Demand Related Ventilation in Laboratories Peter James and Lisa Hopkinson September 2009 Professor Peter James is Co-Director, and Lisa Hopkinson, is Research Officer on the Higher Education Environmental Performance Improvement (HEEPI) project. This is based at the University of Bradford, and mainly funded from the HEFCE Leadership, Governance and Management (LGM) initiative. It aims to improve the environmental performance of universities and colleges through identification and dissemination of best practice, events and network building activities, and development of sector capacity. See www.heepi.org.uk for more details, and contact information. Disclaimer: This paper has been prepared in good faith as an objective account of the discussions at, and matters arising from, Labs21 UK events. The points made by presenters are reported without comment, and should not be construed as being endorsed or accepted by HEEPI. The paper does not constitute technical guidance, and is not a substitute for appropriate professional advice on the subject matter being discussed. The paper also features presentations by, or about, specific suppliers. These are included as examples and sources of information, and do not constitute an endorsement of any specific products. Demand Related Ventilation in Laboratories Contents 1. Introduction .................................................................................................................................. 3 2. Principles of Demand Related Ventilation ........................................................................... 3 2.1 Fume Cupboards and Demand Related Ventilation ................................................................. 4 2.2 Room Based Demand Related Ventilation .................................................................................. 5 2.3 System Level Demand Related Ventilation ................................................................................. 6 3. Demand Related Ventilation at the University of Cambridge – Paul Hasley, Chris Lawrence and Phil Mulholland .................................................................................................... 6 4. Demand Based Control for Significant Energy Reduction in Laboratories – Gordon Sharp ................................................................................................................................... 8 5. Discussion .................................................................................................................................. 11 Appendix 1 – The Labs21 Design Philosophy....................................................................... 12 Appendix 2 - HEEPI Energy Benchmarks for Laboratories ............................................... 14 September 2009 www.goodcampus.org 2 Demand Related Ventilation in Laboratories 1. Introduction Laboratories have many environmental impacts. One of the most serious is their consumption of large quantities of energy. This can be 4-5 times greater than offices on a square metre basis. The most important component of energy demand in many laboratories is ventilation, and the associated conditioning of air. This can often comprise 30-40% of total energy consumption, mainly in the form of fan power. The plant is also a major component of capital expenditure. This paper1 summarises the presentations and discussion both at, and following, a May 2009 workshop on Variable Air Volume and Demand Related Ventilation at the University of Cambridge. It has also drawn on relevant points made at other recent HEEPI events on laboratory energy efficiency and environmental performance.2 The events have highlighted the fact that recent ventilation approaches have been very supply focused, so that air is supplied and extracted with little relationship to actual requirements. Moving to demand related ventilation (DRV), in which air flow is varied according to hazard, and other factors, could therefore create considerable energy benefit, provided that safety is not compromised. The Cambridge workshop was organised by the S-Lab programme of HEEPI (Higher Education Environmental Performance Improvement), a not-for-profit project which supports UK universities and colleges in becoming more sustainable through benchmarking, sharing best practice, and other actions. It also involved a collaboration with the US Labs21 initiative, via HEEPI’s creation of a UK Labs21 programme (see www.labs21.org.uk). Labs21 began as a collaboration of Federal laboratories to improve energy efficiency and share best practice between them through better networking and staff exchanges. It was founded by the US Environmental Protection Agency, with additional support from the US Department of Energy, and is now managed by the International Institute for Sustainable Laboratories (IISL). 