12/05/14 DESIGN NO. _____ SECTION 15594 FUEL STORAGE EQUIPMENT PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. 1.02 1.03 RELATED SECTIONS A. Division 1 Sections (General Requirements) B. Divisions 2 to 9 Sections C. Division 15 Sections D. Division 16 Sections SUPPLEMENTAL SUBMITTALS A. B. NYCSCA Provide labor, materials and equipment required for the installation of a complete system for the storage of No. 2 fuel oil. Product specific requirements are contained herein; Section 15501, General Provisions for Heating, Ventilating and Air Conditioning Work shall be referred to for general requirements. Shop Drawings: 1. Equipment assembly-type drawing. Include dimensions, required clearances and method of field assembly, components, location and size of each field connection. 2. Provide dimensioned detailed piping layout. 3. For tanks, provide size and capacity, connection details, support and installation details. 4. Wiring Diagrams: Submit manufacturer's electrical requirements for power supply and control wiring for gauging, leak detection and overfill alarm systems. Clearly differentiate between portions of wiring that are factory-installed and portions to be field-installed. Federal, New York City and State Permits and Approvals: Submit a copy of all approved permits from the Department of Buildings, Fire Department, Department of Environmental Protection (Air Resources), Environmental FUEL STORAGE EQUIPMENT 15594 - 1 12/05/14 DESIGN NO. _____ Protection Agency (Federal), Department of Highways, and any other department having jurisdiction. C. An affidavit in duplicate, stating that the thickness of steel, inside and outside welding, and painting of the oil storage tanks fully comply with the requirements specified shall be obtained from the manufacturer and delivered to the Authority before tanks are shipped from factory. D. Submit all certificates of approval issued by the various agencies and all other departments having jurisdiction. E. Provide a set of Manufacturer’s guarantees for fuel storage and detection systems. F. Provide where directed two (2) charts and a sounding device (type based on headroom) for determining the amount of oil in tank when measured manually. G. Field quality-control test reports. H. Maintenance Data 1. I. 1.04 NYCSCA Maintenance Manual Contractor’s start-up and demonstration affidavit. QUALITY ASSURANCE A. Perform all Work in accordance with Rules and Regulations of the various government agencies, municipalities and utility companies. B. New York City and State Compliance: Obtain without charge to the Authority, the permits required for work in connection with this installation from the Department of Buildings, Fire Department, Department of Environmental Protection (Air Resources), Department of Highways, Utilities Company, any and all other department having jurisdiction. Secure all permits before starting the Work. C. Seismic Compliance. Fuel oil storage equipment shall be seismically braced/restrained in accordance with NYC Building Code Chapter 16. D. Special Inspections are required on any installation of fuel oil storage tanks, fuel oil piping, fuel oil storage vaults and all other items and accessories, in accordance FUEL STORAGE EQUIPMENT 15594 - 2 12/05/14 DESIGN NO. _____ with the requirements of New York City Construction Codes. NYCSCA E. At the completion of the Work, file all necessary final applications and relevant papers, Drawings, Amendments, and all other items and accessories and secure for the Authority all the approvals from the Building and Fire Department. F. Certificates of approval issued by the Building Department (CID), Fire Department, Department of Highways, and all other departments having jurisdiction in connection with this Work shall be submitted before final payment is made. G. Contractor shall register, file applications and obtain all related permits, certifications and approvals required by all agencies including but not limited to: 1. Plumbing Inspection - sign off (DOB/CID). 2. Fuel Oil Storage Inspection /Tests /Permit - (DOB/ Fire Department). 3. Environmental Protection Agency (Federal). 4. Compliance with New York State D.E.C. 6 N.Y.C.R.R. Part 612,613 and 614 with regard to fuel oil piping and storage systems. H. Testing of material shall be in accordance with Section §28-113 of the NYC Administrative Code (reference Section MC 301.5 of the 2014 NYC Mechanical Code). Whenever the NYC Construction Codes or the Rules of the Department of Buildings requires that material be listed or labeled and material proposed to be used is not so listed or labeled, the use of such material shall be subject to prior approval by the Commissioner (Office of Technical Certification and Research OTCR) and such material shall be used only to the extent set forth in such approval. Materials that were previously approved by the Board of Standards and Appeal (BSA) or by the Department (MEA) before the effective date of the NYC Construction Codes may continue to be used, but only to the extent set forth in such approval, and only if such approval is not specifically amended or repealed by the Commissioner. I. Fuel-oil storage and piping systems shall comply with the requirements of Chapter 13 of the 2014 NYC Mechanical Code and to the extent not otherwise provided for in the FUEL STORAGE EQUIPMENT 15594 - 3 12/05/14 DESIGN NO. _____ NYC Mechanical Code shall comply with the requirements of NFPA 31-2011. J. 1.05 All aboveground and underground storage facilities with a combined storage capacity of over 1,100 gallons shall also comply with the requirements of the New York State Department of Environmental Conservation’s Petroleum Bulk Storage Code per Section MC 1301.2. WARRANTY A. All warrantees shall be for one year and are to use the date of Substantial Completion as the warranty start date. PART 2 - PRODUCTS 2.01 OIL STORAGE TANKS A. Provide cylindrical fuel oil storage tanks of dimensions shown on the Drawings as per Section MC 1305.12. B. Tanks located below ground, inside or outside of buildings, shall comply with any one of the following design standards, as appropriate for the specific installation as determined by the engineer: 13 C. 13 NYCSCA 1. UL 58; such tanks shall be listed and labeled. 