Eagle Eye Power Solutions IEEE Guide Interpretation based upon IEEE 450-2010, 1106-2005, 1188-2005 MONTHLY INSPECTIONS VLA VRLA NiCad Maintenance Activities (Perform ALL items checked for your battery type) Verify float voltage at the battery terminals X X X X X X X X X X X X X X X X X EEPS Solution IBEX Series Inspect general appearance and cleanliness of battery room or cabinet, racks, and batteries. Inspect for evidence N/A Visual of terminal, connector, and rack corrosion Verify charger output current and voltage Verify battery electrolyte levels Verify ambient temperature and ventilation systems Inspect for any unintentional battery grounds Record pilot cell's voltage, specific gravity, and electrolyte level Inspect all installed battery monitoring systems are operational IBEX Series ELM Series / SG-Series IBwatch / IBEX-Series GFL-Series SG-Series IBwatch / ELM-Series QUARTERLY INSPECTIONS VLA X X X Maintenance Activities (Perform ALL items checked for your battery type in addition to monthly VRLA NiCad inspections) X X Verify voltage of each cell Verify specific gravity of at minimum 10% of battery string cells X X Verify temperature of a representative sample of at minimum 10% of the battery cells X Verify float voltage & current at the battery terminals X Verify cell internal ohmic resistance values EEPS Solution IBwatch / IBEX-Series SG-Series IBwatch / BTM-Series IBEX Series IBwatch / IBEX-Series YEARLY INSPECTIONS VLA X X X X Maintenance Activities (Must perform ALL items checked for your battery type in addition to monthly and EEPS Solution VRLA NiCad quarterly inspections) SG-Series Verify specific gravity of all battery cells IBEX-Series X Verify AC ripple current IBEX-Series X Record each cell temperature IBwatch / IBEX-Series X X Verify cell-to-cell and terminal connection resistance X Inspect cell condition of each cell in contrast to the monthly inspection. Verify the structural integrity of the battery rack N/A Visual This guide is based upon IEEE 450-2010, 1106-2005, 1188-2005, and recommendation 1491. This does not substitute for use of those documents. We recommend that you thoroughly review each document prior to developing a maintenance program. Please contact Eagle Eye Power Solutions at 877-805-3377 or email at info@eepowersolutions.com for additional support. Copyright 2015 Eagle Eye Power Solutions, LLC