JB-QB-5EiX fire alarm control panel operation manual

advertisement
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Hello!
Thanks to use JB-QB-5EiX Fire Alarm Control Panel!
This customer manual will let you know the super function of this fire alarm control panel step by
step.
Our Stipulations
In below descriptions:
 Words or chart symbol included in【】express press key,for example:
【
page key,
reset
key.
【Reset】expresses


】expresses upturn
Each device which is connected with fire alarm control panel is arranged with one logic
address. This address is expressed via sub number, zone number and location number. The
sub number is this panel number or controller panel number. The combination of sub number,
zone number and location number confirms one addressable device. Relevant device address
assignment is referred to Appendix A.
Device address expression format is SSZZNNN. SS expresses this panel number or controller
panel number. ZZ expresses device zone number of this panel. NNN expresses location
number.
1 General
1.1 Application Scope
This panel is suitable to be used in normal industrial and residential buildings.
1.2 Standard Compliance
BS EN 54 Part 2
1.3 Terminology
1.3.1 Supervise signal:control panel supervised other input signal excluding fire alarm and
fault signal, such as, water level detection, intrusion detection, pressure, temperature, air
conditioner and so on.
1.3.2 Fire alarm trigger device:smoke detector, heat detector, manual call point,
hydrant call point, multi-sensor and other device.
1.3.3 Supervise signal input device: signal input module device which can acquire
supervising signal.
1.3.4 Fire alarm control (associated control ) device:includes remote control module,
external control output unit and audible and visible sounder control unit.
1.3.5 Bus device:fire alarm trigger device, supervise signal input device and remote control
module for associated control application.
1.3.6 Start:fire alarm control panel sends out control signal to associated controlled device.
1.3.7 Response:feedback signal of associated control device
1.3.8 Analog value : bus equipment produced digital code which expresses sensitive
1
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
phenomenon value. For example, smoke detector analog value has relation with site smoke
density (direct ratio), heat detector analog value has relation with site temperature (direct
ratio).
1.4 Characteristics











2
Complete English information display.
Black box record function.
2500 units intelligent bus device capacity
5 pieces manual external control units
Alarm address information 2nd conversion-accurately positioning alarm address
( English input)
Site programmable fire alarm control function
Be able to send alarm information to fire repeater and CRT system
Detector data quantification function
Bus device type automatic recognition
Closed-circuit wiring
CAN bus networking function
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
2 Principle of operation
Fire alarm control panel operation principle:when fire parameter exceeds one threshold
value, fire alarm trigger device will be activated and send out alarm signal to fire alarm
control panel. After fire alarm control panel confirms fire alarm signal, it will send out audible
and visible alarm signal. It will display fire alarm position simultaneously and record fire
alarm time. Based on pre-set program, it will send out control command to associated
operation devices. Fire alarm control panel operation principle diagram is show in Fig.1.
LCD
Keyboard
power switch
unit
LED
main control unit
control output
contact
Bell
Printer
Sound & Light
siren
Bus device
Fire Alarm Repeater
Fig.1 Fire alarm control panel schematic diagram
3
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
3 Technical Data
Sheet 1
fire alarm control panel technical data
Main power supply
AC 220V (+10%~-15%) ,50HZ
Back-up power supply
DC 24V,12AH(built-in)
work consumption
Supervising status:≤30W;alarm status:≤50W(all 25 units
fire detectors are in fire alarm status)
Basic supervise capacity
10 loops,250 addressable points per loop;
External control unit
5 pieces
External control unit contact
capacity
DC 30V,1A.
Polling cycle
≤10 seconds(single point continuous searching in
abnormal situation)
Signal transmission distance
≤1000 m(RVS-2×1.0mm2)
;≤1500 m(RVS-2×1.5mm2)
;
Alarm line wiring method
2-wire bus
Voltage in alarm bus
24V (18V~26V)
Operation temperature
0℃~55℃
Relative humidity
≤95%
Black box record number
Be able to keep latest 999 pieces records, including opening
machine, close machine, reset, fire alarm, supervising,
associated operation and fault alarm).
Associated
operation
programmable number
100 pieces, including OR1, OR2 & AND logic.
Location conversion capacity
10×250 pieces, each can have 20 English characters.
Fire alarm output relay
1 set(KA1、KA2), voltage free contact, close when there is
fire alarm
Fault output relay
1 set(YA1、YA2)
,voltage free contact, close when there is
fault
4
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
4 External appearance、size、weight
This fire alarm control panel adopts wall mounted structure. There is internal 12AH
rechargeable battery. The structure is compact and beautiful.
4.1 External Appearance
Fig.2 FACP External Drawing
5
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
4.2
Internal drawing
Fig.3 FACP internal structure diagram
4.3 External Size
H×W×T(mm3)
:540×380×127。
6
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
4.4 Installation dimensional drawing
R3
8
mounting
hole
400
entrance
hole
90
540
250
R
5
290
380
Fig.4 FACP installation dimensional drawing
4.5 Installation method
This fire alarm control panel adopts wall mounted method.