2. UL 1316; such tanks shall be listed and labeled; or 3. Alternate tank design and construction standards contained in Article D below. Tanks located above ground, inside or outside of buildings, shall comply with any one of the following design standards, as appropriate for the specific installation as determined by the engineer: 1. UL 80; such tanks shall be listed and labeled. 2. UL 142; such tanks shall be listed and labeled; or 3. ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 or 2; such tanks shall be listed or labeled; or 4. Alternate tank design and construction standards contained in Article D below. FUEL STORAGE EQUIPMENT 15594 - 4 12/05/14 DESIGN NO. _____ D. Each tank shall be fabricated of Class "A" steel plates made by the open hearth or basic oxygen process. The plates shall be free from physical imperfections, such as lamination, cracks, mill scale, etc. Steel must be new, in good condition, and free from rust. Tanks shall be welded throughout using double butt or double lap welds, and shall conform to the requirements of Section MC 1305.14. E. Welding for tanks shall be done by competent and American Society of Mechanical Engineers (ASME) Certified welders in a first-class manner. Lapped seams shall be not less than 2" and shall be continuously welded inside and outside. Nozzles for manholes and outlets for pipe connections shall also be continuously welded inside and outside. F. Openings: Provide openings shown on the Drawings, located on top of shell of each tank. Size of opening for each pipe connection shall be the size of pipe connected except as otherwise shown. Each manhole opening shall have a 3/8" thick or heavier steel cover plate with two (2) 1/2" diameter steel lift handles welded to plate, and shall be provided with 1/8" thick oil resistant ring gasket, and all other items and accessories. Provide in manhole cover plate a 3", half coupling with brass plug, welded to a 3" I.P.S. hole in plate. Cover plate and gasket shall be secured by 5/8" diameter brass bolts and nuts as required. Couplings for pipe connections shall be continuously welded inside and outside of tank and plates. Tank openings shall be plugged until pipe connections are made. G. Tank pressure. The tank shall be designed for the maximum static head that will be imposed with the normal vent piping filled with oil as per Section MC 1305.7.4. H. Ladder: From the manhole opening to the bottom of each tank, provide a ladder having 3/8 x 2½" bar steel sides not less than 16" apart and 3/4" diameter steel rod rungs spaced on about 12" centers. Rungs shall go through the sides and be welded in place. Ladder shall be fastened to tank with angle clips, and all other items and accessories. I. Paints and coatings used in the interior of building for oil tanks shall not: NYCSCA FUEL STORAGE EQUIPMENT 15594 - 5 12/05/14 NYCSCA DESIGN NO. _____ 1. Exceed the VOC content limits established in the Green Seal Standard GS-11 Paints, First Edition May 20, 1993. 2. Exceed the VOC content limit of 259 g/L established in the Green Seal Standard GC-03, Anti-Corrosive Paints, Second Edition, January 7, 1997. J. Storage tanks shall be thoroughly cleaned and painted on the outside at the factory with two coats of a heat resistant primer type of paint, and with one coat of black finish paint. The primer type of coating shall be of different shades to facilitate inspection of the painting. All damaged spots shall be touched up. (Refer to Section 09900: Painting). K. Identification (per Section MC 1305.14.1.5): At the time of installation, all storage tanks shall bear a permanently-fixed plate, spot welded or equivalent, bearing the name of the tank manufacturer, the gage of the material, and capacity of the tank. Shop fabricated storage tanks shall be installed without structural alteration. L. Provide emergency vent connections as per DEC and UL requirements for listed/labeled UL 80 tanks, UL 142 tanks and tanks built according to ASME Pressure Vessel Code Section VIII Division 1 or 2. Per Section MC 1305.8, fuel oil tanks designed in accordance with Section MC 1305.14 (alternate tank design and construction standards for oil-storage tanks other than those conforming to ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 or 2, UL 58, UL 80, UL 142, or UL 1316) shall not require emergency relief vent piping. The use of a self-closing manway cover, a manway cover provided with long bolts that permit the cover to lift under internal pressure, or other type emergency relief vent device, shall be prohibited. Reference Section MC 1305.8.1. M. Provide platform and ladder to tank exterior to accommodate access to manway cover. 