2. Principles of Demand Related Ventilation Demand related ventilation (DRV) is an approach which varies ventilation levels in accordance to occupancy, use and other factors. In some cases, such as night setback on fume cupboards (see below), the variation is fixed and relatively inflexible. However, in others ventilation is varied very quickly in responses to changes in state – an approach described as demand controlled ventilation (DCV). Demand related ventilation can be applied at a number of levels: The device (especially fume cupboards) The room The system. The most effective approaches will be those which integrate action at all three levels. 1 The contents of this paper are the responsibility of the authors, but they have benefited greatly from the advice and review of Geoffrey Bell, Mike Dockery, Gordon Sharp and other Labs21 experts. 2 Details of, and presentations from, the events can be viewed at www.labs21.org.uk. September 2009 www.goodcampus.org 3 Demand Related Ventilation in Laboratories 2.1 Fume Cupboards and Demand Related Ventilation Research by a supplier, Phoenix Controls, suggests that most fume cupboards are typically used for under two hours a day, on average, and in many cases for only an hour a day or less.3 Hence, there is considerable scope to reduce ventilation levels at other times. 2.1.1 Constant Air Volume (VAV) Fume Cupboards Traditional laboratory design has been based on a constant air volume (CAV) approach. This involves the same amount of air always being supplied to the ventilated spaces, and exhausted from them. Variations in sash opening are generally dealt with by the provision of a by-pass channel. Air flows through this vary inversely with the amount of sash opening. Cupboards of this type are conventionally designed with a face velocity (the speed at which air travels through the open sash area) of 0.5 metres per second (m/s). If CAV fume cupboards are not provided with a by-pass then the velocity across the sash opening will increase as the sash is lowered, which can lead to unstable conditions. There can also be occasions when by-pass fume cupboards have a higher than normal face velocity even when the sash is closed due to the problem of balancing the by-pass in the closed position. The main means of achieving demand related ventilation (DRV) with CAV devices is through two-state approaches, in which face velocities are reduced to a lower, standby, level when the device is not on use, such as night-time. Achieving this safely may require the sashes to be closed. CAV systems that have this capability can also take advantage of proximity sensing technology (see below). 2.1.2 Variable Air Volume (VAV) Fume Cupboards Variable Air Volume (VAV) devices vary air flows in response to load. They provide a specified face velocity setpoint for all sash positions, but adjust volume flow in accordance with the sash level. Hence, when the sash is low or closed, the movement of air is reduced. A typical VAV cupboard will have a 4:1 turndown on exhaust, and 7:1 turndown on supply air, and ideally have a response time of less than one second. However, not all designs are capable of such a rapid response. VAV approaches often have higher first costs than CAV, largely because of their complex control systems. However, this can be more than offset by reductions in the sizes, and therefore capital cost, of air handling and air conditioning installations. In operation, they have the benefits of: 3 Lower energy consumption, from reduced exhaust and supply fan requirements and, in cases where incoming air is conditioned, a reduction in the amount of air which needs to be conditioned for humidity and/or temperature (see Table 1 for a comparison with CAV). Increased safety because there is much less risk of the turbulent air flows and consequent spillage arising from sudden changes in fume cupboard face velocities that can arise in conventional CAV systems. Quoted in a presentation to the Cambridge workshop. September 2009 www.goodcampus.org 4 Demand Related Ventilation in Laboratories Finer control, and much more detailed monitoring, of pressurisation in laboratories so that any problems can be quickly identified and dealt with. Realising the full benefits of VAV requires sashes to be lowered or closed as much as possible. This can be achieved by: Voluntary action by users, and/or Automatic closure (or semi-closure) based on sensing user proximity to the device. As discussed below, there are differences of view on the value of each of these methods, and the safety of the latter. Table 1 – Carbon, Energy and Cost Impacts of Fume Cupboards4 Type Electricity Heat Annual Cost Annual kWh/annum kWh/annum CAV 1,019 28,305 £794 5,784 VAV – Poor 510 14,153 £397 2,892 42 1,179 £33 241 CO2 Emissions (kg) Sash Management VAV – Perfect Sash Management Source: University of Cambridge calculations, based on data from Carbon Trust Good Practice Guide 320 and usage of 1 hour per day. 2.2 Room Based Demand Related Ventilation Specification of the number of air changes per hour in each room is a key feature of the design of laboratory heating, ventilation and cooling (HVAC). Multiple air changes are necessary for a variety of reasons, including: Maintaining air freshness by replenishing oxygen, and removing carbon dioxide, odours and other unwanted substances (usually determined by CIBSE guidance on minimum