PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. (Important Changes Since PCFLO Version 3.7: Linear and Nonlinear Components of Load and Generation at a Bus are Now Specified Entirely Separately, as Highlighted in Bold Type. Also, Nonlinear DPF is now in pu instead of %) BUS DATA (File = BDAT, one record per bus. May use CSV/TSV format if preferred) Variable Columns Format Comments Number 1-4 I4 Name 5 - 16 A12 Type 17 I1 1 = Swing Bus 2 = PV Bus 3 = PQ Bus Linear P Generation 18 - 25 F8 Percent Linear Q Generation 26 - 33 F8 Percent Linear P Load 34 - 41 F8 Percent Linear Q Load 41 - 49 F8 Percent Desired Voltage 50 - 57 F8 Percent Shunt Reactive Q Load 58 - 65 F8 Percent @ Voltage = 100% Maximum Q Generation 66 - 73 F8 Percent Minimum Q Generation 74 - 81 F8 Percent Page 1 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. Control Area 82 - 83 I2 Remote-Controlled Bus Number 84 - 87 I4 Used for controlling voltage at a remote bus. For these cases, the desired voltage specified above applies to the remote bus. Connection Type for Shunt Reactive Q Load 88 - 89 I2 0 or 1 = Grounded Wye. Otherwise, ungrounded wye or delta (i.e. no zero sequence path) Subtransient R, X (Pos. Sequence) 90 - 97 98 - 105 F8 F8 Series impedance of motor or generator, in percent Subtransient R, X (Neg. Sequence) 106 - 113 114 - 121 F8 F8 Series impedance of motor or generator, in percent Subtransient R, X (Zero Sequence) 122 - 129 130 - 137 F8 F8 Series impedance of motor or generator, in percent (ignoring connection type and grounding impedances) (do not multiply by 3) Connection Type for Subtransient Impedances 138 - 139 I2 0 or 1 = Grounded Wye. Otherwise, ungrounded wye or delta (i.e. no zero sequence path) Grounding Impedance R, X for SubTransient Impedances 140 - 147 148 - 155 F8 F8 Series impedance from wye point to ground, in percent. (do not multiply by 3). Nonlinear Device P Generation 156 - 163 F8 P Generation that comes from the nonlinear device, in percent. Nonlinear Device P Load 164 - 171 F8 P Load of the nonlinear device, in percent. Page 2 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. Nonlinear Device Displacement Power Factor 172 - 179 F8 Per Unit (positive for lagging is positive, negative for leading). Nonlinear Device Type I4 1 2 3 4 5 6 7 8 9 180 - 183 = = = = = = = = = 2-pulse current source 2-pulse voltage source 6-pulse current source 6-pulse voltage source 12-pulse current source 12-pulse voltage source 18-pulse current source 18-pulse voltage source Diversified 6-pulse current source (like type 3, but with the 11 & 13th harmonics multiplied by 0.75, the 17 & 19th harmonics by 0.50, and all higher harmonics by 0.25) Single-phase electronic GY-GY Single-phase electronic Delta-GY Magnetic fluorescent GY-GY Magnetic fluorescent Delta-GY User-specified type 14 10 = 11 = 12 = 13 = 14 = ... ... ... 33 = User-specified type 33 Nonlinear Device Phase Shift 184 - 191 F8 Degrees for positive sequence, on system side with respect to device side. This is the additional phase shift by which the current injection phase angles will be advanced for positive sequence, and delayed for negative sequence. Connection Type for Harmonics Model of Linear Load 192 - 193 I2 0 or 1 = Grounded Wye. Otherwise, ungrounded wye or delta (i.e. no zero sequence path) Page 3 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. CSV/TSV Header and Structure for Bus Data File BDAT A 1 :Bus Data : : : :Bus :Number :(I) I 9 Shunt Reactive Q Load (%) (F) Q 17 Negative Sequence Subtransient R (%) (F) B 2 Bus Name (A) C 3 Linear P Generation (%) (F) Bus Type (I) J 10 Maximum Q Generation (%) (F) R 18 Negative Sequence Subtransient X (%) (F) D 4 K 11 Minimum Q Generation (%) (F) S 19 Zero Sequence Subtransient R (%) (F) E 5 Linear Q Generation (%) (F) L 12 Bus Control Area (I) M 13 RemoteControlled Bus No. (I) T 20 Zero Sequence Subtransient X (%) (F) U 21 Connection Type for Subtransient R and X (I) Page 4 