4.6 Weight
This fire alarm control panel weight is around 17.5Kg.
7
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
5 Installation, commission
5.1 External wiring terminal layout diagram
T11+
T11+
T11-
T11T12+
loop alarm bus 3
T12+
T12-
T12-
T21+
T21+
T21-
T21T22+
loop alarm bus 4
T22+
T22-
T22-
T31+
T31+
loop alarm bus 5
T32+
T32-
T32-
T41+
T41+
loop alarm bus 9
T41-
T41T42+
loop alarm bus 8
T31-
T31T32+
loop alarm bus 7
loop alarm bus 6
T42+
loop alarm bus 10
T42-
T42-
Loop board 1
Loop board 2
Dig.5 FACP external wiring terminal layout diagram
8
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
The control panels and controllers can establish master-slave network via CAN
Bus. When control panels and controllers are connecting with each other, the 2 panels
CAN interface which is located in CAN bus terminals should connect 240Ω end of line
resistor.
5.2 Installation Technical Requirement




5.3
Fire alarm control panel should have good earth protection. There is earth
symbol inside the panel. Earth requirement should comply with the relevant
requirement of BS EN 54 Part 2.
Fire alarm control panel should be installed in the room or location where
there is person in charge. The panel should be tightly fixed onto the wall
with ancillary tight screw. The distance from the panel bottom side to the
floor should be 1.5 meters. Both sides should have more than 0.5 meters space
to make operation and maintenance as easy as possible.
24V power supply line adopts fire resistant multi-line plastic flexible cord
2
whose sectional area is no less than 2.5mm . When the transmit distance is
2
less than 1000 meters, the signal line adopts RVS-2×1.0mm twin-color
twisted multi-stock plastic flexible cord. When the transmit distance is
2
less than 1500 meters, the signal line adopts RVS-2×1.5mm twin-color
twisted multi-stock plastic flexible cord.
Before commission, construction side should install bus devices into proper
positions and connect them into alarm bus based on construction blueprint
and various bus device operation manuals.
Commission step
5.3.1 Wiring
1) Based on construction blueprint, check and make sure that all input output
lead lines specifications which are connected to this panel will meet design
drawing requirement.
2) Use 500V megameter to check all input output lead lines, whose earth resistor
valve should be equal or great than 200MΩ. If the lead lines cannot meet
this requirement, please ask construction person to eliminate the fault
before move to next step operation.
3) Connect lead lines based on “external wiring terminal layout diagram”.
5.3.2 Open machine
Open fire alarm control panel front shutter, simultaneously switch on main power supply and
back-up power supply switch. After the control panel is initialized, indicator LEDs and sounders
will go through self-testing and show stand by interface (Dig.6). The power supply LED flashes.
At this time, push down 【menu】key and control panel enters commission status. Input correct
password (Dig.7) and the operator will see commission menu (Dig.8). Attention, various front
serial numbers in the commission menu does not express commission steps or turns.
9
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Dig.6 FACP stand by interface
Security
Please entry supervisor password
★★★★
Dig.7 input password display interface
Include blew 3 functions :
1. Device test
2.Type settings
3.Record select
Test menu
1. Time
2. Register
3. Browse
4. Location
5. Program
6. System
7. Settings
8. Exchange
9. Customize
0. Exit
Press number key to select function
Dig.8 commission menu interface
5.3.3 Set up time
In the commission menu, push down 【1】key to set up system time (Dig.9). Attention,
wrong time will not be accepted by the system. If this control panel is master panel
in the network system, after master panel time is setting, all controller time in
the network system will be automatically setting.
10
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
1.Time
10/03/2007 10:37:00
ENTER-confirm,ESC-return
Dig.9 Time setup interface
5.3.4 Register device
All external devices, which include fire detectors, external control output unit
connected device and fire repeater, should be first registered in the system before
they can play respective roles. This register process is device registering. In
commission menu, push down 【2】key to enter device register function (Dig.10), is
able to register bus device (Dig.11) and other external devices (Dig.12). Notice,
in Dig.12, only when this panel is master panel in the networking system, the No.
4 item “ controller” can be displayed in the LCD screen.