ventilation rates). Ensuring that there is sufficient air to ‘feed’ all extracted devices, such as fume cupboards (if the supply air is insufficient, contained air can leak back into the room). Removal of heat created by occupancy, equipment, lighting and solar gain. In some cases, requirement for negative pressure in room. 4 Hasley, P., 2009. Energy Efficent Operation of Laboratories at University of Cambridge Using Variable Air Volume (VAV) Ventilation. Presentation at HEEPI event Cutting Energy Use with Variable Air Volume (VAV) in Labs, Hospitals and Other Heavily Serviced Spaces - New examples and research in the UK and USA, 14 May 2009, University of Cambridge. Available at: www.labs21.org.uk September 2009 www.goodcampus.org 5 Demand Related Ventilation in Laboratories As these factors are difficult to calculate in advance, room air changes tend to be estimated conservatively. As with fume cupboards, one simple method of demand related ventilation (DRV) is a two stage approach, with a standby level for periods when space is unoccupied (e.g. night setback). A more complex approach is that of demand controlled ventilation (DCV), in which air flows are varied in response to changes in ambient concentrations of monitored substances. This method is already used to gauge room occupancy in a variety of environments, based on monitoring levels of carbon dioxide, which is exhaled by humans at relatively constant rates. Ventilation can then be increased as concentrations rise. Gordon Sharp’s presentation describes an extension of this approach to laboratories, with sensing of harmful substances such as volatile organic compounds (VOCs). 2.3 System Level Demand Related Ventilation DRV savings can be optimised when combined with a modular approach to plant. For plant which operates most efficiently at full load, installing several small-mid sized units instead of one large unit can allow them to be switched in and out, in line with demand. DRV can also enable lower diversity factors. Diversity is defined as “designing and operating a system at a lesser capacity than the sum of all the included facilities when running at peak demand.”5 A laboratory fume cupboard ventilation system whose exhaust capacity is the same as that of all the individual cupboards would have a diversity factor of 100%. In CAV systems diversity factors have to be high (often 100%) as there is little variation in the air flows from the fume cupboards. However, device and room DCV approaches create a greater variation in flows, and make it unlikely that all cupboards will be operating at full capacity simultaneously. A safe level of diversity is determined by a number of factors, including: Number and density of fume hoods. Minimum laboratory/room air change rates. Heating and cooling loads. Fume hood usage patterns. Extent of sash closure. In practice, diversity factors have been reduced to as little as 50% for central plant without compromising safety, as has been the case at, for example, a recent Oxford University laboratory. This translates into lower capital and operating costs from lowered requirements for cooling, heating, reheating, fan power, ductwork and piping, and space. 3. Demand Related Ventilation at the University of Cambridge – Paul Hasley, Chris Lawrence and Phil Mulholland The University of Cambridge has an energy bill of £10.2 million a year, of which 10% is from the Chemistry Laboratory (which has over 300 fume cupboards). The university has a good record in energy efficiency and environmental management, being highly 5 DiBerardinis L., Baum J. S., First M., Gatwood G. T., and Seth A., 2001. Guidelines for Laboratory Design: Health and Safety Considerations. 3rd Edition. Pub: Wiley New York. September 2009 www.goodcampus.org 6 Demand Related Ventilation in Laboratories commended by HEEPI Green Gowns 3 times in 4 years and achieving first class honours in the People & Planet Green League 2007 and 2008. Nonetheless, there is scope for further energy efficiency measures. Table 2 – Carbon, Energy and Cost Impacts of Chemical Laboratories6 Electricity Gas kWh/m2 Annual Cost Annual kWh/m2 (£ million) CO2 Emissions (tonnes) Cambridge 371 332 £1.243 7,204 160 160 £0.549 3,189 132 175 £0.485 2,850 264 175 £0.838 4,807 Chemical Laboratory DECs – Typical Lab (100 = D/E) CIBSE Typical HE Science Lab HEEPI Typical Chemical Science Lab The Chemical Laboratory has a gross internal floor area of 27,603 m2. It was originally constructed in 1958, and was recently refurbished in order to support increasing academic activity (through more fume cupboards, and other ways), and to reduce energy consumption. Table 2 compares its actual energy consumption, costs and carbon emissions with various benchmarks. (See Appendix 2 for more information on the HEEPI benchmarks). Three key principles in the energy aspects of the refurbishment were: 5 year paybacks (a requirement of the Salix Trust funding which financed part of the work). No interference with lab operational demands. No compromises on health and safety. A VAV solution was adopted for the new fume cupboards, and a key design