F 6 Linear P Load (%) (F) G 7 Linear Q Load (%) (F) N 14 H 8 Desired Voltage (%) (F) O 15 Connection Type for Shunt Reactive Q Load (I) Positive Sequence Subtransient R (%) (F) V 22 Grounding Impedance R for Subtransient Impedances (%) (F) W 23 Grounding Impedance X for Subtransient Impedances (%) (F) P 16 Positive Sequence Subtransient X (%) (F) X 24 Nonlinear Device P Gen (%) (F) PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. Y 25 Nonlinear Device P Load (%) (F) Z 26 Nonlinear Device Displacement Power Factor (%) (F) AA 27 Nonlinear Device Type (I) AB 28 Nonlinear Device Phase Shift (Degrees) (F) AC 29 Linear Load Connection Type (I) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The header lines must begin with a colon so that they will be properly treated as comments. Any line beginning with a colon is treated as a comment. Page 5 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. LINE AND TRANSFORMER DATA (File = LDAT, one record per branch. May use CSV/TSV format if preferred) Variable Columns Format Comments FROM BUS Number 1-4 I4 TO BUS Number 5-8 I4 Circuit Number 9 - 10 I2 R, X (Positive/Negative Sequence) 11 - 22 23 - 34 F12 F12 Series impedance, in percent Charging (Positive/Negative Sequence) 35 - 46 F12 Percent, for entire length of line Rating 47 - 54 F8 Percent Minimum Tap, or Minimum Phase Shift Angle 55 - 61 F7 Per unit tap, or degrees, FROM BUS side wrt. TO BUS side Maximum Tap, or Maximum Phase Shift Angle 62 - 68 F7 Per unit tap, or degrees, on FROM BUS side wrt. TO BUS side Tap Step Size, or Phase Shift Step Size 69 - 75 F7 Per unit, or degrees Tap 76 - 82 F7 Per unit, on FROM BUS side Phase Shift 83 - 90 F8 Degrees, FROM BUS side wrt. TO BUS side Voltage-Controlled Bus Number 91 - 95 I5 Used for controlling voltage at a remote bus. For these cases, the desired voltage specified applies to the remote bus. Page 6 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. Voltage-Controlled Bus Side 96 - 97 I2 When controlling the voltage at a remote bus, enter 1 when the remote bus is on the FROM BUS side of the transformer. Enter 2 when the remote bus is on the TO BUS side of the transformer. Desired Voltage for Voltage-Controlled Bus, or Desired Active Power Flow for Phase Shifting Transformer 98 - 105 F8 Percent Voltage, or Percent Active Power (FROM BUS toward TO BUS) R, X (Zero Sequence) 106 - 117 118 - 129 F12 F12 Series impedance, in percent (ignoring connection type and grounding impedances), (do not multiply by 3) Charging (Zero Sequence) 130 - 141 F12 Percent, for entire length of line Connection Type for Transformers and Shunt Elements 142 - 143 I2 For transformers: Type FROM BUS 0 or 1 GY 2 GY 3 Y 4 Y 5 6 GY 7 Y 8 9 TO BUS GY Y GY Y GY Y For shunt elements: 0 or 1 = Grounded Wye. Otherwise, ungrounded wye or delta (i.e. no zero sequence path) Page 7 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. Grounding Impedance R, X 144 - 155 156 - 167 F12 F12 Series impedance from wye point to ground, in percent Applies to wye-connected transformers and shunt elements. (do not multiply by 3) Resistive Skin Effect Factor for Positive/Negative Sequence 168 - 175 F8 Harmonic h (h > 2, fractional values OK) at which the conductor resistance is double the fundamental frequency resistance. Resistive Skin Effect Factor for Zero Sequence 176 - 183 F8 Harmonic h (h > 2, fractional values OK) at which the conductor resistance is double the fundamental frequency resistance. This value applies to the combined conductor and grounding resistance. Page 8 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. CSV/TSV Header and File Structure for Line and Transformer Data File LDAT A B 1 2 :Line and Transformer Data : : :From To :Bus Bus :(I) (I) I 9 Max. Tap (pu), or Max. Phase Angle (Deg.) (F) Q 17 Zero Sequence X (%) (F) C 3 Circuit Number (I) J 10 Tap Step Size (pu) or Phase Shift Step Size (Deg.) (F) R 18 Zero Sequence Charging (%) (F) D 4 Positive Sequence