16000-1 section 16000

advertisement
____________________________________________________
SECTION 16000 – GENERAL ELECTRICAL REQUIREMENTS
PART 1- GENERAL
1.01
1.02
DESCRIPTION
A.
This Section includes the general provisions applicable to
electrical work and testing of the completed electrical
systems. Where conflicts exist the requirements of other
sections take precedence over the requirements of this
section.
B.
Process equipment, pumps, electrically operated valves;
plumbing, HVAC equipment, etc. are specified in other
Sections and are not a part of Division 16. The electrical
connections to these devices and the requirements for
motors, starters, motor control centers, panelboards and
other work are specified in the appropriate sections of
Division 16.
C.
Division 16 covers, is be construed as a complete description
of all the construction required.
D.
The Contractor shall provide all labor, materials, equipment,
appliances and tools and perform all work necessary for the
completion of all electrical work as shown on the contract
drawings, described in the specifications, as required to
properly and completely operation all electrical systems, in
compliance with all applicable codes, regulations, and Long
Island Power Authority requirements.
E.
Electrical Contractor shall provide all conduit, wiring, fittings,
terminations, and all devices necessary to provide power and
control for the sewage pumping station complete. The
electrical contractor shall provide all terminations at and
between devices, controls and equipment
QUALITY ASSURANCE
A.
All electrical work shall be performed by licensed electricians
experienced in the type of work included in this project. The
electricians shall be familiar with all electrical standards,
codes, ordinances and laws.
16000-1
B.
The electrical contractor shall provide an on site supervisor
with a minimum of three (3) years experience in pump station
power and control requirements.
C.
All work shall comply with:
D.
1.03
1.
Requirements of the Long Island Power Authority (LIPA).
2.
National Electrical Code (NEC).
3.
Federal, state and local ordinances, codes, regulations.
4.
Requirements of Underwriters Laboratories, (UL) for all
equipment provided for which UL standards have been
established.
Obtain and pay for all permits and inspections required.
Electrical inspections shall be made and approved by the
Board of Fire Underwriters or other state and/or local authority
having jurisdiction
SUBMITTALS
A.
The Contractor shall submit shop drawings in accordance
with Section 01300.
B.
Copies of all required permits.
C.
Catalog cuts and shop drawings of all materials and
equipment.
D.
Installation instructions and operation and maintenance
manuals for all equipment.
E.
Three (3) copies of electrical inspection certificates.
F.
As-built wiring diagrams, ladder and single line drawings and
circuit directories.
16000-2
1.04
1.05
1.06
DELIVERY STORAGE AND HANDLING
A.
Deliver equipment in crates or cartons and do not uncrate
until ready for installation.
B.
Store all materials and equipment in accordance with the
manufacturers’ recommendations.
C.
Temporarily close all pipe openings to prevent obstruction.
JOB CONDITIONS
A.
Make arrangements with the Long Island Power Authority to
provide temporary and permanent electrical service to the
pumping station.
B.
The construction drawings indicate the general scope of the
electrical work. If any changes are required to comply with
codes or Long Island Power Authority requirements, the
contractor shall, notify engineer to obtain approval prior to
installing any unspecified materials or equipment.
SCHEDULING/SEOUENCING
A.
Before installing electrical work, the contractor shall review
the project with the Long Island Power Authority and verify
compliance with all applicable codes arid regulations.
B.
The Contractor shall notify the engineer at least 48 hours in
advance of all starting of work, suspension of work and/or
testing.
PART 2- PRODUCTS
2.01
GENERAL
A
Unless otherwise approved the contractor shall supply only
the equipment specified, from one source and manufacturer.
B
All material and equipment shall be new and of the best
quality and shall conform to UL standards and carry the UL
label.
16000-3
2.02
2.03
2.04
NAMEPLATES
A.
Provide nameplates for all items of equipment.
B.