3/8" x 2½" bar steel sides not less than 16" apart and 3/4" diameter steel rod rungs spaced on about 12" centers. Rungs shall go through the sides and be welded in place. Ladder shall be fastened to tank with angle clips, and all other items and accessories, as per OSHA requirements. FUEL STORAGE EQUIPMENT 15594 - 6 12/05/14 2.02 3 NYCSCA DESIGN NO. _____ OIL FILL AND VENT TERMINALS A. The fill opening shall be equipped with a tight metal cover. See Article 3.02.A.5. B. Each fill port shall be permanently marked with the American Petroleum Institute (API) symbol for #2 fuel oil: Green (color), Hexagon (symbol). Each fuel oil tank vent terminal shall be fitted with a hood. Fill terminal and vent hood shall each be identified by an approved permanent marking, with the tank number to which it is connected. C. Spill Containment (for fill pipes serving tanks greater than 660 gallons per Section MC 1305.6.6) 1. In ground spill containment: Storage tank fill lines shall terminate in a 5 gallon watertight spill containment manhole. The spill Containment manhole shall have hinged, locking waterproof covers that eliminates water and debris infiltration; cast iron base easily threads onto tank riser; cover actuated push drains opens when the cover is closed and closes when the tank is open; round access manhole mounts flush with concrete grade to avoid plow damage and EBW test plug. Spill Containment Manhole shall be EBW Inc Model 705-445-01. 2. Wall spill containment: Storage tank fill lines shall terminate at the fill station in a wall type spill container. The fill station shall have a minimum of 3.5 gallon holding capacity for spills and include: a door-seal, locking handle, NEMA 4 rated enclosure, Kamvalok "dry" disconnect fill adapter and dust cover. The enclosure shall be equipped with mounting couplings for 2" diameter galvanized mounting pipes or the enclosure can be surface mounted on the wall using mounting brackets. Cabinet shall be 12 gauge carbon steel and be equipped with 1/2" NPT drain connection. The door shall match the cabinet construction and be fully gasketed with a neoprene gasket. The door shall mount to the cabinet with a full length stainless steel piano hinge on one side and latch with locking handle on the opposite side. The entire interior shall be prime coated and painted with white enamel. Exterior shall be given two coats of exterior latex paint color to match adjacent exterior building finish. FUEL STORAGE EQUIPMENT 15594 - 7 12/05/14 DESIGN NO. _____ Provide with the spill containment fill station Civacon (Kamvalok) 1700D SERIES (1771D-SSXXX) Dry Disconnect Cam and Groove Quick Coupling and Kamvalok dust cover manufactured by OPW Engineered Systems. Both coupling devices shall be stainless steel body and guide fins with Buna N seals. The couplings shall be hydrostatically tested up to 200 psig for couplings up to 2", and 150 psig for couplings up to 3". Provide a redundant safety check valve. Check valve shall be a swing type, 125 class and shall be mounted in the fill pipe as close to the spill container as possible. Spill Containment Fill station shall be Type 2-CS1 as manufactured by Preferred Utilities Mfg. or Model SF-WALL-F as manufactured by Analytical & Combustion Systems. D. Vent hood shall be of galvanized cast iron and shall have a free area of not less than the vent pipe area. E. Overfill station: Provide near tank fill terminal an overfill alarm and silencing station and caution sign capable of monitoring each tank. The alarm station shall have NEMA construction, as required by Code and contain integral alarm bell, light for each tank and alarm silencing pushbutton. Overfill Alarm Station for the tanks shall be activated by the tank level gauge. An alarm signal from the tank gauge mounted high level switch shall energize bell and light(s). If the fill operator does not manually silence bell, in one minute it will silence automatically. Light shall remain lit until tank level drops below high level set point. Preferred Model FA-AVXDE, (Caution Sign, Preferred Model FA-S); Pneumercator Model No. LC100X ASC; OMNTEC Model No. RAS-X. F. Provide anti-siphon valve (per Section MC 1301.4) at highest points in Fuel Oil Suction line and spring loaded lever gate valve, between suction oil valve and duplex oil strainer. 8 2.03 TANK LEVEL GAUGES AND LEAK DETECTION A. NYCSCA Provide microprocessor based tank gauging system for central monitoring of fuel levels and leaks in all fuel oil storage tanks and any sumps or containers at shaft bases that contain oil risers per Section MC 1305.9.4 in the project. The system shall include an indicating instrument, level and leak detection sensors. The FUEL STORAGE EQUIPMENT 15594 - 8 12/05/14 DESIGN NO. _____ instrument shall have die-cast aluminum housing or NEMA type enclosure. Provide a continuous digital indication of tank contents directly in gallons, on-demand indication of contents in inches, and English language alarm displays, identifying each tank by a number. System shall contain all calibration adjustments. Flush mounted on the unit shall be an audible alarm and pushbuttons for liquid depth, alarm silencing and data recall. The system shall provide an output proportional to tank content in gallons, tank number and automatically silenced overfill alarm. Identify the tank that is in alarm condition. The system shall be Factory Mutual or U.L. Listed. B. Leak detector locations for single wall, above ground tanks and shaft bases: The system shall be capable of distinguishing between water and/or hydrocarbons and annunciating the specific alarm. - within tank vault/containment area - at any sumps or containers at the base of shafts that contain oil risers per Section MC 1305.9.4 C. Each system shall include the following: Display Unit: Preferred: TG-EL-D4A-E0-0-0 Pneumercator: TMS2000-21-81 OMNTEC: SCA-OEL8000II Level Sensor: Preferred: TG-EL-WF-C Pneumercator: Model MP-450 Pneumercator: Model MP-46xS-restricted spaces) OMNTEC: MTG-X OMNTEC: MTG-F (restricted spaces) Leak Detector: Preferred: HD-A2-C Pneumercator: Model LS-600-LDBN OMNTEC: LS-ASC 2 9 Connecting cable for level sensor and leak detector Preferred: #21655, Pneumercator 3 #18 AWG or OMNTEC EC-4 or EC 12: Sensor Cable and OMNTEC EC-2: Probe Cable. 