issue was how to ensure a high level of sash closure. Four options were identified: 6 Voluntary user actions. Automatic sash closers. Fixed setback of fume cupboard face velocity. Usage based control, linked to presence detection. Standardised to a 27,603 m2 gross internal floor area. Hasley, P. 2009. See footnote 4. September 2009 www.goodcampus.org 7 Demand Related Ventilation in Laboratories Voluntary user actions were seen as important, but unlikely to be sufficient due to resistance or indifference by many students and researchers, and the need for constant re-education to take account of student and researcher turnover. Automatic sash closure devices were also rejected on the grounds of high capital cost, difficulties in retro-fit installation, ongoing maintenance requirements, and poor user acceptance. Fixed setback of face velocity (typically by stepping down from 0.5 m/s to 0.3 m/s during night time hours) was rejected for the Chemistry Laboratory due to concern that there could be 24/7 use, and difficulties in applying to all designs of fume cupboard. (However, night setback has been used in new CAV installations with two-position sash control in the University’s Physics of Medicine building). Usage based control (UBC) was the preferred option. These also reduced face velocities from 0.5 m/s to 0.3 m/s, but only when presence detectors indicated that a zone in front of the cupboard was unoccupied. Risk assessments concluded that they posed no threat to safety. The system was straightforward to install (as it was provided by the supplier of the fume cupboard VAV controls, Phoenix), required no maintenance, and was invisible to users. A simple example of UBC in practice is a room with a single fume cupboard with 400 litres/second extract with the sash fully open, and 50 litres/s supply offset. When no operator is present, even with the sash fully open, the cupboard is in standby mode at 240 litre/s extract and 190 litre/s make-up air. When an operator enters the detection zone, the cupboard immediately switches to standard mode at 400 litres/s, and the make-up air increases to 350 litre/s, with a response time of under a second. UBC also has a considerable impact on diversity. In a standard VAV system, the worst case scenario of all users leaving their sashes open requires the system to run at 100% (i.e. no diversity). With UBC, modelling suggests that the worst case is sashes fully open for only 10-20% of the time on average. This enables the laboratory to be operated safely with a diversity factor of 65%. Of course, UBC (or VAV for that matter) does not suit every lab facility. There are many variables that will impact on system performance from a diversity and energy standpoint, including number of hoods, density of hoods in labs, minimum air change rates, heating / cooling loads, and usage patterns. The most appropriate system approach needs to be evaluated for each facility. In undertaking this evaluation, the University found the results obtained by Critical Airflow using Phoenix’s LabPro modelling software to be helpful. This involves building a profile of a facility, then running a series of calculations to forecast capital costs, life cycle costs and diversity potential for a range of options (CAV, 2-position CAV, VAV, UBC). 4. Demand Based Control for Significant Energy Reduction in Laboratories – Gordon Sharp Gordon is a Board Member of the International Institute for Sustainable Laboratories, a prominent member of ASHRAE technical committees, former MD of Phoenix Controls, and September 2009 www.goodcampus.org 8 Demand Related Ventilation in Laboratories now Chairman of Aircuity, Inc., a recently established company selling DCV applications in the USA. (Note that Aircuity does not have technical approval to sell in the EU, but hopes to achieve it by the end of 2010). Gordon noted that minimum air change rates in the US are still fixed at around 6-12 air changes per hour (ACH) (or 10-20 for vivariums). However, for the majority of time lab air is clean and there is no need for dilution. On the other hand, there are times when increasing the supply of air above conventional rates could be valuable, e.g. in loss of containment emergencies. The implication is that there is no one ventilation rate that is right all the time. An appropriate ventilation rate can only be determined by reference to the quality of air, which is the major criteria for ventilation of laboratories (but, ironically, the one factor that is not being monitored). In practice, and where dilution is the main driver of airflow, Gordon believes that ACH can safely be brought down to 2-4 ACH (for labs) or 6-8 ACH (for vivariums) for much of the time. The point was illustrated using the analogy of overhead sprinklers. These monitor the air and are only activated if a problem is detected. Gordon suggested that continuously ventilating laboratories and fume cupboards at high rates ‘just in case’ of contamination, was the equivalent of continuously sprinkling water in a building just in case of fire. The alternative approach is to link air changes dynamically