Building Safety Division December 9, 2013 Josh Miller 6025 Metcalf Lane Overland Park, KS 66210 NEXUS IT TI 7512 WEST 80TH STREET, OVERLAND PARK, KANSAS PLAN REVIEW NUMBER PRS2013-00902 The Planning and Development Services Department reviewed the plans submitted on December 2, 2013. The following comments are from various divisions within the Planning and Development Services Department. When resubmitting your plans, include a cover letter complete with project name, address, and plan review number, and indicate how you have addressed each plan review comment. Please refer to the enclosed guidelines (Attachment A) and sample cover letter (Attachment B). Building Safety Division - Plan Review The following comments are from the Building Safety Division-Plan Review. Direct any questions regarding these issues to Gregory Maggiore, M.C.P. at (913) 895-6248. Code references for this review: 2012 International Building Code..................................................................…. IBC 2012 International Fire Code ........................................................................…. IFC 2012 International Plumbing Code ...............................................................…. IPC 2012 International Mechanical Code ............................................................…. IMC 2012 International Fuel Gas Code ................................................................…. IFGC 2012 International Energy Conservation Code .............................................…. IECC 2011 National Electric Code .........................................................................…. NEC 2010 ADA Standards for Accessible Design ................................................….ADA Overland Park Municipal Code .....................................................................…OPMC Building Safety Division/Plan Review 913/895-6205 Fax 913/895-5016 Josh Miller December 9, 2013 Page 2 of 4 1. The design shows new exterior wall construction to replace the single sheet metal siding on the east wall. The design shows new exterior wall construction on the north side of the building. Please provide a section detail of the proposed new construction as required by IBC Section 107.2.1. Please verify with Daniel Zeigler, Planner from the Planning Division all colors and cladding or siding materials. 2. The design shows new exterior knee walls to be built to support new windows in what was once an opening flush with the exterior slab. Please provide a section detail of the proposed new construction as required by IBC Section 107.2.1. Please verify with Daniel Zeigler Planner from the Planning Division all colors, cladding and or siding materials. 3. The design shows a new exterior wall to replace the single sheet metal siding on the east wall. The design shows new exterior knee walls to be built to support new windows in what was once an opening flush with the exterior slab. Please verify there is a foundation wall under the proposed new construction as required by IBC Section 1809.5. 4. Verify how compliance with the Americans With Disabilities Act (ADA) regarding the path of travel to the altered area will be accomplished. As adopted by the State of Kansas, responsibility for enforcement of 2010 ADA is passed on to local jurisdictions, including the City of Overland Park. Plans for a permit are being reviewed for compliance with 2010 ADA. Elements of the building affecting accessibility, along the path of travel to the remodeled or altered area, are required to comply with 2010 ADA to the maximum extent feasible provided the cost is not disproportionate to the cost of such alteration. Cost is considered disproportionate if it exceeds 20 percent of the cost of the alteration of $19,400.00. Please verify the rear egress door is on an accessible route. Providing an accessible route at this location would comply with parts of this code section. 5. Please provide a hi-lo drinking fountain as required by ADA Sections 211, 202.4, 602, and IPC Table 403.1 as amended by OPMC 16.130.403.1. Please locate the new hilo drinking fountain in an area that accessible to all occupants. 6. Please verify the faucets provided where occupants can come in contact with hot water have anti scald devices as required by IPC Section 607.1.2. 7. Sheet P1 shows a wall clean out in close proximity to new HVAC equipment. Please verify there is adequate clearance for rodding as required by IPC Section 708.8. 8. The design shows the 60” x 60” ramp platform dimensions taken from out side the guards/hand rails. Please revise the ramp platform design to provide a clear 60” x 60” platform as required by ADA Section 405.7. Josh Miller December 9, 2013 Page 3 of 4 9. Please provide an elevation detail of the new ramp that shows the required hand rails and edge protection as required by ADA Sections 405.8 and 405.9 and IBC Section 107.2.1. 10. Please revise the height of the counter or portions of the counter (sink area) to 34” AFF as required by ADA Section 308 and IBC Section 1109. 11. Please provide interior elevations of the toilet rooms as required by Section 107.2.1. Please address details and requirements of ADA Chapter 10 for fixture and accessory locations. Please address the requirements of IBC Section 1210 for interior finishes. 12. Please specify the closers (if provided) shall be adjusted to meet the required sweep period as required by ADA Section 404.2.8.1 13. Please verify the new front and rear egress doors are more than 24” from the adjacent window or provide information that the glazing meets IBC Section 2406.4.2 requirements for safety glazing. 14. Please verify the glazing adjacent to the ramp meets the requirements of IBC Section 2406.4.6 for safety glazing. 15. The drawings do not specify the U value for the glazing on the exterior walls. Please revise the design to specify fixed fenestration U value of 0.38 or better; entrance doors 0.77 or better; and SHGC of .040 or better as required by IECC Table C402.3. 16. Please provide information that verifies the lighting design complies with the energy code as required by IECC Section 405. 17. Please verify that off street parking for passenger vehicles will or will not be provided. Current Planning Division The following comments are from the Current Planning Division. Questions regarding these issues should be directed to Danielle Zeigler at (913) 895-6194. 1. Thank you for providing the pictures of the building with the proposed changes to the windows and doors. What will the finish materials be for the new east wall and north wall of the building? 2. Looking at the pictures, will the building be painted? If so, please provide the color. Josh Miller December 9, 2013 Page 4 of 4 3. The new ground-mounted mechanical unit to the north of the building is required to be screened from view. Will the fence around the rear of the property remain, to screen the unit? If not, please provide landscaping around the new unit. If you have questions or alternatives to discuss on the above-mentioned items please contact the appropriate person or me at this office, (913) 895-6248 or at greg.maggiore@opkansas.org. Gregory Maggiore – M.C.P. Multidisciplined Code Official Senior cdm Enclosure c: Travis Lindemoen, 7512 W. 80th, Overland Park, KS 66204