2. Register
1. Register bus device
2. Other device
0. Return
Press number key to select function
Dig.10 Equipment Registering Menu
Dig.11 Register bus device interface
11
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
registered device
numbers
Register other device
1.Extl control unit
2.Fire Alarm Repeater panel
3.Printer
4.Slave
5
1
Yes
03
Dig.12 Register other external device interface
5.3.5 Browse registered information
Browse system registered device situation, such as device number, register value,
position information, total numbers and so on. In commission menu, push 【3】key
to enter register browse function (Dig.13).
device registered
value
device
number
device type
device location information
(pls refer to 5.3.6)
01L :225
3. Browse
001
002
003
004
005
006
007
27
28
27
28
27
28
27
SMOK room 1001
SMOK
SMOK
SMOK
SMOK
SMOK
SMOK
Loop 1 device
total number
UP DOWN-page,LEFT RIGHT-loop,ESC-return
Dig.13 Browse registered information interface
If the device has confirmed to be connected into the system, but in “register
browse”, the operator cannot browse this device number. The operator can see this
device operation status in “parameter test”. In commission menu (Dig.8) push 【7】
->【1】 key to enter parameter test function (Dig.14). There are two display methods
for parameter test function. One is digital display. Another is curve display. Push
【menu】key to be able to make conversion between these two display methods.
device registered
value
Device test
01L
loop number
No: 001
RegValue: 27
CurValue: 11 27
Type: HEAT
device current
smoke value
UP DOWN LEFT RIGHT- page
MENU-linear
mode,ESC-return
-
Fig.14 Device test interface
12
device current
heat value
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Each detector analogue value has 2: smoke value and heat value. Based on fire
detector type, we can judge whether current value is smoke value or heat value. If
the detector type is heat detector, the current value is referred to heat value.
Other type devices are referred to smoke value. If fire detector current value is
lower than 12, the detector will be not registered into the system. The detector
should be replaced. External control output unit is assigned to No.11 zone. It takes
the addresses from No.1 to No.5. It only has one value and does not matter with heat
or smoke value.
If detector actual type is not same as displayed type, the operator can enter
“type settings” to modify detector type to actual type. In commission menu, push
7】key->【2】key to enter type setting function (Dig.15).
number range which
need to re set-up device type
Type settings
Range: 01L-008N-009N
Type: SMOK
MENU-type,ENTER-confirm,ESC-return
Fig.15 type setup interface
Notice: here type setup cannot do sub-division to output module.
5.3.6 Edit device position information
Position information is detector installation position. If there is fire alarm,
the operator will accurately find the alarm position. In commission menu (Dig.8)
push 【4】 key to enter position information editing function/position description
(Dig. 16).
4.Location
Number: 01L-111N
Location:
ABCD
ENTER-confirm,ESC-return
Fig.16 Edit location information interface
This function supports English and digits input. When input device number, if
push 【menu】key, the LCD screen “number” behind will have one “*”symbol. At
this time, if the operator push 【confirmation】key to confirm input numbers, the
control panel will not assign out original position information. The panel will treat
current position place information as this number’s position information. This
13
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
process is one very simple position information copy function. Copy previous one
position information to this number to simplify the device position information
editing which has been installed in the same place.
In addition, we can use computer to set up device position information. In
control panel close-down status, please use RS485/RS232 converter to connect MA and
MB to computer serial port. Power on panel and enter into commissioning menu and
push down 【8】key and come into “Exchange”function. At this time, we can use computer
based special software to edit, upload and download device position information.
5.3.7 Associated operation programming
Associated operation programming is used to set up: when fire alarm control panel
receives fire alarm signal, if the system is under automatic status, how it should
implement fire alarm control function, that is: under what kind of fire alarm signal,
it should control what kind of fire associated operation devices. In commission menu
(Dig.8), push 【5】key to enter associated operation programming function (Dig.17),
the system supports 3 logic relations: “AND”, “OR1”, “OR2”.
“AND”logic expresses:any one piece device alarms which has been set into
Condition 1 range, and any one piece device also alarms which has been set into
Condition 2 range, it will send out control signal to associated operation device
which has been set into activation range.
“OR1”logic expresses:any one piece device alarms which has been set into
Condition 1 range, or any one piece device alarms which has been set into Condition
2 range, it will send out control signal to associated operation device which has
been set into activation range.
“OR2”logic expresses:any two pieces devices alarm which have been set into
Condition 1 range, or any two pieces device alarm which have been set into Condition
2 range, it will send out control signal to associated operation device which has
been set into activation range.
After set up needed associated operation programming data, all data items in
next page should be set as 0. If we set 5 pieces (one piece per page, start from
Page 0) programming data, we need to set No.5 page data item as 0.
Page 01
5.Program
Logic :
Condition1:
Condition2:
Associate:
AND
01S-01L- 001N-010N
01S- 01L- 021N-022N
01S- 03L- 001N-001N
MENU-logic,ENTER-save,ESC-return
Fig.17 associated control programming interface
In addition, we can use computer to set up associated operation programming
information. In control panel close-down status, please use RS485/RS232 converter
to connect MA and MB to computer serial port. Power on panel and enter into
commissioning menu and push down 【8】key and come into “Exchange”function. At
14
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
this time, we can use computer based special software to edit, upload and download
associated operation programming information.
