detcon inc. Detcon Model 1010-N1 Rack Panel Mount Control Enclosure Operator’s Installation & Instruction Manual July 15, 2004 • Document #2655 • Version 1.1 Table of Contents 1.0 Introduction 1.1 Description 1.2 Specifications 1.3 Remote Reset 1.4 Installation 1.5 Start-Up 1.6 Maintenance and Repair 1.7 Spare Parts 1.8 Warranty Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.1 1.0 INTRODUCTION Detcon Model 1010-N1 Rack consists of 3 major assemblies: 1. The NEMA 1 rack mount control enclosure. 2. The single channel digital control modules. 3. The remote mount gas sensor assemblies. The NEMA 1 control enclosure is detailed in section 1.0 of the manual, the control modules in section 2.0, and applicable sensor assemblies in section 3.0. 1.1 DESCRIPTION Detcon Model 1010-N1 along with Model 10B digital control modules is designed to serve as a host assembly for up to ten remote mount gas detection sensor assemblies. The control enclosure is rated NEMA 1 suitable for installation in non-hazardous locations. The single channel modular design supports application flexibility wherein multiple function gas detection systems can be configured in any combination up to ten channels. All control modules are plug-in front panel accessible for easy maintenance and repair. The control enclosure houses a modular power supply (Model PS100-10B) which includes, as standard operating controls, a power on/off switch and a line power fuse. Discreet output terminal strips located on the controller motherboard are provided for sensor terminations, Form C dry contact alarm outputs (normally open, normally closed and common) for two alarms plus fault, 4-20 mA outputs for remote recording devices, and RS-485 serial Modbus™. Additional terminations are provided for VAC power in, VDC power in, and remote alarm reset. Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located on the controller mother board. 1.2 SPECIFICATIONS Electrical Classification NEMA 1 Dimensions 19"W, 5.25"H, 8"D Capacity 10 Single Channels Power Input 117VAC/24 VDC Alarm Contacts Discreet Fault, Low, High, per Channel 5 Amp @ 30VDC/5 Amp @ 125VAC Common, Normally Open and Normally Closed Outputs Discreet 4-20 mA DC Serial RS-485 Modbus™ Operating Temperature Range -40°F to +175°F Power Consumption <5 Watts per Channel (includes gas sensor and control module) Warranty One Year Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.2 1.3 REMOTE RESET The reset function is effective when the Model 10B's respective alarms have been programmed in the latching position and alarm conditions have passed. The alarm reset function is common to all controllers and is activated by closing the circuit between the two reset contacts. A normally open momentary switch is suitable. 1.4 INSTALLATION 1. Securely mount the 1010-N1 rack enclosure in accordance with Figure 1. Fig. 1 5.25 .375 Panel cutout (centered) 17.75" x 5" Panel depth - 8" 2.25 .218 Slot Detail use 10-32 screw 19 Note: Reference figure 2 for wiring terminations Caution: Observe correct polarity when terminating all input/output field wiring. Failure to do so may result in circuit damage on power up. Typical Each Channel Alarm Jumper Tabs Fig. 2 L1 VAC IN N GND VDC IN + – A(+) RS-485 B(–) Shield Normally Closed Common Low Alarm Normally Open Normally Closed Common High Alarm Normally Open Normally Open Common Fault Alarm Normally Closed + Common 4-20 mA Output + Signal (mA) External Reset Close to Reset + – Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.3 Sensor 2. Connect 117VAC input to the terminal strip labeled “VAC IN” (L1, N, GND). 3. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+ and –). 4. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip (labeled RESET) located on the controller mother board. 5. If applicable, terminate the discrete 4-20 mA output to external device(s). Terminals are labeled “(+) 420” and “(–) 4-20”. 6. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “A (+)”, “B (–)”, and “SHLD”. 7. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate field wiring from sensors to Model 1010-N1 rack lugless terminal strips located on the controller mother board. 7. Alarm relay outputs may be discrete, zoned, or common via gold plated jumper tabs. Configure accordingly. Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete. 1.5 START-UP Upon completion of all field wiring: Depress the power switch located on the front panel. Note that each Model 10B controller digital display illuminates. Varying readings may occur during sensor warm-up. A 10 second alarm delay will occur on power up. Refer to sections 2.0 and 3.0 for additional start-up detail. 1.6 MAINTENANCE AND REPAIR The Detcon Model 1010-N1s modular design allows for minimum down time during maintenance and/or repair. A model 10B control module may be changed by turning the latch knob clockwise until it stops and then sliding it out of the panel by pulling on the latch knob. To install, slide the 10B control module into the 1010-N1 control enclosure and then secure by turning the latch knob counter-clockwise until it stops. See section 3 for more information on the 10B control module. The Model PS100-10B 100 watt power supply can be replaced by turning the latch knobs clockwise until they stop and then sliding it out of the panel. A new power supply can then be installed or the existing one repaired. It is recommended that VAC and VDC power be removed from the 1010-N1 motherboard before doing maintenance on, or replacing the power supply. Replacement of the power switch, or fuse holder is accomplished by: removing the power supply from the panel; disconnecting the plug from its respective header; remove the wires from the plug of the component to be replaced; snap the component out of the PS100-10B face plate and then reassembly with the new component. Reference the PS100-10B schematic/wiring diagram in figure 3 for wiring details Replacement of the power supply itself is accomplished by: removing the PS100-10B power supply module from the panel; disconnecting the 2 connectors from the back of the power supply; removing the 4 screws that mount the power supply to the bracket; then reassembly with the new power supply. Reference the PS100-10B schematic/wiring diagram in figure 3 for wiring details. Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.4 Fig. 3 This side toward front of power supply assembly Power Supply DC Out 16ga x 9" BLK 16ga x 9" RED + + + +S –S – – – Power Supply GND N L 1 6 Power Supply P1 VAC In 16ga x 6" GND - GRN N - WHT L1 - BLK 1 16ga x 6" 2 16ga x 6" 3 P2 Power Switch BLK 16ga x 6" BLK 16ga x 6" TAN 22ga x 6" TAN 22ga x 6" RED 16ga x 6" RED 16ga x 6" D1 6A 50V P5 P3 Fuse L1 In N In GND In +DC In –DC In +DC Out –DC Out D2 6A 50V BLK 16ga x 3" BLK 16ga x 3" P4 1.7 SPARE PARTS 0224 951-585510-100 360-GPFC11-024 2812 298-000000-000 320-3217-1 2806 320-32800-1 910-000008-003 Gold plated jumper tab PS-100 100 watt modular power supply (complete plug-in power supply module) 110 watt, 24 VDC switcher power supply (replacement power supply for PS100-10B) 24 VDC lamp for power switch 2 amp 3AG slow blow fuse Power switch assembly Green switch cap (for power switch) Fuse holder Assembly Model Series 10 Blank Plate 1.8 WARRANTY Detcon inc., as manufacturer, warrants under intended normal use each new Model 1010-N1 rack control enclosure to be free from defects in material and workmanship for a period of one year. The warranty period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas. Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 77381 Mailing Address: P.O. Box 8067, The Woodlands, Texas 77387-8067 phone 888-367-4286, 281-367-4100 • fax 281-292-2860 • www.detcon.com • sales@detcon.com Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.5