7 For projects that utilize pneumatic control system, the electrical system shall receive general inputs from the leak detector and provide indication of the required alarm status. Refer to Electrical Section 16701: Auxiliary Signal System. For projects System/Direct NYCSCA that utilize a Digital Control, Building Management BMS/DDC, Temperature FUEL STORAGE EQUIPMENT 15594 - 9 12/05/14 DESIGN NO. _____ Controls Contractor (TCC) shall integrate overfill/underfill level and leak detection system into the BMS/DDC system by providing control and monitoring points as indicated in specification section 15985. Upon sensing a leak or high or low fuel oil level, a general alarm shall be initiated at the operator’s workstation. Temperature Controls Contractor shall integrate the fuel leak/overfill/under-fill monitoring and alarm system general trouble signal into the BMS/DDC system by hardwiring digital input signal into the nearest available LonWorks controller or providing a LonPoint module. Per Section MC 1305.9.4, the Temperature Controls Contractor shall shut down the oil transfer pumps upon a detection of a leak at any sumps or containers at the base of shafts that contain oil risers. 7 PART 3 – EXECUTION 3.01 INSTALLATION OF TANKS Tanks shall be installed in accordance with the provisions of Sections MC 1305.13.1 through MC 1305.13.4. A. Below ground: Tanks located below ground, inside or 13 outside of buildings, shall comply with the following requirements: 1. Containment: Fuel-oil tanks having a capacity of more than 660 gallons shall be provided with secondary containment intended to prevent any leakage of fuel oil from the tank from entering the environment. The capacity of the containment shall equal or exceed the capacity of the tank served. 2. Burial: Regardless of capacity, fuel-oil tanks shall be buried with the top of the tank at least 2 feet below ground. Tanks shall be placed in firm soil and shall be surrounded by clean sand or welltamped earth, free from ashes or other corrosive substance, and free from stones that will not pass a 1-inch mesh. 13 15 3. 4. NYCSCA Anchorage: floating. Anchor fuel oil tanks to prevent Distance to foundations: Regardless of capacity, no fuel-oil tank shall be buried within 3 feet of any foundation wall or footing. FUEL STORAGE EQUIPMENT 15594 - 10 12/05/14 DESIGN NO. _____ 5. B. Above ground, on the lowest floor inside a building: Tanks located above ground, on the lowest floor inside of buildings, shall comply with the following requirements: 1. 16 2. C. Containment: Fuel-oil tanks having a capacity of more than 660 gallons storage shall be provided with secondary containment intended to capture any leakage of fuel oil from the tank. The capacity of the containment shall equal or exceed the capacity of the tank served. For fuel storage, the capacity shall include the portion of the tank up to the height of the containment. Special limitations near subways: Regardless of capacity, fuel-oil tanks located within the outer lines of the subway or within 20 feet of the outside line of a subway wall shall be placed within a welded steel oil tight pan of not less than No. 18 Gage metal suitably reinforced and of capacity to contain the contents of the tank. For the purpose of the foregoing requirement, a subway shall be deemed to include any subsurface railroad or rapid transit roadbed. Above ground, above the lowest floor inside a building: Tanks located above ground, above the lowest floor inside of buildings, shall comply with the following requirements: 1. NYCSCA Special limitations near subways: Regardless of capacity, no fuel-oil tank shall be placed within 20 feet of the outside line of a subway wall. For the purpose of the foregoing requirement, a subway shall be deemed to include any subsurface railroad or rapid transit roadbed. Per Section MC 1305.13.3.5, fuel-oil tanks, fueloil-burning equipment, and related equipment shall be provided with secondary containment area intended to capture any leakage of fuel oil. Floor drains shall be prohibited in containment areas. For tanks, the capacity of the containment area shall equal or exceed 2 times the capacity of the tank served. For fuel storage, the capacity shall include the portion of the tank up to the height of the containment. For fuel-oil-burning equipment the capacity of the containment area shall equal or exceed 1.5 times the fuel capacity of the equipment. FUEL STORAGE EQUIPMENT 15594 - 11 12/05/14 D. 19 DESIGN NO. _____ 2. Per Section MC 1305.13.3.6, fuel-oil tanks shall be filled by means of a transfer pump supplied from a primary storage tank located on the lowest floor. Refer to Sections 15510, 15590, 15592, 15593 and Drawings. 3. Per Section MC 1305.13.3.7, indicators and alarms shall be provided for fuel oil tanks and rooms containing fuel-oil-burning equipment, including a level sensor for height and capacity of fuel oil, high and low levels, and leak detection. The float switch shall be provided within the containment areas and shall be arranged so as to sound an alarm and stop the transfer pump in case of failure of the tank or the control in the tank. These indicators shall be connected to a local audible alarm in the tank room and to a remote alarm located at a supervising station (Refer to Section 16701 Auxiliary Signal Systems). The wiring shall comply with the New York City Electrical Code. Per Section MC 1305.13.4, tanks located above ground, outside of buildings, shall comply with the following requirements: 1. NYCSCA Containment. Regardless of capacity, each fuel-oil storage tank shall be protected by an embankment or dike. Such protection