5.3.8 Other parameters set
Record select This control panel can record fire alarm, supervising, start,
response, fault, event into black box. Beside fire alarm, all other types are
optional items. It can make a choice between record and non-record. In commission
menu, push 【7】key->【3】key to enter record select function (Fig.18). Each item
has both “Yes” and “not necessary” 2 options. The users can do setting based
on their own application requirement.
Record select
01/05
Record supervisory signal
Yes
MENU-status,ENTER-save,ESC-return
Fig.18 Record select function interface
System management,in commission menu, push 【6】 key to enter system management
function (Fig.19), there are several important operation parameters shown as below
in the system management:
01/12
6.System
Real-time print AlarmInfo
Yes
MENU-status
ENTER-save,ESC-return
Fig.19 system management function interface
1) Permit real-time printing: set whether it should print out alarm message
in alarm situation.
2) Fire repeater broken line fault: whether to permit poll fire repeater, if
yes, when there is communication fault between the panel and fire repeater,
it will send out fault information.
3) This panel number:to be used to set up this panel number.
4) Linkage activation only in automatic status: we use associated operation
device response signal as associated operation condition logic relation.
It is called as linkage activation. In normal situation, linkage activation
is not restricted by fire alarm control panel automatic and manual status.
That is, it can be implemented in manual status. But due to safety concern,
it can also be implemented in automatic status, same as other alarm signals.
15
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Here, if we set “yes”, concerned linkage activation only can be
implemented in automatic status.
5) Send alarm information to CRT:whether to send alarm information to CRT or
not.
6) Communicate with Center Panel: set up”yes”, activate the communication
function with central control panel;if several JB-QB-5EiX control panels
want to use CAN bus to establish networking system, this item should be set
as “no”.
7) This panel capacity:each loop can connect 250 addressable bus devices. But
due to customer consideration, maybe we will reduce the addressable device
points for each loop to meet specific project addressable points requirement.
The panel loop capacity is fixed in our factory and the user cannot modify
the capacity by themselves.
8) Z102:if this control panel is JB-QB-5EiX closed-loop fire alarm control
panel, please set this item as “NO”.
Password setup
The control panel can be set up as different level password to distinguish
user authorization level. There are three sub items in “Test Menu>>Customize>>
Password settings”: “Distributor Password”,“Client Password”,“Operator
Password”. These items can be used to set up distributor password, client
password and operator password. The distributor password can use all control
panel functions. But it cannot change distributor password. The client password
can use all control panel functions. But it cannot change distributor password
and client password. The operator password functions are limited to silence,
reset, browse historical record, disable equipment and set up time. There are
10 pieces operator passwords at maximum.
After set various parameters, the panel returns to stand by interface. The
system will move to normal supervising status.
16
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
6 Use、operation
6.1 information display and inquiry
This control panel has fire alarm (refer to 6.2), supervising alarm (refer to 6.3), fire alarm
control (associated operation control) (refer to 6.4), fault alarm (refer to 6.5) and disable functions
(refer to 6.6). When control panel is under these statuses, the LCD display screen will have
relevant display to indicate various status detailed information. The screen has been divided into 6
parts to display these statuses. These 6 parts are: basic information display zone (take 1 line), fire
alarm information display zone (take 2 lines), supervising information display zone (take 2 lines),
associated operation information display zone (take 2 lines), fault information display zone (take 2
lines), disable information display zone (take 1 line). Interface shown these information is called
as information interface (Fig.20).
Fig.20 Information display interface
Basic information display zone:display control panel model, current time, first fire alarm
zone number and alarm time, audible and visible sounder status (activated, fault and disabled) and
so on. When there is fire alarm or audible and visible sounder status, it will not show this panel
model. Basic information display zone displayed content is shown in Fig.21 and Fig.22.
Fig.21 basic information display zone content(1)
Fig.22 basic information display zone content (2)
17
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Fire alarm information display zone:display fire alarm total, current fire alarm number,
fire alarm zone number, alarm time, device type and device position information. When fire alarm
number is more than 1 piece, the fire alarm information will be automatically shown circulated.
Fire alarm information display zone displayed content is shown as Dig.23.
Dig. 23 fire alarm message display zone content
Supervising information display zone:display supervisory alarm total, current page,
supervised device zone position number, alarm time, device type and device position information.
Supervising information display zone displayed content is show in Dig.24.
Dig.24 monitoring information display zone content
Associated information display zone:display associated operation total, activated total (in
current associated operation information, how many devices are in the activated status), response
total ( in current associated operation information, how many devices are in the response status),
current page number, associated operation device zone position number, activated time, response
time, device type or device position information. Associated information display zone displayed
content is show as Fig.25.
Fig.25 associated control information display zone content
18
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Fault information display zone: display fault total, current page number, fault device zone
position number, alarm time, device type and device position information. Fault information
display zone displayed content is shown in Fig.26.
Fig.26 fault information display zone content
Disabled information display zone:display disabled total, current page number, disabled
device zone position number, device type and device position information. Disabled information
display zone displayed content is show in Fig.27.
