Site issues with Earth leakage Abstract General: This document examines one of the most common site issues with UPS systems, which is the tripping of the earth leakage protection, Residual Current Device (RCD) also known as an Earth Leakage Circuit Breaker (ELCB). Technical Description: One of the most common site issues with UPS systems is the tripping of the earth leakage circuit breakers ELCB / RCD. To examine this in greater detail, we need to look at this device: ELCB’s contain a core-balance transformer and work on the following simple principal: If the current which goes out on the phase does not return on the neutral, or on another phase, in the event of a three phase type, it will be detected as an earth fault through an imbalance in the core balance transformer and this imbalance will activate a tripping coil so that the circuit will be disconnected. Therefore, if one comes in contact with a live appliance, the current, which flows through this person to return to earth, is sufficient to trip a 30mA RCD instantly. Principles of Operation of a Standard RCD / ELCB Schematic diagram of RCD connected to earth fault showing principle parts of installation. COIL to detect Most Common Problems: When a customer calls with a problem with a tripping RCD, one should never assume that our unit is faulty without doing the required troubleshooting. 1) The EN50091 permits a leakage of up to 3.5 mA per pluggable appliance. If the customer has 10 appliances connected with an average 3 mA per appliance, we can have units tripping even without a faulty appliance. We should try and ascertain if it still trips when the UPS is connected on it’s own, if possible on a dedicated RCD. If this is the case, we should replace the unit, if not we should ask the customer to have his installation and other appliances checked. 2) There are also issues when power electronics are connected. Some SMPS loads cause high leakage after being switched on. In such cases we should recommend a selective type of RCD. These RCD’s have a slight delay, which allows them to overcome this relative short period of earth leakage. 3) In a new electrical installation RCD’s may trip due to an error in the wiring, such as neutral wires being mixed up at distribution board Tripping Currents The most common tripping current for an RCD is 30mA but there are also types with a tripping of 10mA and 100mA tripping current to offer shock protection. There is also a 300mA and 500mA, which gives overall protection against risk of fire from electrical faults in wiring etc. These are usually used at the main distribution board in a TT network, where the main fuse may not react fast enough in the event of a short circuit to earth.