INSTALLATION INSTRUCTIONS

advertisement
INSTALLATION INSTRUCTIONS
AR24
REMOTE CONTROLLED SURGICAL LIGHT
TEC-B-0022 REV5
1/14
Page 1
EQUIPMENT LABELS AND SPECIFICATIONS
ATTENTION, CONSULT MANUAL FOR FURTHER INSTRUCTIONS.
INDICATES SPECIAL USER ATTENTION.
AC VOLTAGE
3A
FUSE TYPE 3 AMP, SLOW BLOW TYPE
5A
FUSE TYPE 5 AMP, SLOW BLOW TYPE
CLASS I, IPXO RATED, CONTINUOUS OPERATION
WARNING
This equipment is intended for use by healthcare professionals only. The Positioning Wand
may cause radio interference or may disrupt the operation of nearby equipment. It may be
necessary to take mitigation measures, such as using the wall control for positioning only.
PERMISSIBLE ENVIRONMENTAL CONDITIONS
DURING TRANSPORT AND STORAGE (IN ORIGINAL PACKAGING MATERIALS)
• AMBIENT TEMPERATURE:
-10° - 60° C (14° - 140° F)
• RELATIVE AIR MOISTURE:
10% - 85%, NO CONDENSATE BUILD-UP
• AIR PRESSURE:
500 hPa - 1060 hPa (14 in-Hg - 31 in-Hg)
DURING USE - FOR DRY LOCATIONS
• AMBIENT TEMPERATURE:
15° - 30° C (60° - 85° F)
• RELATIVE AIR MOISTURE:
30% - 60% NON CONDENSING
• AIR PRESSURE:
700hPa - 1060 hPa (20.7 in-Hg - 31.3 in-Hg)
AR24 INSTALL • REV5
Page 2
The lighthead Data Labels contain the lighthead
model number, bulb type, fuse type, electrical specifications
and product serial number.
LIGHTHEAD LABEL
GRAND RAPIDS, MI · 1.616.656.2900
! REFER TO ACCOMPANYING DOCUMENTS !
ELECTRICAL RATING
INPUT
20VAC
BULBS TYPE
CAT. NO.
3.6A
H24100
AR24
72W
60Hz
24V
100W
SERIAL NO.
0000
Manufactured for SKYTRON by DAI-ICHI SHOMEI CO., LTD. TOKYO, JAPAN
AR24
WALL CONTROL LABEL
WALL CONTROL LABEL
GRAND RAPIDS, MI · 1.616.656.2900
GRAND RAPIDS, MI · 1.616.656.2900
! REFER TO ACCOMPANYING DOCUMENTS !
ELECTRICAL RATING
INPUT
120VAC
OUTPUT
FUSE
3A
1.75A
20VAC
CAT. NO.
! REFER TO ACCOMPANYING DOCUMENTS !
B5-011-99
ELECTRICAL RATING
210W
60Hz
INPUT
7.2A
144W
OUTPUT
SLOW BLOW
SERIAL NO.
FUSE
0000
Manufactured for SKYTRON by DAI-ICHI SHOMEI CO., LTD. TOKYO, JAPAN
DUAL FIXTURE
120VAC
5A
3.5A
20VAC
CAT. NO. B5-011-100
420W
60Hz
14.4A
288W
SLOW BLOW
SERIAL NO.
0000
Manufactured for SKYTRON by DAI-ICHI SHOMEI CO., LTD. TOKYO, JAPAN
QUAD FIXTURE
AR24 INSTALL • REV5
Page 3
MOUNTING GUIDELINE
1/2" DIA
ALL-THREAD ROD
(See Note 1)
ELECTICAL
J-BOX
(See notes)
9-1/16"
8-1/2"
15"
Finished Ceiling
3/4"
20-1/2"
(Minimum Ceiling Opening)
FIXTURE
23-7/8"
(Square)
1. 1/2" Diameter support rod centered in fixture opening for total
support of light. All labor and materials for fabrication, 1/2" nuts
and washers (2 each required) for fixture attachment, contractor
supplied.