Fig. 27 shield information display zone content
Each display zone just displays one piece corresponding information. When information
amount is more than 1 piece and focal point is located in this display zone, the operator can use
【 】 or 【 】key to browse other information in this display zone.
Push【 】or【 】to switch display focal point, display other corresponding status information
outside the basic information display zone. If the display zone has display focal point, it will have
“>>”symbol before the information content display. Only the display zone which has display
focal point can use page-turn function to browse this display zone other information.
6.2 Fire alarm
In normal supervising status, the panel polls each registered detector, closely
supervises each detector current smoke density or heat value. Make calculation and
recognition for this parameter based on algorithm. If it meets fire alarm
establishing condition, it will immediately move to fire alarm status. At this time,
the control panel will implement below steps:
1) Send out fire alarm sound, panel front fire alarm LEDs will be illuminating.
2) LCD screen fire alarm display zone displays current fire alarm detailed
information, updating fire alarm total and so on.
19
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
3) Printer(when printer is installed and under real-time printing option)
prints out fire alarm address and fire alarm time.
4) Control panel fire alarm voltage free output contacts KA1 and KA2 are closed.
5) Activate audible and visible sounder.
6) If the associated operation is under automatic status, based on pre-set logic
relation, the panel will send out control signal to associated control
devices.
7) Write alarm records into black box.
8) Send out fire alarm information to fire repeater and CRT(if it is permitted
to send out the information).
The control panel fire alarm status can only be eliminated by manual reset
operation.
6.3 Supervising alarm
Supervising signal is input signal connected into control panel. But these
signals are not fire alarm system internal signals. These signals include water level
detection, intrusion detection, pressure, temperature, air conditioner and other
various signals. When control panel receives these input signals, it will move to
supervising alarm status, at this time, the control panel will implement below steps:
1) Send out supervising alarm sound, illuminating panel front supervising LEDs.
2) LCD screen supervising display zone displays current supervising detailed
information, updated supervising total and so on.
3) Printer (install this ancillary product and permit real-time printing
optional function) prints out supervised device address and alarm time.
4) If the associated operation is under automatic status, based on pre-set logic
relation, the control panel will send out control signal to associated
operation devices.
5) Write alarm records into black box(if it is permitted to write ).
6) Send out fire alarm information to fire repeater and CRT(if it is permitted
to send out the information).
The control panel supervising alarm status can only be eliminated by manual reset
operation.
6.4 fire alarm control(associated operation control)
When audible and visible sounder or other fire associated operation devices are
activated, the control panel will implement below steps:
1) Send out associated operation sound, illuminating panel front associated
operation LEDs.
2) LCD screen associated operation display zone displays current associated
operation detailed information, updated associated operation total,
response total and so on.
3) Printer (install this ancillary product and permit real-time printing
optional function) prints out associated operation device address and
activated time.
20
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
4) When it receives activated device response signal, based on pre-set logic
relation, it will send out control signal to associated operation device.
That is linkage activation (under manual status whether it can do linkage
activation based on “system management” “only in automatic status
linkage activation”setting).
5) Write associated operation records into black box(if it is permitted to
write ).
6) Send out associated operation information to fire repeater and CRT(if it
is permitted to send out the information).
6.5 Fault alarm
When there are below situation, the control panel will send out fault alarm
signal:
1) Control panel to fire detection supervising abnormal due to control panel
to fire detector link line broken, short circuit, detector to base link line
broken and detector self-damaged.
2) Wiring line between control panel and fire repeater broken and short circuit,
which make communication unusual.
3) Wiring line between control panel and AV sounder or fire associated
operation device broken and short circuit, which make supervising unusual.
4) Main power supply (AC220V power supply) voltage is lower than 187V,
including power failure.
5) Back-up power supply (control panel internal back-up power supply) power
failure or internal 24V output is lower than 21.8V, back-up power supply
battery does not charge.
For above 1)
、2)
、3)faults, the control panel will implement below steps:
1) Send out fault warning sound, illuminating panel front fault LEDS.
2) LCD screen fault display zone displays current fault detailed information,
updating fault total and so on.
3) Printer (install this ancillary product and permit real-time printing
optional function) prints out fault device address and activated time.
4) Control panel fault voltage free contacts YA1 and YA2 are closed.
5) Write fault records into black box(if it is permitted to write ).
6) Send out associated operation information to fire repeater and CRT(if it
is permitted to send out the information).
For above 4)
、5)faults, the control panel will implement below steps:
1) Send out fault sound, illuminating corresponding main and back-up power
supply fault LEDs.
2) Printer (install this ancillary product and permit real-time printing
optional function) prints out fault device address and activated time.
3) Control panel fault voltage free contacts YA1 and YA2 are closed.
4) Write fault records into black box(if it is permitted to write).
21
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
After fault is eliminated, all fault signal can be reset by automatic way or
manual way.