shall have a capacity at least 1½ times the capacity of the tank so surrounded (including the portion of the tank up to the height of the containment) and shall be at least 4 feet high, but in no case shall the protection be higher than 1/4 the height of the tank when the height of the tank exceeds 16 feet. Embankments or dikes shall be made of earthwork with clay core, of masonry, of reinforced concrete or of steel. Earth work embankments shall be firmly and compactly built of good earth free from stones, vegetable matter, or other similar material, and shall have a flat section of at least 3 feet (914 mm) at the top and a slope of at least 1½ (457 mm) rise to 2 feet (610 mm) of run on all sides. Concrete, masonry or steel dikes shall be designed so as to contain safely all of the oil in the tank so surrounded. Embankments or dikes shall be continuous and unpierced, and the outside toe shall be located at least 5 feet (1524 mm) inside of the property line, and no less than 5 feet (1524 mm) from a driveway or parking area. FUEL STORAGE EQUIPMENT 15594 - 12 12/05/14 DESIGN NO. _____ 2. Distances to buildings, lot lines, and other tanks: Storage tanks of a capacity greater than 330 gallons shall be not less than 1¼ tank diameters and in no case less than 10 feet from the tax lot line, the nearest building or adjacent tank. However, in no case shall the clearance between individual tanks and the tax lot line be less than the distance fixed by the following formula: M.C. = 10 + 4[(G -275)/5000] where: M.C. = minimum clearance from nearest surface of tank to tax lot line, in feet. G = capacity of tank, in gallons. 3. 23 Means of egress. Tanks shall be located so as not to obstruct or interfere with any means of egress. 3.02 FILL AND VENT PIPING A. NYCSCA Fill piping: Fill piping shall requirements of Section MC 1305.6. comply with the 1. Fill piping shall be a minimum of 2” in diameter or 3” for No. 6 fuel oil. 2. Termination location: A fill pipe shall terminate outside of a building at or above grade at a point least 2 feet from any building opening and 5 feet away from any subway grating at the same or lower level. A fill pipe shall terminate in a manner designed to minimize spilling when the filling hose is disconnected. If facilities exist for an oil delivery truck to drive onto the premises, the fuel-oil terminal may be located elsewhere other than the curb. 3. Separate fill piping: Each storage tank shall be provided with a separate fill pipe, except that where a battery of tanks containing the same grade of oil is installed, a common fill and header pipe may be installed. 4. Check valve: Where the top of the storage tank is above the fill pipe terminal, the fill pipe shall be connected to the top of the tank and provided FUEL STORAGE EQUIPMENT 15594 - 13 12/05/14 DESIGN NO. _____ with a shut-off valve and swing check valve, both of which shall be located at the fill pipe terminal. The shut-off valve and swing check valve may be installed in an accessible location inside the building at or below the level of the fill pipe terminal. B. 5. Terminal opening: The fill opening shall be equipped with a tight metal cover designed to discourage tampering. All fill pipe terminals shall be of an approved type and shall be provided with lugs for embedding in concrete. In lieu of lugs, a set screw or threads to fasten the terminal to the fill pipe may be used. The outer flange of the fill pipe terminal or the seal cap shall be permanently marked: FUEL OIL. The fill pipe terminal shall be threaded or provided with other equivalent means to receive the seal cap. The seal cap shall be suitably slotted for receiving an opening wrench, and an oilproof gasket inserted in a groove in the fill pipe terminal shall be provided so as to make the seal cap leakproof. A strainer shall not be required but if used, shall be of at least 1/8-inch mesh. Where a storage system for volatile flammable oil and a storage system for fuel oil are to be used in the same premises, the terminal of the fuel-oil pipe shall be provided with a left-handed thread and the fill pipe fitting shall be of a different size than that required for the fill pipes to the tanks containing the volatile flammable oil. 6. Spill containment: For fill pipes serving tanks greater than 660 gallons, an approved overflow/spill containment device shall be provided. Normal vent piping: Normal vent piping shall comply with the requirements of Section MC 1305.7. 1. 20 NYCSCA Normal vent sizes shall comply with the sizes listed in Section MC Tables 1305.7(1) and 1305.7(2); provided, however, for tanks other than those complying with the alternate tank design and construction standards contained in Section MC 1305.14, the normal vent shall not be smaller in size than the supply pipe. FUEL STORAGE EQUIPMENT 15594 - 14 12/05/14 DESIGN NO. _____ 2. NYCSCA Termination location: The location of the normal vent pipe terminations shall comply with the following: a. Liquid fuel normal vent pipes shall terminate outside of buildings in a nonhazardous location at a point not less than 2 feet measured vertically or horizontally from any building opening and not less than 2 feet nor more than 12 feet above the fill pipe terminal. b. If the normal vent pipe terminal is not visible from the fill pipe terminal location, a 1- inch tell-tale line shall be connected to the tank and shall parallel the fill pipe and terminate at the fill pipe terminal with an unthreaded end. Such tell-tale lines shall be provided with a check valve set to prevent flow of surface water to the storage tank. c. Normal vent pipes shall terminate sufficiently above the ground to avoid being obstructed with snow or ice. d. Normal vent pipes from tanks containing heaters shall be extended to a location where oil vapors discharging from the normal vent will be readily diffused. 