[Project Name] Project No: [ ] Section Insulated 07 42 Metal 13 Panels Section 07 42 43 PART 1 – GENERAL 1.1 DESCRPTION .1 Supply factory insulated metal panels for wall systems as specified and as shown on drawings. .2 Work furnished and included: .1 All steel faced, factory foamed insulated panels with side lap seals for walls, ceilings and/or roofs as detailed on drawings. .2 Sealants between metal panel components. .3 Related flashings, trims, and extrusions. .4 Fasteners and washer plates. .3 Related work not included: .1 Supply and installation of structural steel support. .2 Supply and installation of roof coping, trim or flashing at parapet and wallroof junctions. .3 Wood blocking. .4 Windows. .5 Doors. .6 Supply and installation of structural steel support. 1.2 STANDARDS .1 Design of insulated metal panel system in accordance to the latest edition of: .1 CSA-S136 for the design of Cold Formed Steel Structural Members .2 National Building Code of Canada 1.3 QUALITY ASSURANCE .1 Supplier shall design and supply work of this Section. .2 Supplier/installer shall have a minimum of 5 years proven experience and must have completed at least 5 major insulated metal panel projects. .3 All walls and openings are to be within ±3 mm (0.12”) of the location shown on architectural drawings. Also, the façade is to be plumb within 1:1000 of the overall height with a maximum of 25mm. 1.4 DESIGN REQUIREMENTS .1 Structural movement: Accommodate movement of supporting structural framing and without causing bowing, buckling, delamination, oil canning, excessive stress on fasteners, or any other detrimental effects. .2 Thermal Movements: Allow for thermal movements from ambient and surface temperature changes by preventing buckling, opening of joints, overstressing of components, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime sky heat loss. .1 Temperature Change (Range): 20 deg C, ambient; 40 deg C, material surfaces. 1.5 PERFORMANCE REQUIREMENTS .1 Air Infiltration: Air leakage through assembly of not more that 0.035 m3/hr/m2 (0.002ft3/min/ft2) of wall area when tested according to ASTM E 283 at the following test pressure difference: .1 Test-Pressure Difference: 1000Pa (20 lbf/sq.ft.). .2 Water Penetration under Static Pressure: No water penetration when tested according to ASTM E 331 at the following test pressure difference: .1 Test-Pressure Difference: 1000Pa (20 lbf/sq.ft.). This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 1 of 6 [Project Name] Project No: [ ] Section Insulated 07 42 Metal 13 Panels Section 07 42 43 .3 Water Penetration under Dynamic Pressure: No water penetration when tested according to AAMA 501.1 .4 Structural Performance: Metal wall panel assemblies shall withstand the effects of the following loads and stresses within limits and under conditions indicated, based on testing to ASTM E 330: .1 Wind Loads: Design wall system to resist {wind loads, positive and negative, expected in this geographical region NBCC climatic data, 50 year probability} {### kPa} without excessive deflection of panels, overstressing of fasteners, or other detrimental effects on wall system. .2 Deflection Limit: Design wall system to L/180. .5 Fire-Performance: .1 Flame Spread Tests: .1 Surface-Burning Characteristics: Provide materials with the following surface-burning characteristics as determined by testing identical products per ASTM E 84: .1 Flame-Spread Index: 25 or less. .2 Smoke-Developed Index: 450 or less. .2 Surface-Burning Characteristics: Provide materials with the following surface-burning characteristics as determined by testing identical products per CAN/ULC S101: .1 Flame-Spread Index: 25 or less. .2 Smoke-Developed Index: 450 or less. .2 Fire Endurance Test: Provide panels to remain in place for not less than 15 minutes, when tested in accordance to CAN/ULC-S101. .3 Fire Growth Test: Provide panels tested in accordance to CAN/ULC-S138 (CAN/ORD 376). .4 Flammability Test: Provide panels tested in accordance to CAN/ULC-S127. .5 Non-combustible Characteristics: Provide core material with the following combustibility characteristics as determined by testing identical products per CAN/ULC-S134 or another testing and inspecting agency acceptable to authorities having jurisdiction. .6 Certification .1 Panels shall be listed by the following agencies as evidence of independent testing and periodic inspections of manufacturing facilities. .2 Panels shall be listed under FM Approvals Class Number 4880 for Class 1 fire rating without height restriction. .3 Wall panels shall be listed under FM Approvals Class 4881. .4 The manufacturer shall be authorized by an independent body such as Intertek, UL or ULC to apply a certification mark as evidence of product and manufacturing review. .5 Where panels will be used in food facilities in the immediate vicinity of materials intended for human consumption, the system used should be satisfactory to the Canadian Food Inspection Agency. 