6.6 Disable function
Disable is: when there is unusual situation for some system components in the
engineering commission, or due to temporarily change environmental application
purpose, it needs to close one or several devices functions via fire alarm control
panel. In “disable setting”, it can do device disable or disable release operation.
In supervising status, push 【menu】key, the LCD screen will make indication to input
password (Fig.28). After input correct password, enter function menu (Fig.29), in
the function menu, there are three function items which include disable setting
(Fig.30), history record and time setting. Push 【1】 and enter disable setting
function.
Security
Please entry supervisor password
★★★★
Fig.28 password validation interface when enter the function menu
Function menu
1. Disabled settings
2. History record
3. Time settings
4. Test Menu
0. Exit
Press number key to select function
Fig. 29 function menu interface
Disabled settings
Number: 01S-00L-000N
ENTER-disable,ESC-enable,RESET-return
Fig.30 shield setup function interface
22
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
The control panel can disable below devices: bus devices, alarm bus, control
output contacts, fire audible and visible sounders and so on. When there is device
which has been disabled, the control panel front disable LEDs will be illuminating.
The disabled information will be displayed in disable display zone. The latest
disable information will always be displayed in most front place.
6.7 History record
History record is black box record. The control panel can record latest 999
pieces relevant information. Even after the control panel power failure, the
information can be kept for ten years. Based on these records, the user can make
judge of control panel, fire detector and other external devices operation status.
The control panel can record below information type which includes fire alarm,
supervising, associated operation (including start and response), fault, event
(such as machine open, close down) and so on. Besides fire alarm record is one must-do
record, other type records are optional. Detailed information is referred to
“record selection” function. In function menu, push 【2】to enter history record
browse function. Its interface is shown in Fig.31.
Fig.31 History record browse interface
In addition, all historical record information of fire alarm control panel can
be uploaded to the computer. The uploaded information can be stored in the computer.
Please use RS485/RS232 converter to connect MA and MB to the computer serial port.
Power on panel and enter into commissioning menu and push down 【8】key and come
into “Exchange”function. At this time, we can use computer based special software
to read historical record information of control panel and store the information
into the computer.
6.8 Sound
The control panel can send out 3 different sounds to make difference for
different alarm status. When there is fire alarm or fire alarm control signal output,
the control panel will send out fire brigade wagon sound. When there is fault alarm,
the control panel will send out ambulance sound. When there is supervising alarm,
the control panel will send out police vehicle sound.
23
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
When there is new alarm information coming, based on the control panel current
status, the panel will decide whether it will send out corresponding alarm sound
or not. The control panel alarm status is arranged from high to low as: fire alarm,
supervising alarm, fire alarm control and fault alarm. If the control panel is
sending out high level alarm sound, when the low level alarm information is coming,
the control panel will not send out this low level alarm sound. If the control panel
is in silence situation, when there is any level alarm information coming, the
control panel will send out this level alarm sound.
Alarm sound can be manually eliminated by pushing 【silence】key. At this time,
the panel front silence LEDs will be illuminating. If the control panel is in sounding
status or non-alarm supervising status, control panel front silence LEDs will be
extinguished.
6.9 Reset
When there is fire alarm, supervising, fire alarm control and fault information,
in information interface or stand by information (main power or back-up power supply
fault does not need to be indicated by LEDs, it is not displayed in the information
interface), push 【reset】key to manually eliminate these information. But if these
alarm signals are still existent, the control panel will quickly establish these
information. Disable information can only be done through disable release operation.
It cannot be eliminated by reset. When the system is reset, its interface is shown
as Fig.32.
system reset…
Fig.32 system reset interface
6.10 Self-testing function
In information interface or stand by interface, push 【self-testing】key to make
testing to LCD display screen, panel front LEDS and sounders. After self-testing,
it will automatically come back to polling status. When the system is in self-testing,
its interface is show in Fig.33.
24
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
System testing
Fig33. system self-testing interface
6.11 Manual control function
The control panel has 5 sets control output contacts, which are used to control
fire associated operation devices. There is corresponding manual direct control
button for each control output. The button is located in control panel front side.
It is indicated by Control 1, Control 2, Control 3, Control 4 and Control 5. The
button is self-locking type button. When the operator pushes down the button, the
button is self-locked. The corresponding red LED in the button is flashing. The
output contact is closed. When push down the button once again, the button springs
back and red LED is extinguished. The output contact is separated. If the
corresponding controlled device response signal is coming, whether the button is
pushed down or spring back, the LED in the button is illuminating.
There is one evacuate button on the control panel. When we push down this button,
all addressable AV sounders in the bus loop will be activated. When we push down
the button once again, all addressable AV sounders in the bus loop will be silenced.
The system cannot automatically identify addressable AV sounders. So we need go
through Test Menu>>Customize>>AV Sounder range and manually set up which devices
are addressable AV sounders.