2. All wiring, conduit, and other electrical materials as well as
installation labor for such materials associated with the installation
of the SKYTRON light fixture to be provided by electrical
contractor. All installations of SKYTRON lighting fixtures should
be under the direct supervision of a SKYTRON service
representative.
3. All wiring to be in accordance with local codes. 120 VAC, 20A
Dedicated Circuit.
4. Wall Control measures 4-1/2" deep, 7-3/4" x 7-3/4".
5. Wall Control to Light Head wiring requires 5 color coded 14AWG
wires to each lighthead.
4-1/2"
3"
3"
1"
7-3/4"
7-3/4"
SIDE VIEW
3-1/2" RECESS DEPTH
BACK VIEW
JUNCTION
BOX
7-3/4"
WALL CONTROL
7-3/4"
6-11/16"
6-11/16"
L
VE
TY
LE
NSI
IR
INTE
0
1
2
IN
3
4
5
WER
PO
L
VE
MA
TY
LE
NSI
IR
INTE
V e
, 125Fus
3A w
Blo
w
Slo
ANCHOR (4)
RECESS
MOUNT
FLANGE
CONTRACTOR
SUPPLIED
FASTENERS
RECESSED MOUNT
AR24 INSTALL • REV5
FRONT
PANEL
ANCHOR (4)
0
V e
, 125Fus
3A w
w Blo
Slo
CONTRACTOR
SUPPLIED
FASTENERS
SURFACE MOUNT
1
2
IN
3
4
5
WER
PO
MA
FRONT
PANEL
Page 4
AR24 ROUGH-IN BOX TYPICAL INSTALLATION
PART # B5-012-41
WARNING
Pay close attention to wiring diagrams and wire color coding. Incorrect wiring may result
in High Voltage (120VAC) being supplied to Low Voltage circuits. This WILL DAMAGE
internal circuitry and components VOIDING WARRANTY.
AR24 INSTALL • REV5
Page 5
INSTALLATION CLEARANCES
To prevent damage to the light fixture the following minimum
clearances must be maintained:
1. Centers of adjacent (two or more) fixtures: 3 feet
2. Top of fixture and overhead building member: 5 inches.
2. Loosen the 1/4 turn screw securing the light assembly to
the housing and lift the edge of the assembly. See figure 2.
PHOTO
EYES
3. Fixture center to side wall: 1-1/2 feet.
WARNING
Risk of FIRE. DO NOT install insulation
within 3 inches of fixture sides nor above
fixture in such a manner to entrap heat.
1/4 TURN
SCREW
PRE INSTALLATION REQUIREMENTS
1. Appropriate metal conduit & wiring installed from wall
control mount to ceiling mounting structure.
2. 1/2" diameter support rod centered in fixture opening.
See Mounting Guideline.
Figure 2.
3. Release the spring pins, disconnect the electrical
connector and remove the assembly from the housing. See figure 3. Set the light assembly aside being careful
not to contact the photo eyes.
3. 120VAC, 20amp dedicated power supply line in separate
conduit to be provided at wall control.
4. Painting and flooring must be complete prior to fixture
installation.
INSTALLATION INSTRUCTIONS
1. Set the fixture on a flat surface and loosen the two 1/4 turn
screws on the cover and remove the cover. See figure 1.
SPRING
PIN
ELECTRICAL
CONNECTOR
Figure 3.
COVER
1/4 TURN SCREWS
NOTE
Figure 1.
AR24 INSTALL • REV5
Failure to follow mounting structure
guidelines may result in poor performance.
Page 6
4. Check mounting structure details (on back page) and
install housing onto threaded rod.
NOTE
7. Remove the shipping retainer (figure 5), install the wiring
connector, reinstall the lighthead assembly in the housing
and secure with the 1/4 turn screw.
SHIPPING RETAINER
Threaded rod must not extend more
than 1 inch inside housing to prevent
interference with light assembly movement.
5. Align lighthead housing front cover screws as shown
in figure 4 for proper lighthead/wall control orientation.