1.6 SAMPLES .1 Submit {standard color, full width panel sections of 11” length showing joints} { standard color, joint sample of panel, 10” in length}, insulation, profile, and finishes for architect’s approval. 1.7 SHOP DRAWINGS .1 Submit shop drawings in accordance with Section [01 33 23]. .2 Indicate layouts, elevations, dimensions and thickness of panels. .3 Show fastening and anchoring details. This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 2 of 6 [Project Name] Project No: [ ] Section Insulated 07 42 Metal 13 Panels Section 07 42 43 .4 Distinguish between factory and field assembled work. .5 No panels shall be fabricated until drawings have been approved by the architect. .6 Drawings shall be signed and sealed by a Professional Engineer, attesting to the ability of the insulated metal panel system to withstand the specified loads. 1.8 MAINTENANCE DATA .1 Provide maintenance data for cleaning and maintenance of panel finishes for incorporation into manual specified in Section [## ## ##]. .2 Submit instructions for repair and removal of panels. 1.9 MOCK-UP [If required] .1 Submit mock-up in accordance with Section [01 43 39]. .2 Erect mock-up panel approximately long x high in location directed by Architect. .3 Mock-up panel shall include all components of the wall system and if approved by Architect may be incorporated in to finished work. .4 Notify 72 hours before installation of mock-up for inspection by Architect. Do not proceed with panel system work until mock-up has been approved. 1.10 PRODUCT DELIVERY, HANDLING AND STORAGE .1 The panels shall be handled and stored in accordance with the manufacturer’s recommended guidelines and good construction practices to prevent permanent distortion and mechanical damage. .2 Store components and materials in accordance with panel manufacturer’s recommendations. 1.11 GUARANTEE .1 For work in this section, warranty by installer against defects or deficiencies in materials or workmanship shall be for a period of one (1) year from date of substantial completion. 1.12 WARRANTY .1 The panel manufacturer shall warranty for one (1) year from the date of substantial completion of the work related to the wall/roof panels. .2 Provide a manufacturer’s written warranty: Furnish panel manufacturer’s written warranty covering failure of factory-applied exterior finish within the warranty period. Warranty period for finish: {20 years} {35 years} {40 years} after the date of Substantial Completion. The values below are based on normal environments and exclude any aggressive atmospheric conditions. .1 {Barrier Series (Polyvinyl Chloride – PVC) will not change colour more than ten (10.0) Hunter ΔE units as determined by ASTM method D-2244-02 at any time for twenty (20) years from date of installation (20.5 yrs from application).} .2 {10000 Series (Polyvinylidene Flouride - PVDF) will not visibly (within 10 metres to the unaided maked eye) crack, chip, or peel (lose adhesion) for thirty-five (35) years from date of application. This does not include minute fracturing that may occur during the normal fabrication process. 10000 Series (Polyvinylidene Flouride - PVDF) will not chalk in excess of a number eight (8) rating, in accordance with ASTM D-4214-98 method D659 at any time for thirty-five (35) years from date of installation (35.5 yrs from application); will not change colour more than five (5.0) Hunter ΔE units as determined by ASTM method D-2244-02.} This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 3 of 6 [Project Name] Project No: [ ] .3 Section Insulated 07 42 Metal 13 Panels Section 07 42 43 {WeatherX™ (Siliconized Polyester - SMP) will not crack, chip, or peel (lose adhesion) for forty (40) years from date of installation (40.5 yrs from application). This does not include minute fracturing that may occur during the normal fabrication process. WeatherX™ (Siliconized Polyester - SMP) will not chalk in excess of a number eight (8) rating, in accordance with ASTM D-4214-98 method D659 at any time for thirty (30) years from date of installation (30.5 yrs from application); will not change colour more than five (5.0) Hunter ΔE units as determined by ASTM method D-2244-02.