The silence button of the control panel can eliminate control panel internal
speaker alarm sounder. In addition, in automatic mode, it can silence activated
addressable AV sounders. When we push down silence button once again, it can enable
the a/v sounders which were activated during automatic mode. It is different from evacuate
button. When we push down silence button, it just silence activated AV sounders. It is not
eliminated from associated control buffer.
6.12 Auto/Manual(hand) Switch
In automatic status, when there is fire alarm, based on associated operation
programming setting logic relation, the control panel will send out control signal
to associated operation devices. In manual/hand status, there is no this kind of
automatic activation. In information interface or stand by interface, push
【manual/auto】key, input correct password, it will do auto/manual status switching.
If the control panel is in auto status, the control panel front auto/manual LEDs
will be illuminating. When the control panel is in manual status, the LEDs will be
extinguished. Input password and do auto/manual switch interface is shown in Fig.34.
25
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Security
Please entry Auto/Hand switch password
★★★★
Fig.34 input password to do auto/manual switch interface
6.13 Lock key/ lock release
There is one indicated “lock key” and “lock release” key switch. When the
key is turned to “locking key” position, the control panel keyboard is locked.
In this condition, the operator just can do “silence” operation. When the lock
is turned to “locking release” position, all keyboard functions are open.
6.14 networking function
Several sets JB-QB-5EiX control panel can establish network alarm system via CAN
bus. Notice: this alarm system is master-slave network rather than equal system. In the
network system, there must have one panel to be used as master panel. If in
“commissioning menu>> system management” menu, set “this panel number” equivalent as
“ master panel number”, this control panel will be automatically become the master panel in the
network. The total number of panels in the network system should be less than 30 sets panels.
Master panel has following functions:
1)receive controller alarm information and display it;
2)control controller’s output module;
3)adjust various controller’s time setting of network system;
4)eliminate controller alarm sounder;
5)reset controller alarm information;
6)when there is communication fault between master panel and controller, the
master panel will send out “controller fault” information. But it should first
register controller in the master panel.“register” method is referred to
“register device”.
Notice:
1.if you want to use CAN bus to establish networking system, you should forbid
“Communicate with Center Panel”function.
2.if the control panel is not in the network system, please set “master panel
number” as 0.
26
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
7 Fault analysis and elimination
Sheet 2
fault and elimination method
fault phenomenon
Reason analysis
Elimination method
When the panel is
open, it does not
do self-testing,
there is on any
response from the
control panel
whether the main
power supply and
back-up power supply
work as normal
check
power
back-up
work as
When the panel is
open
and
do
self-testing, the
LEDs flashing is
slow and the sound
is not strong
Programming chip is
not
installed
tightly
Fix the chip tightly
once again
When the panel is
open,
the
LCD
displays clobber
characters
Library
chip
or
programming chip is
broken or does not
fixed tightly
Replace or fix the
chips tightly once
again
When the panel is
open, control panel
LEDs and sounder
self-testing is ok,
but the LCD screen
does
not
have
back-light
and
display
LCD screen contrast
gradient is too small
to see its display
content
Adjust
main
board
contrast
gradient
potentiometer
When the panel is
open, the left top
side of LCD screen
displays
“verification
and wrong!”
1. control panel
main power supply and
back-up power supply
voltage is low;
2. chip which keeps
data is broken.
Close down the power
supply and open the
panel once again, if it
still cannot solve the
issue, please contact
the
product
manufacturer.
When the panel is
open, the left top
side of LCD screen
displays “ main
power supply and
back-up
power
supply voltage is
lower!”
Main power supply
and back-up power
supply voltage is low
and the system cannot
work as normal.
Check whether the 220V
main power supply is
normal or not.
whether main
supply
and
power supply
normal
27
remark
Individual
detector
makes
fault alarm
Detector in one
sub-line
makes
fault alarm
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
1. the connection 1.check whether this
line between fire detector base 24V is
detector
and working as normal;
control panel is 2. If the line is normal
short circuited or and
detector
base
broken;
voltage is normal,
2. fire detector please replace the
falls off;
detector.
3. fire detector is
damaged;
1. the connection
line between this
sub-line and main
line
is
short
circuited or broken;
2. one detector
fault in sub-line
makes
isolator
activated.
1.
check
whether
this
sub-line voltage is normal or
not;
2. check whether sub-line
isolator is activated or not. If
it
is
activated,
we
can
confirm that there is one fault
detector behind this isolator.
Please open the panel once
again and enter “parameter
testing” function to browse
this
sub-line
detectors
operation status to find fault
fire detector.
There is fire or
smoke cause factor
in
the
fire
detector
testing
zone, but the fire
detector makes fire
alarm
There is dust or
damage in the fire
detector.
Replace fire detector
Main power supply
fault
LEDs
is
illuminating
Main power supply
voltage is lower than
187V
Check whether main
power supply is working
as normal
Back-up
power
supply fault LEDs
is illuminating
Back-up
power
supply
is
power
failure or internal
24V output is lower
than 21.8V.
