ ~@.il.. ~~ 3~iij,a.@.@ -'~a~~aaa~ §-' ffidlm~I~~ t-u ~ I ~ I I i ~ ~ 71 ~~ I-~ :~i ~~ ~ 1&1 i I I i I , t-' Q : ~ ~ c a: " , ~I :i ~ ~ ~ ~ ~ ~ ~ ~ ~ . ~ t)( W ~ ~ i ~ m I I i j I I 5 ; I .. ~ III 1:8m18Itll Ii.. ~8. 5 5 im~..~ ~~ ~.~!I. ~5 I i~!!~!!~ /-0 .. _O- I ,.. @~'t' I i.. Ii ..~ Ie ~~ Wi . II ;~ 72 2 -1 4 Amendments 3 A Sl,PPLY TO WATTMETER ANDOR TEMPERATURE INDICATOR r SIGNAL TO S1 AND S2 ON WATTMETER '\ r~~# ...#... ~, ." , ## , ,## I , '" I ." , : B ONCE THROUGH . , ; , , . I: . TWICE THROUGH . . ... ~' .' "'. ,-' ( ~ ~ . Sl.fIPL V FROM FITTED LOOM "--The supplier 18 req..-ed ~--- to detlVer goods strIctly acc«~ Remove all sharp edgeS and burrs. - - I \Dimensions: mm \ by: suppiiersresponsibility. drawi1g. (afIP«1ent inspection is the --- !Drawnby: JB IChecked to Fractions Decimals - Limits unless otherwise stoteo :Projec:tion - t 1/6'. t 0.25 mm !Issue: 1 TITLE: --'-' HTL: ~ KINGS SOMBORNE P. A. HI.. TON LTC - HAMPSHIRE )-OOtri~ 1. -EN<:LANO - ~-~