SECTION 281326.01
ACCESS CONTROL REMOTE DEVICES
PART 2 PRODUCTS
2.1
GENERAL
A.
The intelligent controller shall be an Ethernet-ready, fault-tolerant host communication
device that provides efficient management of a large network of access panels in any
system design.
B.
The intelligent controller shall use an RS-232, 2-wire RS-485, or Ethernet link to connect to
a Windows or Linux host.
C.
The intelligent controller shall be capable of elaborate processes and procedures without
host intervention.
D.
Once configured, the intelligent controller shall function independently of the host, and
shall be capable of controlling access, managing alarms, and interfacing with an array of
hardware devices, all while providing the decision-making oversight that each system
configuration requires.
E.
The intelligent controller shall provide centralized biometric template management
and support a wide range of reader technologies, including Wiegand, magnetic
stripe, and biometric 2-wire RS-485 connectivity.
F.
The intelligent controller shall be capable of supporting up to 64 doors in paired and
or alternate reader configurations with peripheral interface devices.
281326.01-1
Honeywell Pro-Watch 6000
Guide Specifications in CSI Format
Release 1, Rev. A, www.security.honeywell.com
2.2
2.3
TECHNICAL SPECIFICATIONS
A.
Primary power: The device shall support twelve to twenty-four volts of direct current (1224VDC) ± three hundred milliamperes (300mA) maximum.
B.
Communication Ports: The device shall provide the following communication ports:
1.
Host Port 0: 10/100 Ethernet
2.
Host Port 1: RS-232, 2-wire RS-485, or Ethernet adapter
3.
Peripheral interface Port 2: 2-wire RS-485
4.
Peripheral interface Port 3: 2-wire RS-485
C.
Inputs: There shall be a dedicated tamper input and a dedicated power monitor input.
D.
Temperature: The device shall tolerate zero to seventy degrees Centigrade (0-70° C)
operational, and minus fifty-five to eighty-five degrees Centigrade (-55-85° C) storage.
E.
Humidity: The device shall tolerate ten to ninety-five percent (10-95%) relative humidity,
non-condensing (RHNC).
F.
Standards:
1.
The device shall comply with UL294 Recognized, CE Compliant, ROHS.
2.
The device shall comply with FCC Part 15 Class A, NIST Certified Encryption.
TECHNICAL FEATURES
A.
B.
Connectivity:
1.
There shall be a Primary Port 10/100 Ethernet.
2.
There shall be an IP Server, IP Client, and DHCP Client.
3.
The device shall support HTTP, TLS, and X.509.
4.
There shall be a back up channel: RS-232, RS-485, or Dial-up.
Access Control: The device shall provide 600,000 Cardholder capacity, 50,000 Transaction
buffer, and If/Then Macro capability.
281326.01-2
Honeywell Pro-Watch 6000
Guide Specifications in CSI Format
Release 1, Rev. A, www.security.honeywell.com
C.
D.
Card Formats:
1.
There shall be eight active card formats per intelligent controller.
2.
The entire card number shall be reported on invalid read.
3.
The device shall support 19-digit (64-bit) (maximum) User ID s and 15-digit
(maximum) PIN numbers.
4.
The device shall be PIV-II, CAC, and TWIC card compatible.
5.
The device shall provide up to 32 access levels per cardholder.
6.
The device shall include activation and deactivation dates.
Card Reader Functions:
1.
The device shall provide multiple card format support by reader.
2.
The device shall provide paired reader support.
3.
The device shall provide alternate reader support.
4.
The device shall provide elevator support.
5.
The device shall provide turnstile support.
6.
The device shall provide biometric device support.
7.
The device shall be Open Supervised Device Protocol (OSDP) compliant.
8.
The device shall provide an occupancy count.
9.
The device shall support multi-occupancy rules.
10.
The device shall provide the following anti-passback support:
a.
Area-based, reader-based, or time-based
b.
Nested area, hard, soft, or timed forgiveness
11.
The device shall support host-based approval rules.
12.
The device shall provide keypad support with programmable user commands and
card input.
281326.01-3
Honeywell Pro-Watch 6000
Guide Specifications in CSI Format
Release 1, Rev. A, www.security.honeywell.com
E.
F.
Database Functions:
1.
The device shall provide a configurable card database.
2.
The device shall support up to nineteen (19) digital card numbers.
3.
The device shall support PIN codes up to fifteen (15) digits.
4.
The device shall provide programmable card activation and deactivation times and
dates.
5.
The device shall provide a card issue code, ADA and VIP flags (up to 32 bits), PIV (75
bits), and Smart Card (200 bits).
6.
The device shall provide up to 128 access levels per user.
7.
The device shall provide the ability to track people and objects.
Intrusion Alarm Functions:
1.
The device shall support entry delays and exit delays.
2.
The device shall provide area monitoring.
3.
The device shall provide standard alarm masking.
4.
The device shall provide control and alarm processing from the keypad.
END OF SECTION