July 24, 2013 Kevin Grant C2K Architecture 107 SE Washington, Suite 758 Portland, Oregon 97214 CINETOPIA 5725 WEST 135TH STREET, OVERLAND PARK, KANSAS PLAN REVIEW NUMBER PRS2013-00513 The Planning and Development Services Department reviewed the plans submitted on June 28, 2013. The following comments are from various divisions within the Planning and Development Services Department. When resubmitting your plans, include a cover letter complete with project name, address, and plan review number, and indicate how you have addressed each plan review comment. Please refer to the enclosed guidelines (Attachment A) and sample cover letter (Attachment B). Building Safety Division - Plan Review The following comments are from the Building Safety Division-Plan Review. Direct any questions regarding these issues to Chad Hoth at (913) 895-6265. Architectural 1. The total occupant load for the building shall include the occupant load for the following areas in the building code summary (Sheet A011): 2. Lobby area including standing areas for the box office and concessions. Mezzanine area (kitchen/storage/office areas). Restaurant area including the outside seating area. The wall types shall be identified on the plans for the following rooms/areas: 104,105,107,106,113, and 146. Building Safety Division/Plan Review 913/895-6205 Fax 913/895-5016 Kevin Grant July 24, 2013 Page 2 of 4 3. Indentify on the plans the running slope percentage of the ramps throughout the project. 4. The elevator machine room shall be enclosed with 1 hour fire-resistance rated fire barrier walls and opening protection for the door per Section 3006.4 of the IBC. 5. A portion of the box office sales counter shall comply with the height requirements (36 inches minimum) per Section 904.3 of ICC ANSI A117.1-2003. 6. It appears elevation view for A701/1 on Sheet A201 is incorrect. 7. Please indicate on the plans the accessible dining spaces for the consumption of food and drink per Section 1108.2.9.1 in the restaurant area of the building. 8. The wheelchair spaces width and depth shall comply with Section 802 of A117.1 in Parlor Theatre Rooms 9, 10, 11 and 12 (Sheet A628). 9. Provide verification that the wall and ceiling finishes installed meet the flame spread and smoke development index per Section 803.1 of the IBC. Structural 10. Please indicate glazing within the guardrail surrounding the escalator is safety glazing (tempered) and has a minimum nominal thickness of ¼ inch per Section 2407.1 of the IBC. 11. Provide engineer design load calculations for glass guardrail surrounding the escalator per Section 1607.8.1 of the IBC. 12. Provide special inspections for the structural steel members installed per 1705.2 of the IBC. 13. Indicate the fire-resistance rated protection for the primary structural frame of the building (Sheet S103) per Section 704.1 of the IBC. 14. Provide section view 6/S106 on Sheet S102. Mechanical 15. Provide fire dampers in the ducts that penetrate the elevator machine room walls per code. 16. Plans shall indentify how the mechanical ducts that penetrate a fire-resistance-rated floor/ceiling assembly are protected in accordance with Section 717.6.1 of the IBC. – Kevin Grant July 24, 2013 Page 3 of 4 See the exhaust duct for the popcorn exhaust hoods (KEH 1 and 2), exhaust for the elevator machine room, exhausts for the first floor restrooms, and the supply ducts within the concealed shafts that are fed from above (FFA) to the roof top units. Electrical 17. Please provide electrical plan notes for noted numbers on Sheets E403 and E404. 18. Please indentify by light fixture schedule the aisle lighting fixtures in the theatres. 19. The aisle lights shall extend the entire aisle stairs on the north side of the “GXL” theaters. – See Sheet E403. 20. Provide means of egress illumination in the “living” and “parlor” theatres per Section 1006.2 of the IBC. 21. Provide exit sign above means of egress Door 105A on the Parlor Corridor side 140 and 233A on upper entry Corridor side 200. 22. Provide emergency illumination for the outside balcony and exit signs at the balcony doors. 23. Provide a smoke and heat detector in the elevator hoistway within 2 feet of the sprinkler head per Section 21.4.2 of NFPA 72. – See Sheet FP101. Current Planning Division Current Planning Division approved submitted plans. Health and Environment Division The following comment is from the Health and Environment Division. Direct any questions regarding this issue to Vincent Jones at (913) 895-6344. 1. Please provide a hand sink in the service corridor near the dish machine area (Sheet FS1: First Floor Food Service). Conditions 1. Submit fire alarm drawings with battery calculations and voltage drop calculations per Section 907.1.2 of the IBC. Kevin Grant July 24, 2013 Page 4 of 4 2. Submit Drawings for kitchen hoods fire suppression systems extinguishing agent calculations, cut sheets of devices, and layout of kitchen equipment to be protected shall be submitted to this office for review and approval prior to installation. Permit applicants must obtain a Johnson County Contractor License prior to issuance of a building permit in the City of Overland Park. For more information, please contact Johnson County Contractor Licensing, (913) 715-2233, 111 South Cherry, Room 1056, Olathe, Kansas 66061, or http://contractorlicensing.jocogov.org. If you have questions or alternatives to discuss on the above-mentioned items, please contact the appropriate person above, or contact me at this office, (913) 895-6265. CHAD HOTH – PLANS EXAMINER cdm Enclsoure c: Brew Bennett, Cinetopia LLC, 12345 SW Horron BLvd, Bewerton, OR 97007