to Indoor Environmental Quality (IEQ) sensing in all significant spaces. This has previously been difficult because of design approaches requiring multiple sensors in each room, which has involved high costs, and required overcoming difficulties in calibration and reliability, which often result in inaccuracy. However, sensor costs are falling, and a new design approach is available. The Aircuity system involves a multiplexed sampling system that sends samples of laboratory air to central sensors at regular intervals. This is done by using a patented networked air sampling architecture to sequentially route air packets to the sensors in the same way that data networks route data packets. The air samples are carried in cables that contain carbon nanotube filled plastic conduits. This avoids cross-contamination of samples during transport. The sensors include ones for VOCs, particles, ammonia, carbon monoxide and carbon dioxide, which are said to be sufficient for 90% of laboratories. In this way a network of labs, typically 20, can be served by one sensor suite, and more expensive sensors can be deployed. The system can be integrated into Building Management Systems and can include web-based data collection and analysis. Typically this enables routine air change rates of 2 ACH, with a maximum dilution of 12-16 ACH for purging in case of any incidents. The sensors take samples every 15 minutes which has been shown to be sufficient to pick up any spills or leakages. In 2008 a comprehensive laboratory IEQ Performance Monitoring Study was carried out at over 18 sites, with over 300 different lab areas. The collected data represented over 1.5 million lab hours and with 20 million sensor values. The averaged results for all sites showed that, for VOCs, for example, low ACH can be used 99.4% of the time, equivalent to a higher flow needed for 1 hour a week (4 events). In the worst case in one lab the threshold was exceeded for 3% of time. Gordon noted that no system was perfect, and that comparisons with conventional approaches needed to take their weaknesses into account. For example, some incidents – e.g. evaporation of solvents or other hazardous substances from spills, or from containers on warm days; September 2009 www.goodcampus.org 9 Demand Related Ventilation in Laboratories poorly operating fume hoods – could occur for hours, whereas they would be picked up within 15-30 minutes using DCV. The Aircuity approach could also provide more flexible incident response, e.g. by rapidly increasing air flows to flush out contaminants. The same principle can be applied to exhaust systems by using sampling in conjunction with variable exhaust velocity. Typically the exhaust is run at a high velocity to get it away from the building but air quality in the plume is often quite clean because of the high dilution rates. By monitoring the contaminant levels in the plume the exhaust levels can be reduced significantly, resulting in enormous, 50-75%, reductions in fan power. Seven exhaust systems in a life science building were monitored over 15 months. It was found that incidents requiring increased air flow occurred ~0.04% time per fan or ~0.3% per building, i.e. potential for savings 99% of the time. Gordon cautioned that the approach requires VAV control of supply and room exhaust as a prerequisite. It is also not applicable for 3 or 4 containment level bio labs, nor for labs with a high fume cupboard density (> 1 fume cupboard per 10 square metres). However, many labs/vivariums and in the US are using it, including the US Food and Drug Administration. Examples included: Arizona State University - a LEED Platinum R&D lab facility was originally retrofitted with this multiplexed sampling system in a small portion of this two lab building complex. This produced annual savings of $55,333 and a less than 11 month payback. Since them the system has been implemented across both buildings (33,000 total gross sq ft) with estimated savings of over $1 million. GreenLab Seattle – a 75,000 sq ft lab, with a 25,000 sq ft vivarium, which considered a design based on multiplexing versus a fixed ACH system (9 for lab, 15 for vivarium). The results showed that the total building energy costs could be cut by $250,000 per year and the gross first cost savings were $1,010,000 (primarily due to plant downsizing). Texas Children’s Hospital – which retrofitted 2 floors of a life science facility, including 28 lab areas. This produced $61,000 annual energy savings with a 1.6 year payback. The sampling revealed many spikes in VOC levels in one lab room resulting from 4 recirculating biosafety cabinets. This was found to be due to technicians using spray bottles of alcohol in prepping samples. Even in this worst case situation the air was ‘clean’ 93% of the time and significant energy was saved even for this lab room. The system is also used in more conventional environments, where it measures carbon dioxide, particles and VOCs for better air quality and demand control ventilation of outside air to save energy. For example, the Bank of America Tower, the second tallest