3. Termination caps: Outer ends of normal vent pipes shall terminate in a weatherproof vent cap or fitting or be provided with a weatherproof hood. All normal vent caps shall have a minimum free open area equal to the cross-sectional area of the normal vent pipe and shall not employ screens finer than No. 4 mesh. 4. Multiple Tanks: A normal vent pipe shall be provided for each storage tank. Normal vent piping from multiple tanks of the same grade oil with not more than 660 gallons aggregate capacity may be combined. Where a battery of storage tanks complying with the alternate tank design and construction standards contained in MC 1305.14 designed to hold the same grade of oil with not more than 660 gallons aggregate capacity is installed, normal vent pipes may be run into a main header. FUEL STORAGE EQUIPMENT 15594 - 15 12/05/14 C. NYCSCA DESIGN NO. _____ 5. Pitch: Normal vent pipes shall drain toward the tank. The normal vent pipes shall have no sags or traps where liquid can collect. 6. Protection: Normal vent pipes shall be located so that they are not subjected to physical damage. 7. Cross-connection: Liquid fuel normal vent pipes shall not be cross-connected with fill pipes, lines from burners or overflow lines from auxiliary tanks. 8. Tanks above the lowest floor: For tanks installed above the lowest floor including any rooftop tanks, the normal vent shall be piped, in an approved manner, into the vent or top of tank of the lowest floor storage tank that supplies the fuel to such tank. A tee is allowed from the normal vent to the overflow piping thereby only requiring two pipes in the riser shaft: supply and overflow piping. Emergency relief vent piping for listed/labeled UL 80 tanks, UL 142 tanks and tanks built according to ASME Pressure Vessel Code Section VIII Division 1 or 2: Each primary tank, the interstitial space of a secondary containment tank and each compartment of a compartment tank complying with UL 142 shall be provided with emergency relief venting. A tank’s emergency relief vent piping and normal vent piping shall be combined. The installation of the combined normal and emergency relief vent shall be in accordance with Sections MC 1305.7 and MC 1305.8.1 through MC 1305.8.4. 1. Piping: The combination normal and emergency relief venting shall be provided through an open vent pipe connected directly, as applicable, to the primary tank, interstitial space or compartment. The use of a self-closing manway cover, a manway cover provided with long bolts that permit the cover to lift under internal pressure, or other type emergency relief vent device, shall be prohibited. 2. Termination: Combination normal and emergency relief vent piping shall terminate outdoors (for tanks on the lowest floor). 3. Tanks above the lowest floor: For tanks installed inside of buildings above the lowest floor, the combination normal and emergency vent piping shall FUEL STORAGE EQUIPMENT 15594 - 16 12/05/14 DESIGN NO. _____ be piped, in an approved manner, into the vent or top of tank of the lowest floor storage tank that supplies the fuel to such tank. A tee is allowed from the combination normal/emergency vent to the overflow piping thereby only requiring two pipes in the riser shaft: supply and overflow piping. 4. 3.03 Capacity: The total relief venting capacity of the combination normal and emergency relief venting shall be in accordance with Section 4.2.5.2 of NFPA 30 and as indicated on the Construction documents. SUPPLEMENTAL INSTALLATION A. Electric Work: 1. Mechanical Contractor to provide at a minimum, control wiring and all other items and accessories to make system fully operational. Per Section MC 1305.9.4, the Temperature Controls Contractor shall shut down the oil transfer pumps upon a detection of a leak at any sumps or containers at the base of shafts that contain oil risers. Equipment shall be provided with terminal boxes to receive connecting conduits. The use of wire nuts in lieu of terminal boxes for the splice connections is prohibited. All electric work shall conform to the requirements of the Bureau of Electrical Control, and other authorities having jurisdiction. NYCSCA 2. Electrical wiring is under Division 16. Electrical Contractor to provide power wiring to leak detection system and all other items and accessories to make system fully operational. 3. Conduit: Wiring shall run in conduit in accordance with the NYC Electrical Code, except the wiring in control cabinets, and where flexible connections are necessary. Conduits shall be not less than 3/4" standard weight galvanized steel conduit, large enough to accommodate the wires specified. Flexible oil tight conduit (Sealtite) shall be U.L. approved. No conduit shall be installed contact with the boiler room floor. 4. Conductors shall be copper of 98% conductivity, and free of splints, flaws, or other defects. They FUEL STORAGE EQUIPMENT 15594 - 17 12/05/14 DESIGN NO. _____ shall be in accordance with the NYC Electric Code, and with Bulletin No. 8, 1963 of the Department of Water Supply, Bureau of Electrical Control. Conductors shall be delivered in their original packages or reels, which shall be marked with the manufacturer's identification and date of manufacture. Conductors manufactured more than one year prior to delivery at the job will not be accepted. 5. 