R (%) (F) K 11 Fixed Tap (pu) (F) S 19 Connect. Type for Trans. and Shunt Elements (I) E 5 Positive Sequence X (%) (F) L 12 M 13 VoltageCont. Bus Number (I) Phase Shift (Deg.) (F) T 20 Grounding R (%) (F) U 21 Grounding X (%) (F) F 6 Pos/Neg Sequence Charging (%) (F) N 14 VoltageCont. Bus Side (I) V 22 Pos/Neg Resistive Skin Effect Factor (F) G 7 Page 9 Min. Tap (pu), or Min. Phase Angle (Deg.) (F) Rating (%) (F) O 15 Desired Volt. at V-Cont. Bus (%) or Desired P in Phase Shifter FROM-TO (%) (F) W 23 Zero Resistive Skin Effect Factor (F) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The header lines must begin with a colon so that they will be properly treated as comments. Any line beginning with a colon is treated as a comment. H 8 P 16 Zero Sequence R (%) (F) PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. AREA INTERCHANGE DATA (File = ADAT, one record per loadflow area. May use CSV/TSV format if preferred) Variable Number Columns Format Comments 1-2 I2 3 I1 Control Bus Number 4-7 I4 Desired Export Power 21 - 28 F8 Percent Solution Tolerance for Export 30 - 35 F6 Percent Name 37 - 56 A20 Tie-Line Loss Assignment Page 10 If non-zero, then power losses on tie lines are assigned equally between the two areas. If zero, the TO BUS area for each tie line is assigned the loss (i.e., meter at the FROM BUS). PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. CSV/TSV Header and File Structure for Area Interchange Data File ADAT A B 1 2 :Area Interchange Data : Tie Line : Loss : Assignment : (1 for : Splitting, : 0 for To :Area Bus :Number Ownership :(I) (I) C 3 Control Bus Number (I) D 4 Desired Export Power (%) (F) E 5 Solution Tolerance for Export (%) (F) F 6 Area Name (A) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The header lines must begin with a colon so that they will be properly treated as comments. Any line beginning with a colon is treated as a comment. Page 11 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. USER-SPECIFIED HARMONIC CURRENT SPECTRAL DATA (File = SPECTRA, one record per harmonic per nonlinear load type. May use CSV/TSV format if preferred) Variable Columns Format Comments Type of Series 1-3 A3 Must be sin for a sine series, cos for a cosine series. All entries in this file must be either sin, or cos, and cannot be mixed. Nonlinear Load Type 5-9 I5 Must be 14, 15, 16, . . . , 33. Harmonic Order 10 - 14 I5 1, 2, 3, etc. Current Harmonic Magnitude 15 - 24 F10 Percent. If the fundamental is given, its magnitude must be 100.0, and the other harmonic magnitudes for the same nonlinear load type are assumed to be relative to 100.0. The actual injection currents will be scaled according to bus load/generation. If the fundamental is not given for a nonlinear load type, then the harmonic magnitudes are assumed to be given on the system base. Current Harmonic Phase Angle 25 - 34 F10 Degrees, using load current convention. If the fundamental angle is given, it must be 0.0. The actual phase angles will be adjusted internally according to bus power factor and fundamental voltage angle. If the fundamental is not given, the phase angles are assumed to be given with respect to the bus fundamental frequency voltage phase angle. Page 12 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. CSV/TSV Header and File Structure for Spectra Data File SPECTRA A B 1 2 :Harmonic Current Spectral Data : :Type of :Series Nonlinear :(SIN or Load :COS) Type :(A) (I) C 3 Harmonic Order (Integer) (I) D 4 Current Harmonic Mag. (%) (F) E 5 Current Harmonic Phase Angle (Degrees) (F) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The header lines must begin with a colon so that they will be properly treated as comments. Any line beginning with a colon is treated as a comment. Page 13 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. SOLUTION OPTIONS (File = OPTIONS. Must use CSV/TSV format.) For Loadflow and Motor Starting (sample file OPTIONS.LF shown below) A B