building in New York, and a LEED platinum building, uses this system for IEQ monitoring and DCV. Gordon provided other examples of buildings which use the sensing system for humidity monitoring and DCV control. Questioned on the mechanical stability of the system and risk of puncturing/piercing, Gordon noted that the system is self-diagnostic and checks itself. September 2009 www.goodcampus.org 10 Demand Related Ventilation in Laboratories 5. Discussion Topics discussed at the various events included: General Health and Safety – There are concerns that DRV approaches are overturning long standing traditional approaches without a sufficient evidence base of their safety. Some critics say that the traditional approach has avoided serious safety issues in labs, and that the ‘precautionary principle’ should apply. It was noted that there have been a few legal cases regarding exposure incidents in traditional CAV installations, but these have usually been settled out of court, and hence are not widely known. They believe that a proper risk assessment undertaken in accordance with the fume cupboard safety standard BS EN 14175 should guard against any safety problems. Safety of User Based Controls – Although these are being used at Cambridge and a number of other locations, some experts have concerns about their safety and value. One criticism is that situations could be imagined in which containment is required, but the face velocity does not increase sufficiently quickly to provide it. (However, no safety incidents have been identified to date). Another criticism is that UBC is a second best alternative – and could discourage - voluntary sash closure, which is cheaper and safer. Implementation can be Difficult – VAV systems are more complex, and several universities have experienced a steep learning curve. However, a growing number of UK universities have made it work, and will apply it in future laboratory designs. System Interactions – A holistic analysis is important as the device, room and system levels interact with each other. One point to watch is that reducing fume cupboard air flows does not result in inadequate room ventilation. Calibration – Some commercial carbon dioxide sensors have had problems of “drifting” out of calibration, with consequent inaccuracies in ventilation rates. It is important to ensure that sensors are guaranteed against this (e.g. “1 percent per year drift maximum”). Recalibration will always be needed at some point, typically every 6 months or so. Room Variations – There can be considerable differences in occupancy, emissions etc. within large rooms, and it is important that these are considered in DRV designs. Sash Management – Several examples were given of effective management. In one laboratory, open sashes are recorded, and users fined after a number of violations. The University of California LabRATS programme also produces stickers and other guidance materials for lab users.7 Commissioning – This is always important in labs, but especially those with DCV as controls and systems must be working effectively to achieve safe operation and energy benefits. The traditional view of commissioning has been that it is a process of testing equipment and control devices at the end of construction in order to prove that they are meeting the design intent. However, the best results are likely to be achieved when commissioning is considered as a form of quality control, and integrated into earlier stages of the design process. 7 See James P. and Hopkinson L., 2009. The Sustainable Laboratory - How Lab Managers and Technicians Can Make an Environmental Difference. September 2009. Available at: www.goodcampus.org September 2009 www.goodcampus.org 11 Demand Related Ventilation in Laboratories Appendix 1 – The Labs21 Design Philosophy The US Labs21 initiative has demonstrated that a new approach to design and operation can result in significant environmental, financial and other benefits. This involves: A design process which has greater integration of sub-systems, and more effective implementation and quality control. Architectural principles which place greater weight on engineering and energy considerations, and adopt more flexible and modular configurations. Engineering principles which seek a greater understanding of energy loads, have more adjustable means of matching supply with demand, and ‘right size’ equipment to closely match actual needs. A series of HEEPI events have identified some differences between Britain and the US, but highlighted five key technical areas where the Labs21 approach is relevant to, and challenges, current practice in the UK: Low energy ventilation design, aimed at reducing the volume and velocity of air movements (and consequent fan energy consumption), by methods such as low pressure drop air handling systems and the use of variable air volume (VAV) fume cupboards. Rethinking fume cupboard ventilation systems, positioning, and operating parameters in order to reduce their volume flow rates, and to optimise the flexibility of laboratory space. Evidence-based design, which uses modelling, real