Nameplates shall be black laminated plastic or bakelite,
approximately ¾”x 2-1/2” x 1/16” with edges beveled.
Lettering shall be engraved, white, with a height of ¼” or
larger.
C.
Provide two holes in nameplates and secure to equipment
with stainless steel screws.
SUPPORTS
A.
Provide all structural supports required for proper attachment
of all equipment. Wall mounted equipment may be directly
secured to walls with approved anchors.
B.
Maintain at least ¼” space between equipment and wall.
Steel channels manufactured by Kindorf shall be used were
necessary
C.
Equipment supported from ceilings shall be installed by
D.
In outdoor areas or where indicated or required, conduit
mounting hardware shall be 316 stainless steel.
MATERIAL AND CONSTRUCTION
A.
2.05
Unless otherwise specified, all enclosures shall be:
1.
Indoor, above ground, dry areas — NEMA 12 316
stainless steel.
2.
Outdoors and other specified area and below grade
areas NEMA 4X 316 stainless steel.
CONDUITS, BOXES, WIRES AND CABLES
B.
Conduit and boxes shall comply with Section 16111.
C.
Wires and cables shall comply with Section 16120.
16000-4
2.06
2.07
LOCKS
A.
Unless otherwise specified all disconnect switch located
outdoors or out off site of the device or devices controlled,
shall be provide with lockable disconnects and locks.
B.
Locks shall be rust proofed. All locks shall be of the type that
will not permit the entrance of water and subsequent
freezing. All locks shall be keyed a-like with a minimum of four
keys.
TOOLS/SPARE PARTS
A.
Provide all tools that are necessary for the proper operation
and maintenance of the electrical system.
B.
Furnish two (2) sets of fuses or circuit breakers for each fuse or
circuit breaker.
C.
Furnish two (2) spare lamp bulbs for each lamp.
PART 3- EXECUTION
3.01
INSPECTION
A.
3.02
Carefully inspect the installed work of other trades and verify
that such work is sufficiently complete to commence any
electrical work.
PREPARATION
A.
The power requirements and sizes of equipment are subject
to change and will be based on the approved product or
substitution actually provided. The contractor is required to
provide as necessary different sized wires, cables conduits,
boxes, starters, overload protection fuses and other electrical
equipment and controls. Equipment shall not be ordered
until shop drawings and other submissions have been made
and approved by the engineer and any other regulatory
authority.
16000-5
3.03
3.04
3.05
PENETRATIONS
A.
Where required, make penetrations prior to the application of
roofing and waterproofing materials and to provide all
sleeves, pitch pockets and other approved.
B.
Seal all duct work and penetrations which enter or leave a
room or structure which may contain a corrosive or
potentially lethal atmosphere.
TESTING
A.
For all 3 phase equipment, check for proper phase sequence
before energizing such equipment.
B.
Upon completion of the work of this Section, conduct all tests
required to secure approval of the installation from all the
owner, the engineer or regulatory agonies.
C.
All systems shall test free from short circuits and ground and
ground of not less than that required by NEC specifications.
D.
Conduct a ground test on each and every circuit. The test
results shall not be less than those required by the NEC.
E.
Test all electrical devices for proper control of motors and
equipment.
F.
Lamp all fixtures with lamps of designated rating, color, etc.
G.
Check amperage in all circuits, and compare to nameplate
data.
ADJUSTMENTS AND FINAL CLEANING
A.
Clean all electrical work; remove all unnecessary labels, soil,
markings and foreign material.
B.
Do not remove labels required by the specifications, laws,
regulations, codes and labels warning of hazards, denoting
special operating and maintenance procedures or labels
with other important or meaningful messages, directions or
warnings.
16000-6
3.06
PROTECTION
A.
Protect the electrical system, during and after installation.
B.
If damaged, immediately make all necessary repairs and
replacements.
END OF SECTION
16000-7
PAGE INTENTIONALLY LEFT BLANK
16000-8
Download