C D 1 2 3 4 One Line Case Title Goes Here :Loadflow and Motor Starting Solution Options : :Optimal P,Q Accel. :Bus Mismatch Factor :Ordering Gauss- for Gauss- for Gauss:Method Seidel Seidel Seidel :(Integer) Start? Start Start :(1-2-3) (T or F) (0.5 pu) (1.2 pu) (I) (L) (F) (F) E 5 Voltage Update Cap for GaussSeidel Start (0.005 pu) (F) K 11 L 12 M 13 N 14 O 15 Limit Output to This Control Area? (I) and This Control Area? (I) and This Control Area? (I) and This Control Area? (I) and This Control Area? (I) F 6 P,Q Mismatch Solution Tolerance (5E-06 pu) (F) G 7 H 8 Disable Remote Disable Volt. Reg. Area by PV Intrchnge Busses? P Adjust? (T or F) (T or F) (L) (L) I 9 J 10 Disable Transf. Ignore Tap Q Limits Adjust. for on PV Voltage Busses? Control? (T or F) (T or F) (L) (L) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The first line of these option files should be the case title. Additional header lines, prior to the actual data, must begin with colons. Any line beginning with a colon is treated as a comment. Page 14 PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. For Short Circuit (sample file OPTIONS.SC shown below) A B 1 2 One Line Case Title Goes Here :Short Circuit Solution Options :Optimal :Bus :Ordering :Method Enter T for Diagonal and Neighbor ZBUS Elements Only (recommended) :(Integer) Enter F for All ZBUS Elements (not recommended and not to be followed by FAULTS) :(1-2-3) (T or F) (I) (L) For Full Harmonics Study (sample file OPTIONS.HS shown below) A B C D E F G H 1 2 3 4 5 6 7 8 One Line Case Title Goes Here :Full Harmonic Solution Options : : Harmonic Load Model :Optimal P,Q Accel. Update Highest for PQ Linear Loads :Bus Mismatch Factor Cap P,Q Harmonic 0 or 1: Resistive-only (recommended) :Ordering Gauss- for Gauss- for Gauss- for Gauss- Mismatch of 2: Parallel R,L Model :Method Seidel Seidel Seidel Seidel Solution Interest 3: Series R,L Model :(Integer) Start? Start Start Start Tolerance (Integer) 4: Ignore PQ Loads (i.e., No Model) :(1-2-3) (T or F) (0.5 pu) (1.2 pu) (0.005 pu) (5E-06 pu) (1 - 49) (0 - 4) (I) (L) (F) (F) (F) (F) (I) (I) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The first line of these option files should be the case title. Additional header lines, prior to the actual data, must begin with colons. Any line beginning with a colon is treated as a comment. Page 15 R 17 Global Resistance Doubling Harmonic (0,2,3,4 …) (I) PCFLO Version 5.2, 500 Bus, Windows 95. http://www.ece.utexas.edu/~grady/, July 28, 1998. For Harmonic Impedance Scan (sample file OPTIONS.HZ shown below) A B C D 1 2 3 4 One Line Case Title Goes Here :Harmonic Impedance Scan : :Optimal P,Q Accel. :Bus Mismatch Factor :Ordering Gauss- for Gauss- for Gauss:Method Seidel Seidel Seidel :(Integer) Start? Start Start :(1-2-3) (T or F) (0.5 pu) (1.2 pu) (I) (L) (F) (F) L 12 Scan This Bus * (I) M 13 and This Bus (I) N 14 and This Bus (I) O 15 and This Bus (I) E 5 F 6 G 7 H 8 I 9 J 10 K 11 Update Cap for GaussSeidel Start (0.005 pu) (F) P,Q Mismatch Solution Tolerance (5E-06 pu) (F) Lowest Harmonic of Interest (Integer) (1 - 49) (I) Highest Harmonic of Interest (Integer) (1 - 49) (I) Number of Steps per Harmonic (Integer) (1 - 100) (I) Phase Sequence 0: Zero 1: Pos. 2: Neg. (0, 1, 2) (I) Limit the Output to Diagonal Elements Only? (T or F) (L) P 16 and This Bus (I) Q 17 Harmonic Load Model for PQ Linear Loads 0 or 1: Resistive-only (recommended) 2: Parallel R,L Model 3: Series R,L Model 4: Ignore PQ Loads (i.e., No Model) (0 - 4) (I) R 17 Global Resistance Doubling Harmonic (0,2,3,4 …) (I) Format: (I) Integer, (F) Floating point, including E±00, (L) Logical, (A) Character Note: The first line of these option files should be the case title. Additional header lines, prior to the actual data, must begin with colons. Any line beginning with a colon is treated as a comment. * Note: A negative number in any of the “Scan This Bus” columns will invoke a scan of all system busses. Page 16