rather than ‘nameplate’ data on equipment energy use, and other techniques, to reduce uncertainty so that overly conservative rules of thumb and safety margins can be avoided. More modular solutions (such as plug-in modular fume cupboards with integrated ductwork) to provide greater flexibility and greatly reduce the cost, time requirements, and disruption of refurbishments. More attention to the design and commissioning of controls, which must work well if design specifications – for both energy efficiency and safety – are to be achieved, but often don’t. Labs21 US has also demonstrated that these technical changes cannot be achieved without a well managed design process that has: More integrated and engineering-led design, to overcome current problems of fragmented decisions by specialists, and a lack of understanding amongst some professionals that heating, ventilation and air conditioning (HVAC) decisions are crucial to laboratory energy and safety performance, and need to be prominent from the earliest stages. September 2009 www.goodcampus.org 12 Demand Related Ventilation in Laboratories Clear sustainability goals, such as target air change rates or energy consumption per m2. Greater involvement by a range of users and facilities staff in order to improve communication within the project team, and to ensure that designs are practical and effective. More integrated and effective commissioning and evaluation so that independent quality control of this aspect exists from the start of the design process. Value engineering to minimise whole-life, rather than first, costs and ensure that removing one element does not – because of the interconnectedness of laboratory systems - have unexpected and costly knock-on effects elsewhere. A HEEPI report explores these issues in greater detail.8 8 Peter James, Mike Dockery and Lisa Hopkinson, Sustainable Laboratories for Universities and Colleges Lessons from America and the Pharmaceutical Sector, University of Bradford: HEEPI, January 2007. Available at: www.goodcampus.org. September 2009 www.goodcampus.org 13 Demand Related Ventilation in Laboratories Appendix 2 - HEEPI Energy Benchmarks for Laboratories9 HEEPI’s laboratory benchmarking programme has found that recent HE laboratories usually have higher consumption per square metre than those built a few years ago. 10 This trend is associated with, for instance, a movement to work being carried out only in contained conditions, such as within fume cupboards, rather than on the open bench. There are also increasing levels of automation in lab equipment (i.e., plug loading), and more complex information systems (most notably at the work bench), all of this running 247 for a variety of reasons. For these and other reasons, it is very common for laboratories to have much higher consumption than their design specification – sometimes two or three times higher. HEEPI has developed benchmarks for different types of laboratories according to energy performance, based on “typical”, “good” and “best” practice that existed in 2003/04, and updated in 2007.11 (Note that even “best” practice within the sector may not reflect leading edge energy efficiency design, or even what is standard practice within the commercial sector). Despite the high energy and water consumption and costs associated with laboratories, there are still very few exemplary sustainable laboratory buildings being developed by universities and colleges in the UK. For a hypothetical 7,000 m2 laboratory building, the typical, good and best energy performance within the sector translates into the following annual energy costs (see Table 1). Table 1: Annual energy costs associated with a hypothetical 7,000 m2 laboratory building with typical, good and best energy performance for the higher education sector12 Type of Laboratory Best Good Typical Medical/biosciences £114,000 £221,000 £326,000 Physical/engineering £68,000 £91,000 £192,000 Chemistry £292,000 £313,000 £365,000 As the table shows, the difference in annual energy costs between the “best” and a “typical” laboratory is around £212,000 for a medical/biosciences lab, £124,000 for a physical/engineering lab and £73,000 for a chemistry lab. Over a 7 year ‘lifetime’ – the normal one planned for in higher education - the difference between the total energy bills of the best and typical laboratories would be £0.5 - 1 million. 9 Based on 2001-02 data obtained from previous HEEPI benchmark workshops. See Results of the HEEPI HE Building Energy Benchmarking Initiative 2003-04, August 2006 www.heepi.org.uk 10 Hopkinson L. and James P., 2007. Sustainable Laboratories for Universities and Colleges - reducing Energy and Environmental Impacts. Report based on a HEEPI benchmarking workshop held on 26 April 2007. Available at: www.goodcampus.org 11 Ibid. 12 Based on July-December 2008 average UK gas and electricity prices of 3.44p/kWh for gas and 10.9p/kWh for electricity. DECC Quarterly Energy Prices, September 2009. Available at http://www.decc.gov.uk/en/content/cms/statistics/publications/prices/prices.aspx September 2009 www.goodcampus.org 14