Set 4

advertisement
_______________________
Last Name, First
CHE426: Problem set #4
1. An engineer has designed a system in which a positive-displacement pump is used to
pump water from an atmosphere tank into a pressurized tank operating at 150 psig. A control
valve is installed between the pump discharge and the pressurized tank.
With the pump running at a constant speed and stroke length, 350 gpm of water is
pumped when the control valve is wide open and the pump discharge pressure is 200 psig.
(a) If the control valve is pinched back to 60 percent open, determine the water flow
rate.
(b) If the pump reduces speed so that the water flow rate is 250 gpm at 60 percent
valve open, determine the pump discharge pressure
2. A 2 L glass jar is half filled with water and half filled with air at a temperature of
293oK. After 92 mg (=10-3 mol, mw = 92) of liquid toluene is added, the jar is sealed. At
293oK, the Henry’s law constant for toluene is KH,g = 0.15 [Matm-1]. Note: M= mol/L,
gas constant = 82.0510-3 Latm/molK
Pt
Air
Ct
Liquid water
Determine the equilibrium partial pressure (atm) of toluene in the gas phase and the
equilibrium concentration (M) of toluene in the water.
3.2 We want to design a control valve for admitting cooling water to a cooling coil in an
exothermic chemical reactor. The normal flow rate is 60 gpm and the minimum flow rate is
25 gpm. To prevent reactor runaways, the valve must be able to provide three times the
design flow rate. The pressure drop through the cooling coil is 5 psi at the design flow rate of
60 gpm. The cooling water is pumped from an atmospheric tank. The water leaving the coil
run into a pipe in which the pressure is constant at 2 psig. Size the control valve and the
pump.
4.2 A process for transferring oil from a storage tank to a separation tower is shown in Figure
P-5b. The tank is at atmospheric pressure, and the tower works at 12.7 psia. Nominal oil flow
is 1000 gpm, its specific gravity is 0.90, and its vapor pressure at the flowing temperature of
90oF is 14.85 psia. The pipe is 8-in. Schedule 40 commercial steel pipe, and the pump
efficiency is 80%. Size a valve to control the flow of oil if the frictional pressure drop in the
line is found to be 6 psi. Use a pressure drop of 10 psi across the valve and estimate the
annual cost if the electricity price is $0.20/kW-hr and the pump operates 8200 hr per year.
Nominal Trim size
Orifice Dia. (in.)
Valve size
(in.)
1/4
3/8
.250 .375
½
.500
3/4
1
.750
.812
Reduced Trim
1.5
2
3
4
6
8
10
1.250 1.625 2.625 3.500 5.000 6.250 8.000
Full Capacity Trim
3/4
1.7
3.7
6.4
11
1
1.7
3.7
6.4
11
12
1½
1.7
3.8
6.6
12
13
25
2
1.7
3.8
6.7
13
19
26
46
31
47
110
32
49
113
195
53
126
208
400
133
224
415
640
233
442
648 1000
3
14
4
6
8
10
Figure P-5a Flow coefficient for Masoneilan’s valve Schedule 40.
Separation
tower
P = 12.7 psia
Crude tank
P = 1 atm
Pump
64 ft
8 ft
4 ft
Figure P-5b An oil transferring system
5.2 A 4-in Masoneilan valve with Cf = 0.9 and full trim has a capacity factor of 195
gpm/psi1/2 when fully opened. The pressure drop across the valve is 10 psi.
(a) Calculate the flow of a liquid solution with density 0.8 g/cm3.
(b) Calculate the flow of gas with average molecular weight of 35 when the valve inlet
conditions are 100 psig and 100oF.
(c) Calculate the flow of the gas from part (b) when the inlet pressure is 5 psig. Calculate the
flow both in volumetric and in mass rate units, and compare the results for a 4-in. Fisher
Controls valve (Cv = 183, Cg = 6650, C1 = 36.3).
6. A control valve is to regulate the flow of steam into a heat exchanger with a design heat
transfer rate of 10 million Btu/hr. The supply steam is saturated at 20 psig. Size the control
valve for a pressure drop of 10 psi and 100% overcapacity. Assume a Masoneilan valve with
Cf = 0.8.
7. The temperature of a CSTR is controlled by an electronic (4 to 20 mA) feedback control
system containing (1) a 100 to 260oF temperature transmitter, (2) a PI controller with integral
time set at 2 minutes and proportional band at 25, and (3) a control valve with linear trim, airto-open action, and Cv = 10 gpm/psi0.5 through which cooling water flows. The pressure drop
across the valve is a constant 25 psi. If the steady state controller output is 12 mA, how much
cooling water is going through the valve? If a sudden disturbance increases reactor
temperature by 10oF, what will be the immediate effect on the controller output signal and
the water flow rate?
8. Develop a dynamic model for the endothermic CSTR as shown in Figure 4-8.
FC
FT
Feed
Product
AT
Figure 4-8 Schematic of an endothermic CSTR.
The process parameters and variables are given by
CA: reactant concentration (initially 0.25 mol/L)
CA0: feed concentration (initially 1.0 mol/L)
Cp: heat capacity of the reactor feed and product (1000 cal/kgK) = Cv
E/R: normalized activation energy (20,000 K)
F: mass feed rate and product rate (10 kg/s)
k0: rate constant (1.97×1024 s-1)
Q: heat addition rate (initially 700,000 cal/s)
T: reactor temperature (initially 350 K)
T0: feed temperature (400 K)
t: time (s)
Vr: reactor volume (100 L)
: the constant density of the reactor feed and product (1 kg/L)
Hrxn: heat of reaction (160,000 cal/mol)
These conditions represent the initial steady-state conditions. At time equal to 10 seconds, a
step change in the heat addition rate is made from 700,000 cal/s to 900,000 cal/s. Plot the
product stream temperature and concentration from 0 to 100 s using two separate graphs. Use
Matlab to plot and label the graph with your name using the Title command. Note: The
solution to this problem is in reference (4) and you should use ode23s (s for stiff) to solve the
ODEs since the ODES describing the reactor are stiff differential equations.
References
1. D.R. Coughanowr and S. LeBlanc, Process Systems Analysis and Control, McGraw-Hill,
3nd edition, 2008.
2. Mass Transfer by Hines and Maddox.
3. Process Modeling, Simulation, and Control for Chemical Engineers by Luyben.
4. Chemical and Bio-Process Control by James B. Riggs and M. Nazmul Karim