} PART 2 – PRODUCTS 2.1 PANEL TYPE: .1 Vicwest Insulated Metal Panels. .1 Panel Width: {42” (1067 mm)} {36” (915 mm)} {30” (762 mm)} {24” (610 mm)}. .2 Panel Thickness: {2” (50 mm)} {2-½” (63 mm), {3” (75 mm)}, {4” (100 mm)}, {5” (125 mm)}, {6” (150 mm)}. .3 Panel to incorporate nominal {1 mm} {9 mm} reveal in side lap. .4 Exterior Sheet: {Stucco embossed} {Flat non-embossed} with {Fluted} {Striated} {Microribbed} {Flat} {Ribbed} profile. .5 Interior Sheet: Stucco embossed with {Fluted} {Flat} profile .2 Panels consisting of a polyisocyanurate core produced by the continuous line method for optimum uniformity and quality will be considered. Laminated or styrene core panels will not be accepted. .3 Panels shall consist of roll formed steel face and liner sheets chemically fused to a foamed in place rigid polyisocyanurate expanded foam core. .4 Panels shall be single piece construction full height or may be stacked in multiple courses for most temperature applications. .5 The steel facing sheets at the longitudinal edges of the panel shall have roll formed male and female interlocking geometry fully supported by the foamed in place insulation core. Ensure insulation-to-insulation contact at the tongue and groove joint. .6 Sealant {that is factory installed} {that is site applied} shall be incorporated into the interlocking geometry. .7 All panels shall use fasteners and washers applied from the exterior and concealed in the panel edge joint, when possible, for positive connection to the structural support. Panels may be partially fastened to the structure using expansion type fasteners into the interior panel face. 2.2 MATERIALS: .1 Liner sheet shall have a nominal core thickness of {0.46 mm (0.018”)} {0.61 mm (0.024”)} {0.76 mm (0.030”)}. Steel shall conform to ASTM A792M Grade 230 with hot dipped aluminum zinc alloy coating to AZM150 or to ASTM A653M SS Grade 230 with hot dipped galvanized coating to Z275. .2 Exterior sheet shall have a nominal core thickness of {0.46 mm (0.018”)} {0.61 mm (0.024”)} {0.76 mm (0.030”)}. Steel shall conform to ASTM A792M Grade 230 with hot dipped aluminum zinc alloy coating to AZM150 or to ASTM A653M SS Grade 230 with hot dipped galvanized coating to Z275. This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 4 of 6 [Project Name] Project No: [ ] Section Insulated 07 42 Metal 13 Panels Section 07 42 43 .3 Core material used in the panel shall be foamed in place multi-component polyisocyanurate insulation, having the following typical physical properties: .1 95% closed cell based on ASTM D2856 .2 35 to 45 kg/m3 (2.2 to 2.8 pcf) density based on ASTM D1622 .3 0.11 MPa (16 psi) compression based on ASTM D1621 .4 Blowing agent for core insulating material to have zero ozone depletion potential .5 Fasteners used to attach panels at concealed joints to the structural frame shall be #14 with hex or washer head and used with joint washers supplied by panel manufacturer. .6 Sealants used in the internal panel joints shall be non-curing mastic sealant, and shall be applied on the warm side of the panel. 2.3 FINISHES The exterior and interior faces of the insulated metal panel and flashings shall receive factory applied coatings. .1 The interior finish to be prepainted with {WeatherX™} {10000} {Barrier} Series. Colour as selected by consultant. .2 The exterior finish to be prepainted with {WeatherX™} {10000} {Barrier} Series. Colour as selected by consultant. PART 3 — EXECUTION 3.1 EXAMINATION .1 Examine alignment of structural steel to ensure that support member alignment shall not exceed the tolerance requirements of CSA Standard S16.1. .2 Report any unsatisfactory conditions to Architect in writing. Do not start work until unsatisfactory conditions are rectified. 3.2 INSTALLATION .1 Install insulated metal wall panels, fasteners, washers and any required sealants in accordance with approved shop drawings. Comply with panel manufacturers general instructions and recommendations for installation and as applicable for project conditions to ensure low temperature and/or weather tight performance of wall panel system. .2 Install concealed fasteners and washers in side lap combined with supplementary fasteners as required to ensure resistance to wind loading and compliance to deflection limitations. .3 Adjacent panels shall be mechanically interlocked at their side lap with the roll formed tongue and groove profile. 3.3 CLEAN-UP .1 Remove protective film at the completion of the project when instructed by the Architect and/or Owner. .2 Panel surface shall be free of deleterious material including dirt, filings caused by drilling or cutting. .3 Remove all debris of this trade and leave work ready for other trades. This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 5 of 6 [Project Name] Project No: [ ] Section Insulated 07 42 Metal 13 Panels Section 07 42 43 .4 Repair or replace damaged panels to the satisfaction of the Architect and/or Owner. The cost of repairing or replacing damaged material will be charged to the responsible party. This specification was created by Vicwest to assist designers. It should be reviewed and modified as required to suit individual project conditions. Page 6 of 6