7 6 3.04 3 NYCSCA Tanks outside of buildings shall be electrically grounded in accordance with the New York City Electrical Code. B. Paint the tank vault(s) or chamber(s) walls and floors with an epoxy coat (oil resistant) as specified in Section 09800: Special Coating. (Reference Article 2.01.E) C. Provide saddles and supports under the oil storage tank(s) of materials and construction as shown on the Drawings. D. The oil leak detector shall be located within the tank vault/containment area and at any sumps or containers at the base of shafts that contain oil risers. Any concrete mounted sensor shall be positioned close to the low point in the containment area inside a 6" x 6" x 2" min. well. Any new slab of the containment shall slope toward the well. The 6" x 6" x 2" min. well shall be sawcut out of the slab if the existing slab is to remain. Vault sensor unit shall interface with Electrical: Auxiliary Signal System Section 16701. The leak sensors at any sumps or containers at the base of shafts that contain oil risers shall interface with the oil transfer pumps by shutting them down upon the detection of a leak. E. Vent piping shall be no smaller than the fuel oil fill piping. In no case shall the vent pipe be downsized to the fill size. F. Provide anti-siphon or foot valve per Section MC 1301.4. INSTALLATION OF THE SPILL CONTAINMENT(FOR FILL PIPES SERVING TANKS GREATER THAN 660 GALLONS) A. The In Ground Spill Containment Manhole shall be set in a concrete pad when the fill lines run to an outside grade location. FUEL STORAGE EQUIPMENT 15594 - 18 12/05/14 DESIGN NO. _____ B. The Wall Spill Containment shall be used on fill lines from fuel oil storage tanks when the lines run to an outside wall. The Spill Container shall be field mounted on two 2" diameter galvanized pipes which shall be secured into a concrete pad or surface mounted and secured to the outside wall using the mounting brackets. The spill container fill box shall be mounted at nominally 3 feet above grade so as to promote visibility and ease of delivery. Provide fill box drain with shutoff valve to facilitate drainage with bucket. An additional sign shall be mounted next to the fill station to alert the oil deliverer of the location of the "Dry Disconnect." The sign shall read: "The Dry Disconnect is located in the Custodian's Office. Do not fill without using Dry Disconnect." 3.05 FIELD QUALITY CONTROL/INTERDISCIPLINARY TESTS AND FUNCTIONAL PERFORMANCE TESTS A. NYCSCA Supervisory Personnel: Provide field service personnel in the employ of the Fuel Storage Equipment and Control System Manufacturer for such time as required to put installed equipment into operation. Supervisory services shall include the following: 1. Training of Personnel. 2. Start-Up Service and Functional Performance Testing B. Training of Personnel: Approved Leak Detection Alarm System manufacturer's representatives shall instruct duly authorized personnel in the operation and maintenance of the systems. Provide a period of 1-day (8 hours per day), not to include travel time for on-site instruction of personnel. This time shall be exclusive of all pre-startup, start-up and service call time. C. Service: Provide the services of a competent field service representative to furnish fuel leak detection service to the facility. Service must be available within 48 hours from the time of notification. D. Oil Storage Tanks Test: Refer to Section 15992: Cleaning and Testing. Tests shall be made in the presence of the Authority (CID). In the event of leakage, tanks shall be made tight and the test repeated. E. Test liquid-level gage systems for accuracy by manually measuring fuel oil levels at different depths while filling tank and checking against gage indication. FUEL STORAGE EQUIPMENT 15594 - 19 12/05/14 DESIGN NO. _____ F. Test leak-detection and monitoring systems for accuracy by manually operating sensors and checking against alarm panel indication. G. Repair any defects and retest as specified above. H. All Interdisciplinary Tests and Functional Performance Tests shall be made in the presence of the Authority (CID). I. Interdisciplinary Pre-Start-Up and Start-Up Tests: The Contractor shall conduct interdisciplinary pre-start up and start up tests as per the manufacturer’s start up procedures. Contractor shall submit signed start up affidavit signed by the factory authorized service representative indicating that all of the manufacturer’s pre-start up and start up procedures have been successfully completed. J. 11 3.06 Functional Performance Tests: Contractor shall also submit signed functional performance testing affidavit signed by the factory authorized service representative indicating that all of the manufacturer’s functional performance tests have been successfully completed. Refer to the Drawings and Section 15985 since a BMS/DDC system is to be provided and the equipment is to be integrated into the BMS/DDC system. COMMISIONING OF OIL STORAGE TANKS, OIL LEAK DETECTION OVERFILL ALARM, AND FUEL LEVEL SYSTEM A. 12 B. HVAC Contractor shall comply with the Commissioning Requirements of Contract Specification Section S01660 for oil storage tanks, oil leak detection, overfill alarm, and fuel level system. All testing of the fuel oil piping system and hydrostatic testing of the tank shall be tested prior to commencement of the commissioning process. END OF SECTION BB:JV:RE: 12/05/14 NYCSCA FUEL STORAGE EQUIPMENT 15594 - 20 12/05/14 DESIGN NO. _____ Notes to Specifier (Delete from Specification) 1. Section 15503 is to be utilized if the project involves construction of a New Building or Addition to building in Seismic Design Category C or D. Section 15503 is also to be utilized if project involves retrofit work in Existing Buildings in Seismic Design Category C or D constructed after LL17/1995 went into effect. Use Section 15504, Vibration Isolation, (without seismic restraints) for retrofit work on Existing Buildings constructed prior to the effective date of LL17/1995 and for any buildings in Seismic Design Category B. 2. The Preferred TG-EL-LF, OMNTEC MTG-X or Pneumercator: Model MP-450-XXX is recommended for all tanks having adequate clearance. In restricted areas, use Preferred TG-EL-WF (wire float), OMNTEC MTG-F or Pneumercator: Model MP-461-XXX. The Preferred TG-EL-WF float is connected via a flexible stainless steel cable to a multi-turn take-up reel within the sensor head. Preferred TG-EL-LF: Float Clearance: 0.63 x Tank I.D. in inches + 8", Preferred TG-EL-WF: Float Clearance: 6¾" radius around vertical centerline. In restricted areas, OMNTEC MTG-F or Pneumercator: Model MP-461-XXX (Flex Probe) may be used. Consult with the OMNTEC or Pneumercator factory to determine the minimum required clearance for MTG-F or MP461-XXX flex probe installation. 