Check whether
power supply is
as normal and
the internal
expired.
28
back-up
working
whether
battery
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
8 Maintenance、repair
Fire alarm control panel is specialized fire device. The operator should be
trained by our company. After the operator has passed our internal training, the
person can do the normal operation. The panel should be located in the rooms where
there is person in charge. It should have do regular management and maintenance.
The panel should be regularly checked to see whether it is working as normal and
do duty record. When there is fault for the panel operation, the operator should
eliminate the fault in time. If the operator cannot solve the panel issue by himself,
he should invite professional persons or manufacturer to help him do panel repair
work.
When the main power supply is power cut and the system uses back-up power supply,
if the control panel sends out back-up battery fault alarm signal, it indicates that
panel internal back-up battery voltage is lower, at this time, the operator should
take other compensation measures to avoid control internal back-up battery
excessively discharges which can damage the battery.
9 Open panel package and checking
After open panel package, check whether panel external appearance is complete
and whether control panel model is same as package box model indication.
In package box, there are below items:
1) One set control panel;
2) One set control panel operation manual;
3) one set certificate of approval;
4) two sets keys(total 4 keys)
,locking key and control panel front key;
5) three pieces screws;
6) eight pieces fuse(2A 2 pieces,3A 2 pieces,5A 4 pieces)
。
10 Others
10.1 Service promise
Concerning any produced provided by our company, our company and our sales office &
after-sale service department will provide the customers with relevant technical data and technical
support. We help the customer do system commission and after-sale service, such as system and
product maintenance and repair work. Our company has established specific customer files and
use computer to manage these files and make quality tracking and we try our best to provide our
customers with best service.
10.2 Quality guarantee
The system device guarantee time is 12 months. In this guarantee period, if our
product quality has made the system product faulted or damaged, our company will
make free repair or replacement.
29
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
10.3 Contact method
WUXI BRIGHTSKY ELECTRONIC CO.,LTD
LUOSHE TOWN,
WUXI CITY,
JIANGSU PROVINCE,214187,
P.R.CHINA
Telephone
+86-510-83340037
Fax
+86-510-83340037
Email
coo@bsky.cn
30
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Annex.A
Device address assignment sheet
Zone number
Position
number
Device
1
1~250
Correspond to the devices in loop 1 alarm bus, position
number is corresponding to bus device code
2
1~250
Correspond to the devices in loop 2 alarm bus, position
number is corresponding to bus device code
3
1~250
Correspond to the devices in loop 3 alarm bus, position
number is corresponding to bus device code
4
1~250
Correspond to the devices in loop 4 alarm bus, position
number is corresponding to bus device code
5
1~250
Correspond to the devices in loop 5 alarm bus, position
number is corresponding to bus device code
6
1~250
Correspond to the devices in loop 6 alarm bus, position
number is corresponding to bus device code
7
1~250
Correspond to the devices in loop 7 alarm bus, position
number is corresponding to bus device code
8
1~250
Correspond to the devices in loop 8 alarm bus, position
number is corresponding to bus device code
9
1~250
Correspond to the devices in loop 9 alarm bus, position
number is corresponding to bus device code
10
1~250
Correspond to the devices in loop 10 alarm bus, position
number is corresponding to bus device code
11
1
Control output unit 1
11
2
Control output unit 2
11
3
Control output unit 3
11
4
Control output unit 4
11
5
Control output unit 5
11
11
Audible and visible sounder
11
12
Loop 1 alarm bus short circuited
11
13
Loop 1 alarm bus broken
11
15
Loop 2 alarm bus short circuited
11
16
Loop 2 alarm bus broken
11
18
No.1 fire repeater
11
19
No.2 fire repeater
11
20
No.3 fire repeater
11
21
No.4 fire repeater
11
22
No.5 fire repeater
11
23
Main power supply
11
24
Back-up power supply
11
25
Power on
11
26
Shut down
31
11
27
JB-QB-5EiX Fire Alarm Control Panel Operation Manual
Lock key
11
28
UnLock key
11
29
Reset
11
30
Auto
11
31
Manual
11
32
Test
11
33
System fault
11
34
Settings mode
11
35
Running mode
11
36
Loop 1 alarm bus
11
37
Loop 2 alarm bus
11
38
Printer
11
40
1 loop T+ line broken
11
41
1 loop T- line broken
11
42
2 loop T+ line broken
11
43
2 loop T- line broken
11
44
Loop 1 fault
11
45
Loop 2 fault
11
46
Loop 3 fault
11
47
Loop 4 fault
11
48
Loop 5 fault
11
49
Loop 6 fault
11
50
Loop 7 fault
11
51
Loop 8 fault
11
52
Loop 9 fault
11
53
Loop 10 fault
11
54
Loop board 1 fault
11
55
Loop board 2 fault
11
56
Loop board 1 checksum
11
57
Loop board 2 checksum
32
Download