HEAD
COVER
SCREWS
FOOT
END
A
Figure 5.
B
8. During the installation process, the Argos II can be
configured to provide additional degrees of articulation for
low angle lighting. This can be accomplished by positioning
the Retainer Plate into the appropriate position within the
housing/enclosure. See figure 6.
2 LIGHT SYSTEM
COVER
SCREWS
A
C
HEAD
FOOT
END
B
COVER
SCREWS
D
RETAINER PLATE
46° POSITION
STD. POSITION
4 LIGHT SYSTEM
Figure 4. Lighthead Orientation
6. Connect the 5 color coded wires from the wall control box
(through conduit) to the lighthead housing junction box
as shown in the wiring diagrams. Observe wire colors
carefully and make all wire connections using wire nuts.
Figure 6.
AR24 INSTALL • REV5
Page 7
9. Observe wire color codes and connect wires from light fixture to wall control wires using wire nuts. See Wiring
Diagrams.
NOTE
To ensure proper performance use
Skytron supplied bulbs ONLY. P.N.
B5-011-32.
CAUTION
CAUTION
Use 14 AWG wire MINIMUM. Make all
wire connections with wire nuts.
Fixture has a thermal protection device.
Blinking light may indicate heat build-up
due to improper installation clearances.
10.Install wall control panel. Refer to figure 7, mounting
guideline (page 3) and wiring diagrams.
FIXTURE GROUND
(GREEN/YELLOW)
OUTPUT
(RED & WHITE)
120 VAC
INPUT
OUTPUT
350 W
120 VAC
INPUT
A
ITY
L
VE
LE
NS
IR
E
INT
0
1
2
TO LIGHTHEAD
(BROWN & YELLOW)
3
4
5
R
IN
MA
WE
PO
V
25 se
, 1 Fu
3A low
B
w
Slo
Figure 7.
NOTE
Depending on length of 1/2 inch threaded rod and finish ceiling construction,
some fixture movement may be noticed
during operation. If so, shims may need
to be added between finished ceiling
and housing to prevent side movement
of the fixture.
AR24 INSTALL • REV5
Page 8
YELLOW
Bulb 24V 100W
BOX
TRANSFORMER
350W
TOUCH PAD
TOUCH PAD
A
WRG
PANEL, front
120 VAC, 20A
INPUT
BROWN
A
BROWN
B
Bulb 24V 100W
RED
B
YELLOW
WHITE
GREEN
WIRING DIAGRAM - 2 LIGHTHEAD SYSTEM
A dedicated circuit with a 20A Circuit Breaker is required for proper operation.
AR24 INSTALL • REV5
TOUCH PAD
TOUCH PAD
AR24 INSTALL • REV5
Bulb 24V 100W
Bulb 24V 100W
BOX
TRANSFORMER
350W
PANEL, front
C
A
WRG
YELLOW
120 VAC, 20A
INPUT
A
BROWN
C
RED
Bulb 24V 100W
Bulb 24V 100W
WHITE
D
B
GREEN
B
D
WIRING DIAGRAM - 4 LIGHTHEAD SYSTEM
Page 9
A dedicated circuit with a 20A Circuit Breaker is required for proper operation.
Page 10
AR24 EYE ADJUSTMENT PROCEDURE
Light needs adjustment when:
A) Light searches from side to side
B) Light does not focus on the spot where the probe is
placed
2. Place your hand behind the probe bulb, at the usable
distance in that room (approximately 6’8”). Move the
probe in the “A” direction. If the light moves past or stops
before the probe, only then, should that eye be adjusted.
NOTE
3. If the spot moves past the probe (spot “A”), move the
eye in the “A” direction. This will bring the light back to
the probe. If the spot stops short of the probe (spot “B”),
move the eye in the “B” direction.
Before adjusting the light, make sure
your probe is charged.
CAUTION
1. Place electrical tape over the three eyes as shown in
Figure AB. The remaining eye will only adjust for the light
in the “A” direction.