3. Edit as required. Use the EBW 705-445-01 on a sidewalk or floor mounted installation and the Preferred Type 2-CS1 or Analytical & Combustion Systems Model SF-WALL-F where the fill lines are located on an outside wall. If necessary, the Analytical & Combustion Systems Model SF-WALL-F can also be field mounted on two 2" diameter galvanized pipes which shall be secured into a concrete pad. 4. HVAC Design Requirements No.6.2.19, Gas and oil schematics must be utilized in Contract Drawings. 5. The salvage of equipment scheduled to be removed is to be addressed in the scoping/design phase of new projects. The A/E of Record shall contact the NYC Department of Education Central Repair Shops in order to determine whether there is any interest in salvaging the components scheduled to be removed. Equipment designated to be salvaged shall be specified by the A/E to be delivered by the Contractor to a location designated by Shops. The specific equipment to be salvaged and specific delivery location shall be precisely detailed in the bid documents. 6. Verify that the Contract Drawings indicate the correct pipe sizes for all fuel oil fills and vents. NYCSCA piping FUEL STORAGE EQUIPMENT 15594 - 21 12/05/14 DESIGN NO. _____ 7. Edit as required. 8. Edit as required. X denotes the number of tanks. 9. Delete the model number for the two tanks if the Drawings show a single tank. Display Unit: Pneumercator model and OMNTEC model is the same for both the single tank and the two tanks. The OMNTEC OEL8000II can simultaneously monitor product levels, water levels, temperatures and leaks for up to 8 tanks. Level Sensor: Multi-Tank Display Unit Preferred Model TG-EL D5 can only use Level Sensor Model TG-EL-WF (not TG-EL-LF). Edit as required. Single-Tank Display Unit, Preferred Model TG-EL-D3 can use Level Sensor Model TG-EL-LF or TG-EL-WF. Edit as required. 10. Not used. 11. Edit as required if no BMS/DDC network is to be provided. 12. This paragraph is intended for projects that must comply with the NYC Green Schools Rating System (generally all capacity projects) and the following CIP projects: a. b. HVAC upgrades (boiler replacements/ BMS/DDC Systems DDC-only systems/ AC upgrades, etc) Temperature Control systems 13. Edit as required. UL 58 and 142 are for steel tanks, UL 1316 is for fiberglass, UL 80 is for oil burner fuel only. Directly buried tanks require prior approval of the Authority and would only be considered for special cases. 14. Not used. 15. If necessary to prevent floating, show anchoring details. Edit as required. 16. Architect to show details of concrete vault with epoxy coating or alternate containment method. 17. Not used. 18. Designer shall verify that the Contract Drawings show the required containment method (double walled tank, separate rupture basin, epoxy applied to floor slab/walls etc.) for spaces located above the lowest floor of a building. NYCSCA FUEL STORAGE EQUIPMENT 15594 - 22 12/05/14 DESIGN NO. _____ 19. Edit as required. If tanks are located above ground outside of a building, show embankment or dike. Delete Article if not applicable. 20. Designer shall combine normal vent and emergency vent for listed/labeled UL 80 tanks, UL 142 tanks and tanks built according to ASME Pressure Vessel Code Section VIII Division 1 or 2 and shall show all vent diameters and run lengths on the Drawings. The design of the combined normal and emergency relief vent shall be in accordance with Sections MC 1305.7 and MC 1305.8.1 through MC 1305.8.4. The total relief venting capacity of the combination normal and emergency relief venting shall be in accordance with Section 22.7.3 of NFPA 3008. 21. Not used. 22. Not used. 23. Designer is to review the requirements of Local Law 100 of 2013. Fill piping that does not terminate in a watertight terminal approved by the Department of Buildings, normal vent piping and applicable emergency vent piping shall terminate at least three feet above the design flood elevation specified in ASCE 24 Table 7-1. * * * NYCSCA FUEL STORAGE EQUIPMENT 15594 - 23 12/05/14 DESIGN NO. _____ LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data: ______________ _____________ ______________ _____________ Wiring Diagrams: ______________ _____________ Federal, NYC & NYS Permits & Approvals: ______________ _____________ Tanks Affidavit: ______________ _____________ Certificates of Approvals: ______________ _____________ Manufacturer’s Guarantees: ______________ _____________ Charts/Sounding Device: ______________ _____________ Field Quality-Control Test Reports: ______________ _____________ Maintenance Data: ______________ _____________ ______________ ____________ 1. Manufacturers Product Data 2. Installation Instructions Shop Drawings: 1. Assembly-type 2. Piping layout 3. Tanks 1. Maintenance Manual Contractor’s Start-Up and Demonstration Affidavit * * * NYCSCA FUEL STORAGE EQUIPMENT 15594 - 24