This adjustment is VERY DELICATE
and only needs to be moved LESS
THAN 2MM. The handle of a screwdriver
will work fine with a LIGHT touch. Tap on
the eye in the direction needed, recheck
the location of the spot as in step #3.
The adjustment is complete when the
light spot stops at the probe.
4. The eye directly across must be adjusted next, Figure
CD. Remove the tape from the eye directly across from
the eye previously adjusted and place it on the adjusted
eye. The same steps should be taken as in steps 2 and
3. If the light moves past the probe (spot “C”), move the
eye in the “C” direction to bring the spot back to the probe.
If the spot stops short of the probe (spot “D”), move the
eye in the “D” direction.
5. Remove the tape from “A” and “B” eyes and check the
adjustment from side to side. If the light wants to wander,
tap either “A” or “B” out away from the center of the light
(less than 2mm).
Figure AB.
AR24 INSTALL • REV5
Page 11
Use the same adjustment procedure in steps 2 through 5
to adjust eyes “EF” and “GH”. Refer to Figures EF and GH.
If further assistance is needed, contact a SKYTRON Service
Representative.
Figure CD.
Figure GH.
Figure EF.
AR24 INSTALL • REV5
Page 12
INSTALLATION CHECK LIST
CK
Make sure light follows Probe at 8'
Check for searching - adjust eyes as necessary
LIGHTS
WALL CONTROL
PROBE
Check hinges on front cover
Remove shipping materials, Gimble retaining brackets
Clean filter/diffuser assembly
Ensure proper orientation of LH within room
Ensure that there are no obstructions that limit travel
Properly oriented
Test for proper function
Check fuse holder
Check operational & warning labels
Wall mounted
Check plastic casing for damage
Check operational & warning labels
Check probe on/off function
NA
AR24 INSTALL • REV5
Page 13
DAMAGED SHIPMENT CLAIM PROCEDURE
Whenever a shipment suffers damage while in the custody
of the transportation company, the responsibility lies with the
transportation company, and the value of the damages can
be collected from the transportation company if the proper
procedures are followed.
When a shipment is received in a damaged condition and
due to the appearance of the containers such as a broken
crate, torn wrapping, or smashed carton, the contents may
have been damaged. That fact should be noted on the Bill of
Lading offered by the transportation company. An example of
an applicable statement would be; "Received in good order
except as noted" or "Crate damaged, possibility of concealed
damage." The addition of these types of statements on
the shipping documents will automatically give grounds for
starting a claim. If damage cannot be identified on the exterior of the
container, but is found when the container is opened, further
unpacking should be stopped immediately and the container
with all wrapping or packing materials should be held. The
transportation company should be notified so an inspector
can be sent. Failure to follow either of these two procedures
may result in an inability to file a claim and collect for damage
done. Returning the container to the sender without such an
inspection may prevent filing a claim, because it will divide the
responsibility for damage and in many cases the transportation
company will return the shipment to the sender without charge
after the inspection.
AR24 INSTALL • REV5
The claim itself may be filed by either the shipper or consignee,
but the consignee must notify the transportation company
and the shipper that the damage has occurred. Remember
that refusal of the shipment or failure to note the possibility of
damage on the shipping documents may jeopardize the claim. Also, acceptance of a damaged shipment which has been
processed properly to allow for filing a claim, will not jeopardize
the position of the consignee. In any case, SKYTRON will
see that damage which is not the fault of the consignee or
his agents is corrected, if the transportation company does
not honor the claim, as long as SKYTRON receives the full
cooperation of the consignee in filing the claim.
Some of the papers needed for filing a claim are in the hands
of the consignee after the shipment has been received. If
SKYTRON must file a claim, we will request these papers by
name from the consignee at such time as the claim is under
discussion. We will require the originals of these papers and
not copies.
Knowledge of the procedures outlined above and your
cooperation in submitting damaged shipment claims will
help both you, our customer, and SKYTRON by assuring the
integrity of our products from manufacturing to installation. 5085 Corporate Exchange Blvd. S.E.
Grand Rapids, MI 49512 • 1.616.656.2900 • FAX 1.616.656.2906
Download